Greenheck Fan SWB 100, SFD, SWB 200, SWB 300 User Manual

Part #455308
®
Centrifugal Utility Fans
Model SWB - Series 100, 200 and 300
Models SFB and SFD
Installation, Operation and Maintenance Manual
Model SWB
Series 300
Model SWB Series 200
Model SWB Series 100
Model SFB
Table of Contents
Motor and Drive Installation
(Units Shipped from Stock) ................ 2
Installation ............................... 3
Affect of Installation on Performance ......... 3
UL/cUL 762 - Restaurant Exhaust ............ 4
Pre-Starting Checks ......................4-5
Belt Drive Fan Maintenance ................. 6
Bearing Lubrication Schedule ............... 6
Motor Maintenance (Belt and Direct Drive) ..... 6
Parts List ................................ 7
Troubleshooting Chart ..................... 8
Model SFD
®
Centrifugal Utility Fans
1
Motor and Drive Installation Instructions
Model SWB units are shipped from stock without motors or drives.
1. Adjust motor pulley to its closed position for maximum fan speed or increments of 1/2 turn open (maximum of 5 turns open) for reduced fan speed. Tighten set screw on flat area only.
4. Install shaft pulley to fan shaft.
2. Install motor pulley to the motor shaft and install motor to the motor plate. Pre-punched holes are provided for most common motor frame sizes.
3. If supplied, install taperlock bushing into shaft pulley.
Centrifugal Utility Fans
2
5. Install drive belt(s). Belts should not be forced over pulleys. Align motor and shaft pulleys with a straight edge. Tighten all set screws.
6. Adjust belt tension. See page 6 for belt tensioning instructions.
®
Installation
Affect of Installation on Performance
Inspect the unit for any damage and report it to the shipper immediately. Also, check to see that all accessory items are accounted for.
Move the fan to the desired location and fasten securely through mounting holes provided in the base angles. The unit must be set level (shimming may be necessary). Flexible duct connections and vibration isolators should be used where noise is a factor.
The motor voltage and ampere rating must be checked for compatibility with the electrical supply prior to final electrical connection. Supply wiring to the fan must be properly fused, and conform to local and national electrical codes.
The discharge is factory set as specified by customer order, however, it can be rotated to other discharge positions in the field if necessary. Removal of the housing bolts allows the discharge to be rotated to the clockwise positions below. For TAD, BD and BAD discharge positions, a portion of the frame angle must be removed.
Clockwise rotation shown. Counterclockwise discharge positions are a mirror image of those shown. Fan rotation is always specified from the drive side of the housing.
Restricted or unstable flow at the fan inlet can cause pre-rotation of incoming air or uneven loading of the fan wheel, yielding large system losses, increased sound levels and structural failure of the fan wheel. Free discharge or turbulent flow in the discharge ductwork will also result in system effect losses.
The examples below show the system layout and inlet and discharge configurations which can affect fan performance.
Discharge Configurations
7o MAX.
POOR
POOR
FAIR
POOR
GOOD
FAIR
Discharge Positions
CW BH CW BAU CW TAUCW UB
CW TH CW TAD
CW DB
CW BAD
POOR
POOR
POOR
Turning
Varies
FAIR
FAIR
POOR
One
Impeller
Dia.
Should be at least 1/2 Impeller Dia.
GOOD
GOOD
Not Greater than
o
Including Angle
60
FAIR
®
Centrifugal Utility Fans
3
3
Gap
Wheel
Radial Gap
Overlap
Wheel
Installation of UL/cUL 762 Listed
Gap
Wheel
Fans for Restaurant Exhaust
The UL/cUL 762 listing for restaurant exhaust is available on Series 200 and 300 SWB fan model sizes 206 - 224 and 327 - 349 with a weatherhood. UL/cUL 762 fans are listed for a maximum operating temperature of 375°F (191°C) and includes an access door and 1inch (25.4 mm) drain connection. An outlet guard is strongly recommended when the fan discharge is accessible. An upblast discharge is recommended. The fan discharge must be a minimum of 40 inches (1016 mm) above the roof line and the exhaust duct must be fully welded to a distance of 18inches (457mm) above the roof surface.
Upblast Discharge
Optional Companion
40 in.**
(1016 mm)
**Per NFPA 96 the fan discharge must be a minimum of 40 in. (1016 mm) above the roof surface.
Weatherhood
Flange
3 Wheel
Diameters
This drawing is for dimensional information only. See the latest edition of NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations for detailed installation instructions, materials, duct connections and clearances.
Series 200 & 300 SWB models are listed for grease removal (UL/cUL 762) File no. MH11745.
18 in.*
(457 mm)
Duct from
*Per NFPA 96 the duct
kitchen
must be of all-welded
hood
construction to a minimum distance of 18 inches (457 mm) above the roof surface.
Alignment of Pulleys and Belts
Check pulleys and belts for proper alignment to avoid unnecessary belt wear, noise, vibration and power loss. Motor and drive shafts must be parallel and pulleys in line as shown below.
Wrong Wrong Right
The adjustable motor pulley is set at the factory for the fan RPM specified by the customer. Fan RPM can be increased by closing or decreased by opening the adjustable motor pulley. Multigroove variable pitch pulleys must be adjusted an equal number of turns open or closed. Any increase in fan speed represents a substantial increase in load on the motor.
To avoid motor overheating and possible burnout, motor load amperes should always be checked and compared to nameplate rating when fan speed is increased.
Wheels
Wheels must rotate freely and not rub on the inlet venturi. Model SWB wheels overlap the inlet venturi as shown in Figure 1. Refer to the SWB fan wheel overlap and radial gap chart for proper dimensions.
Pre-Starting Checks
WARNING
Always disconnect power before working on or near a fan. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
Models SFD and SFB wheels do not overlap the venturi, but have a gap between the inlet venturi and the wheel (Fig. 2). Wheel position is preset at the factory and the unit is test run. Wheel movement may occur during shipment or installation and wheel alignment may be necessary.
Model SWB
Fig. 1
Model SFD or SFB
Fig. 2
Centrifugal Utility Fans
4
®
On belt drive units, centering can be accomplished
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
ta
t
io
n
R
o
ta
t
io
n
Backward Inclined
Forward Curved
Airflow
Airflow
Backward Inclined Forward Curved
Airflow
These are the original drawings on the Illustrator file when I opened it. The IOM had the wheel layered on top of the scroll. I will incorporate the wheel on the scroll without creating an additional layer in the InDesign file.
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Airflow
Airfoil
R
o
ta
t
io
n
R
o
ta
t
io
n
Backward Inclined
Forward Curved
Airflow
R
o
t
a
t
i
o
n
Airflow
Airfoil
Airfoil
by (a) loosening the inlet cone bolts to move the inlet cone or by (b) loosening the bearings in order to move the shaft. Wheel and inlet cone overlap can be adjusted by loosening the wheel hub set screws and moving the wheel to the desired position. Tighten all fasteners and set screws securely and realign drive pulleys after adjustment.
Approximate Wheel Clearance Dimensions
Unit Size
SWB
SWB
SFD SFB
Series
100
Series
200
SWB
Series
300
6 106 206 —3⁄8
7.5 107 207 —3⁄8 9 9 108 208 —1⁄2
10 10 110 210
12 212
113 213
15 115 215
116 216 18 118 218 20 120 220 22 222
124 224 25 —3⁄4 27 3277⁄8 30 33015⁄16
11
333 11⁄16 336 13⁄16 340 11⁄4 344 17⁄16 349 19⁄16
SWB SFD SFB
Overlap
7
3
3
1
1
5
5
3
16
88
2288164
(10)
(10)
(11)
(13)
(13)
(16)
(16)
(18)
(19)
(22)
(24)
(27)
(30)
Tolerance
(32)
(37)
(40)
Overlap
inches (mm)
1
(6)
4
1
(6)
4
1
(6)
4
1
(6)
4
1
(6)
4
3
(10)
8
3
(10)
8
3
(10)
8
3
(10)
8
1
(6)
4
3
(10)
8
3
(10)
8
3
(10)
8
3
(10)
8
3
(10)
8
1
(13)
2
Radial
Gap
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
5
(4)
32
3
(5)
16
3
(5)
16
3
(5)
16
3
(5)
16
1
(6)
4
5
(8)
16
5
(8)
16
Gap Gap
(10)
(10)
1
(13)
1
1
(13)
2
—1⁄2 —1⁄2 —1⁄2 — —1⁄2 —5⁄8 —5⁄8
—3⁄4 —3⁄4 — — — — — — — —
Wheel Rotation
Rotation direction of the wheel is critical and incorrect rotation will result in reduced air performance, increased motor loading and possible motor burnout.
Check wheel rotation by momentarily energizing the unit and noting if rotation is in the same direction as the airflow at the outlet and conforms to the rotation decal affixed to the unit.
NOTE
Models SFD and SFB units should be operated only when attached to the system for which they were designed. Without proper system static pressure,
— —
(13)
2
(13)
2
(13)
(13)
(13)
(13)
(16)
(16)
(19)
(19)
(19)
the motor could be overloaded.
Wheels as viewed from the drive side:
Backward Inclined
Forward Curved
Airflow
Airfoil
Airflow
n
o
i
t
a
t
o
R
R
o
t
a
t
i
o n
Airflow
®
Centrifugal Utility Fans
5
Blower Maintenance (Belt Drive)
Belts tend to stretch after a period of time. They should be periodically checked for tension and wear. When replacing belts, use the same type as supplied with the unit. Replacement of belts should be accomplished by loosening the tensioning “L-Bolts” so the belts may be removed by hand. Do not force belts on or off as this may cause breakage of cords and lead to premature belt failure.
Belt tension should be adjusted to allow 1/64 in. of belt deflection per 1 in. of belt span. For example, a 16 in. belt span should have 16/64 in. or 1/4 in. of deflection with moderate thumb pressure at mid-point between the pulleys. (Fig. 3). Refer to Greenheck’s Product Application Guide, “Measuring Belt Tension” for additional information—FA/127-11 found online at www.greenheck.com under the library section.
Fig. 3
Belt Span
Deflection =
Belt Span
64
• Lubrication interval is based on 12 hour per day operation and maximum 160°F housing temperature. For 24 hour per day operation, the interval should be cut in half.
• Lubricant should be added with the shaft rotating and until clean grease is seen purging from the bearing. The lubrication interval may be modified based on the condition of the purged grease. If bearing is not visible to observe purged grease, lubricate with number of shots indicated in chart for bore size.
• For conditions including high temperatures, moisture, dirt or excessive vibration, consult the factory for a specific lubrication interval for your application.
• Lubricant should be a high quality lithium complex grease conforming to NLGI Grade 2. Factory recommends Mobilux EP-2.
• The use of synthetic lubricants will increase lubrication intervals by approximately 3 times.
In addition to lubricating the bearings at specified intervals, set screws in the bearing collars should be checked for tightness. A bearing collar which has loosened will cause premature failure of the fan shaft. Fasteners attaching the bearings to the drive frame should also be checked.
Shaft bearings are the most critical moving part of a fan. Therefore, special attention should be given to keeping the bearings clean and well lubricated. Proper lubrication provides for reduction in friction and wear, transmission and dissipation of heat, extended bearing life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper grease applied at regular intervals is required. See the recommended bearing lubrication schedule below.
If unusual conditions exist - temperatures below 32°F or above 200°F, moisture or contaminants - more frequent lubrication is required.
Recommended Bearing Lubrication Schedule
Relubrication Schedule in Months
Standard Grease
Fan
RPM
To 250 12 12 12 12 12
500 12 12 11 10 8
750 12 9 8 7 6 1000 12 7 6 5 4 1250 12 6 5 4 3 1500 12 5 4 3 2 2000 12 3 3 2 1 2500 12 2 2 1 0.5 3000 12 2 1 0.5 0.25 3500 12 1 0.5 0.25 x 4000 12 0.5 0.25 x x 5000 12 0.25 x x x
Number
of Shots
1
2
-1
4 8 8 10 16
Bearing Bore, inches
1
1
8
- 1
1
2
15⁄8
- 1
7
8
115⁄16
- 2
3
27⁄16
16
- 3
Motor Maintenance (Belt & Direct Drive)
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to exterior surfaces only. Removing dust and grease buildup on the motor housing assures proper motor cooling. Use caution and do not allow water or solvents to enter the motor or bearings. Under no circumstances should motors or bearings be sprayed with steam, water or solvents.
Many fractional horsepower motors are permanently lubricated for life and require no further lubrication. Motors supplied with grease fittings should be greased in accordance with the manufacturer’s recommendations.
Wheel and Fastener Maintenance
Wheels require very little attention when exhausting clean air, however, air heavily laden with grease or dirt will tend to accumulate on the wheel causing unbalance. Wheels exhausting dirty or grease-laden air require frequent cleaning to assure smooth and safe operation.
All fasteners, including set screws in the bearing collars, should be checked for tightness each time maintenance checks are performed.
A proper maintenance program will help preserve the performance and reliability designed into the fan.
Centrifugal Utility Fans
6
®
Parts List
1
4
6
12
7
5
8
2
3
9
10
Always provide the unit model and serial number when requesting parts or information.
Replacement Parts
1. Scroll housing
2. Drive frame - base angle
3. Intake support panel
4. Inlet ring and cone
5. Wheel (specify rotation)
®
11
6. Drive frame assembly
7. Pillow block bearings
8. Fan shaft
9. Shaft pulley
10. Belt
12
13
11. Motor pulley
12. Belt tensioning bolts
13. Motor plate
14. Motor
Centrifugal Utility Fans
14
7
Troubleshooting
Problem Cause Corrective Action
Wheel Rubbing Inlet
V-Belt Drive
Excessive Noise
Bearings
Wheel Unbalance
Fan Check wheel for correct rotation. Increase fan speed.*
Low CFM
Duct System See page 4.
Fan Resize ductwork. Access door, filters, grills not installed.
High CFM
Duct System
Static Pressure Wrong
Duct system has more or less restriction than anticipated
Fan Check rotation of wheel. Reduce fan speed.
High Horsepower
Duct System
Electrical Supply
Fan Doesn’t Operate
Drive Check for broken belts. Tighten loose pulleys.
Motor
Lubrication Check for excessive or insufficient grease in the bearing.
Overheated Bearing
Mechanical
NOTE: Always provide the unit model and serial numbers when requesting parts or service information. * Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor
and result in burnout.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Tighten sheaves on motor/fan shaft. Adjust belt tension. Align sheaves properly (see page 4). Replace worn belts or sheaves.
Replace defective bearing(s). Lubricate bearings. Tighten collars & fasteners.
Clean all dirt off wheel. Check wheel balance, rebalance in place if necessary.
Change obstructions in system. Use correction factor to adjust for temperature/altitude. Resize ductwork. Clean filters/coils. Change fan speed.*
Check rotation of wheel. Adjust fan speed.
Resize ductwork. Check proper operation of face and bypass dampers. Check filters and access doors.
Check fuses/circuit breakers. Check for switches off. Check for correct supply voltage.
Assure motor is correct horsepower and not tripping overload protector.
Replace damaged bearing. Relieve excessive belt tension. Align bearings. Check for bent shaft.
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Greenheck Centrifugal Utility Fan catalog provides additional information describing the equipment, fan performance, available accessories, and specification data.
®
Phone:(715)359-6171•Fax:(715)355-2399•E-mail:gfcinfo@greenheck.com•Website: www.greenheck.com
455308 • SWB / SFB / SFD, Rev. 6, June 2011 Copyright 2011 © Greenheck Fan Corporation
8
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
Loading...