Model SMD-203 is a leakage rated smoke damper with 3V style
blades. The SMD-203 has been qualified to 2,000 fpm (10.2 m/s) and
4 in. wg (1 kPa) for operational closure in emergency smoke control
situations. Model SMD-203 may be installed vertically (with blades
running horizontally) or horizontally and is rated for airflow and leakage
in either direction.
Ratings
Leakage: UL 555S leakage class III
Pressure:4 in. wg (1 kPa) - differential pressure
Consult factory for sizes available in
6 in. wg (1.5 kPa)
Velocity:Operational rated to 2000 fpm
(10.2 m/s). Rating is for airflow in
either direction through damper.
Temperature: 350°F (177°C) depending on the actuator
Standard Construction
Frame:5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. 432mm) high to maximize
free area and performance.
Blades:16 ga. (1.5mm) galvanized steel,
reinforced with 3 longitudinal
structurally designed vee’s.
Seals:Flexible stainless steel jamb seals.
Linkage:Concealed in jamb.
Axles:
Bearings:Bronze sleeve type
1
⁄2 in. (13mm) dia. plated steel
Model SMD-203
Smoke Dampers
Steel 3V Blades
UL 555S Leakage Class III
Model SMD-203 meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:104)
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555S (Listing #R13317)
Greenheck Fan Corporation certies that the
model SMD-203 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certied Ratings
Programs. The AMCA Certied Ratings Seal
applies to air performance ratings only.
Size Limitations
Minimum Size:
(203mm W x 152mm H)
Maximum Size:Single Section - 32 in. W x 50 in. H
(813mm W x 1270mm H)
36 in. W x 48 in. H
(914mm W x 1219mm H)
Multiple Section - 144 in. W x 100 in. H
(3658mm W x 2540mm H)
288 in. W x 50 in. H
(7315 mm W x 1270mm H)
8 in. W x 6 in. H
Optional Features
• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Smoke detectors
• Sealed transition and sleeves
• Fail open
LH
RH
* W&H dimensions furnished approximately 1/4 in. (6mm) undersize.
Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
Pressure Drop Data SMD-203
5D6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three congurations shown. All
data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC
system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This conguration has the lowest pressure drop of the three test congurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This conguration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This conguration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.
model SMD-203 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certied Ratings
Programs. The AMCA Certied Ratings Seal
model SMD-203 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certied Ratings
Programs. The AMCA Certied Ratings Seal
model SMD-203 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certied Ratings
Programs. The AMCA Certied Ratings Seal
applies to air performance ratings only.
Application Data
5 3 / 8 in.
5 in.
Right hand drive is show n
Left hand drive available upon re quest
LH RH
A
Sleeve Length
V aries
6 in.
3 3 /
4
1 1 / 2 in.
max.
in.
5 3 /
8
in.
5 in.
Right hand drive is show n
Left hand drive available upon request
LH RH
A
Sleeve Length
V aries
6 in.
3 3 / 4
1 1 / 2 in. max.
B*
S
T*
in.
Damper Sleeve Dimensional Data
The drawings below and corresponding table show the position of the SMD-203 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.
in. (mm)
"A" Dimension
StandardMaximum
All Dampers*7 3/16 in. (183)12 (305)
When Height is
12 (305)12 (305)
11 in. (279) or less
with OCI
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed
within the wall.
Actuators and Accessories Space
Envelopes
Externally mounted actuators always require space outside of the damper sleeve. The “S” dimension illustrates
the clearance required for various available actuators.
On dampers less than 18 in. (457mm) high, actuators may
also require clearances above and/or below the sleeve.
“B” and “T” dimensions are worst case clearance requirements for some dampers less than 18 in. (457mm) high.
All damper sizes under 18 in. (457mm) high do not require
these worst case clearances. If space availability above
or below the damper sleeve is limited, each damper size
should be individually evaluated.
Actuator
Type/Model
ML4XXX Series Honeywell5 1/4 in. (133mm)3/4 in. (19mm)6 in. (152mm)
B*T*S
With OCIWith OCI
120 Volt AC
MS4XXX Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
MS4120 Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
24 Volt AC
ML8XXX Series Honeywell5 1/4 in. (133mm)3/4 in. (19mm)6 in. (152mm)
MS8XXX Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
MS8120 Series Honeywell6 in. (152mm)3/8 in. (10mm)6 in. (152mm)
Pneumatic (psi)
331-4551 Siemens1 in. (25mm)6 1/4 in. (159mm)6 1/2 in. (165mm)
331-2976 Siemens2 3/8 in. (60mm)12 1/8 in. (308mm)9 1/4 in. (235mm)
MK2-7121 Invensys3 3/4 in. (95mm)16 1/2 in. (419mm)10 in. (254mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
50 in.
32 in. (813mm)
50 in.
32 in. (813mm)
64 in. (1626mm)
50 in.
96 in. (2435mm)
(1270mm)
(1270mm)
32 in. (813mm)
(1270mm)
Damper Sizing Information
D* +
2 in. (51mm) +T
s
D*
TYPE R
16 in. (406mm)
Min.
2 1 / 8 in.
D* + 2 in. (51mm)+T
s
TYPE O
W
*
H*
W*
+ 2 in. (51mm)+T
s
H* + 2 in. (51mm)+T
s
W*
H*
TYPE C
H* + 2 in. (51mm)+T
s
(54mm)
16 in. (406mm)
Min.
2 1 /8 in.
(54mm)
16 in. (406mm)
Min.
W* + 2 in. (51mm)+T
s
(54mm)
2 1 / 8 in.
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.
The following gures show maximum damper section size and assembly congurations for multi-section dampers.
Double Section
Single Section
Transitioned Damper
Dimensions
When a re/smoke damper is being used in conjunction with round or oval ductwork, the
SMD-203 can be supplied in a factory sleeve with round or oval transitions on both ends
of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show
overall damper size.
These dimensions are furnished approximately 1/4 in. (6mm) undersize, except round and oval dimensions which are approximately 1/8 in. (3mm) undersize.
*
Ts = (2)(Sleeve Thickness)
Specifications
Smoke Dampers meeting the following specications shall be furnished and installed where shown on plans and/or as described in
schedules. Dampers shall meet the requirements of NFPA 92A, 92B,
101 & 105 and further shall be tested, rated and labeled in accordance with the latest edition of UL Standards 555S. Dampers shall
have a low leakage design qualied to UL555S Leakage Class III.
Each damper /actuator combination shall have a UL555S elevated
temperature rating of 250°F (121°C) minimum and shall be operational at maximum design air flow at its installed location. Each
damper shall be supplied with an appropriate actuator installed by
the damper manufacturer at the time of damper fabrication. Damper
actuator shall be (specier select one of the following) electric type
for 120 (24 or 230) Volt operation or pneumatic type for 25 psi minimum (30 psi maximum) operation.
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with
three longitudinal grooves for reinforcement. Damper frame shall
be galvanized steel formed into a structural hat channel shape with
reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a tighter seal
against leakage as pressure on either side of the damper increases.
Jamb seals shall be stainless steel compression type. Blades shall be
completely symmetrical relative to their axle pivot point, presenting
identical resistance to airflow in either direction or pressure on either
side of the damper.
The Damper Manufacturer's submittal data shall certify all air performance pressure drop data is licensed in accordance with the AMCA
Certied Ratings Program for Test Figures 5.2, 5.3, and 5.5. Damper
air performance data shall be developed in accordance with the latest edition of AMCA Standard 500-D. Dampers shall be labeled with
the AMCA Air Performance Seal.
Damper must be rated for mounting vertically (with blades running
horizontal) or horizontally and be UL 555S rated for leakage and
airflow in either direction through the damper.