Model SEFSD-211
Application
Model SEFSD-211 is a severe environment 316SS combination
fire smoke damper with 3V style blades. The SEFSD-211 has
been qualified to 2000 fpm (10.2 m/s) and 4 in. wg (1.0 kPa) for
operation and dynamic closure in emergency fire smoke situations.
Model SEFSD-211 may be installed vertically (with blades running
horizontal) or horizontally and is rated for airflow and leakage in
either direction.
Combination FIRE SMOKE DAMPERS
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 1
Dynamic Closure Rating: Actual ratings are size dependant
Maximum Velocity: 2000 fpm (10.2 m/s)
Maximum Pressure: 4 in. wg (1.0 kPa)
UL 555S Leakage Rating
Leakage Class: I
Operational Rating: Actual ratings are actuator
dependant
Maximum Velocity: 2000 fpm (10.2 m/s)
Maximum Pressure: 4 in. wg (1.0 kPa)
Maximum Temperature: 350ºF (177°C) —Depending on
actuator
1
⁄2 Hours
Standard Construction
Frame: 5 in. x 1 in.(127mm x 25mm) 16 ga.
(1.5mm) 316 stainless steel hat
channel with reinforced corners . A
low profile head and sill are used on
sizes less than 17 in. (432mm) high
to maximize free area and
performance.
Blades: 16 ga. (1.5mm) 316 stainless steel,
reinforced with 3 longitudinal
structurally designed vee’s.
Seals: Extruded silicone rubber blade
seals. Flexible 316 stainless steel
jamb seals.
Linkage: 316 stainless steel, concealed in
jamb.
Axles: 1/2 in. (13mm) diameter 316
stainless steel.
Bearings: 316 stainless steel sleeve type.
Closure Device: 165º F (74ºC) RRL
316 Stainless Steel 3V Blades
UL 555S Leakage Class I
UL555 11⁄2 Hour Fire Resistance Rating
Model SEFSD-211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B 101 & 105
ICBO Uniform Building Codes
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshall
Listing #: 3225-0981:103 (fire)
Listing #: 3230-0981:104 (smoke)
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 &555S (Listing #R13317)
Greenheck Fan Corporation certifies that the model
SEFSD-211 shown herein is licensed to bear the
AMCA Seal. The ratings shown are based on tests
and procedures performed in accordance with
AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air performance ratings only.
Size Limitations
Minimum Size:
Maximum Size:
Single Section: 24 in. W x 30 in. H
(Horizontal or Vertical Mount)
(610mm W x 762mm H) or
22 in. W x 36 in. H (Vertical Mount)
(559mm x 914mm)
Multiple Section: 48 in. W x 30 in. H
(Horizontal or Vertical Mount)
(1219mm W x 762mm H) or
88 in. W x 72 in. H (Vertical Mount)
2235mm x 1829mm)
Optional Features
•OCI(Openclosedindicationswitches)-not316SS
•165ºF(74°C),212ºF(100°C),and350ºF(177°C)RRLavailable-
thermal device not 316SS.
•TOR(remoteoverrideof165ºF[74°C]closureallowsdamperto
perform smoke management functions during a fire emergency)
-not 316SS.
•Electricorpneumaticactuatorstoaccomplishsmokemanagement
and system functions.
8 in. W x 6 in. H
(203mm W x 152mm H)
RH
LH
* W & H dimensions furnished approximately 1/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
Pressure Drop Data SEFSD-211
5D 6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All
data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC
system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high
entrance and exit losses due to the sudden changes of area in the system.
3
(1.201 kg/m3).
AMCA 5.2 Pressure Drop SEFSD-211
5D 6D
5D
D
=
4 (W) (H )
3.14
Figure 5.3
Figure 5.2
500 0.04 500 0.02 500 0.01 5000.01
1000 0.14 10000.07 10000.04 1000 0.06
15000.31 15000.16 15000.09 1500 0.13
2000 0.55 20000.29 20000.1620000.23
2500 0.86 25000.45 25000.2525000.36
30001.24 30000.65 30000.3630000.52
3500 1.69 3500 0.89 3500 0.49 3500 0.70
4000 2.20 4000 1.16 4000 0.64 4000 0.92
12 in. x 12 in. (305mm x 305mm)
24 in. x 24 in. (610mm x 610mm)
36 in. x 36 in. (914mm x 914mm)
12 in. x 48 in. (305mm x 1219mm)
5000.03
1000 0.10
1500 0.23
2000 0.41
2500 0.63
3000 0.91
3500 1.24
48 in. x 12 in. (1219mm x 305mm)
Greenheck Fan Corporation certifies that the model
SEFSD-211 shown herein is licensed to bear the
AMCA Seal. The ratings shown are based on tests
and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements
of the AMCA Certified Ratings Programs. The AMCA
Certified Ratings Seal applies to air performance
ratings only.