Greenheck Fan RDU, RBUMO, RBU User Manual

1
Greenheck Model RBU, RBUMO and RDU fans are thoroughly inspected and test run at the factory, however damage may occur during handling and shipping. Consequently, it is important that the unit be carefully inspected for visible and concealed damage before beginning installation. Report any damage to the shipper immediately. In addition, assure all accessory items are accounted for.
INSTALLATION
LIFTING
fan by the motor, belt tube, damper frame, windband or accessories.
Carefully lift the fan to the roof curb and install fasteners in all holes provided in the unit base. The windband does not need to be removed for the lifting operation.
SERVICE ACCESS
MOTOR OUT OF AIRSTREAM
Model RBUMO simplifies inspection and servicing with the “motor out of the airstream” design. A removable motor cover enables quick and easy access to the motor, belt, and drives from the roof deck (Fig. 2).
Servicing of propeller and bearings can easily be accomplished by removing the fan panel/windband assembly from the fan base.
REMOVABLE WINDBAND
By removing the bolts from the four windband mounting brackets, the windband can be removed. With the windband removed, access to the fan can be gained through the butterfly dampers. This service feature applies to models RBU, RBUMO and RDU (Fig. 1).
Lifting Lug
Fig. 2
Fig. 1
GREENHECK
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171
www.greenheck.com
®
READ AND SAVE THESE INSTRUCTIONS
Models RBU/RBUMO/RDU Upblast Propeller Roof Fans Belt Drive and Direct Drive
PN 455700
Installation, Operation and Maintenance Manual
2
ELECTRICAL CONNECTIONS
Before electrical connections are made, the supply voltage, phase and ampere capacity must be checked for compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to local and national electrical codes.
The supply wires are then connected to an optional safety disconnect switch (if supplied) or wired directly to the motor.
For belt drive units in Emergency Smoke Removal installations, the electrical supply must be kept out of the airstream. They may also require an isolated power supply so that if power is cut to the building in the event of a fire, the fan will continue to operate. Check the local and national electrical codes for emergency smoke removal fans.
** WARNING **
Disconnect and secure to the “off” position all electrical power to the fan prior to inspection or service.
Caution must be used when working around the fusible link damper lifters. They may release the dampers unexpectedly.
Models RBU, RBUMO and RDU may have fusible link damper lifters and all models RBUMO with high temperature options have fusible link damper lifters under spring tension. RBUMO fans UL listed as “Power ventilators for smoke control systems” in sizes 42, 48, 54 and 60 have extra heavy duty fusible link damper lifters under high spring tension that, for safety reasons, must be pinned to prevent accidental release. See Fig. 3 below for details on how to secure the lifter arms.
FAILURE TO COMPLY WITH THESE SAFETY PRECAUTIONS MAY
RESULT IN SERIOUS INJURY OR DEATH!
WARNING! These fans have extra heavy duty fusible link damper lifters under very high spring tension that must be pinned so they can not be accidentally tripped when servicing the fan. The
fusible link damper lifters are located under the butterfly damper blades. Fig. A, shows where the safety pin MUST be placed when the fan is being serviced. Fig. B, shows where the safety pin is placed for storage when the fan is in service. Fan sizes 20, 24, 30 and 36 also have fusible link damper lifters, but they do not have the ability to be pinned when servicing due to differences in lifter designs. In either
case, extreme care must be taken when working around the damper lifter assemblies or serious bodily injury or death may result.
For Models RBUMO with high temperature option - UL Listed
Models RBUMO with High Temperature Option - UL Listed will bear the label shown at right. For fan sizes 42, 48, 54 and 60 Figs. A and B apply.
Safety Pin Storage Locations
Safety pins installed
to prevent closure while servicing fan
Fig. A
Fig. B
Fig. 3
Electrical - This equipment must be installed with remote overload protection having adequate rating as to voltage, frequency, horsepower and full load current per phase. Where connected to a circuit protected by fuses, use time delay fuses. For supply connection use wires rated for at least 90°C (194°F)
Installation - When connecting electrical power to this fan, do not restrict motor movement. Motor must have sufficient movement for possible future belt or wheel adjustment.
IMPORTANT
00453547
U
L
R
C
VENTILATOR FOR SMOKE CONTROL SYSTEMS. 76Y9
US LISTED