Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Models: PVe-20
PVe-35
PVe-45
PVe-55
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components
may be hot enough to cause pain or injury. Allow
time for cooling before servicing.
CAUTION
Precaution should be taken in explosive
atmospheres.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
Model PVe Heat Recovery Unit
1
Receiving
Upon receiving the product, check to make sure
all items are accounted for by referencing the bill
of lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of
the bill of lading which is countersigned by the
delivering carrier. A Carrier Inspection Report should
be filled out by the carrier upon arrival and the Traffic
Department. If damaged upon arrival, file claim
with carrier. Any physical damage to the unit after
acceptance is not the responsibility of Greenheck Fan
Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Machined parts coated with rust preventive should
be restored to good condition promptly if signs of
rust occur. Immediately remove the original rust
preventive coating with petroleum solvent and clean
with lint-free cloths. Polish any remaining rust from
surface with crocus cloth or fine emery paper and oil.
Do not destroy the continuity of the surfaces. Wipe
clean thoroughly with Tectyl® 506 (Ashland Inc.) or
the equivalent. For hard to reach internal surfaces or
for occasional use, consider using Tectyl® 511M Rust
Preventive or WD-40® or the equivalent.
Handling
Units are to be rigged and moved by the provided
lifting points or fork lifting points (see page 4). Handle
each piece in such a way as to keep from scratching
or chipping the coating. Damaged finish may reduce
ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the unit and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
Inspection and Maintenance during
Storage
While in storage, inspect units once per month. Keep
a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate all moving components by hand
ten to fifteen revolutions to distribute lubricant on
motor and bearings. If paint deterioration begins,
consideration should be given to touch-up or
repainting. Units with special coatings may require
special techniques for touch-up or repair.
Model PVe Heat Recovery Unit
2
Table of Contents
PlateHeat
Exchanger
EXHAUST AIR
Exhaust
Fan
OUTDOOR
AIR
Basic Operation
Basic Operation . . . . . . . . . . . . . . 3
Installation
Supplemental Installation, Operation and
Maintenance Manuals . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . 3
Installation Stages . . . . . . . . . . . . . 4
Lifting with a Crane or Forklift . . . . . . . . 4
Roof Curb and Rail Mounting
Recommended Roof Opening . . . . . . . . 4
Service Clearances . . . . . . . . . . . . 5
Roof Curb Mounting . . . . . . . . . . . . 6
Curb Dimensions and Weights . . . . . . . . 6
Ductwork Connections . . . . . . . . . . . 6
Rail Mounting / Layout . . . . . . . . . . . 7
Access Panel Description and Location . . . 7
Dimensional Data . . . . . . . . . . . . . 8
Drain Trap . . . . . . . . . . . . . . . 8
Electrical Information
General Electrical Information . . . . . . . . 9
Control Center Components . . . . . . . . . 10
Electric Heater Application/Operation . . . . . 10
Optional Accessories
Frost Control Application/Operation . . . . . 11
Economizer Application/Operation . . . . . . 11
Variable Frequency Drives and Wiring . . . . 12-13
Typical Wiring Diagram . . . . . . . . . . . 14
Sensors and Lights . . . . . . . . . . . . 15
Remote Control Panel and Wiring . . . . . . 16
Sensors Mounted by Factory . . . . . . . . 17
Sequence of Operation
Start-Up
General Start-Up Information . . . . . . . . 18
Optional Accessories . . . . . . . . . . . 19
Unit Start-Up, Fans . . . . . . . . . . 20-21
Routine Maintenance Checklist
Overview. . . . . . . . . . . . . . . . . 22
General . . . . . . . . . . . . . . . . . 23
Fan Belts. . . . . . . . . . . . . . . . . 23
Fan Motors . . . . . . . . . . . . . . . . 23
Fan Wheel and Fasteners . . . . . . . . . . 24
Fan Bearings . . . . . . . . . . . . . . . 24
Filters . . . . . . . . . . . . . . . . . . 24
Door Seal Maintenance . . . . . . . . . . . 24
Parts List . . . . . . . . . . . . . . . . . 25
Sequence of Operation . . . . . . . . . . . 25
Troubleshooting – Airflow . . . . . . . . . . 26
Troubleshooting – Unit . . . . . . . . . .27-28
Maintenance Log . . . . . . . . . . . 29-31
Warranty . . . . . . . . . . . . . Backcover
The PVe brings in fresh outdoor air and removes stale
exhaust air from the building. Prior to discharging
the exhaust air, the plate heat exchanger transfers
energy from the exhaust air to the incoming outdoor
air. When used in the cooling mode, heat energy is
transferred from incoming outdoor air to the exhaust
air. Simply put, this unit preconditions the outdoor air
to save money on heating and cooling costs.
SIDE VIEW
RETURN DUCT
SUPPLY DUCT
Supplemental Installation,
Operation and Maintenance
Manuals
Refer to the following Installation, Operation and
Maintenance Manuals for additional details:
Part #462844 — Exhaust Weatherhood
Additional manuals are available for each accessory
used in the PVe. These additional manuals are
provided by the respective manufacturers and are
included with unit shipment.
Installation
The system design and installation should follow
accepted industry practice, such as described in the
ASHRAE Handbook.
Adequate space should be left around the unit for
filter replacement and maintenance. Sufficient space
should be provided on the side of the unit for routine
service and component removal should that become
necessary.
See Service Clearances and Access Panel Description
sections for more details.
WARNING
All factory provided hoisting and fork lifting points
must be used when lifting the unit. When rigging for
hoisting with a crane, spreader bars must be used.
Failure to comply with this safety precaution could
result in property damage, serious injury or death.
See Installation Stages for additional details.
Model PVe Heat Recovery Unit
3
Installation Stages
Once the PVe Heat Recovery Ventilator is delivered
to the jobsite, the actual installation occurs in several
distinct stages.
1. Installation location must be carefully considered.
Service clearances needed for later maintenance
of the unit must be taken into consideration,
access to Return Air and Discharge Air ducting
must be anticipated. And structural support
of the unit must be taken into consideration.
See appropriate sections of this manual for
further information. If electric wiring is going
to be brought into the cabinet from beneath
(recommended), preparations for that step must
be taken during the planning stage. If possible, a
GKD curb should be installed prior to installation
of roofing materials so that flashing can be run up
the sides of the curb.
2. Hoisting the cabinet can be accomplished with
either a crane or a fork lift. If a forklift is used, the
forks must extend all the way through the cabinet
and project from the far side. The forks should
be padded with a layer of ¼-inch thick plywood
or other suitable material. If a forklift is used, the
cabinet cannot be lowered directly onto the GKD
curb unit because the forks will be in the way. It
will be necessary to set the unit onto appropriate
dunnage for final lowering after the forks are
removed.
If a crane is used, hoisting points are provided at
each corner of the cabinet. Small, padded hooks
must be inserted into the hoisting points. There
is very little internal clearance inside the cabinet
base and the use of large lifting hooks will either
dig into the cabinet structure or else interfere with
the seating of the cabinet on the GKD curb.
2. Physical installation of the unit should be
completed prior to installation of electrical wiring.
Condensate drains should be connected and if
necessary, heat strips installed on the drains to
prevent freezing of the traps. A final check should
be made to ensure that the unit has been installed
level by using the bottom of the cabinet as a
reference, not the top (the cabinet roof is sloped
to the rear). Ensure that all ductwork has been
properly and permanently assembled.
3. Prior to wiring the unit, installer should verify that
all optional accessories are accounted for. Verify
that electric components such as motors are rated
properly for the voltage actually being used. Note
that some of the illustrations and pictures used in
this manual show the use of three phase power
and if the user actually has single phase power,
there will be minor variations present. The unit
should be wired according to the supplied wiring
diagrams and Best Practices. Careful testing
and balancing of the power source should be
accomplished at this time.
Model PVe Heat Recovery Unit
4
Lifting
Forklift lifting
points
Crane hoisting points
(typical)
Lifting with a Crane
1. Before lifting, be sure that all shipping material
has been removed from unit.
2. To assist in determining rigging requirements,
weights are shown below.
3. Unit must be lifted by simultaneously hoisting
at all four corner lifting points provided on base
structure, ensuring proper load distribution and
support at each corner.
4. Rigger to use suitable mating hardware to attach
to unit corner lifting points.
5. Spreader bar(s) must
span the unit to
prevent damage to
the cabinet by the lift
cables.
6. Always test-lift the
unit to check for
proper balance
and rigging before
hoisting to desired
location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting the unit and setting on
the curb.
The weights shown are a
worst case scenario based
on the sheet metal and
component weights for
the unit. These weights
include sheet metal weights
added together with the
largest motors, blowers and
accessories for the units.
Unit Weights (lbs.)
Model
PVe-201300
PVe-351600
PVe-452100
PVe-552700
Approx.
Weight
Lifting with a Forklift
Unit base rail includes forklift lifting locations. Use
weights shown to determine forklift size requirements.
Roof Curb and Rail Mounting
CLEARANCE
B
C
A
D
When installed on a roof, a typical installation
will include at least one roof penetration in order
to deliver return air to the unit from the space.
Additionally, a second roof penetration may be used
for supply air discharge to the space.
Service Clearances
C
B
CLEARANCE
Intake and Discharge Options
OptionBottomTopSide End
OA IntakeX
SA DischargeXX
RA IntakeX
EA DischargeX
OA - Outdoor Air
SA - Supply Air (to the space)
RA - Return Air (from the space)
EA - Exhaust Air
SA Discharge
OA Intake
CLEARANCE
D
D
B
A
C
EA Discharge
SA Discharge
D
ModelABCD
PVe-20
PVe-35
PVe-45
PVe-55
All dimensions are shown in inches (millimeters). The
weatherhoods include 2-inch aluminum mesh filters that
are removed out of the end of the hood as shown in this
drawing and require extra clearance for removal.
36
(920)
48
(1220)
60
(1530)
72
(1830)
36
(920)
36
(920)
36
(920)
36
(920)
A
36
(920)
36
(920)
36
(920)
36
(920)
60
(1530)
60
(1530)
60
(1530)
60
(1530)
E
RA Intake
F
Duct Dimensions
ModelABCDEF
PVe-20
PVe-35
PVe-45
PVe-55
All dimensions are shown in inches (millimeters).
10.7
(280)
11.9
(310)
14.1
(360)
16.4
(420)
Position the unit roof opening such that the Return Air
Intake will line up with the corresponding ductwork.
If applicable, adjust position to also accommodate
the SA Discharge vent. Make certain that proposed
positioning of the unit still maintains recommended
service clearances.
12.2
(310)
13.7
(350)
16.0
(410)
19.2
(490)
10.3
(270)
11.4
(290)
13.3
(340)
15.9
(450)
11.8
(300)
13.1
(340)
14.5
(370)
18.6
(480)
22.0
(570)
34.0
(870)
46.0
(1170)
60.0
(1530)
14.0
(360)
14.0
(360)
14.0
(360)
14.0
(360)
Do not face the Outdoor Air Intake of the unit into
prevailing wind and also keep the air intake away
from any other exhaust fans. Likewise, position the
Exhaust Air Discharge opening away from any other
outdoor air intakes of other equipment.
When cutting duct openings, cut opening one inch
larger (25 mm) than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof
is constructed of combustible materials, area within
the roof curb must be ventilated, left open or covered
with non-combustible material which has an “R” value
of at least five (5). If area within curb is left open,
higher radiated sound levels may result.
Where the supply or warm air duct passes through
a combustible roof, a clearance of one inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.
Model PVe Heat Recovery Unit
5
Roof Curb Mounting
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Turning
Vanes
Roof curb assembly and mounting instructions are
contained in the Roof Curb Assembly Instructions
supplied with Model GKD roof curb.
Rooftop PVe units require curbs to be mounted first,
in accordance with their appropriate instructions.
Curb unit is to be installed and then duct connections
are to be made prior to setting of the unit.
1. Factory Supplied Roof Curbs: Roof curbs are
Model GKD. The GKD ships in a knockdown kit
(which includes duct adapter) and requires field
assembly by others. Assembly instructions are
included with the GKD curbs.
2. Install Curb: Locate the assembled curb over
roof opening and verify precise location of curb
relative to the roof opening, in accordance with
dimensions given previously. Fasten curb loosely
in place and then shim as needed to ensure a
level installation. Tighten roof fastening hardware
and then re-check for level. Verify that diagonal
dimensions of installed curb are plus or minus
1/8-inch of each other.
3. Install Ductwork: Install needed ductwork in
accordance with SMACNA and AMCA guidelines.
Duct adapter is provided to support ducts prior
to setting the unit.
4. Install Insulation: One-inch deep insulation
pans are provided with the curb assembly. Set
the insulation pans per instructions and then
install insulation in the pans prior to setting
the unit. Insulation is not provided by the unit
manufacturer, it is to be supplied by others.
5. Set the PVe Unit: Lift unit to a point directly
above the curb and duct openings. Guide unit
carefully while lowering in order to align with duct
openings. The roof curb will seat in a recess in
the base of the PVe unit. Verify that the unit is
properly seated on the curb and is level.
Unit Side
1.895
Unit Base
Curb Dimensions and Weights
L
W
Unit SizeLW
PVe-2099.436.8195
PVe-3599.444.6216
PVe-45105.956.3261
PVe-55111.771.3316
All dimensions are shown in inches.
Ductwork Connections
Examples of poor and good fan-toduct connections are
shown below. Airflow
out of the fan should
be directed straight or
curve the same direction
as the fan wheel rotates.
Poor duct
installation will
result in low
airflow and other
system effects.
n
o
i
t
a
t
o
R
Length of Straight Duct
GOOD
Curb Weight
(lbs.)
4.844
1.549
Curb Cap Details for Factory Supplied Roof Curbs
Model PVe Heat Recovery Unit
6
Roof Curb
0.775
Dimensions are shown in inches.
Insulation Pan
Recommended Discharge Duct Size and Length
Unit Size Blower Size Duct Size Straight Duct Length
PVe-20914 x 1436
PVe-351020 x 2036
PVe-451220 x 2036
PVe-551528 x 2860
All dimensions are shown in inches.
• Recommended duct sizes are based on velocities across the
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project.
Refer to plans for appropriate job specific duct size and/or
velocity limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
Rail Mounting / Layout
D
C
AB
An alternative method of unit installation is to mount
the unit on rails supplied by others. The purpose of
mounting the unit on either rails or the GKD curb is to
elevate the unit away from moisture conditions and
to provide proper clearance for installation of water
drain traps.
• Rails should be designed to handle the weight of
the PVe unit, taking into consideration weight per
square inch on bearing surfaces. Rails should be
positioned as shown in the drawing below, taking
into consideration proper load distribution and
support by roof support elements.
• Make sure that rail positioning does not interfere
with either the RA Intake duct or the optional
straight down SA Discharge duct.
• Rails should extend beyond the unit a minimum
of 12 inches.
• Set unit on rails.
Access Panel Description and
Location
5
3
2
1
Filters
1
2
Optional OA Damper
Optional RA Damper
Optional Face and Bypass Dampers
Plate Heat Exchanger
Optional Preheater
4
Isometric view of
PVe on rails
C
AB
Side view of
PVe on rails
Unit SizeA
PVe-2051413.257.75
PVe-3551412.006.50
PVe-4551415.5010.5
PVe-5551418.7513.25
All dimensions are shown in inches.
*Zones B and C identify regions/zones where rails may
not be place due to ductwork.
B*C*D
D
3
4
5
Plate Heat Exchanger
Control Center
Blowers
Model PVe Heat Recovery Unit
7
Dimensional DataDrain Trap
Filters
Filters
Face/Bypass Damper
Plate Heat
Exchanger
Outdoor Air Hood
B
AD
CLEARANCE
C
D
D
CLEARANCE
C
D
D
The PVe plate heat exchanger is provided with two
stainless steel drain pans and each is equipped with
a one inch MPT drain fitting. A drain trap must be
installed on each drain fitting to allow excess water
to flow out of the drain pans. More importantly,
though, due to the negative internal static pressure
inside the PVe cabinet, installing drain traps prevents
outdoor air from being pulled into the cabinet and
consequently causing overfilling of the drain pans or
misting of PVe components.
To ensure the drain trap works properly, the trap
height must account for the difference in static
pressure between ambient conditions outside the
unit and the negative static pressure inside the PVe
cabinet. An assumption of 3.0 in. wg differential is
normally sufficient for all PVe units and this would
require a trap design as shown. If the internal static is
believed to be higher, consult the factory.
Outdoor Air Hood
Outdoor
Air Hood
Bypass
Damper
Face
Filters
Damper
Filters
Face/Bypass Damper
Plate Heat
Exchanger
Top view
AD
Plate Heat
Exchanger
Exhaust
Air Hood
Control Center
E
C
B
Filters
Side view
Unit
Size
PVe-20
PVe-35
PVe-45
PVe-55
ABCDE
104.1
(2650)
104.1
(2650)
110.6
(2810)
116.5
(2959)
59.7
(1520)
59.7
(1520)
59.7
(1520)
59.7
(1520)
41.5
(1060)
49.2
(1250)
61.1
(1560)
76.1
(1940)
All dimensions are shown in inches (millimeters).
Door handles, hinges and other protrusions are not
included in the dimensions above. Dimensions are
rounded up to the nearest .1 inch (2.54 millimeters).
20.3
(520)
25.2
(640)
25.2
(640)
25.2
(640)
4 in.
Refer to local codes to determine drainage
2 in.
requirements. If draining onto a roof, place a drip pad
20.7
(530)
17.7
(450)
19.0
(490)
beneath the drain outlet to protect the roof. If draining
onto a roof is not acceptable, a drain line must be
attached to the drain trap. The drain line must be
pitched away from the unit at least 1/8-inch per foot.
On longer runs, an air break should be incorporated
to ensure proper drainage. Local codes may require
drainage into a waste water system.
Drainage problems result not only from improper
23.8
(610)
drain trap design, but also from lack of maintenance
in the PVe cabinet. Algae can form in the drain pans
and traps and cause reduced water flow, which can
in turn result in a backup in the drain system. Regular
maintenance and inspection will prevent this from
occurring. If the drains have a cleanout opening, be
sure and close the opening after cleaning and refill
the trap with water.
Model PVe Heat Recovery Unit
8
Electrical Information
The unit must be electrically grounded in accordance
with the current National Electrical Code, ANSI/
NFPA 70. In Canada, use current CSA Standard
C22.1, Canadian Electrical Code, Part 1. In addition,
the installer should be aware of and comply with
any local ordinances or electrical power company
requirements that might apply. System power wiring
must be properly fused and conform to the local and
national electrical codes. System power wiring is to
the main disconnect (door interlocking disconnect
switch standard on most units) or distribution block
and must be compatible with the ratings shown on
the nameplate: supply power voltage, phase, and
amperage (Minimum Circuit Amps - MCA, Maximum
Overcurrent Protection - MOP). All wiring beyond this
point has been done by the manufacturer and cannot
be modified without affecting the unit’s agency /
safety certification.
If field installing an additional disconnect switch, it
is recommended that there be at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and
size according to the rating plate.
If power supply is desired through the bottom of unit,
run the wiring through the curb, cut properly aligned
holes in the insulation pan and the bottom of the PVe
cabinet bottom and wire to the disconnect switch.
Seal penetrations to prevent leakage or air infiltration.
The electric supply to the unit must meet stringent
requirements for the system to operate properly.
Voltage supply and voltage imbalance between
phases should be within the following tolerances.
If the power is not within these voltage tolerances,
contact the power company prior to operating the
system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at
all line disconnect switches. Readings must fall within
the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive
voltage imbalance between the phases will cause
motors to overheat and eventually fail. Maximum
allowable imbalance is 2%. To determine voltage
imbalance, use recorded voltage measurements in
this formula.
Key:V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with wiring material having a temperature rating of
at least 105ºC.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
Most factory supplied electrical components are
pre-wired. To determine what electrical accessories
require additional field wiring, refer to the unit-specific
wiring diagram located on the inside of the unit
control center access door. The low voltage control
circuit is 24 VAC and control wiring should not exceed
0.75ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft.18
200 ft.16
300 ft.14
450 ft.12
Minimum
Wire Gauge
Control wires should not be run inside the same
conduit as that carrying the supply power. Make sure
that field supplied conduit does not interfere with
access panel operation.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit
control center and wired in place of the remote
switch (typically between terminal blocks R and G
on the terminal strip (refer to Typical Control Center
Components). The relay must be rated for at least
5 amps and have a 24 VAC coil. Failure to comply
with these guidelines may cause motor starters to
“chatter” or not pull in which can cause contactor
failures and/or motor failures.
Model PVe Heat Recovery Unit
9
Typical Control Center Components
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter
3. Motor Starter
4. Power Distribution Blocks
5. 24 VAC Control Transformer
6. 24 VAC Terminal Strip
7. Temperature Sensor with Override (used for
Economizer Mode)
8. Dirty Filter Sensor
9. Dirty Filter Sensor
1
4
5
6
7
Electric Heater Application/Operation
Factory installed electric heaters are optionally
provided in order to provide preheat frost control.
An electric preheater warms the outdoor air prior to
being drawn through the PVe plate heat exchanger.
Electric heaters are available in 208, 230, or 460 VAC.
Refer to heater nameplate for voltage rating.
Preheaters: If an optional preheater is supplied with
the unit, it is installed as a single stage on/off control.
Preheaters are single-point wired at the factory. A
thermocouple type
temperature sensor
is mounted in the
outdoor airstream
after the preheater and
that thermocouple will
switch the preheater
on. See Frost Control
Application/Operation
for typical set points.
If the temperature falls
below the set point
and a pressure drop
sensor is triggered, the
preheater will turn on.
23
98
Model PVe Heat Recovery Unit
10
Optional Accessories
Frost Control Application/Operation
Cold climates, in combination with higher indoor
humidity levels, may cause frost to form on the plate
heat exchanger. To protect against the formation of
frost, a temperature sensor is installed to measure
the temperature of the air leaving the plates in the
exhaust airstream. There are three different methods
of frost control that may optionally be used. These
options are installed, wired and pre-set at the factory.
To identify specific components, see the included
unit-specific schematic wiring diagram.
1. Timed Exhaust frost control The supply blower cycles on and off based on a
factory provided and installed timer. The timer is
located on the right hand side (low voltage side)
of the control module.
2. Plate heat exchanger bypass – Open/Closed When the exhaust air leaving the exchanger
(cube) drops below the adjustable set-point, both
the face and bypass dampers will allow air to
bypass the cube. This allows warm exhaust air
to melt any frost on the cube. Once the exhaust
air temperature rises above the set-point, the unit
returns to normal operation.
3. Electric preheat frost control An electric preheater can optionally be built into
the outdoor air intake. When the temperature
of the exhaust air leaving the plate unit (the
cube) drops below the adjustable set-point, the
preheater will switch on. Once the exhaust air
temperature increases, the preheater will switch
off.
Frost Threshold Temperatures
Indoor RH @ 70°FFrost Threshold Temp
20%-5º F
30%-5º F
40%-5º F
Timed exhaust frost control includes a timer in
addition to the thermostat and pressure sensor. The
timer is located on the right hand side of the control
module (low voltage side). When timed exhaust frost
control is initiated, the timer will turn the supply
blower on and off to allow the warm exhaust air
to defrost the cube. Default factory settings are
5minutes off and 30 minutes on.
Plate (cube) bypass. The plate bypass frost control
function is essentially the same as Economizer
mode (see below) except that it is initiated by
temperature sensors for the purpose of frost removal
or prevention.
Electric preheat frost control includes an electric
heater at the outdoor air intake, an airflow pressure
switch and a temperature sensor. See also Electric
Heater Application / Operation. When electric preheat
frost control is initiated, the electric preheater will
turn on and warm the incoming air to prevent frost
accumulation on the cube.
Economizer Application/Operation
Under certain conditions, the most efficient use of
the PVe Heat Recovery Ventilator includes bypassing
the incoming outdoor air around the plate heat
exchanger. When cooling air is being called for and
the outdoor air temperature is below a pre-set point,
the PVe will switch to Economizer Mode. Integral
face and bypass dampers will cycle into a bypass
condition, allowing incoming cool air to flow past
the cube, rather than flow through it. Economizer
Mode is strictly temperature initiated and dependent
on the Temperature Sensor with override located in
the control center. See component #7 on the Typical
Control Center Components illustration.
The typical temperature setting corresponds to the
indoor air relative humidity as shown in the Frost
Threshold Temperatures table and represents when
frost can occur. An increase in pressure drop would
indicate that frost is occurring. Both the pressure
sensor AND the outdoor air temperature sensor
must trigger in order to initiate frost control. The
two sensors together insure that frost control is
only initiated during a real frost condition. Field
wiring of a light (or other alarm) between 6 & C in
the control center will notify personnel when unit is
in frost control mode (refer to Remote Panel Wiring
schematics for wiring details). The following explains
the three options in more detail.
Model PVe Heat Recovery Unit
11
Variable Frequency Drives for Energy Recovery Blowers
Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided
for modulating or multispeed control of the blowers. One VFD is provided for each blower (supply air and
exhaust). The VFD’s provided are either Yaskawa model V1000 or J1000. Refer to the tables in this section for
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an
example wiring diagram has been provided in this manual for reference). When making adjustments outside of
the factory set points, refer to Yaskawa VFD instruction manual, which can be found online at www.drives.com.
For technical support, contact Yaskawa direct at 1-800-927-5292.
IGS-S+R-R+
MPACAMAC+VA2A1PCP2P1
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
MA MB MCACAMAC+VA1SCS5S4S3S2S1
V1000
OPTION 1 - 0-10 VDC CONTROL
USER TO PROVIDE ISOLATION AS REQUIRED
A1 AC
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
USER TO PROVIDE CONTACTS AND ISOLATION
AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER A1-01 CHANGE TO 2
PARAMETER d1-01 FOR NEW 60Hz SET TING
PARAMETER d1-02 FOR NEW 40Hz SET TING
PARAMETER d1-03 FOR NEW 30Hz SET TING
PARAMETER A1-01 CHANGE TO 0
0-10 VDC CONTROL SIGNAL (BY OTHERS)
WIRED TO A1 (+) AND AC (COMMON)
0 VDC=30 Hz
10 VDC=60 Hz
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4SC
NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 40 Hz.
S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.
J1000
Factory Set Points
Variable Frequency Drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:
Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30
and 60Hz
Multispeed: Digital contact closures by others
command the VFD to run at multiple speed settings:
• SC to S4 - Drive runs at 40Hz
• SC to S5 - Drive runs at 30Hz
CO2 Sensor: A digital contact closure from an
optional factory provided CO2 sensor sends the
VFD to high or low speed depending on CO2 ppm
levels at the sensor.
The terminal locations for Modulating (option 1) and
Multispeed (option 2) are shown on the left. Most
of the set points in the VFDs are Yaskawa factory
defaults. However, a few set points are changed at
Greenheck and are shown in the tables on the next
page. These settings are based on the VFD mode
selected.
To gain access to change set points on the V1000 and
J1000 drives, parameter A1-01 needs to be set at “2”.
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.
Drive Operation
SC to S1 contact for On/Off
A1 (0-10 VDC) referenced to AC. Can use +15 VDC
from +V
Model PVe Heat Recovery Unit
12
Factory Set Points - continued
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”.
Then go to A1-03 and change it to “1110” and press
enter. The drive is now reset back to the settings
programmed at Greenheck. This option is not
available on the J1000.
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
A1-01Access Level22
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec.30 sec.
C6-02Carrier Frequency11
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H3-04Terminal A1 Bias50%50%
A1-01Access Level00
Setting
V1000J1000
Motor
FLA
Motor
FLA
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C02 DROPS BELOW 700 PPM)
(FULL SPEED WHEN C02 RISES ABOVE 800 PPM)
Parameter
A1-01Access Level22
b1-01Reference Source (Frequency)00
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec.30 sec.
C6-02Carrier Frequency11
d1-01Frequency Reference 160 Hz30 Hz
d1-02Frequency Reference 230 Hz60 Hz
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H3-10A2 Not UsedFNA
A1-01Access Level00
Setting
V1000J1000
Motor
FLA
Motor
FLA
MULTISPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
A1-01Access Level22
b1-01Reference Source (Frequency)00
b1-17VFD Start-Up Setting11
C1-01Acceleration Time30 sec.30 sec.
C1-02Deceleration Time30 sec.30 sec.
C6-02Carrier Frequency11
d1-01Frequency Reference 160 Hz60 Hz
d1-02Frequency Reference 240 Hz40 Hz
d1-03Frequency Reference 330 Hz30 Hz
d1-04Frequency Reference 460 Hz60 Hz
d2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H1-04
H1-05
H1-06
H3-10A2 Not UsedFNA
A1-01Access Level00
Multfunction Input Sel 4
(Terminal S4)
Multifunction Input Sel 5
(Terminal S5)
Multifunction Input Sel 6
(Terminal S6)
Setting
V1000J1000
Motor
FLA
33
44
5NA
Motor
FLA
Model PVe Heat Recovery Unit
13
Typical Wiring Diagram
Following is an example of a typical wiring diagram for the PVe. It is representative of circuitry that may be
found in any PVe unit, but it is not intended to be unit-specific. Each PVe unit has a detailed wiring diagram
located within the control panel. This diagram illustrates typical factory wiring and also illustrates circuits that
must be field wired. Included with this drawing are 1) variable frequency drives on the blowers, 2) outdoor
air and exhaust air dirty filter switches, 3) motorized outdoor air and exhaust air intake dampers, 4) electric
preheater, and 5) timed exhaust frost control. Many other factory installed and wired accessories are available.
Model PVe Heat Recovery Unit
14
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit
control center. Field wiring of a light (or other alarm)
to these contacts will notify maintenance personnel
when filters need to be replaced.
The switch has not been set at the factory due to
external system losses that will affect the switch. This
switch will need minor field adjustments after the unit
has been installed with all ductwork complete. The
dirty filter switch is mounted in the unit control center.
To adjust the switch, the unit must be running with
all of the access doors in place. The adjusting
screw is located on the top of the switch. Open the
filter compartment and place a sheet of plastic or
cardboard over 50% of the filter media. Replace
the filter compartment door. Check to see if there
is power at the alert signal leads (refer to electrical
diagram).
Whether there is power or not, turn the adjustment
screw on the dirty filter gauge (clockwise if you did
not have power, counterclockwise if you did have
power) until the power comes on or just before the
power goes off. Open the filter compartment and
remove the obstructing material. Replace the door
and check to make sure that you do not have power
at the alert signal leads. The unit is now ready for
operation.
CO2 Sensor
This accessory is often used to provide a modulating
control signal to a variable frequency drive to raise
and lower airflow in relationship to the CO2 levels
in the space. This strategy is often referred to as
Demand Control Ventilation and provides further
energy savings to the system. Follow instructions
supplied with sensor for installation and wiring details.
Service Outlet
120 VAC GFCI service outlet ships
loose for field installation. Requires
separate power source so power is
available when unit main disconnect is
turned off for servicing.
Vapor Tight Lights
Vapor tight lights provide light to each of the
compartments in the energy
recovery unit. The lights are wired
to a junction box mounted on the
outside of the unit. The switch to
turn the lights on is located in the
unit control center. The switch
requires a separate power source
to allow for power to the lights
when the unit main disconnect is
off for servicing.
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (senses blower side
of filters)
Positive pressure connection is toward the ‘back or
bottom’ of the switch. (senses air inlet side of filters)
Model PVe Heat Recovery Unit
15
Remote Control Panel and Wiring
Schematics
The remote panel is a series of junction boxes ganged
together and includes a stainless steel faceplate. The
remote panel is available with a number of different
alarm lights and switches to control the unit. The
remote panel ships loose and requires mounting and
wiring in the field
The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Time delay override
• Economizer light
• Frost control light
• Exhaust air dirty filter light
• Outdoor air dirty filter light
Indicator Lights powered by the ER Unit
R
C
G
Y1
Y2
W1
6
7
12
PS2
C
PS3
NO
C
NO
NC
NC
Unit On/Off
Frost Control
Economizer
Supply Dirty Filter
Exhaust Dirty Filter
Refer to Electrical Connections section for Field Control
Wiring recommendations.
7-Day Timer or On/Off Switch
7-Day Timer
R
Terminal Block
S1 - Unit On/Off
C
G
in Unit
Control Center
For 7-Day Timer, use blue and black wires.
Red wires should be capped off.
Hand/Off/Auto Switch
Dirty Filter Indicator (power by others)
PS2
C
NC
NC
Hot
L1
PS3
NO
C
NO
Refer to Pressure Switch for voltage and load ratings.
Supply Dirty Filter
Exhaust Dirty Filter
R
Terminal Block
Control Center
On
Off
Auto
C
G
BMS
Hand/Off/Auto Switch allows the unit to
“Off” - off
“On” - Manual Operation
“Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.
Model PVe Heat Recovery Unit
16
in unit
Sensors Mounted by Factory
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for
the controls contractor to connect the Building Management System for monitoring purposes.
OAF-P
OAI
EAPEF-A
FROM
OUTSIDE
OA
FILTER
EP-P
RAF-P
RAI
FROM
INSIDE
RA
FILTER
Temperature Sensors - 1K Ohm RTD
Drawing
Labels
Terminal Strip Labels
OAIOA/Supply Inlet Temp
OAAPOA After Plate Temp
RAIRA/Exhaust Inlet Temp
EAPExhaust After Plate Temp
OADSupply Discharge Temp
Pressure Sensors (analog or digital)
Drawing
Labels
Terminal Strip Labels
OAF-POA Supply Filter Pressure
RAF-PRA Exhaust Filter Pressure
EP-P
(2 sensors)
OAP-P
(2 sensors)
Exhaust Plate Pressure
Outdoor Air Plate Pressure
PLATE
HEAT
EXCHANGER
OAP-P
OAAPOAF-A
SUPPLY
BLOWER
EXHAUST
BLOWER
OAD
TO
OUTSIDE
TO
INSIDE
Amp - Current Sensors (analog or digital)
Drawing
Labels
Terminal Strip Labels
EF-AExhaust Fan Amps
OAF-ASupply Fan Amps
Model PVe Heat Recovery Unit
17
Start-Up
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit
to OFF at disconnect switch(es). Unit may have
multiple power supplies.
WARNING
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Do not operate energy recovery ventilator without
the filters and birdscreens installed. They prevent
the entry of foreign objects such as leaves, birds,
etc.
CAUTION
Do not run unit during construction phase. Damage
to internal components may result and void
warranty.
General Start-Up Information
Every installation requires a comprehensive startup to ensure proper operation of the unit. As part
of that process, the following checklist must be
completed and information recorded. Starting up
the unit in accordance with this checklist will not
only ensure proper operation, but will also provide
valuable information to personnel performing future
maintenance. Should an issue arise which requires
factory assistance, this completed document
will allow unit experts to provide quicker resolve.
Qualified personnel should perform start-up to ensure
safe and proper practices are followed.
Unit Model Number _______________________________
Unit Serial Number _______________________________
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check as items are
completed.
o Disconnect and lock-out all power switches
o Remove any foreign objects that are located in the
energy recovery unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
(e.g. PVe-20)
(e.g. 10111000)
o Rotate the fan wheels by hand and ensure no parts
are rubbing. If rubbing occurs, refer to Start-Up
section for more information.
o Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more
information).
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood
(refer to Routine Maintenance section).
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify control wire gauge (refer to the Electrical
Connections section).
o Install exhaust inlet motorized damper (see Unit
Accessories section)
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Thermometer
• Tachometer
• Incline manometer or equivalent
Start-Up Checklist
The unit will be in operational mode during start-up.
Use necessary precautions to avoid injury. All data
must be collected while the unit is running. In order to
measure volts & amps, the control center door must
be open, and the unit energized using a crescent
wrench to turn the disconnect handle.
Check line voltage at unit disconnect
_______ L1-L2 volts
_______ L2-L3 volts
_______ L1-L3 volts
Correct fan rotation direction
Supply Fan Yes / No
Exhaust Fan Yes / No
Model PVe Heat Recovery Unit
18
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit? Frost Control Application / Operation section:SettingFactory Default
YesNoFrost Control set point35ºF
Differential2ºF
TimerRefer to IOM
YesNoFrost Control ModulatingRefer to IOM
Economizer Application / Operation section:
YesNoEconomizer (temperature)
Set point65ºF
Offset20ºF
Differential2ºF
YesNoEconomizer (enthalpy)
Set pointD
Optional Accessories section: Operational
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesNo CO
YesNo Service OutletYes No N/A
YesNo Vapor Tight LightsYes No N/A
YesNo Remote Control PanelYes No N/A
SensorYes No N/A
2
Variable Frequency Drives section: Operational
YesNo Blower VFDsYes No N/A
Damper section: Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
Model PVe Heat Recovery Unit
19
Unit Start-Up
Belt Span
Deflection =
Belt Span
64
WRONGWRONG
WRONGCORRECT
MOTOR
FAN
MOTOR
R
o
t
a
t
i
o
n
Backward Inclined
R
o
t
a
t
i
o
n
Backward Inclined
Refer to Parts List section for component locations.
Fans
The PVe models contain two
forward curved (supply &
exhaust) fans. These forward
curved fans should be checked
for free rotation. If any binding
occurs, check for concealed
damage and foreign objects
in the fan housing. Be sure to
check the belt drives per the
start-up recommendations in
the following section.
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.),
consult Greenheck to determine if the unit can
operate safely at the new conditions.
Fan Performance Modifications
Due to job specification revisions, it may be
necessary to adjust or change the sheave or pulley to
obtain the desired airflow at the time of installation.
Start-up technician must check blower amperage
to ensure that the amperage listed on the motor
nameplate is not exceeded. Amperage to be tested
with access doors closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by
Greenheck, have been carefully selected for the
unit’s specific operating condition. Utilizing different
components than those supplied could result in
unsafe operating conditions which may cause
personal injury or failure of the following components:
• Fan Shaft • Bearings • Motor
• Fan Wheel • Belt
Tighten all fasteners and set screws securely and
realign drive pulleys after adjustment. Check pulleys
and belts for proper alignment to avoid unnecessary
belt wear, noise, vibration and power loss. Motor and
drive shafts must be parallel and pulleys in line (see
diagrams in this section).
Belt Drive Installation
1. Remove the protective coating from the end of
the fan shaft and assure that it is free of nicks and
burrs.
2. Check fan and motor shafts for
parallel and angular alignment.
3. Slide sheaves on shafts. Do not
drive sheaves on as this may
result in bearing damage.
4. Align fan and motor sheaves
with a straight-edge or
string and tighten.
Model PVe Heat Recovery Unit
20
Forward Curved
Exhaust Fan
5. Place belts over sheaves. Do not pry or force
belts, as this could result in damage to the cords
in the belts.
6. With the fan off, adjust the belt tension by moving
the motor base. (See belt tensioning procedures in
the Routine Maintenance section of this manual).
When in operation, the tight side of the belts
should be in a straight line from sheave to sheave
with a slight bow on the slack side.
WRONGWRONG
WRONGCORRECT
Direction of Fan Wheel Rotation
Blower access is labeled on unit. Check for proper
wheel rotation by momentarily energizing the fan.
Rotation is determined by viewing the wheel from the
drive side and should match the rotation decal affixed
to the fan housing (see Rotation Direction figures).
If the wheel is rotating the wrong way, direction can
be reversed by interchanging any two of the three
electrical leads. Check for unusual noise, vibration, or
overheating of bearings. Refer to the Troubleshooting
section of this manual if a problem develops.
t
t
a
i
o
o
n
R
n
o
i
t
a
t
o
R
Airflow
Forward Curved
Fan RPM
Supply fan and exhaust fan will have an adjustable
motor pulley (on 15 HP and below) preset at the
factory to the customer specified RPM. Fan speed
can be increased or decreased by adjusting the pitch
diameter of the motor pulley. Multigroove variable
pitch pulleys must be adjusted an equal number
of turns open or closed. Any increase in fan speed
represents a substantial increase in load on the
motor. Always check the motor amperage reading
and compare it to the amperage rating shown on the
motor nameplate when changing fan RPM. All access
doors must be installed except the control center
door. Do not operate units with access doors open or
without proper ductwork in place as the fan motors
will overload.
Vibration
Excessive vibration may be experienced during initial
start-up. Left unchecked, excessive vibration can
cause a multitude of problems, including structural
and/or component failure. The most common sources
of vibration are listed.
equipment should be consulted. If the problem is
wheel unbalance, in-place balancing can be done.
Generally, fan vibration and noise is transmitted
to other parts of the building by the ductwork. To
eliminate this undesirable effect, the use of heavy
canvas connectors is recommended.
Refer to the
Troubleshooting
section of this manual
for corrective actions.
If observation cannot
locate the source of
vibration, a qualified
technician using
vibration analysis
Model PVe Heat Recovery Unit
21
Maintenance Overview
The Greenheck PVe Heat Recovery Ventilator is quite
simply an interface unit that takes in outdoor air and
either heats or cools that air and then delivers that air
into the building HVAC system for further heating or
cooling. The heating and cooling that is done in this
unit is accomplished by taking heat energy out of the
air being exhausted to the outdoors and transferring
that heat energy to the incoming replacement air. If
the outdoor air is being used for cooling, some of the
heat energy is transferred from the incoming warm
outdoor air to the exhaust air.
Most all the components found in this unit are typical
of what would normally be found in other air handlers.
There is an air propulsion system consisting of
two belt driven blowers; one to draw in outdoor air
through the Plate Heat Exchanger, and the other to
draw stale indoor air from the building through the
Plate Heat Exchanger and then exhaust it. There are
various optional motorized dampers and sensors that
may also be found in the unit.
The heart of the PVe unit is the Plate Heat Exchanger
and this is the component that actually accomplishes
heat energy recovery. It has no moving parts and the
only real maintenance issues are to keep the internal
surfaces clean and to protect the aluminum plates
from damage.
In addition to the typical maintenance issues shown
in following pages, periodic visual inspection of
the Plate Heat Exchanger is required. Such visual
inspections should be recorded and record made of
any observations.
The surfaces of the flat aluminum plates within
the Plate Heat Exchanger permit complete visual
inspection of both supply and exhaust sides of the
unit. Small amounts of dust present in either side of
the Plate Heat Exchanger will not affect performance.
If appreciable amounts of dust or dirt accumulate,
the Plate Heat Exchanger can be cleaned with hot
water (180ºF) or a detergent that does not damage
aluminum surfaces. Spray water evenly across the
surfaces at a pressure between 22 and 55 psig. Do
not force sharp objects against the heat transfer
surfaces or damage to the flat plates may occur.
Model PVe Heat Recovery Unit
22
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit
to OFF at disconnect switch(es). Unit may have
multiple power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Once the unit has been put into operation, a routine
maintenance program should be set up to preserve
reliability and performance. Items to be included in
this program are:
Lubrication
Apply lubrication where required
Dampers
Check for unobstructed operation
Fan Belts
Check for wear, tension, alignment
Motors
Check for cleanliness
Blower Wheel & Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
Bearings
Check for cleanliness
Check set screws for tightness
Lubricate as required
External Filter
Check for cleanliness - clean if required
Internal Filter
Check for cleanliness - replace if required
Door Seal
Check if intact and pliable
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication.
Apply lubrication where required. Any components
showing excessive wear should be replaced to
maintain the integrity of the unit and ensure proper
operation.
Fan Belts
Belts must be checked on a regular basis for
wear, tension, alignment, and dirt accumulation.
Premature or frequent belt failures can be caused by
improper belt tension (either too loose or too tight)
or misaligned sheaves. Abnormally high belt tension
or drive misalignment will cause excessive bearing
loads and may result in failure of the fan and/or motor
bearings. Conversely, loose belts will cause squealing
on start-up, excessive belt flutter, slippage, and
overheated sheaves. Both loose and tight belts can
cause fan vibration.
When replacing belts on multiple groove drives, all
belts should be changed to provide uniform drive
loading. Do not pry belts on or off the sheave. Loosen
belt tension until belts can be removed by simply
lifting the belts off the sheaves. After replacing belts,
insure that slack in each belt is on the same side of
the drive. Belt dressing should never be used.
Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.
The proper belt setting is the lowest tension at which
the belts will not slip under peak load operation. For
initial tensioning, set the belt deflection at 1/64-inch
for each inch of belt span (measured halfway between
sheave centers). For example, if the belt span is
64 inches, the belt deflection should be oneinch
(using moderate thumb
pressure at mid-point
Deflection =
Belt Span
64
of the drive). Check
belt tension two times
during the first 24hours
of operation and
periodically thereafter.
Belt Span
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup
on the motor housing assists proper motor cooling.
Never wash-down motor
with high pressure spray.
Greasing of motors is
only intended when
fittings are provided.
Many fractional motors
are permanently
lubricated for life and
require no further
lubrication.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Model PVe Heat Recovery Unit
23
Fan Wheel & Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively
clean environment. Some bearings are relubricatable
and will need to be regreased depending on fan use.
Check your bearings for grease zerk fittings to find
out what type of bearing you have. If your fan is not
being operated under normal use, bearings should be
checked monthly for lubrication.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
purchased). Filters should be checked and cleaned
on a regular basis for best efficiency. The frequency
of cleaning depends upon the cleanliness of the
incoming air. These filters should be cleaned prior to
start-up.
Clean filters by rinsing with a mild detergent in warm
water.
Filter Size and Quantities
Unit Size
PVe-2012 x 25 x 233
PVe-3516 x 25 x 233
PVe-4520 x 25 x 233
PVe-5524 x 24 x 233
All dimensions in inches.
Pleated Filter SizeQuantity
Supply and ExhaustSupplyExhaust
Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the
outdoor air side of the unit.
Exhaust Air Filters: Access to the exhaust air filters
is through the door labeled as “Filter Access” on the
exhaust air side of the unit.
Refer to Access Door Descriptions section for
additional information on filter locations.
Door Seal Maintenance
Slip-on type seal is installed on the door. Inspect at
least annually to ensure that seal is still pliable and
intact.
Internal Filter Maintenance
The PVe units are always provided with 2-inch,
pleated filters in the outdoor air and exhaust
airstreams. These filters should be checked per
a routine maintenance schedule and replaced as
necessary to ensure proper airflow through the
unit. See table for pleated filter size and quantity
for each unit. Replacement filters shall be of same
performance and quality as factory installed filters.
Filter type must be pleated design with integral metal
grid. Two acceptable filter replacements are Aerostar
Series 400 or Farr 30/30®.
Model PVe Heat Recovery Unit
24
Parts List
4
8
6
3
1. Supply blower
• Forward curved fan
• Adjustable motor mount for belt tensioning
• Adjustable sheaves for speed control
2. Vibration isolators (quantity 4 per blower)
• Neoprene
3. Aluminum plate heat exchanger
4. Supply weatherhood with 2-inch aluminum mesh
filter
5. Exhaust weatherhood with birdscreen
6. Supply and exhaust air filter racks for
2-inch pleated, 30% efficient filters
7. Electrical control box (standard features)
• Single point power
• Disconnect interlocked with access door
• Motor starters for the supply and exhaust
blower
• 24 VAC, control circuit with terminal strip
Not depicted on this image
8. Exhaust blower
• Forward curved fan
• Adjustable motor mount for belt tensioning
• Adjustable sheaves for speed control
1
2
Sequence of Operation
Basic Unit
The PVe units are prewired such that when a call for
outside air is made (via field supplied 24 VAC control
signal wired to unit control center), the supply and
5
exhaust fan are energized and optional motorized
dampers open. The PVe is normally slaved (24 volt) to
the roof top air handler. When the roof top air handler
starts, the auxiliary contactor in the air handler closes
to start the PVe.
Summer Operation
Outdoor air is preconditioned (temperature is
decreased) by the transfer of energy from the cooler,
drier, exhaust air via the aluminum heat exchanger.
The preconditioned air is typically mixed with return
air going back to the air handler for final conditioning.
Economizer Operation: Refer to Economizer
Application/Operation section.
Winter Operation
Outdoor air is preconditioned (temperature is
increased) by the transfer of energy from the warmer,
more humid exhaust air via the aluminum heat
exchanger. The preconditioned air is typically mixed
with return air going back to the air handler for final
conditioning.
Frost Control Operation: Refer to Frost Control
Application/Operation section.
Other Accessories:
Dirty Filter Sensor: Refer to Optional Accessories
section
CO2 Sensor: Refer to Optional Accessories section
VFD on Blowers: VFDs on blowers are often used
as part of a demand control ventilation system. This
type of system takes advantage of varying occupancy
through the use of CO2 sensors to monitor space CO2
levels. If CO2 levels are low in the space, the VFD will
operate the blowers at minimum airflow required by
code. As the space occupancy increases and CO2
levels increase, the VFD will increase the amount
of fresh outdoor air being brought in to offset the
CO2 levels in the space (exhaust airflow is increased
proportionally as outdoor airflow increases). As CO2
levels come back down, the airflow will decrease
back to minimum requirements.
Model PVe Heat Recovery Unit
25
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,
prior to contacting the factory, please determine the following information:
Unit #1Unit #2Unit #3Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in
accordance with SMACNA and AMCA guidelines.
Model PVe Heat Recovery Unit
26
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.
Defective motor or capacitor.Replace.
Replace fuse or reset circuit breaker and check
amps.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Motor starter overloaded.Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the coil.
CFM too high.Check cfm and adjust drives if needed.
Static pressures are higher or lower than
design.
Blower rotation is incorrect.Check rotation and reverse if necessary.
Motor voltage incorrect.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Check for On/Off switches. Check for correct
supply voltage.
Check for broken or loose belts. Tighten loose
pulleys.
Shorten wiring run to mechanical room or
install a relay which will turn unit on/off. Consult
Factory for relay information.
Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.
If higher, ductwork should be improved.
If lower, fan rpm should be lower.
Check motor nameplate versus supplied
voltage.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Low airflow (cfm)
High airflow (cfm)
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Dirty filter.
Leaks in ductwork.Repair.
Elbows or other obstructions may be
obstructing fan outlet.
Improve ductwork to eliminate losses using
good duct practices.
Check for correct drives and rpm with catalog
data.
For 3-phase, see Direction of Fan Wheel
Rotation under Unit Start-Up section.
Follow cleaning procedures in Routine
Maintenance section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed
if necessary.
Induce Ps into system ductwork. Make sure
grilles and access doors are installed. Decrease
fan speed if necessary.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Model PVe Heat Recovery Unit
27
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Exhaust Only frost control sensors are tripping.
Adjust frost temperature sensor set point as
needed.
Excessive noise
or vibration
Fan wheel rubbing on inlet.
Bearings.
Wheel out of balance.Replace or rebalance.
Loose wheel on shaft.Tighten wheel setscrew.
Loose motor or blower sheave.Tighten sheave setscrew.
Belts too loose.Adjust belt tension after 24 hours of operation.
Belts too tight.
Worn belt.Replace.
Motor base or blower loose.Tighten mounting bolts.
Buildup of material on wheel.Clean wheel and housing.
Bearing and drive misaligned.Realign.
Noise being transmitted by duct.
Adjust wheel and/or inlet cone. Tighten wheel
hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate
bearings. Tighten collars and fasteners.
Loosen to maintain a 3/8 inch deflection per
foot of span between sheaves.
Make sure ductwork is supported properly.
Make sure ductwork metal thickness is sized for
proper stiffness. Check duct size at discharge to
ensure that air velocities are not too high.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Model PVe Heat Recovery Unit
28
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model PVe Heat Recovery Unit
29
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model PVe Heat Recovery Unit
30
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model PVe Heat Recovery Unit
31
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck Catalog Heat Recovery Ventilator, Model PVe,
provides additional information describing the equipment,
fan performance, available accessories, and specification
data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at: www.amca.org.