Greenheck Fan 455924 ERV-251, 455924 ERV-521, 455924 ERV-361, 455924 ERV-582, 455924 ERV-581 User Manual

...
®
Energy Recovery Ventilators
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Models: ERV-251 ERV-361 ERV-521 ERV-581 ERV-522 ERV-582
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electric Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to the unit while it is running.
Model ERV Energy Recovery Unit
1
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle each piece in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
Inspection and Maintenance during Storage
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate all moving components by hand ten to fifteen revolutions to distribute lubricant on motor and bearings. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Model ERV Energy Recovery Unit
2
Table of Contents
Basic Operation
Basic Operation . . . . . . . . . . . . . . 3
Installation
Supplemental Installation, Operation and
Maintenance Manuals . . . . . . . . . . . 3
Installation Concerns. . . . . . . . . . . . 3
Lifting . . . . . . . . . . . . . . . . . . 4
Roof Curb and Rail Mounting
Recommended Roof Opening . . . . . . . . 4
Roof Curb Mounting . . . . . . . . . . . . 5
Curb Dimensions and Weights . . . . . . . . 5
Ductwork Connections . . . . . . . . . . . 5
Rail Mounting / Layout . . . . . . . . . . . 6
Service Clearances . . . . . . . . . . . . 7
Electrical Information
General Electrical Information . . . . . . . . 8
Control Center Components . . . . . . . . . 9
Electric Heater Application/Operation . . . . . 9
Unit Accessories. . . . . . . . . . . . . . 9
Access Panel Description and Location . .10-11
Dimensional Data . . . . . . . . . . . . 12-13
Optional Accessories
Frost Control Application/Operation . . . . . 14
Economizer Application/Operation . . . . . . 15
Variable Frequency Drives and Wiring . . . .16 -17
Typical Wiring Diagram . . . . . . . . . . . 18
Sensors and Lights . . . . . . . . . . . . 19
Remote Control Panel and Wiring . . . . . . 20
Sensors Mounted by Factory . . . . . . . . 21
Sequence of Operation Start-Up
Unit . . . . . . . . . . . . . . . . . . . 22
Optional Accessories . . . . . . . . . . . 23
Fan . . . . . . . . . . . . . . . . . . . 24
Energy Recovery Wheel . . . . . . . . . . 25
Routine Maintenance Checklist
General . . . . . . . . . . . . . . . . . 26
Fan Belts. . . . . . . . . . . . . . . . . 26
Fan Motors . . . . . . . . . . . . . . . . 26
Fan Wheel and Fasteners . . . . . . . . . . 27
Fan Bearings . . . . . . . . . . . . . . . 27
Filters . . . . . . . . . . . . . . . . . . 27
Door Seal Maintenance . . . . . . . . . . . 27
Energy Recovery Wheel Maintenance
Accessing Energy Recovery Wheel . . . .27-2 8
Removing Wheel Segments . . . . . . . . 28
Cleaning Wheel Segments . . . . . . . . 29
Wheel Belt . . . . . . . . . . . . . . . 29
Wheel Bearing . . . . . . . . . . . . . 29
Parts List . . . . . . . . . . . . . . . . . 30
Sequence of Operation . . . . . . . . . . . 31
Troubleshooting – Airflow . . . . . . . . . . 32
Troubleshooting – Unit . . . . . . . . . 33-34
Maintenance Log . . . . . . . . . . . . . 35
Warranty . . . . . . . . . . . . . Backcover
The ERV brings in fresh, outdoor air and removes stale, exhaust air. Prior to discharging the exhaust air, the energy recovery wheel transfers energy from the exhaust air to the outdoor air at an efficiency of 70-80%. Simply put, this unit preconditions the outdoor air to save money on heating and cooling costs.
Exhaust air
from building
Exhaust air discharged
outside
Outdoor
air
Energy Recovery
Wheel
Preconditioned air
sent to space
Supplemental Installation, Operation and Maintenance Manuals
Refer to the following Installation, Operation and Maintenance Manuals for additional details:
Part #460988 — ERV-522 and ERV-582 Curbs
Part #462844 — ERV Exhaust Weatherhood
Installation
The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook.
Adequate space should be left around the unit for filter replacement and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.
See Service Clearances and Access Panel Description sections for more details.
WARNING
All factory provided lifting lugs must be used when lifting the unit. Failure to comply with this safety precaution could result in property damage, serious injury or death.
Model ERV Energy Recovery Unit
3
Lifting
SUPPLY
DISCHARGE
EXHAUST
INTAKE
U
V
0.50
0.50
U
V
EXHAUST
INLET
SUPPLY
DISCHARGE
1. Before lifting, be sure that all shipping material has been removed from unit.
2. To assist in determining rigging requirements, weights are shown below.
3. Unit must be lifted by all lifting lugs provided on base structure.
4. Rigger to use suitable mating hardware to attach to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent damage to the cabinet by the lift cables.
Recommended Roof Opening
ERV-251, 361, 521 and 581
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
10. Check to be sure that gasketing has been applied to the curb prior to lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
Unit Weights
Unit Size Approx. Weight (lbs)*
ERV-251 340
ERV-361 860
ERV-521 1290
ERV-581 1470
ERV-522 3230
ERV-582 3700
*Weight assumes outdoor unit with
filters, weatherhoods and outdoor air intake damper.
ERV-522 and 582
Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the corresponding ductwork. Be sure to allow for the recommended service clearances when
Unit Size U V
ERV-251 26.5 20
ERV-361 43 26
ERV-521 58 35
ERV-581 60 30
ERV-522 62 36
ERV-582 77 38
All dimensions are in inches.
positioning opening (see Service Clearances). Do not face the outdoor air intake of the unit into prevailing wind and keep the intake away from any other exhaust fans. Likewise, position the exhaust discharge opening away from outdoor air intakes of any other equipment.
When cutting only duct openings, cut opening 1 inch (25mm) larger than duct size to allow clearance for installation. Area enclosed by roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R” value of at least 5. If area within curb is open, higher radiated sound levels may result.
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A.
Model ERV Energy Recovery Unit
4
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Length of Straight Duct
GOOD
POOR
GOODPOOR
Tu rning
Vanes
Roof Curb Mounting
W
L
W
L
Roof Curb
Side of Unit
Base
1-inch Insulation
E
D
C
A
B
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Tu rning
Vanes
Roof curb details including duct location dimensions, are available on ERV-522 & 582 Roof Curb Assembly Instructions, Part #460988.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory Supplied Roof Curbs: Roof curbs are Model GPI or GPNS for the ERV-251, 361, 521,
581. The GPI or GPNS ships assembled and includes a duct adapter.
Roof curbs are Model GKD for the ERV-522 and
582. The GKD ships in a knockdown kit (includes duct adapter) and requires field assembly (by others). Assembly instructions are included with the GKD curbs.
2. Install Curb: Locate curb over roof opening and fasten in place. (Refer to Recommended Roof Openings). Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper unit operation, it is important that the installation be level. Shim as required to level.
3. Install Ductwork: Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.
Curb Outside Dimensions - continued
Curb Cap Details for Factory Supplied Roof Curbs
Unit Size A
B C D E
ERV-251 1.75 2.00 1.00 1.125 0.750
ERV-361 1.75 2.00 1.00 1.200 0.875
ERV-521 1.75 2.00 1.00 0.813 0.875
ERV-581 1.75 2.00 1.00 0.813 0.750
ERV-522 1.813 4.00 1.75 1.000 0.750
ERV-582 1.938 4.125 1.938 1.125 0.625
All dimensions are in inches.
Ductwork Connections
Examples of poor and good fan-to-duct connections are shown. Airflow out of the fan should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result in low airflow and other system effects.
Curb Outside Dimensions and Weights
Recommended Discharge Duct Size and Length
ERV-251, 361, 521 and 581
Unit Size L W Curb Weight (lbs.)
ERV-522 and 582
ERV-251 42.5 30.5 60
ERV-361 58.5 47.5 115
ERV-521 63.5 63.5 160
ERV-581 71.8 66 185
ERV-522 120.5 80.5 520
ERV-582 142.25 93 700
All dimensions are in inches. Weights are for 12-inch high GPI type curbs.
Model Blower Size Duct Size Straight Duct Length
ERV-251 10 9 x 9 36
ERV-361 10 14 x 14 36
ERV-521 12 20 x 20 36
ERV-581 15 28 x 28 60
ERV-522S 15 28 x 28 60
ERV-522H 18 32 x 32 60
ERV-582 20 34 x 34 72
All dimensions shown in inches.
• Recommendedductsizesarebasedonvelocitiesacrossthe
cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.
• Straightductlengthswerecalculatedbasedon100%effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
Model ERV Energy Recovery Unit
5
OUTDOOR AIR INTAKE END
OUTDOOR AIR INTAKE END
OUTDOOR AIR INTAKE HOOD
OUTDOOR AIR INTAKE END
B
SUPPLY/EXHAUST
OPENING
A
OUTDOOR AIR SIDE
OUTDOOR AIR INTAKE END
AB
SUPPLY /EXHAUST
OPENING
OUTDOOR
AIR
INTAKE
HOOD
OUTDOOR AIR SIDE
OUTDOOR AIR SIDE
OUTDOOR AIR INTAKE END
OUTDOOR AIR INTAKE HOOD
OUTDOOR AIR INTAKE END
B
SUPPLY/EXHAUST
OPENING
A
Rail Mounting / Layout
 • RailsdesignedtohandletheweightoftheERVshouldbepositionedasshownonthediagram(railsby
others).
 • Makesurethatrailpositioningdoesnotinterferewiththesupplyairdischargeopeningortheexhaustair
intake opening on the ERV unit. Avoid area dimensioned “B” below.
 • Railsshouldextendbeyondtheunitaminimumof12inchesoneachside.  • Setunitonrails.
ERV-251 ERV-361 ERV-521 ERV-581
Isometric view of
ERV on rails
ERV-522 ERV-582
Isometric view of
ERV on rails
All dimensions are in inches.
6
Side view of ERV on rails
Unit Size A
ERV-251 4.50 16
ERV-361 4.75 18
ERV-521 5.75 24
ERV-581 4.875 22
Model ERV Energy Recovery Unit
Side view of ERV on rails
B
Unit Size A
B
ERV-522 4.625 32
ERV-582 4.875 33.25
All dimensions are in inches.
Cassette slides out*
Access Panels
Access Panels
Exhaust
Side
Outdoor
Air Side
Service Clearances
Intake Hood
Exhaust
Hood
Cassette slides out*
Access Panels
Access Panel
Access Panel
Cassette slides out*
Access Panels
Access Panels
Exhaust
Side
Outdoor
Air Side
Exhaust
Side
Outdoor
Air Side
Cassette
Cassette
Access PanelAccess Panel
Access Panel
Access Panel
Cassette
Cassette
Supply Weatherhood
Exhaust Weatherhood
Access PanelAccess Panel
Access PanelAccess Panel
Access Panel
ERV-251, 361, 521 and 581 units require minimum clearances to perform routine maintenance, such as filter replacement, energy wheel cassette inspection, and fan belt adjustment. Blower and motor assemblies, energy recovery wheel cassette and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances, refer to
drawings below for these dimensions.
ERV-251, ERV-361, ERV-521, ERV-581 ERV-522, ERV-582
X
R
T
X
*ERV-251, 361, and 521 only.
Arrangement A
T
R
S
*ERV-251, 361, and 521 only.
Recommended Service Clearances
Unit Size R S T X
ERV-251 32 30 30
ERV-361
ERV-521
ERV-581
ERV-522 38
ERV-582 42
All dimensions are in inches.
Arrangement B, C or D
(30 for maintenance)
(39 for maintenance)
(32 for maintenance)
44
60
65
30 30
40 40
40 40
X
X
Arrangement A
X
X
X
X
Arrangement B, C or D
Model ERV Energy Recovery Unit
7
Electrical Information
The unit must be electrically grounded in accordance with the current National Electrical Code, ANSI/NFPA
70. In Canada, use current CSA Standard C22.1, Canadian Electrical Code, Part 1. In addition, the installer should be aware of any local ordinances or electrical company requirements that might apply. System power wiring must be properly fused and conform to the local and national electrical codes. System power wiring is to the unit main disconnect (door interlocking disconnect switch standard on most units) or distribution block and must be compatible with the ratings on the nameplate: supply power voltage, phase, and amperage (Minimum Circuit Amps - MCA, Maximum Overcurrent Protection
- MOP). All wiring beyond this point has been done by the manufacturer and cannot be modified without affecting the unit’s agency / safety certification.
If field installing an additional disconnect switch, it is recommended that there is at least four feet of service room between the switch and system access panels. When providing or replacing fuses in a fusible disconnect, use dual element time delay fuses and size according to the rating plate.
If power supply is desired through bottom of unit, run the wiring through the curb, cut a hole in the cabinet bottom, and wire to the disconnect switch. Seal penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent requirements for the system to operate properly. Voltage supply and voltage imbalance between phases should be within the following tolerances. If the power is not within these voltage tolerances, contact the power company prior to operating the system.
Voltage Supply: See voltage use range on the rating plate. Measure and record each supply leg voltage at all line disconnect switches. Readings must fall within the allowable range on the rating plate.
Voltage Imbalance: In a 3-phase system, excessive voltage imbalance between phases will cause motors to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded voltage measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
WARNING
To prevent injury or death due to electrocution or contact with moving parts, lock disconnect switch open.
Most factory supplied electrical components are prewired. To determine what electrical accessories require additional field wiring, refer to the unit specific wiring diagram located on the inside of the unit control center access door. The low voltage control circuit is 24 VAC and control wiring should not exceed
0.75 ohms.
Refer to Field Control Wiring Length/Gauge table for wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft. 18 200 ft. 16 300 ft. 14 450 ft. 12
Minimum
Wire Gauge
Control wires should not be run inside the same conduit as that carrying the supply power. Make sure that field supplied conduit does not interfere with access panel operation.
If wire resistance exceeds 0.75 ohms, an industrial­style, plug-in relay should be added to the unit control center and wired in place of the remote switch (typically between terminal blocks R and G on the terminal strip (refer to Typical Control Center Components). The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to “chatter” or not pull in which can cause contactor failures and/or motor failures.
CAUTION
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105ºC.
Model ERV Energy Recovery Unit
8
Typical Control Center Components
Rooftop
Exhaust
Hood
Intake Hood
Rooftop
Exhaust Hood
Intake
Hood
Rooftop
Exhaust Hood
Intake
Hood
1. Main Disconnect (non-fusible, lockable)
2. Motor Starter – Exhaust Air Fan
3. Motor Starter – Outdoor Air Fan
4. Motor Contactor – Energy Wheel
5. 24 VAC Control Transformer
6. 24 VAC Terminal strip
7. Fuses for blower motors
5
1
6
7
2 3 4
Exploded Detail
of Terminal Strip
ERV-251, 361, 521, 581
Electric Heater Application/Operation
Factory installed electric heaters can be provided for preheat frost control. An electric preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. Electric heaters are available in 208, 230, or 460 VAC (refer to heater nameplate for voltage).
Preheaters: Preheaters are standard as 2-stage, step control. Step control heaters are designed with multiple stages made up of equal increments of heating capability. For example, a 10 kW heater with two stages will be composed of two 5-kW stages. Preheaters are single point wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the outdoor airstream after the preheater to turn the preheater on. See Frost Control Application/Operation for typical set points. If the temperature falls below the set point and the wheel pressure drop sensor is triggered, the first stage of the preheater will turn on. If the first stage does not satisfy the set point, the second stage will also turn on.
Electric Preheater:
The preheater is single point wired to the unit control center. Access to the preheater control panel is through the outdoor air filter door.
Access to Control Center Components
is gained through the access panel indicated.
ERV-522
ERV-582
Unit Accessories
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory mounted.
Exhaust Weatherhood
The exhaust weatherhood is shipped separately as a kit with its own instructions.
Dampers
Backdraft dampers are always included as an integral part of the exhaust hood assemblies. Motorized outdoor air and exhaust air dampers are optional and are factory mounted (and wired) at the intake.
Model ERV Energy Recovery Unit
9
Access Panel Description and Location
Interior
Outdoor Air
Inlet
Exhaust Air
Discharge
Rooftop
Exhaust
Hood
Intake
Hood
Exhaust Air
Inlet
Outdoor Air
Discharge
Rooftop
Exhaust
Hood
Intake
Hood
Rooftop
Exhaust Hood
Intake Hood
Interior
Rooftop
Exhaust Air
Inlet
Outdoor Air Inlet
Exhaust Air Discharge
Exhaust Hood
Intake Hood
Outdoor Air
Discharge
ERV-251, ERV-361, ERV-521, ERV-581 ERV-522
5
1
2
3
2
6
3
3
4
4
1
Arrangement A
Arrangement A
5
1
2
3
2
6
3
3
4
4
1
10
Arrangement B, C or D
1
Outdoor air blower and motor
Energy wheel cassette
Energy wheel cassette
Internal filters
2
Outdoor air intake damper
Frost control
Outdoor air sensors
Main disconnect
3
Electrical control center
Internal filters
4
Model ERV Energy Recovery Unit
Exhaust air blower and motor
Arrangement B, C or D
1
2
Exhaust blower and motor
Electric control center
Main Disconnect
Energy wheel cassette
3
Internal filters
Frost control
Outdoor air sensors
4
5
6
Preheater controls
Outdoor air intake damper
Supply blower and motor
Exhaust air intake damper
Interior
Rooftop
Exhaust Air
Inlet
Outdoor Air Inlet
Exhaust Air Discharge
Exhaust Hood
Intake
Outdoor Air
Discharge
Rooftop
Exhaust Hood
Intake
Hood
ERV-582
2
3
4
1
3
Arrangement A
2
3
4
1
3
1
2
3
4
Arrangement B, C or D
Exhaust blower and motor
Electric control center
Main disconnect
Supply blower and motor
Exhaust air intake damper
Energy wheel cassette
Internal filters
Frost control
Outdoor air sensor
Preheater controls
Outdoor air intake damper
Model ERV Energy Recovery Unit
11
Dimensional Data
Arrangement A
A
B
C
Outdoor Air Inlet
Q xP
Exhaust Air Discharge
LxK
C
B
A
D
E
Arrangement B
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Intake Hood
Exhaust Hood
Outdoor Air Discharge
LxK
Exhaust Air Inlet
FxG
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Intake Hood
Arrangement A
A
B
C
Outdoor Air Inlet
Q xP
Exhaust Air Discharge
LxK
C
B
A
D
E
Arrangement B
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Intake Hood
Exhaust Hood
C
B
A
D
E
Arrangement C
Exhaust Hood
C
B
A
D
E
Arrangement D
Exhaust Hood
Outdoor Air Discharge
LxK
Exhaust Air Inlet
FxG
Intake Hood
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Intake Hood
B
A
D
E
Arrangement B
FxG
LxK
Intake Hood
Exhaust Hood
C
B
A
D
E
Arrangement D
Exhaust Hood
C
B
A
D
E
Arrangement B
Exhaust Air Inlet
FxG
Outdoor Air Discharge
LxK
Intake Hood
Exhaust Hood
ERV-251, 361, 521 and 581
Unit Size
ERV-251 46 34 27 12 8
ERV-361 62 51 34 18 15
ERV-521 67 67 44 16 15
ERV-581 75 70 67 16 22
All dimensions are in inches.
Exterior Dimensions
A B C D E
Unit Size
ERV-251 10 16 63⁄4 7 10 16
ERV-361 18 18 83⁄8 111⁄2 19 18
ERV-521 24 24 103⁄4 131⁄2 26 26
ERV-581 22 27 16 183⁄4 28 48
All dimensions are in inches.
Unit Opening Dimensions
F G K L Q P
Arrangement A Arrangement B
Arrangement C Arrangement D
12
Model ERV Energy Recovery Unit
Outdoor Air Discharge
L x K
Exhaust Air Inlet
F x G
Exhaust Air Discharge
L x K
Outdoor Air Inlet
Q x P
C
B
A
C
B
D
A
E
Outdoor Air Discharge
L x K
Exhaust Air Inlet
H x J
Exhaust
Hood
Intake
Hood
C
B
D
A
E
Outdoor Air Discharge
L x K
Exhaust Air Inlet
F x G
Exhaust
Hood
Intake
Hood
C
B
D
A
E
Outdoor Air Discharge
L x K
Exhaust Air Inlet
H x J
Exhaust
Hood
Intake
Hood
ERV-522 and 582
Unit Size
A B C D E
Exterior Dimensions
ERV-522S 124 84 64 16 19
ERV-522H 124 84 64 16 19
ERV-582H 146 97 77 171⁄2 263⁄4
All dimensions are in inches.
Unit Size
Unit Opening Dimensions
F G K L Q P
ERV-522S 48 25 16 185⁄8 60 25
ERV-522H 48 25 19 22 60 25
ERV-582H 60 28 23 25 70 30
All dimensions are in inches.
Arrangement A Arrangement B
Arrangement C Arrangement D
Model ERV Energy Recovery Unit
13
A1 B1 15
16 18 A2
0.20
0.41.0
0.60.8
0.20
0.41.0
0.60.8
T1
T2
T21 MIN
T11 MIN
Timer Scale
Dip Switch
Optional Accessories
Frost Control Application/Operation
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:
1. Timed Exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control All of these options are provided with a thermostat
(with probe) mounted in the outdoor air intake compartment and a pressure sensor to monitor pressure drop across the wheel.
Frost Threshold Temperatures
Indoor RH @ 70°F Frost Threshold Temp
20% -10º F
30% -5º F
40% 0º F
The typical temperature setting corresponds to the indoor air relative humidity as shown in the Frost Threshold Temperatures table and represents when frost can occur. An increase in pressure drop would indicate that frost is occurring. Both the pressure sensor and the outdoor air temperature sensor must trigger in order to initiate frost control. The two sensors together insure that frost control is only initiated during a real frost condition. Field wiring of a light (or other alarm) between 6 & C in the control center will notify personnel when unit is in frost control mode (refer to Remote Panel Wiring schematics section for wiring details). The following explains the three options in more detail.
Timed exhaust frost control includes a timer in addition to the thermostat and wheel pressure sensor. When timed exhaust frost control is initiated, the timer will turn the supply blower on and off to allow the warm exhaust air to defrost the energy recovery wheel. Default factory settings are 5 minutes off and 30 minutes on. Use the following test procedure for troubleshooting.
Testing (refer to Timer Faceplate drawing below)
• Jumperthewheel
pressure switch in the unit control center. Set the Timer Scale for T1 and T2 to 1 minute. Set the Timer Settings for T1 and T2 to 1.0. Set the dip switch to the down position. (normal position)
• Turnthetemperature
sensor up as high as possible. The supply blower should cycle on for one minute, then turn off for one minute.
Model ERV Energy Recovery Unit
14
• Aftertesting,settheTimerScaleasfollows: T1 = 10 minutes, T2 = 1 hour
• SettheTimerSettingsasfollows: T1 = 0.5, T2 = 0.5 The timer is now set for 5 minutes off and 30 minutes on. Remember to remove the jumper.
Electric preheat frost control includes an electric heater (at outdoor air intake) and an airflow pressure switch (located at the preheater) in addition to the thermostat and pressure sensor on wheel. (Refer to Electric Heater Application/Operation for electric preheater location). When electric preheat frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel to avoid frosting. Use the following test procedure for troubleshooting.
Testing:
• Turnthethermostatashighasitwillgoand
jumper the wheel pressure sensor. The heater should turn on.
• Ifitdoesn’t,eitherputtheoutdoorairsidedoors
on or temporarily jumper the airflow pressure switch in the preheater control center to avoid nuisance tripping of the pressure switch. Also check the airflow switch pressure tap located at the supply discharge blower to ensure the tubing is connected and the tap is not blocked.
Remember to remove the jumpers.
Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure sensor. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed of the wheel. Reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air condition from reaching saturation, thus, eliminating condensation and frosting. If the outdoor air temperature is greater than the frost threshold temperature OR the pressure differential is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The temperature and pressure differential set points are set at the factory, but are field-adjustable (refer to VFD section for more information). The variable frequency drive will be fully programmed at the factory.
Economizer Application/Operation
The energy recovery wheel operation can be altered to take advantage of economizer operation (free cooling). Two modes are available:
1. De-energizing the wheel
2. Modulating the wheel
A field supplied call for cool (Y1) is required.
De-energizing the wheel is accomplished with a signal from a Temperature or Enthalpy sensor mounted in the air intake compartment. This primary sensor will de-energize the energy wheel when the outdoor air temperature (factory default is 65ºF) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable set point. An Override temperature sensor is also furnished in the outdoor air intake compartment to deactivate economizer mode. The Override (with field adjustable set point) is set at some temperature lower than the primary sensor (factory default is 50ºF). Effectively, the two sensors create a deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned.
Testing
Temperature Sensor with Override
• TurnbothTemperatureand
Override thermostats down as low as they go. The wheel should be rotating.
• TurntheTemperaturesensor
up as high as it goes, and keep the Override sensor as low as it will go. The wheel should stop rotating.
• Turnbothsensorsashighastheywillgo.The
wheel should start rotating.
• SettheTemperaturesensoratdesiredpoint
for economizer operation to begin. Set the Override sensor at desired point for economizer operation to end (factory default is 65ºF and 50ºF, respectively).
Enthalpy Sensor with Override
• Turnunitpoweroff.Disconnect
C7400 Solid State Enthalpy Sensor from terminal So on the enthalpy controller. Also, disconnect the
620 ohm resistor from terminal Sr on the enthalpy controller. Turn unit power on. The LED on the enthalpy controller should light and the energy recovery wheel should not rotate.
•Turnunitpoweroff.Reconnect620
ohm resistor to terminal Sr on the enthalpy controller. Turn unit power
Enthalpy
on. The LED on the enthalpy controller
Controller
Temperature
Sensor with
Override
Enthalpy
Sensor with
Override
should not light and the energy recovery wheel should energize and rotate.
If these steps provide the results described, the enthalpy economizer is working properly.
• Turnunitpoweroff.ReconnectC7400SolidState
Enthalpy Sensor to terminal So.
Modulating the Wheel
In applications in which an internal heat gain is present in the space, the rotational speed of the energy wheel may be modulated (via variable frequency drive) to avoid overheating the space during the winter. The speed of the energy wheel will be controlled in response to the discharge temperature set point.
Sequence of Operation: The variable frequency drive is fully programmed at the factory (refer to VFD section for more information). A “call for cool” must be field wired to the unit (terminals provided in unit ­refer to wiring diagram in unit control center) to allow for initiation of economizer mode. When the space calls for cooling, factory supplied controls will drive the following wheel operations:
TAO > T
TAO < T
and
TAO > T
TAO < T
and
TAO < T
RA
RA
SA
RA
SA
Wheel runs at full speed.
(maximum energy recovery)
Wheel is stopped.
(no energy recovery)
Wheel will modulate to maintain
discharge temperature.
Where (TOA) is the outdoor air temperature set point, (TRA) is the return air temperature set point, and (TSA) is the supply air discharge thermostat set point.
Model ERV Energy Recovery Unit
15
Variable Frequency Drives for Energy Recovery Blowers
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
MPACAMAC+VA2A1PCP2P1
IGS-S+R-R+
V1000
MA MB MCACAMAC+VA1SCS5S4S3S2S1
J1000
OPTION 1 - 0-10 VDC CONTROL
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
USER TO PROVIDE ISOLATION AS REQUIRED
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
WIRED TO A1 (+) AND AC (COMMON)
0-10 VDC CONTROL SIGNAL (BY OTHERS)
10 VDC=60 Hz
0 VDC=30 Hz
A1 AC
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4 SC
NEITHER S4 OR S5 CONTACT CLOSED DRIVE SPEED = 60 Hz.
DRIVE SPEED = 40 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
S5 TO SC CONTACT CLOSED (BY OTHERS) DRIVE SPEED = 30 Hz.
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER n01 CHANGE TO 1
PARAMETER n22 FOR NEW 40Hz SET TING
PARAMETER n21 FOR NEW 60Hz SET TING
PARAMETER n23 FOR NEW 30Hz SET TING PARAMETER n01 CHANGE TO 0
USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided for modulating or multi-speed control of the blowers. One VFD is provided for each blower (supply air and
exhaust).TheVFD’sprovidedareeitherYaskawamodelV1000orJ1000.Refertothetablesinthissectionfor
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an example wiring diagram has been provided in this manual for reference). When making adjustments outside of the factory set points, refer to Yaskawa VFD instruction manual, which can be found online at www.drives.com. For technical support, contact Yaskawa direct at 1-800-927-5292.
16
Model ERV Energy Recovery Unit
Factory Set Points
Variable Frequency Drives (VFDs) for the blowers are factory setup to operate in one of the three following modes:
Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30 and 60Hz
Multi-speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
 •SCtoS4-Driverunsat40Hz  •SCtoS5-Driverunsat30Hz
CO2 Sensor: A digital contact closure from an
optional factory provided CO2 sensor sends the VFD to high or low speed depending on CO2 ppm levels at the sensor.
The terminal locations for Modulating (option 1) and Multi-speed (option 2) are shown on the left. Most of the set points in the VFDs are Yaskawa factory defaults. However, a few set points are changed at Greenheck and are shown in the tables on the next page. These settings are based on the VFD mode selected.
To gain access to change set points on the V1000 and
J1000drives,parameterA1-01needstobesetat“2”.
To prevent access or tampering with drive settings on either drive, change parameter A1-01 to “0”.
Drive Operation
SC to S1 contact for On/Off
A1 (0-10 VDC) referenced to AC. Can use +15 VDC
from +V
Factory Set Points - continued
Resetting the drive to factory defaults
To reset the drive back to Greenheck factory defaults go to parameter A1-01 and set it to “2”. Then go to A1-03 and change it to “1110” and press enter. The drive is now reset back to the settings programmed at Greenheck.
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
A1-01 Access Level 2 2
b1-17 VFD Start-Up Setting 1 1 C1-01 Acceleration Time 30 sec. 30 sec. C1-02 Deceleration Time 30 sec. 30 sec. C6-02 Carrier Frequency 1 1
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H3-04 Terminal A1 Bias 50% 50%
A1-01 Access Level 0 0
MULTI-SPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
A1-01 Access Level 2 2
b1-01 Reference Source (Frequency) 0 0
b1-17 VFD Start-Up Setting 1 1
C1-01 Acceleration Time 30 sec. 30 sec.
C1-02 Deceleration Time 30 sec. 30 sec.
C6-02 Carrier Frequency 1 1
d1-01 Frequency Reference 1 60 Hz 60 Hz
d1-02 Frequency Reference 2 40 Hz 40 Hz
d1-03 Frequency Reference 3 30 Hz 30 Hz
d1-04 Frequency Reference 4 60 Hz 60 Hz
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H1-04
H1-05
H1-06
H3-10 A2 Not Used F NA
A1-01 Access Level 0 0
Multi-Function Input Sel 4
(Terminal S4)
Multi-Function Input Sel 5
(Terminal S5)
Multi-Function Input Sel 6
(Terminal S6)
Setting
V1000 J1000
Motor
FLA
V1000 J1000
Motor
FLA
3 3
4 4
5 NA
Motor
FLA
Setting
Motor
FLA
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C02 DROPS bELOW 700 PPM)
Parameter
A1-01 Access Level 2 2
b1-01 Reference Source (Frequency) 0 0
b1-17 VFD Start-Up Setting 1 1
C1-01 Acceleration Time 30 sec. 30 sec.
C1-02 Deceleration Time 30 sec. 30 sec.
C6-02 Carrier Frequency 1 1
d1-01 Frequency Reference 1 60 Hz 30 Hz
d1-02 Frequency Reference 2 30 Hz 60 Hz
d2-02 Ref Lower Limit 50% 50%
E2-01 Motor Rated FLA
H3-10 A2 Not Used F NA
A1-01 Access Level 0 0
Setting
V1000 J1000
Motor
FLA
Motor
FLA
Variable Frequency Drives for Energy Recovery Wheel
Optional factory installed VFD for the energy recovery wheel is programmed at the factory per the settings shown below for economizer and frost control modes.
TheVFDprovidedisaYaskawamodelJ1000.Refer
to the VFD instruction manual that ships with the unit when making adjustments.
Parameter Setting–J1000 A1-01 Access Level 2 b1-17 VFD Auto Start 1
C6-02 Carrier Frequency 2
d2-01 Ref Upper Limit 100% or 66%* d2-02 Ref Lower Limit 5% E2-01 Motor Rated FLA Motor FLA
E2-03 Motor No-Load Current
H1-02
H2-01
Multi-Function Input
(Terminal S2)
Multi-Function Output
(MA, MB, MC)
Economizer Signal Source (0-10 VDC)
H3-03
H3-04
L1-01 Elect Thermal Overload 2 L4-01 Frequency Detection Level 20 A1-01 Access Level 0
*36 inch wheel is 66% (40 Hz). All other wheels are 100% (60 Hz).
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
Must be less than
FLA
6
5
Setting
Honeywell
Module
0 100
99 0
Carel
Controller
Model ERV Energy Recovery Unit
17
FACTORY SUPPLIED AND WIRED
G
MULTI-VOLTAGE PRIMARY
24 SECONDARY
TR1
C
FU5
TO UNIT
MAIN POWER
L3
L2
L1
DS1
SUPPLY DAMPER
D2
ENERGY WHEEL
R1
R
TR1
SO
SR
3
FR
FC
2-10V
-
+
1
TR
5
4
2
SR+
RETURN AIR SENSOR
MIXED AIR
SENSOR
T T1
620 OHM RESISTOR OR
OUTDOOR AIR
SENSOR
SO+
4
S1
VFD-W
L3
3
4
SC
L2
L1
MCT3MA
T2
T1
PS1
NO CCOM NO
TS1
6
FROST CONTROL
A1T1A2
B1
16
15
T1
ENERGY WHEEL
S1
R1
LEGEND
CC COMPRESSOR CONTACTOR CF CONDENSING FAN CONTACTOR CH COMPRESSOR SUMP HEATER D DAMPER DB POWER DISTRIBUTION BLOCK DL DAMPER LIMIT SWITCH DS DISCONNECT SWITCH EC ECONOMIZER CONTROLLER FCS CONDENSOR FAN CYCLE SWITCH FU FUSES FU5 CONTROL TRANSFORMER FUSES (NOT ON CLASS II) FZ1 FREEZE PROTECTION HPS HIGH PRESSURE SWITCH (MANUAL RESET) LPS LOW PRESSURE SWITCH PS1 WHEEL FROST PRESSURE SWITCH PS2 SUPPLY DIRTY FILTER PRESSURE SWITCH PS3 EXHAUST DIRTY FILTER PRESSURE SWITCH R1 ENERGY WHEEL RELAY/CONTA CTOR R2 OCCUPIED/UNOCCUPIED RELAY R3 EXHAUST BLOWER VFD RELAY R4 SUPPLY BLOWER VFD RELAY R5 MODULATING WHEEL FROST CONTROL RELAY R6 ECONOMIZER RELAY R7 COMPRESSOR INTERLOCK RELAY R8 EVAP RELAY (INDIRECT) R9 EVAP RELAY (DIRECT) R10 UNIT RELAY S1 FAN SWITCH S2 ROTATION SENSOR REED SWITCH S3 ROTATION SENSOR REED SWITCH S4 CALL FOR HEAT SWITCH S5 BYPASS SWITCH S6 CALL FOR COOL SWITCH (FIRST STAGE) S7 CALL FOR COOL SWITCH (SECOND STAGE) ST MOTOR STARTER T1 FROST CONTROL TIMER TYPICAL SETTINGS t1(OFF) = 5 MIN., t2(ON) = 30 MIN. T2 ROTATION SENSOR TIMER T3 ROTATION SENSOR TIMER T4 ECONOMIZER WHEEL JOG TIMER TYPICAL SETTINGS t1(OFF) = 3 HRS., t2(ON) = 10 SEC. T5 EVAP DELAY OFF TIMER T6 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) T7 COMPRESSOR MINIMUM OFF TIMER (TYP. 3 MIN.) TR TRANSFORMER TS1 FROST CONTROL THERMOSTAT (JUMPER - HEAT ) CLOSES ON TEMP. DECREASE TYPICAL SETTING 5º F. TS2 ECONOMIZER LOW LIMIT THERMOSTAT (JUMPER - HEAT ) OPENS ON TEMP. DECREASE TYP. SETTING 20º OFFSET OR 50ºF. TS3 ECONOMIZER UPPER LIMIT THERMOSTAT (JUMPER - HEAT) CLOSES ON TEMP. DECREASE TYP. SET TING 65º F./2º DIFF. TS4 ROOM OVERRIDE SENSOR TS5 INLET AIR POST HEATER LOCKOUT THERMOSTAT (AFTER WHEEL) CLOSES ON TEMP. DECREASE TYPICAL SETTING 65º F. TS6 INLET AIR COMPRESSOR LOCKOUT THERMOSTAT (JUMPER-HEAT) OPENS ON TEMP. DECREASE TYPICAL SETTING 60º F./2º DIFF.
A2 A1
o FIELD WIRED
FIELD CONTROL WIRING RESISTANCE SHOULD NOT EXCEED 0.75 OHM. IF RESISTANCE EXCEEDS 0.75 OHM THEN CONSULT FACTORY. USE 14 GAUGE MINIMUM WIRE THICKNESS FOR CONTROL WIRING.
REPLACEMENT FUSES: MUST HAVE A MINIMUM I.R. RATING OF 5 KA
CAUTION:
UNIT SHALL BE GROUND IN ACCORDANCE WITH N.E.C. POWER MUST BE OFF WHILE SERVICING.
USER INTERFACE CONNECTIONS:
*
*
*
*
*
*
o
*
*
*
*
*
*
*
*
D1
EXHAUST DAMPER
GROUND
FR FC
CR
CR
FROST CONTROL INDICATOR
6C
12 C
ROTATION INDICATOR
DIRTY FILTER INDICATOR SHOWN AS 24V POWER FROM UNIT.
SUPPLY DIRTY FILTER SWITCH
EXHAUST DIRTY FILTER SWITCH
DIRTY FILTER INDICATOR SHOWN AS 24V POWER FROM UNIT.
USER INTERFACE CONNECTIONS:USER INTERFACE CONNECTIONS:USER INTERFACE CONNECTIONS:
USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICATOR DEVICES.USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICATOR DEVICES.USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICATOR DEVICES.
USER TO VERIFY THAT TR1 CAN HANDLE THE VA LOAD OF INDICATOR DEVICES.
TO FR AND FC
ON VFD-W
SEE BELOW FOR TERMINAL CONNECTIONS
C
NC NO
NC
C
NO
ECONOMIZER CONTROL
S6
Y1
MOTOR
MOTOR
EXHAUST FAN
SUPPLY FAN
SC
R4
R3
1
L1
L3
L2
S1
1
0-10 VDC
0-10 VDC
3
FR
VFD-S
3
FC
T1
T3
T2
SC
L1
L3
L2
S1
FR
VFD-E
FC
T1
T3
T2
VFD-E O.L.
MB MC
R3
27
EXHAUST FAN
VFD-S O.L.
MB MC
R4
27
SUPPLY FA N
6R38
*
*
6
2
NC
S2
1
T2
C
12
MC
ROTATION SENSOR
MA
ON VFD-W
TO MA AND MC
*
EC
THERMOSTAT(S) TS1,
24 VAC
THERMOSTAT CONTROLLER(S)
OA-SENSOR
SENSOR
COM
o
PS2
PS3
Typical Wiring Diagram
Following is an example of a typical wiring diagram located in the unit control center. This wiring diagram includes a legend highlighting which accessories were provided with the unit. Factory wiring and field wiring are also indicated. This particular example includes 1) variable frequency drives on the blowers requiring a modulating input, 2) modulating energy recovery wheel with factory controls for economizer, 3) energy recovery wheel rotation sensor, 4) outdoor air and exhaust air dirty filter switches, 5) motorized outdoor air and exhaust air intake dampers, and 6) timed exhaust frost control. Many other factory installed and wired accessories are available.
Model ERV Energy Recovery Unit
18
Rotation Sensor
The rotation sensor monitors energy recovery wheel rotation. If the wheel should stop rotating, the sensor will close a set of contacts in the unit control center. Field wiring of a light (or other alarm) between terminals R & 12 in the unit control center will notify maintenance personnel when a failure has occurred (refer to Remote Panel Wiring Schematics section for wiring details).
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the outdoor air filters, exhaust air filters or both. If the pressure drop across the filters exceeds the set point, the sensor will close a set of contacts in the unit control center. Field wiring of a light (or other alarm) to these contacts will notify maintenance personnel when filters need to be replaced.
The switch has not been set at the factory due to external system losses that will affect the switch. This switch will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to the unit control center or in unit control center.
To adjust the switch, the unit must be running with all of the access doors in place, except for the compartment where the switch is located (exhaust intake compartment). Model ERV units require the opening around the control center to be covered (with cardboard, plywood, etc.) to set up the dirty filter switch.
The adjusting screw is located on the top of the switch. Open the filter compartment and place a sheet of plastic or cardboard over 50% of the filter media. Replace the filter compartment door. Check to see if there is power at the alert signal leads (refer to electrical diagram).
Whether there is power or not, turn the adjustment screw on the dirty filter gauge (clockwise if you did not have power, counterclockwise if you did have power) until the power comes on or just before the power goes off. Open the filter compartment and remove the obstructing material. Replace the door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for operation.
CO2 Sensor
This accessory is often used to provide a modulating control signal to a variable frequency drive to raise and lower airflow in relationship to the CO2 levels in the space. This strategy is often referred to as Demand Control Ventilation and provides further energy savings to the system. Follow instructions supplied with sensor for installation and wiring details.
Service Outlet
120 VAC GFCI service outlet ships loose for field installation. Requires separate power source so power is available when unit main disconnect is turned off for servicing.
Vapor Tight Lights
Vapor tight lights provide light to each of the compartments in the energy recovery unit. The lights are wired to a junction box mounted on the outside of the unit. The switch to turn the lights on is located in the unit control center. The switch requires a separate power source to allow for power to the lights when the unit main disconnect is off for servicing.
Setscrew (on front of switch) must be manually adjusted after the system is in operation.
Negative pressure connection is toward the ‘front or top’ of the switch. (senses blower side
of filters)
Positive pressure connection is toward the ‘back or bottom’ of the switch. (senses air inlet side of filters)
Model ERV Energy Recovery Unit
19
Remote Control Panel and Wiring
G
C
R
7-Day Timer
S1 - Unit On/Off
Terminal Block
in Unit
Control Center
G
C
R
On Off
BMS
Auto
Terminal Block
in unit
Control Center
W1
12
7
6
Y2
Y1
G
C
R
NC
C
NC
C
NO
NO
Exhaust Dirty Filter
Supply Dirty Filter
Rotation Sensor
Economizer
PS2
PS3
Frost Control
Unit On/Off
NC
NC
NO
C
NO
C
Exhaust Dirty Filter
Supply Dirty Filter
Hot
L1
PS2
PS3
Schematics
The remote panel is available with a number of different alarm lights and switches to control the unit. The remote panel ships loose and requires mounting and wiring in the field
The remote panel is available with the following options:
 • Uniton/offswitch  • Uniton/offlight  • 7-daytimeclock  • Hand/off/autoswitch  • Timedelayoverride  • Economizerlight  • Frostcontrollight  • Exhaustairdirtylterlight  • Outdoorairdirtylterlight  • Wheelrotationsensorlight
Refer to Electrical Connections section for Field Control Wiring recommendations.
7-Day Timer or On/Off Switch
Indicator Lights powered by the ER Unit
Dirty Filter Indicator (power by others)
For 7-Day Timer, use blue and black wires. Red wires should be capped off.
Hand/Off/Auto Switch
Hand/Off/Auto Switch allows the unit to “Off” - off “On” - Manual Operation “Auto” - Unit is controlled by BMS, RTU, etc.
NOTE: RTU controllers are by others.
Refer to Pressure Switch for voltage and load ratings.
Model ERV Energy Recovery Unit
20
Sensors Mounted by Factory
RAI
RAF-P
RA
FILTER
OAAWOAF-A
OAD
SUPPLY BLOWER
TO
INSIDE
FROM
INSIDE
EW-P
OAW-P
ENERGY WHEEL
EAWEF-A
OAI
OA
FILTER
OAF-P
TO
OUTSIDE
FROM
OUSTIDE
EXHAUST BLOWER
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for the controls contractor to connect the Building Management System for monitoring purposes.
Temperature Sensors - 1K Ohm RTD
Drawing Labels Terminal Strip Labels
OAI OA/Supply Inlet Temp OAAW OA After Wheel RAI RA/Exhaust Inlet Temp OAD Supply Discharge Temp EAW Exhaust After Wheel Temp
Pressure Sensors (analog or digital)
Drawing Labels Terminal Strip Labels
OAF-P OA/Supply Filter Pressure OAW-P Outdoor Air Wheel Pressure RAF-P RA/Exhaust Filter Pressure EW-P Exhaust Wheel Pressure
Amp - Current Sensors (analog or digital)
Drawing Labels Terminal Strip Labels
OAF-A Supply Fan Amps EF-A Exhaust Fan Amps
Model ERV Energy Recovery Unit
21
Start-Up
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
Do not operate energy recovery ventilator without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to internal components may result and void warranty.
General Start-Up Information
Every installation requires a comprehensive start­up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed.
Unit Model Number _______________________________
Unit Serial Number _______________________________
Energy Wheel Date Code __________________________
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check as items are
completed.
o Disconnect and lock-out all power switches
o Remove any foreign objects that are located in the
energy recovery unit.
o Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and accessories for tightness.
(e.g. ERV-361)
(e.g. 04C99999 or 10111000)
(e.g. 0450)
o Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing. If rubbing occurs, refer to Start-Up section for more information.
o Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more information).
o Filters can load up with dirt during building
construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood (refer to Routine Maintenance section).
o Verify that non-motorized dampers open and close
properly.
o Check the tightness of all factory wiring
connections.
o Verify control wire gauge (refer to the Electrical
Connections section).
o Verify diameter seal settings on the energy
recovery wheel (refer to Start-Up section for more information).
SPECIAL TOOLS REQUIRED
• VoltageMeter(withwireprobes)
• AmperageMeter
• Thermometer
• Tachometer
• Inclinemanometerorequivalent
Start-Up Checklist
The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must be collected while the unit is running. In order to measure volts & amps, the control center door must be open, and the unit energized using a crescent wrench to turn the disconnect handle.
Check line voltage at unit disconnect _______ L1-L2 volts _______ L2-L3 volts _______ L1-L3 volts
Motor Amp Draw
  •SupplyFan •ExhaustFan
_______ L1 amps ______ L1 amps _______ L2 amps ______ L2 amps _______ L3 amps ______ L3 amps
  •EnergyWheel
_______ L1 amps _______ L2 amps _______ L3 amps
Fan RPM _______ Supply Fan ______ Exhaust Fan
Correct fan rotation direction Supply Fan Yes / No Exhaust Fan Yes / No
Model ERV Energy Recovery Unit
22
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit?
Frost Control Application / Operation section: Setting Factory Default
Yes No Frost Control set point 5ºF
Differential 2ºF Timer Refer to IOM
Yes No Frost Control Modulating Refer to IOM
Economizer Application / Operation section:
Yes No Economizer (temperature)
Set point 65ºF
Offset 20ºF
Differential 2ºF
Yes No Economizer (enthalpy)
Set point D
Yes No Economizer (modulating) Refer to IOM
Optional Accessories section: Operational
Yes No Wheel Rotation Sensor Yes No N/A
Yes No OA Dirty Filter Sensor Yes No N/A
Yes No EA Dirty Filter Sensor Yes No N/A
Yes No CO2 Sensor Yes No N/A
Yes No Service Outlet Yes No N/A
Yes No Vapor Tight Lights Yes No N/A
Yes No Remote Control Panel Yes No N/A
Variable Frequency Drives section: Operational
Yes No Blower VFDs Yes No N/A
Yes No Wheel VFD Yes No N/A
Damper section: Operational
Yes No Outdoor Air Damper Yes No N/A
Yes No Exhaust Air Damper Yes No N/A
Model ERV Energy Recovery Unit
23
Unit Start-Up
Belt Span
Deflection =
Belt Span
64
WRONG WRONG
WRONG CORRECT
WRONG WRONG
WRONG CORRECT
MOTOR
FA N
MOTOR
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Airflow
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
Backward Inclined
Forward Curved
Refer to Parts List section for component locations.
Fans
The ERV models contain two forward curved (supply & exhaust) fans. These forward curved fans should be checked for free rotation. If any binding occurs, check for concealed damage and foreign objects in the fan housing. Be sure to check the belt drives per the start-up recommendations in the following section.
CAUTION
When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult Greenheck to determine if the unit can operate safely at the new conditions.
Fan Performance Modifications
Due to job specification revisions, it may be necessary to adjust or change the sheave or pulley to obtain the desired airflow at the time of installation. Start-up technician must check blower amperage to ensure that the amperage listed on the motor nameplate is not exceeded. Amperage to be tested with access doors closed and ductwork installed.
Forward Curved
Exhaust Fan
5. Place belts over sheaves. Do not pry or force belts, as this could result in damage to the cords in the belts.
6. With the fan off, adjust the belt tension by moving the motor base. (See belt tensioning procedures in the Routine Maintenance section of this manual). When in operation, the tight side of the belts should be in a straight line from sheave to sheave with a slight bow on the slack side.
Direction of Fan Wheel Rotation
Blower access is labeled on unit. Check for proper wheel rotation by momentarily energizing the fan. Rotation is determined by viewing the wheel from the drive side and should match the rotation decal affixed to the fan housing (see Rotation Direction figures). If the wheel is rotating the wrong way, direction can be reversed by interchanging any two of the three electrical leads. Check for unusual noise, vibration, or
overheating of bearings. Refer to the Troubleshooting section of this manual if a problem develops.
Fan Belt Drives
The fan belt drive components, when supplied by Greenheck, have been carefully selected for the unit’s specific operating condition. Utilizing different components than those supplied could result in unsafe operating conditions which may cause personal injury or failure of the following components:
 •FanShaft •Bearings •Motor  •FanWheel • Belt
Tighten all fasteners and set screws securely and realign drive pulleys after adjustment. Check pulleys and belts for proper alignment to avoid unnecessary belt wear, noise, vibration and power loss. Motor and drive shafts must be parallel and pulleys in line (see diagrams in this section).
Belt Drive Installation
1. Remove the protective coating from the end of the fan shaft and assure that it is free of nicks and burrs.
2. Check fan and motor shafts for parallel and angular alignment.
3. Slide sheaves on shafts. Do not drive sheaves on as this may result in bearing damage.
4. Align fan and motor sheaves with a straight-edge or string and tighten.
Model ERV Energy Recovery Unit
24
Fan RPM
Supply fan and exhaust fan will have an adjustable motor pulley (on 15 HP and below) preset at the factory to the customer specified RPM. Fan speed can be increased or decreased by adjusting the pitch diameter of the motor pulley. Multi-groove variable pitch pulleys must be adjusted an equal number of turns open or closed. Any increase in fan speed represents a substantial increase in load on the motor. Always check the motor amperage reading and compare it to the amperage rating shown on the motor nameplate when changing fan RPM. All access doors must be installed except the control center door. Do not operate units with access doors open or
without proper ductwork in place as the fan motors will overload.
Vibration
Excessive vibration may be experienced during initial start-up. Left unchecked, excessive vibration can cause a multitude of problems, including structural and/or component failure. The most common sources of vibration are listed.
Many of these conditions can be discovered by
careful observation.
Wheel Unbalance Drive Pulley Misalignment Incorrect Belt Tension Bearing Misalignment Mechanical Looseness Faulty Belts Drive Component Unbalance Poor Inlet/Outlet Conditions Foundation Stiffness
Refer to the Troubleshooting section of this manual for corrective actions. If observation cannot locate the source of vibration, a qualified technician using
vibration analysis equipment should be consulted. If the problem is wheel unbalance, in-place balancing can be done.
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To eliminate this undesirable effect, the use of heavy canvas connectors is recommended.
Energy Recovery Wheel
The ERV models contain a total energy recovery wheel. The wheels are inspected for proper mechanical operation at the factory. However, during shipping and handling, shifting can occur that may affect wheel operation. The wheel is accessible through the access door marked “Energy Wheel Cassette Access”. For the ERV­251, 361, 521, and 522, the wheel cassette(s) slide out. Due to the size and weight of the ERV­581 and 582 wheels, they remain stationary and all maintenance is performed in place. There is room inside the unit to perform energy recovery wheel servicing.
Turn the energy recovery wheels by
Adjustable
Air Seals
hand to verify free operation. The wheel should rotate smoothly and
Drive Belt
should not wobble.
Drive Pulley
Inside layout of ERV-361
Inside layout of ERV-522
Bearing
Support
Label
showing
cassette
serial #
and date
code
Drive Belt
Inspect the drive belt. Make sure the belt rides smoothly through the pulley and over the wheel rim.
Air Seals
Check that the air seals located around the outside of the wheel and across the center (both sides of wheel) are secure and in good condition. Air seal clearance is determined by placing a sheet of paper, to act as a feeler gauge, against the wheel face. To access seals, enter the unit for the ERV-581 and 582, or pull out the cassette for the ERV-251, 361, 521, and 522, following the instructions in the Energy Recovery Wheel Maintenance section. To adjust the air seals, loosen all eight seal retaining screws. These screws are located on the bearing support that spans the length of the cassette through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper.
Replace cassette into unit, plug in wheel drive, replace access door and apply power. Observe by opening door slightly (remove filters if necessary to view wheel) the wheel should rotate freely at about 50-60 RPM.
Model ERV Energy Recovery Unit
25
Routine Maintenance
Belt Span
Deflection =
Belt Span
64
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
Once the unit has been put into operation, a routine maintenance program should be set up to preserve reliability and performance. Items to be included in this program are:
Lubrication
Apply lubrication where required
Dampers
Check for unobstructed operation
Fan Belts
Check for wear, tension, alignment
Motors
Check for cleanliness
Blower Wheel & Fasteners
Check for cleanliness Check all fasteners for tightness Check for fatigue, corrosion, wear
Bearings
Check for cleanliness Check set screws for tightness Lubricate as required
External Filter
Check for cleanliness - clean if required
Internal Filter
Check for cleanliness - replace if required
Door Seal
Check if intact and pliable
Energy Recovery Wheel
Check for cleanliness - clean if required Check belt for wear Check pulley, bearings, and motor
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication. Apply lubrication where required. Any components showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation.
Model ERV Energy Recovery Unit
26
Dampers
Check all dampers to ensure they open and close properly and without binding. Backdraft dampers can be checked by hand to determine if blades open and close freely. Apply power to motorized dampers to ensure the actuator opens and closes the damper as designed.
Fan Belts
Belts must be checked on a regular basis for wear, tension, alignment, and dirt accumulation. Premature or frequent belt failures can be caused by improper belt tension (either too loose or too tight) or misaligned sheaves. Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result in failure of the fan and/or motor bearings. Conversely, loose belts will cause squealing on start-up, excessive belt flutter, slippage, and overheated sheaves. Both loose and tight belts can cause fan vibration.
When replacing belts on multiple groove drives, all belts should be changed to provide uniform drive loading. Do not pry belts on or off the sheave. Loosen belt tension until belts can be removed by simply lifting the belts off the sheaves. After replacing belts, insure that slack in each belt is on the same side of the drive. Belt dressing should never be used.
Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced before new belts are installed.
The proper belt setting is the lowest tension at which the belts will not slip under peak load operation. For initial tensioning, set the belt deflection at 1/64­inch for each inch of belt span (measured half­way between sheave centers). For example, if the belt span is 64 inches, the belt deflection should be one inch (using moderate thumb pressure at mid-point of the drive). Check belt tension two times during the first 24 hours of operation and periodically thereafter.
Fan Motors
Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only. Removing dust and grease buildup on the motor housing assists proper motor cooling. Never wash-down motor with high pressure spray. Greasing of motors is only intended when fittings are provided. Many fractional motors are permanently lubricated for life and require no further lubrication.
Fan Wheel & Fasteners
Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe operation. Inspect fan impeller and housing for fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness. A proper maintenance program will help preserve the performance and reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require no further lubrication under normal use. Normal use being considered -20ºF to 120ºF and in a relatively clean environment. Some bearings are re-lubricatable and will need to be regreased depending on fan use. Check your bearings for grease zerk fittings to find out what type of bearing you have. If your fan is not being operated under normal use, bearings should be checked monthly for lubrication.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the supply weatherhood (if the weatherhood option was purchased). Filters should be checked and cleaned on a regular basis for best efficiency. The frequency of cleaning depends upon the cleanliness of the incoming air. These filters should be cleaned prior to start-up.
To access these filters, remove bottom bolt in the access door on the side of the weatherhood. Slide the access door up and then pull bottom out to remove door. Then, slide the filters out (see picture at right).
Clean filters by rinsing with a mild detergent in warm water.
Outdoor air intake hood
mesh filter access
Internal Filter Maintenance
The ERV units will typically be provided with 2-inch, pleated filters in the outdoor air and exhaust airstreams. These filters should be checked per a routine maintenance schedule and replaced as necessary to ensure proper airflow through the unit. See table for pleated filter size and quantity for each unit. Replacement filters shall be of same performance and quality as factory installed filters. Filter type must be pleated design with integral metal grid. Two acceptable filter replacements are Aerostar Series 400 or Farr 30/30®.
Filter Size and Quantities
Unit Size
ERV-251 16 x 25 1 1
ERV-361 16 x 20 2 2
ERV-521 16 x 25 3 3
ERV-581 16 x 20 6 6
ERV-522 16 x 25 7 7
ERV-582 20 x 25 6 6
All dimensions in inches.
Internal
Filter Size
Quantity
Supply
Quantity
Exhaust
Outdoor Air Filters: Access to the outdoor air filters is through the door labeled as “Filter Access” on the outdoor air side of the unit.
Exhaust Air Filters: Access to the exhaust air filters is through the door labeled as “Filter Access” on the exhaust air side of the unit.
Refer to Access Door Descriptions section for additional information on filter locations.
Door Seal Maintenance
ERV-251, 361, 521, and 581: Closed cell foam
tape is installed on the perimeter of the door. Inspect at least annually to ensure that the seal is still intact.
ERV-522 & 582: Slip-on type vinyl seal is installed on the perimeter of the door openings. Inspect at least annually to ensure that seal is still pliable and intact.
Energy Recovery Wheel Maintenance
Annual inspection of the energy recovery wheel is recommended. Units ventilating smoking lounges and other non-clean air spaces should have energy recovery wheel inspections more often based upon need. Inspections for smoke ventilation applications are recommended bimonthly to quarterly until a regular schedule can be established.
Accessing the Energy Recovery Wheel in Models ERV-251, 361, 521 and 581
Disconnect power to the ERV. Remove access panel(s) labeled “Energy Wheel Cassette Access”.
Unplug the wheel drive motor. The center channel must be removed to access the energy wheel cassette. Use a 5/16 inch open or closed wrench to remove the three (3) fasteners that hold the center channel in place.
Pull the cassette halfway out as shown. (Except on ERV-581, wheel is stationary).
When service is complete, reattach the center channel before putting access panels back in place.
Access to wheel through
outdoor air filter door
Model ERV Energy Recovery Unit
27
Accessing the Energy Recovery Wheel in
Bracket Segment Retainer
Lift away from segment
Catch Segment Retainer
Push toward center
Center of Wheel
Spoke
Inside of wheel rim
Models ERV-522 and 582
Disconnect power to the ERV. Remove access panel(s) labeled “Energy Wheel Cassette Access”, which reveals the energy wheel cassette. There are additional panels that must be removed in order to slide out the cassettes. (See pictures providing additional visual information).
Unplug the wheel drive motor and pull the cassette halfway out as shown.
NOTE: ERV-522 has two energy wheels with access panels for both wheels. Wheels slide out on opposite corners.
Energy recovery wheels for ERV-582 are hard-wired and not designed to slide out.
This panel must be removed before the energy wheel can slide out. (ERV-522 only)
Removing the Energy Recovery Wheel in ERV-251
First, remove the drive belts and the collars in both bearings. On the pulley side of the cassette, remove the four (4) fasteners that hold the bearing support channel in place. Once the bearing support is removed the wheel can be pulled from the cassette. To replace the wheel, reverse this procedure.
Removing the Energy Recovery Wheel Segments ERV-361, 521, 581, 522 and 582 (stainless steel rim)
Steel retainers are located on the inside of the wheel rim. Push the retainer towards the center of the wheel, then lift up and away to release segments.
28
Model ERV Energy Recovery Unit
Important! Place retainers back in the original position before rotating the energy recovery wheel, otherwise damage to retainer will occur.
Wheel segment removed
Cleaning the Energy Recovery Wheel
If the wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only excessive buildup of foreign material needs to be removed. Discoloration and staining of energy recovery wheel does not affect its performance.
Thoroughly spray wheel matrix with household cleaner such as Fantastik® or equivalent. Gently rinse with warm water and using a soft brush remove any heavier accumulation. A detergent/water solution can also be used. Avoid aggressive organic solvents, such as acetone. The energy recovery wheel segments can be soaked in the above solution overnight for stubborn dirt or accumulation.
After cleaning is complete, shake the excess water from the wheel or segments. Dry wheel or segments before placing them back into the cassette. Place wheel or segments back into cassette by reversing removal procedures.
CAUTION
Do not clean energy recovery wheel segments with water in excess of 140ºF (60ºC).
Do not dry energy recovery wheel segments in air in excess of 140ºF (60ºC).
The use of a pressure washer to clean segments is not recommended. Damage could result.
Energy Recovery Wheel Belt
Inspect belts each time filters are replaced. Belts that look chewed up or are leaving belt dust near the motor pulley may indicate a problem with the wheel. Be sure to inspect wheel for smooth and unrestricted rotation. If a belt requires replacement, contact the local Greenheck
Wheel Belt & Pulley
representative. Instructions for replacement will ship with the new belt.
Energy Recovery Wheel Bearing
In the unlikely event that a wheel bearing fails, the bearing is behind a removable plate on the wheel support beam which is accessible through the outdoor air filter door (and exhaust filter door on the ERV­522 and 582). Contact the local Greenheck representative for detailed
Wheel Bearing
instructions on how to replace the bearing.
Model ERV Energy Recovery Unit
29
Parts List
6
9
5
Inside layout of ERV-361 Inside layout of ERV-522
(shown with intake weatherhood, exhaust weatherhood, outdoor air filters, and exhaust air filters)
7
8
3
4
1. Supply blower
 • Forwardcurvedfan  • Adjustablemotormountforbelttensioning  • Adjustablesheavesforspeedcontrol
8
4
3
1
2
5
9
1
3
4
7
6
6. Optional exhaust weatherhood with birdscreen
7. Optional supply and exhaust air filter racks for 2 inch pleated, 30% efficient filters
2. Vibrations isolators (quantity 4 per blower)
 • Neoprene
3. Energy recovery wheel cassette
 • onewheelonmodelsERV-251,361,521&581  • twowheelsonmodelsERV-522&582
4. Removable energy recovery wheel segments
5. Optional supply weatherhood with 2 inch aluminum mesh filter
8. Electrical control box (standard features)
 • Singlepointpower  • Disconnectinterlockedwithaccessdoor  • Motorstartersforthesupplyblower,exhaust
blower and energy wheel motors
 • 24VACcontrolcircuitwithterminalstrip
9. Exhaust blower
 • Forwardcurvedfan  • Adjustablemotormountforbelttensioning  • Adjustablesheavesforspeedcontrol
Model ERV Energy Recovery Unit
30
Sequence of Operation
Basic Unit
The ERV units are prewired such that when a call for outside air is made (via field supplied 24 VAC control signal wired to unit control center), the supply fan, exhaust fan and energy wheel are energized and optional motorized dampers open. The ERV is normally slaved (24 volt) to the roof top air handler. When the roof top air handler starts, the auxiliary contactor in the air handler closes to start the ERV.
Summer Operation
Outdoor air is preconditioned (temperature and moisture levels are decreased) by the transfer of energy from the cooler, drier, exhaust air via the energy recovery wheel. The preconditioned air is typically mixed with return air going back to the air handler for final conditioning.
Economizer Operation: Refer to Economizer Application/Operation section.
Winter Operation
Outdoor air is preconditioned (temperature and moisture levels are increased) by the transfer of energy from the warmer, more humid exhaust air via the energy recovery wheel. The preconditioned air is typically mixed with return air going back to the air handler for final conditioning.
Frost Control Operation: Refer to Frost Control Application/Operation section.
Other Accessories:
Rotation Sensor: Refer to Optional Accessories section
Dirty Filter Sensor: Refer to Optional Accessories section
CO2 Sensor: Refer to Optional Accessories section
Variable Frequency Drive (VFD) on Blowers: VFDs
on blowers are often used as part of a demand control ventilation system. This type of system takes advantage of varying occupancy through the use of CO2 sensors to monitor space CO2 levels. If CO2 levels are low in the space, the VFD will operate the blowers at minimum airflow required by code. As the space occupancy increases and CO2 levels increase, the VFD will increase the amount of fresh outdoor air being brought in to offset the CO2 levels in the space (exhaust airflow is increased proportionally as outdoor airflow increases). As CO2 levels come back down, the airflow will decrease back to minimum requirements.
Model ERV Energy Recovery Unit
31
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low, prior to contacting the factory, please determine the following information:
Unit #1 Unit #2 Unit #3 Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Pressure Drop Across Energy Recovery Wheel
Outdoor Air Side
Exhaust Air Side
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in accordance with SMACNA and AMCA guidelines.
Model ERV Energy Recovery Unit
32
Troubleshooting – Unit
Symptom Possible Cause Corrective Action
Blown fuse or open circuit breaker.
Defective motor or capacitor. Replace.
Replace fuse or reset circuit breaker and check amps.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Motor starter overloaded. Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long (resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated. Voltage supplied to starter coil must be within +10% / -15% of nominal voltage stated on the coil.
CFM too high. Check cfm and adjust drives if needed.
Static pressures are higher or lower than design.
Blower rotation is incorrect. Check rotation and reverse if necessary.
Motor voltage incorrect.
Motor horsepower too low.
Shorted windings in motor. Replace motor.
Check for On/Off switches. Check for correct supply voltage.
Check for broken or loose belts. Tighten loose pulleys.
Shorten wiring run to mechanical room or install a relay which will turn unit on/off. Consult Factory for relay information.
Need to increase supply power or use a special control transformer which is sized for the actual supply power.
If higher, ductwork should be improved. If lower, fan rpm should be lower.
Check motor nameplate versus supplied voltage.
See specifications and catalog for fan curves to determine if horsepower is sufficient.
Low airflow (cfm)
High airflow (cfm)
Unit damper not fully open. Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Dirty filter or energy wheel.
Leaks in ductwork. Repair.
Elbows or other obstructions may be obstructing fan outlet.
Belt slippage. Adjust belt tension.
Blower fan speed too high.
Filter(s) not in place. Install filters.
Insufficient static pressure (Ps) (airflow resistance).
Improve ductwork to eliminate losses using good duct practices.
Check for correct drives and rpm with catalog data.
For 3-phase, see Direction of Fan Wheel Rotation under Unit Start-Up section.
Follow cleaning procedures in Routine Maintenance section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed if necessary.
Induce Ps into system ductwork. Make sure grilles and access doors are installed. Decrease fan speed if necessary.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Model ERV Energy Recovery Unit
33
Troubleshooting – Unit
Symptom Possible Cause Corrective Action
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Exhaust Only frost control sensors are tripping.
Adjust frost temperature sensor set point as needed.
Energy wheel does
NOT turn
Energy wheel runs
intermittently
Air seals are too tight.
“Economizer” sensors are operating.
No power to wheel motor.
Wheel drive belt.
VFD overload. (OL1 on readout)
Wheel motor overloads are tripping, due to rubbing between wheel and air seals.
Fan wheel rubbing on inlet.
Bearings.
Wheel out of balance. Replace or rebalance.
Loose wheel on shaft. Tighten wheel setscrew.
Loose motor or blower sheave. Tighten sheave setscrew.
See Energy Recovery Wheel under Unit Start-Up section.
Adjust temperature or enthalpy set points as needed.
Make sure wheel drive is plugged in. Verify power is available.
Check for loose or broken belts. Replace belts (consult factory).
Refer to VFD section. Compare motor amp rating to setting in VFD. Adjust accordingly.
Recheck air seals, make sure they are not too tight. See Energy Recovery Wheel under Unit Start-Up Section.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Belts too loose. Adjust belt tension after 24 hours of operation.
Excessive noise
or vibration
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or service information.
Belts too tight.
Worn belt. Replace.
Motor base or blower loose. Tighten mounting bolts.
Buildup of material on wheel. Clean wheel and housing.
Bearing and drive misaligned. Realign.
Noise being transmitted by duct.
Loosen to maintain a 3/8 inch deflection per foot of span between sheaves.
Make sure ductwork is supported properly. Make sure ductwork metal thickness is sized for proper stiffness. Check duct size at discharge to ensure that air velocities are not too high.
Model ERV Energy Recovery Unit
34
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model ERV Energy Recovery Unit
35
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Greenheck Catalog Energy Recovery Ventilator, Model ERV, provides additional information describing the equipment, fan performance, available accessories, and specification data.
Phone:(715)359-6171•Fax:(715)355-2399•E-mail:gfcinfo@greenheck.com•Website: www.greenheck.com
455924 • Model ERV IOM, Rev. 6, February 2009 Copyright 2009 © Greenheck Fan Corp.
36
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at: www.amca.org.
Loading...