Greenheck Temperature Interlock User Manual

Page 1
Document #471738
Temperature Interlock
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
General Description
Description
Product Specification
Temperature Interlock
International Mechanical Code (IMC) 2006 section
507.2.1.1 Compliant Electrical Package
Provide Greenheck Fan Corporation temperature interlock electrical package as shown on plans and in accordance with the following specification:
The temperature interlock(s) consists of an adjustable thermostat, junction box, fire proof/leak proof threaded fitting (Evergreen Quik-Seal® and/or Evergreen Compression Seal), and shall be a self-contained unit or as part of another pre-engineered electrical control package.
The temperature interlock package shall close a relay powering the fans when the set temperature is reached at the thermostat. The interlock shall hold the circuit closed upon fan switch being turned off until the temperature at the sensor decreases below the set point at which point the timed relay will begin a countdown. Once the countdown has expired and as long as the temperature has remained below the set point, the fans shall shut down.
The temperature interlock package shall be constructed by Greenheck Fan Corporation in accordance with International Mechanical Code. The manufacturer shall provide, upon request, the necessary data that confirms compliance with the code listed above.
Due to continuous research, Greenheck Fan Corporation reserves the right to change specifications without notice.
box or can be added to a pre-engineered fan control center.
Purpose
To meet IMC 2006 section 507.2.1.1, interlock between exhaust fans and cooking equipment. This system will utilize a temperature sensor in the exhaust duct collar or in capture area of hood to detect heat generated from cooking operations and automatically activate the exhaust fans if not already turned on. Field wiring may be required depending on location of components.
Product Application
The temperature interlock is designed to be used with Type I and Type II Hoods. It is not to be used in conjunction with exhaust fire dampers. Greenheck recommends using one interlock per hood system (activates all fans linked to system simultaneously).
Performance Goals
Automatically energize the exhaust fans when cooking equipment generates heat. Basic controls will be provided with a thermostat and will consist of an 8x8 electrical box with controls and a labeled terminal strip to hook-up incoming power and fan starters. An adjustable delay is used to keep the exhaust fans running when the thermostat initially closes to prevent the fan from cycling on and off at startup and shut down. Fans will shut down automatically 20 minutes after the thermostat opens its contact. The time delay can be adjusted from 1-100 minutes based on jobsite requirements.
®
Temperature Interlock
1
Page 2
Table of Contents
Product Specification ........................1
General Description ..........................1
Receiving and Handling .......................2
Installation
Hood Mounting ...........................3
Duct Collar Mounting ......................3
Electrical Connections
Thermostat Connections ...................4
Breaker Panel to Control Box or
Fan Control Center ......................4
Circuit Connections .......................4
Calibration .................................4
Control Circuit Diagrams ....................5-6
Testing ...................................7
Operation ..................................7
Troubleshooting .............................7
Maintenance ...............................7
Frequently Asked Questions ...................8
Replacement Parts ..........................8
Codes and Standards Compliance ..............8
Our Commitment ............................8
Receiving and Handling
Upon receiving the equipment, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Make sure the equipment does not suffer any heavy vibrations or knocks.
Storage
If a temperature interlock must be stored prior to installation it must be protected from dirt and moisture. Indoor storage is recommended. For outdoor storage, cover the hood with a tarp to keep it clean, dry, and protected from UV (ultraviolet) radiation damage.
Improper storage which results in damage to the unit will void the warranty.
Temperature Interlock
2
®
Page 3
Installation
19.525 inches
3 inch air space
2 inch typical
Exhaust Area
Supply Area
(optional)
Sensor Install
(cut out area)
Control Box Mounting
Locate an area with enough space to mount the control box and fasten to the wall. Avoid installing the control box in environments with high magnetic and/or radio frequency interference.
NOTE
Control box may be factory mounted. If so, continue to the next section.
Thermostat Installation - Hood Mounting
Recommended thermostat mounting location is in the flat interior of the hood and at least 8 inches (20.32cm) from light fixture.
3. Place the junction box provided over the fitting on top of the hood, keeping the fitting centered in the box.
4. Thread the thermostat into the compression seal fitting and tighten to 35 ft-lbs. (4.84 m-kgs).
Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. A 11⁄8to 1¼-inch (28.58 to 31.75 mm) diameter hole must be cut into the duct 2inches top. Center the hole along the side of the duct. Make sure that the thermostat will not interfere with any fire system nozzles, or other items installed in the exhaust duct. If an exhaust fire damper is present the hood exhaust collar, it must be removed prior to thermostat installation.
(50.8 mm) above the hood
1. Locate the flat
2. Insert the Evergreen Compression Seal fitting into
Hood Plan View
area(s) at the top
(28.58 to 31.75 mm)
interior of the hood in front of the filters, towards the front of the hood. A 1
1
8 to
1¼ inch (28.58 to 31.75
mm) diameter hole must
be cut into the top of the capture tank. Make
Hood Surface
sure the thermostat will not interfere with the fire system nozzles and is not within 8 inches
(20.32cm) of the light fixtures.
the hole from the inside of the hood, making sure the gasket is placed on the fitting before inserting it into the hole. Install the lock washer and 11⁄2inch (38mm) nut on the threaded portion of the compression seal fitting and tighten securely.
Compression Seal
PN 452614
Gasket
Exploded View (Components)
Octagon Extension
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
(28.58 to 31.75 mm)
Hood Exhaust Collar (front side)
2 inches
(50.8 mm)
2. Insert the Evergreen Quik-Seal fitting into the hole from the inside of the duct, making sure the gasket is placed on the fitting before inserting it into the hole. Install the lock washer and 1
1
2inch (38.1mm) nut on the threaded portion of the Evergreen Quik-Seal fitting and tighten securely.
Gasket
1/2 inch Quik-Seal
Octagon Extension
PN 451168
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
Exploded View (Components)
3. Place the junction box provided over the fitting and tack weld the junction box to the exhaust duct keeping the fitting centered in the box. (Welding optional).
4. Thread thermostat into Evergreen Quik-Seal fitting and tighten to 35 ft-lbs
(4.84 m-kgs).
NOTE
All field installation and wiring of electrical equipment must be done to meet NEC and local codes.
®
Temperature Interlock
3
Page 4
Electrical Connections
Thermostat Connections
1. Run two 14 awg 90°C minimum conductors from each temperature sensor to the appropriate electrical circuit connections. (See Step 3 for connection options).
2. In junction box, connect leads on thermostat to the 14 awg conductors using appropriate size wire nuts.
• Wires are interchangeable with one another.
Wire thermostats in parallel if there are multiple
thermostats utilized.
3. The thermostat(s) wires will land on terminals T1-A and T1-B
CAUTION
Do not connect temperature sensor in series with each other, nor in series with fan power. This can permanently damage the sensors. On/off cycling of the fans will result during start-up and shutdown periods. Use the thermostat for control wiring only.
Calibration
Thermostat is preset by factory to 95°F and has a slow make and break contact. It will make contact on a temperature rise and break contact on temperature fall. The temperature set point may have to be adjusted slightly depending of both ambient and cooking conditions. The adjustment knob is located on the back of the thermostat. Use a small blade screwdriver to make the adjustments.
1. Turn counterclockwise to increase the temperature set point, turn clockwise to decrease the temperature set point.
2. Quarter revolution in either direction corresponds to a 22.5°F adjustment. Be sure to make small adjustments, about 1/16 of a turn (≈6°F) or less at one time.
3. Do not exceed more than one-half revolution in either direction.
4. Check system operation before making additional adjustments.
Switch Connections to Control Box or Fan Control Center
1. Connect a Single Pole Single Throw (SPST) switch to terminals S1H and S1. This is the same whether temperature interlock is in a separate control box or integrated with a kitchen fan control center.
Circuit Connections
1. Standard Interlock Control
120VAC, 10 or 15 amp circuit to terminals H1
and N1
120VAC, 24VAC or other control circuit for fan
starter activation (factory separated from main power connection shown in previous bullet)
- Control circuit power to terminal CP1
- Terminal CP2 to fan starter coils (hot)
2. Kitchen Fan Control Center Integration (KFCC)
120VAC, 15 amp circuit to H1 and N1 in fan
control center
- No additional control circuits are required
- Fan starters are factory-wired
Temperature Interlock
4
®
Page 5
Control Circuit Diagram (Standard Control)
This is an example of a generic wiring diagram for standard control. It provides temperature interlock
function for two exhaust fans and one supply fan. (All starters provided by others, external to this control box).
8 inches
8 inches
4 inches
This Control Panel only provides control power to signal operation of supply and exhaust starters. Starters are NOT provided by manufacturer. Starters to be provided by, wired and mounted by others.
®
Temperature Interlock
5
Page 6
Control Circuit Diagram (Fan Control Center)
This is an example of a generic wiring diagram for temperature interlock integration into a KFCC.
It provides temperature interlock function for one exhaust fan and one supply fan.
To see your job specific drawing, look on the inside panel of the KFCC cabinet.
12 inches
LIG
H T
S FANS
18 inches
6 inches
Temperature Interlock
6
®
Page 7
Testing
Troubleshooting
1. Turn fan switch on, then off to ensure proper fan operation before cooking equipment is started. Once this is verified, testing can proceed.
2. For testing only, locate the time delay relay. Turn the time adjustment knob counterclockwise to the first mark in order to expedite the testing process. Make a note as to where the timer was originally set.
3. Heat up cooking equipment with fans off. Once the temperature reaches the set point of the thermostat the fans will start, preferably within 5minutes. If the fans take more than 5 minutes to start, decrease the temperature set point by turning the adjustment screw 1/16 turn clockwise. Do not apply direct flame to the thermostat
4. If an adjustment was made in Step 3, repeat now.
5. After verification of fan start-up, shut down cooking equipment. The fan switch should still be in the off position. Once cooking equipment has cooled, the thermostat will open triggering the timer to begin. Once time has expired, the fans will shut down. Thermostat operation can be verified by checking voltage (120V) between T1-B and neutral on either the control box or KFCC. 120V will be present when the thermostat senses heat.
6. Once proper operation has been verified, set the dial on the timer relay to its original setting (approximately 20 minute delay).
Fans do not turn on automatically upon cooking equipment activation.
Check wiring to control panel or relay box, thermostats must be wired in parallel
• Temperature set point to high, decrease set point
• No power to fans, check breakers/starters/relays
Fans do not shut off.
• Switch must be in the off position
• Cooking equipment hot, wait for it to cool
• Temperature set point too low, increase set point
Ensure wires connected to appropriate control circuit
• Time delay too great, turn down timer
Fans do not turn on quick enough.
• Decrease temperature set point
Maintenance
Daily
Clean thermostat with cloth and degreaser. Keep clean for best performance. (Can clean weekly depending upon grease accumulation).
Weekly
Dependant on grease production and grease filter type, clean thermostat.
CAUTION
The probes should never be exposed to direct flame. This can cause permanent damage to the probe.
NOTE
During testing, if fans do not start automatically in the first 10 minutes of cooking equipment activation, manually start fans to avoid accidental fire system dump due to heat build-up.
Operation
1. Turn fans on and off using the fan switch. It is normal for the fans to remain running after the switch is turned off. The exhaust thermostat will open after heat is no longer present under the hood which will activate the timer to begin its countdown. Once time has expired, fans will shut down. The timer is adjustable from 1-100 minutes. The recommended time delay setting is approximately 20 minutes.
2. In the event that the cooking equipment is started without turning the fans on manually, the fans will turn on automatically and remain running with the presence of heat under the hood. The exhaust thermostat will open after heat is no longer present under the hood which will activate the timer to begin its countdown. Once time has expired, fans will shut down.
Seasonal
May have to change temperature setting on back of thermostat if ambient kitchen temperatures fluctuate between summer and winter seasons.
Whom to call
Contact your local Greenheck representative.
What to have ready for the call
Sales order, serial number and description of product.
Sales Order Number ________________________
Serial Number ______________________________
®
Temperature Interlock
7
Page 8
Frequently Asked Questions
Replacement Parts
What temperature is the thermostat set from the factory?
95º Fahrenheit.
Will the temperature interlock automatically start/ stop the fans?
When connected properly to fan starters the
temperature interlock will automatically control the fans without input from the user. However, it is intended to be used as a back-up to manual control.
May I connect the power going to my fan directly through the control box?
No, the control box should only use control voltage
only (24-120V), and a separate 120V power source is required to run the temperature interlock controls. Greenheck recommends the use of starters sized for each fan.
What is the purpose of the timer in the control box?
The timer is used to delay the shut down of the fans
to prevent fan on/off cycling while the temperature in the exhaust duct can reach steady state. Without the delay, cycling could occur both on startup or shutdown of cooking equipment. The delay is typically set at 20 minutes.
Can I use one control box for multiple hood systems?
This can be done, however, it is not recommended.
Any one of the thermostats would turn on all hoods running on that control box. It is better to have one hood/fan per control box, plus a significant energy savings can be obtained if one or more of the hoods is not in operation.
Can I still turn my fan on and off?
Yes, the temperature interlock is designed to be
operated with a typical on/off switch. The fan may not turn off immediately after turning the fan switch off, it will sense when the cooking operations have cooled and then turn off.
Part
Number
383923
451168
830125
380926
381460
384905
384908
383271
452614
Thermostat, Vulcan 1C2B9 5/8-inch Type C
Evergreen Quik-Seal, 1/2-inch #171 (1-1/8 inch hole size)
Extension, Octagon (drilled) SC55151-1/2 (380928)
Cover, Octagon Box SC#54-C-1RACO 722
Enclosure, 8X8X4 NEMA3R ELMATE RC-884-SC3R
Terminal Block, Single Pole, DIN-RAIL MT, ABB ZS6
Jumper, DIN-RAIL Terminal Block 2 Pole ABB JB6-2
Timer SSAC #KRDB424 SPST 1-100 min.
Evergreen Compression Seal, 5/8-inch, #302
Description
Codes and Standards Compliance
• UL 710
• National Fire Protection Association (NFPA 96)
• International Mechanical Code (IMC) 2006 Section 507.2.1.1
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
471738 • Temperature Interlock, Rev. 2, November 2012 Copyright 2012 © Greenheck Fan Corporation
8
Loading...