Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
to comply with instructions could result in personal injury and/or property damage!
and/or property damage.
Tubular Centrifugal Fans
TCB Inline
Level 1 & 2
TCBRU Roof Upblast
Level 1 & 2
General Safety Information
Only qualified personnel should install this fan.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. If more
information is needed, contact a licensed professional
engineer before moving forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC) and the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electric Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than max cataloged fan
RPM. Adjustments to fan speed significantly effects
motor load. If the fan RPM is changed, the motor
current should be checked to make sure it is not
exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to a duct while the fan is
running.
TCBRS Roof Supply
Level 1 & 2
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
CAUTION
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
DANGER
Pour écarter les risques d’incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l’installation ou l’entretien.
ATTENTION
Lors de toute intervention sur la soufflante, le moteur
peut être suffisamment chaud pour provoquer une
douleur voire une blessure. Laisser le moteur refroidir
avant toute maintenance.
ATTENTION
Faire preuve de précaution dans les atmosphères
explosives.
®
Tubular Centrifugal Fans1
Page 2
®
Table of Contents
General Safety Information .................... 1
Receiving ................................ 2
Unpacking ............................... 2
Handling ................................. 2
Storage .................................2-3
Inspection and Maintenance During Storage .... 3
Removing from Storage ..................... 3
General Information
Unit and System Identification Tags ........... 4
Pre-Installation Information .................. 4
Electrical Disconnects ...................... 4
Moving Parts ............................. 4
Guards - Motor Cover, Weatherhood, Shaft,
Belt, Inlet or Outlet Guard .................. 4
Access Doors ............................. 4
Air Pressure and Suction .................... 4
Fans - Rigging and Lifting ..................... 5
Installation
Effect of Installation on Performance .......... 5
Typical Installations ........................ 6
Installation of UL/cUL 762 Listed Fans
for Restaurant Exhaust ...................6-7
Drain Connection .......................... 7
Duct Connection .......................... 7
Sealant / Gasket / Seal Replacement .......... 7
V-Belt Drives
V-Belt Drive Installation ..................... 8
Alignment of Pulleys and Belts ............... 8
Radial Gap, Overlap and Wheel Alignment
Radial Gap and Alignment ................... 8
Method for Centering Wheel ................. 8
Radial Gap and Overlap Dimensions ........... 9
Field Coating Touch-up ....................... 9
Unit Start-Up
Visual Inspection of Equipment .............. 10
Check .................................. 10
Additional Steps for Initial Start-Up ........... 10
Upon receiving the product, check to ensure all items
are accounted for by referencing the delivery receipt or
packing list. Inspect each crate or carton for shipping
damage before accepting delivery. Alert the carrier
of any damage detected. The customer will make
notification of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading which
is countersigned by the delivering carrier. If damaged,
immediately contact your Greenheck Representative.
Any physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Fans are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by configuration and size. Handle in
such a manner as to keep from scratching or chipping
the coating. Damaged finish may reduce the ability of
the fan to resist corrosion. Fans should never be lifted
by the shaft, fan housing, motor, belt guard, windband,
or accessories.
Storage
Fans are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the fan and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
• Rotate fan wheel monthly and purge bearings once
every three months
• Energize fan motor once every three months
• Store belts flat to keep them from warping and
stretching
• Store unit in a location which does not have vibration
• After storage period, purge grease before putting fan
into service.
If storage of fan is in a humid, dusty or corrosive
atmosphere, rotate the fan and purge the bearings once
a month. Improper storage which results in damage to
the fan will void the warranty.
Tubular Centrifugal Fans2
INDOOR -
fans and accessories is indoors, above grade, in a low
humidity atmosphere which is sealed to prevent the entry
of blowing dust, rain or snow. Temperatures should be
The ideal environment for the storage of
Page 3
evenly maintained between 30° to 110°F (-1° to 43°C),
wide temperature swings may cause condensation and
“sweating” of metal parts. All accessories must be stored
indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to remove any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ inches
(89 mm)
off
the floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR - Fans designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the fan. The fan should be
elevated on an adequate number of wooden blocks
so it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight and space for periodic inspection. To minimize
water accumulation, place all fan parts on blocking
supports so rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Fan wheels should be blocked to prevent spinning
caused by strong winds.
Removing from Storage
As fans are removed from storage to be installed in their
final location, they should be protected and maintained
in a similar fashion until the fan equipment goes into
operation.
Prior to assembly and installation of the unit and system
components, inspect the fan assembly to make sure it is
in working order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base and accessories for
tightness.
2. Rotate the fan wheel by hand and assure no parts
are rubbing. Access to the wheel is obtained through
a bolted panel located on the side of the fan housing
3. Ensure proper wheel settings for radial gap and
alignment. Refer to Radial Gap, Overlap and Wheel
Alignment section on page 8.
Inspection & Maintenance During Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Thoroughly wipe clean
with Tectyl® 506 (Ashland Inc.) or the equivalent. For
hard to reach internal surfaces or for occasional use,
consider using Tectyl® 511M Rust Preventive, WD-40®
or the equivalent.
®
Tubular Centrifugal Fans3
Page 4
®
General Information
To ensure a successful installation, the instructions in
this manual should be read and adhered to. Failure to
comply with proper installation procedures may void the
warranty.
Unit and System Identification Tags
Each fan has a permanently affixed manufacturer’s
engraved metal nameplate containing the model
number and individual serial number.
The tag shown is an example of an identification
nameplate on the fan. The information provides general
details about the fan,
as well as containing
specific information
unique to the unit.
When contacting
your Greenheck
representative with
future needs or questions, please have the information
on this label available. Tags are mounted in an area
which is clearly visible, usually on the side of the fan
housing.
Pre-Installation Information
Before installation, it is important to be certain the
mounting surface will bear the operating weight of the
unit. For proper unit operation, it is also important that it
be operated in a completely level position.
For further details on safety practices involving
industrial and commercial fans, please refer to AMCA
Publication410.
Guards – Motor Cover, Weatherhood,
Shaft, Belt, Inlet or Outlet Guard
Do not operate fans without proper protective devices in
place. Failure to do so may result in serious bodily injury
and property damage. Check local codes to ensure
compliance for all protective devices.
Access Doors
Before opening access doors, ensure the fan wheel has
stopped moving and that the wheel has been secured
from being able to rotate. Do not operate fan without
access door in its fully closed position.
Provisions to open and remove the access door is
required for periodic cleaning and maintenance. The
access door is clearly labeled and indicates that access
to this location must be maintained. Any enclosure
openings required to reach the access panel shall be
large enough to allow for the removal of the panel.
Air Pressure and Suction
In addition to the usual hazards associated with rotating
machinery, fans also create a dangerous suction at the
inlet. Special caution needs to be used when moving
around a fan, whether it is in operation or not. Before
start-up, make sure the inlet area is clear of personnel
and loose objects.
Electrical Disconnects
All fan motors should have disconnects located in close
visual proximity to turn off electrical service. Service
disconnects shall be locked-out when maintenance is
being performed.
Moving Parts
All moving parts must have guards to protect personnel.
Refer to local codes for requirements as to the number,
type and design. Fully secure fan wheel before
performing any maintenance. The fan wheel may start
“free wheeling” even if all electrical power has been
disconnected. Before the initial start-up or any restart,
check the following items to make sure that they are
installed and secure.
• Do not spin fan wheel faster than the maximum
cataloged fan rpm.
• Adjustments to fan speed significantly effects motor
load. If the fan RPM is changed, the motor current
should be checked to make sure it is not exceeding
the motor nameplate amps.
Tubular Centrifugal Fans4
Page 5
Fans - Rigging and Lifting
1 Fan
Wheel
Dia.
0 5 10 15 20 25 30 35 40 45
FPM x 100
Outlet Velocity
Good
Poor
Length of Straight Duct
DISCHARGE DUCT TURNS
NON-DUCTED INLET CLEARANCE
1.2
1.0
0.8
0.6
0.4
0.2
0
Static Pressure Losses
Curve 1
Curve 2
Curve 3
SYSTEM EFFECT FACTOR CURV
Installation
IMPORTANT
Fans should never be lifted by shaft, motor, motor
cover or accessories.
Fans are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size.
TCB Inline models have mounting brackets located at
the ends of the fan housing with which slings can be
attached (Fig. 1). TCBRU Roof Upblast models can be
lifted by lifting lugs located above the motor cover of the
fan (Fig. 2). TCBRS Roof Supply fans can be lifted by
lugs located on the hood rails (Fig. 3).
Handle in such a manner as to keep from scratching or
chipping the coating. Damaged finish may reduce ability
of fan to resist corrosion.
• Use standard lifting rigging practices.
• ALL lifting brackets on each component must be
utilized at the same time.
• Fan to be kept level during lifting and installation.
Move the fan to the desired location. Check and tighten
fasteners throughout the unit and then fasten securely
through mounting holes provided in the base angles.
The unit must be set level (shimming may be necessary).
Flexible duct connections and vibration isolators should
be used where noise is a factor.
The motor voltage and ampere rating must be checked
for compatibility with the electrical supply prior to final
electrical connection. Supply wiring to the fan must
be properly fused and conform to local and national
electrical codes.
Effect of Installation on Performance
Any installation with inlet or discharge configurations
that deviate from these recommendations may result in
reduced fan performance. Restricted or unstable flow
at the fan inlet can cause pre-rotation of incoming air
or even loading of the fan wheel yielding large system
losses and increased sound levels. Free discharge or
turbulent flow in the discharge ductwork will also result
in system effect losses.
The most common inlet and discharge conditions which
affect fan performance are:
INLET DUCT TURNS
Fig. 1
Turning
Vanes
Installation of a duct turn or elbow too close to the
fan inlet reduces fan performance because air is
loaded unevenly into the fan wheel. To achieve full fan
performance there should be at least one to two fan
wheel diameters between the turn or elbow and the fan
inlet.
DISCHARGE DUCT TURNS
Poor
Fig. 2
Good
1 Fan
Wheel
Dia.
GoodPoor
Length of Straight Duct
Fig. 3
®
Fan performance is reduced when duct turns are made
immediately off the fan discharge. To achieve cataloged
fan performance, there should be at least one equivalent
duct diameter of straight ductwork between the fan
discharge and any duct turns.
Tubular Centrifugal Fans5
Page 6
®
Typical Installations
No
Airflow
Minimum duct at discharge
Fan off, Louvers in down position
Fan
Exterior Wall
Exhaust air
exiting the
building
Minimum
duct at
discharge
Fan
Exterior Wall
Airflow
Horizontal Ceiling Hung
Vertical Ceiling Hung
Horizontal Base Mount
OptionalMountingRails
Motor at 3 or 9o'clock position
AB
Following are typical mounting installations for model
TCB (horizontal or vertical). For horizontal TCB’s
with motor in the 3 or 9 o’clock position or vertical
installations, additional mounting rails are recommended.
Mounting rail dimensions are shown for field fabrication.
Horizontal Ceiling Hung
Motor at 3 or 9
o'clock position
Optional
Mounting
Rails
A
Horizontal Base Mount
Vertical Ceiling Hung
B
Vertical Base Mount with airflow up or down
B
Optional
Mounting
Rails
Installation of UL/cUL 762 Listed
Fans for Restaurant Exhaust
This section is to provide additional information when
dealing with fans used in applications involving greaseladen air.
All units used in
applications with greaseladen air are to be installed
in accordance to NFPA
96, IMC 2203 and local
codes. Consult local code
authorities for your specific
requirements.
Fans shall be located in an easily accessible area of
adequate size to allow for service or removal. Exhaust
fans with ductwork connected to both ends shall have
access for cleaning and inspection within 3 ft. (915 mm)
of each end of the fan (NFPA 96).
Maintain a minimum clearance of at least
18inches (457mm) to combustible material and
6inches (152mm) to either limited-combustible or
noncombustible material (NFPA 96).
Fans are to be installed with the motors in the 3 or
9 o’clock (C or G) positions. Motors located in this
configuration may cause an unbalanced load that
should be considered if isolators are to be used.
Equalized loading between isolators can be achieved
through the use of mounting rails.
It is recommended to install the fan near the end of the
duct run. This limits the amount of positive pressure
in the system. The diagram illustrates an inline fan
exhausting air near the final termination point. See
local codes and NFPA 96 for any restrictions and
requirements for wall terminations.
*Depth dimension is the center distance between holes in the front and rear
mounting brackets.
Tubular Centrifugal Fans6
⁄22618 3⁄814 x 1416 x 16
1
⁄22618 3⁄814 x 1416 x 16
3
⁄43323 7⁄818 x 1822 x 22
1
⁄43726 3⁄820 x 2028 x 28
1
⁄24429 5⁄824 x 2434 x 34
3
⁄46248 1⁄838 x 3852 x 52
1
⁄219 7⁄816 x 1618 x 18
1
⁄826 x 2640 x 40
5
⁄832 x 3246 x 46
Roof Opening
TCBRUTCBRS
Page 7
Drain Connection with UL/cUL 762
(TRAP BY OTHERS)
ENERGY RECOVERYPLENUM
SUBFLOOR
1.25 NPT
.75 NPT
*BASED ON STANDARD VEKTOR ERS CURB HEIGHTS
*
*
ROOFCURB
P.O.BOX 410 SCHOFIELD, WISCONSIN 54476-0410
TITLE
DRAWN BY
ECO
B
ENG. REF.
DATE
SUPERSEDES
SCALE
CAD DRAWING NO.
FAUST
06/29/2009
1/8
VK-ERS
N = Negative fan pressure (inches W.C.)H = N - 0.5 inches minimum
H/2
H/2
H
1.25 inch minimum
N
FAN ON
FAN OFF
14.750
14.000
NOTE: INSULATION OR OTHER MEANS OF FREEZE PROTECTION MAY BE REQUIRED IN CERTAIN CLIMATES
(TRAP BY OTHERS)
ERS DRAIN SUBMITTAL
A drain is provided for single-point drainage of water
and residue. Drains are located 90° from the motor
location to allow for removal of grease and moisture.
When installed correctly, one of the two housing drains
will be located on the bottom. This drain is used to
remove any accumulated grease and/or cleaning
solutions. Some means for collection of this residue
must be provided, either a container directly under the
drain or use an adapter and pipe to carry the residue to
a remote collection point. Remove drain plug prior to
connection to grease collection device.
Positive Pressure Trap
1.25 inch
minimum
Connect
this end
to fan drain.
H/2H/2
H
N = Negative fan pressure (inches W.C.)
H = N - 0.5 inches minimum
N
FAN ONFAN OFF
Duct Connections
Inline fans shall be connected to the exhaust duct by
flanges securely bolted as shown in the figures below
(NFPA 96). Flexible connectors shall not be used. Units
supplied with matching companion flanges are to have
this part welded to the ductwork and then bolted to
the fan. Gaskets used in the over-lapping connection
style shall not be positioned in a manner to have direct
contact with the grease.
Fan flange
Fan flange
Sealant rated for
1500°F (815°C)
Sealant Connection
Minimum 1 inch
(25 mm) flange
1/4 inch (6mm) carbon
or stainless steel bolts
Over-Lapping Connection
Welded companion flange
1x1x1/4 inch (25x26x6 mm) angle
Airflow
Gasket rated for
1500°F (815°C)
1/4 inch (6mm) carbon
or stainless steel bolts
Sealant / Gasket / Seal Replacement
Repair or replace sealant / gasket as needed.
Replacement sealant or gasket shall be rated for 1500ºF
(815ºC) and shall be grease tight. See Sealant and Overlapping Connection figures for proper installation.
Replace access door or bearing cover gasket material
as needed. Gasket material for the access door is 1/2 x
1/2 inch (13 x 13 mm). Gasket for the bearing cover is
1/8 x 1/2 inch (4 x 13 mm).
A mechanical seal, located inside the bearing cover,
is used to keep grease from penetrating into this area.
Contact your Greenheck Representative with the fan’s
serial number for appropriate sizing and part numbers
for a replacement seal or gasket material.
®
Tubular Centrifugal Fans7
Page 8
®
V-Belt Drives
Wheel
Cone
Wheel
Cone
Inlet
Cone
Inlet
Cone
V-Belt Drive Installation
1. Remove the protective coating from the end of the
fan shaft using mineral spirits or another similar
solvent. Check to ensure that the shaft is free of
nicks and burrs.
2. Slide sheaves on shafts. Do not drive
sheaves on as this may result in
bearing damage.
3. Align fan and motor sheaves
with a straight edge or
string and tighten.
4. Place belts over
sheaves. Do not
pry or force belts,
as this could result
in damage to the
cords in the belts.
5. Adjust the tension until the belts appear snug. Run
the unit for a few minutes and allow the belts to “set”
properly.
6. With the fan off and disconnect locked out, adjust
the belt tension by moving the motor pivot plate.
When in operation, the tight side of the belts should
be in a straight line from sheave to sheave with a
slight bow on the slack side.
Alignment of Pulleys and Belts
Check pulleys and belts for proper alignment to avoid
unnecessary belt wear, noise, vibration and power loss.
Motor and drive shafts must be parallel and pulleys in
line as shown in Figure 4.
CORRECTWRONGWRONGWRONG
Aligning sheaves with
a straight edge
Radial Gap, Overlap and Wheel
Alignment
Wheels must rotate freely and not rub on the inlet cone.
ModelTCB, TCBRU and TCBRS wheels overlap the
inlet cone. Refer to the table on the next page for the
proper dimension.
Radial Gap and Alignment
Efficient fan performance can be maintained by having
the correct radial gap, overlap and wheel alignment.
These items should be checked after the fan has been
in operation for 24 hours and before start-up when the
unit has been disassembled.
Radial Gap: Adjust inlet cone position such that the
radial gap between the wheel cone and inlet cone is
evenly distributed around the wheel.
Radial gap is adjusted by loosening the inlet cone/
ring bolts and centering the cone/ring on the wheel. If
additional adjustment is required to maintain a constant
radial gap, loosening the bearing bolts and centering the
wheel is acceptable as a secondary option.
Overlap: Overlap is adjusted by loosening the wheel
hub from the shaft and moving the wheel to the desired
position along the shaft.
The transition between the inlet cone and wheel should
be as shown; there is a smooth feel to the profile when
moving from one component to the other.
Overlap
Overlap
A
Radial
Gap
Figure 4
The adjustable motor pulley is set at the factory for
the fan RPM specified by the customer. Fan RPM can
be increased by closing or decreased by opening the
adjustable motor pulley. Multigroove variable pitch
pulleys must be adjusted an equal number of turns
open or closed. Any increase in fan speed represents a
substantial increase in load on the motor.
To avoid motor overheating and possible burnout, motor
load amperes should always be checked and compared
to nameplate rating when fan speed is increased.
Tubular Centrifugal Fans8
Radial
Gap
Straight
Straight
Edge
Edge
Wheel
Inlet
Inlet
Cone
Cone
Level 1
Cone
Level 2
Method for Centering Wheel: On belt drive units,
centering can be accomplished by (a) loosening the inlet
cone bolts to move the inlet cone or by (b) loosening
the bearings in order to move the shaft. Wheel and inlet
cone overlap can be adjusted by loosening the wheel
hub set screws and moving the wheel to the desired
position. Tighten all fasteners and set screws securely
and realign drive pulleys after adjustment.
Page 9
Radial Gap and Overlap Dimensions
Fan SizeLevel
09
10
12
13
16
18
22
24
30
36
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
OverlapA
inches (millimeters)
1
⁄4 (6)
1
⁄2 (13)33⁄16 (81)
1
⁄4 (6)
1
⁄4 (6)37⁄16 (87)
1
⁄4 (6)
3
⁄8 (10)4 (102)
1
⁄4 (6)
7
⁄16 (11)47⁄16 (113)
1
⁄4 (6)
7
⁄16 (11)57⁄16 (138)
3
⁄8 (10)
1
⁄2 (13)63⁄8 (162)
3
⁄8 (10)
9
⁄16 (14)713⁄16 (198)
3
⁄8 (10)
11
⁄16 (17)97⁄16 (240)
1
⁄2 (13)
11
⁄16 (17)109⁄16 (268)
1
⁄2 (13)
15
⁄16 (24)123⁄4 (324)
Field Coating Touch-Up for
Scratched Areas
Standard coating and color is Greenheck’s RAL 7023
Concrete Grey. Failure to perform touch-ups may result
in rust or corrosion and accelerate the fade in color and
is not covered under warranty.
TOUCH-UP PAINT REPAIR KIT CONTENTS
• One Zinc Clad Aerosol Can
• One pint (recoat epoxy primer grey) with
one pint (recoat epoxy primer catalyst)
• One quart H.S. Polyurethane
• One Scotch-Brite scratch pad
• Two 1-1/2 inch wide paint brushes
• Four pint-sized empty cans for mixing
• One quart-sized empty can for mixing
• Zinc repair instructions
• MSDS sheets
To order a coating repair kit, please reference
Greenheck’s part number HAZ2597 PNT FIELD REPAIR
KIT, RAL 7023 CONCRETE GREY. Please contact
factory with your fan’s serial number for colors other
than our standard.
®
Tubular Centrifugal Fans9
Page 10
®
Unit Start-Up
Visual Inspection of Equipment
The equipment type and arrangement should be verified
as ordered at once when it arrives at the jobsite. If
a discrepancy is found, the local Greenheck Sales
Representative must be notified immediately so that
corrective action may be investigated. Also verify
electrical conformance to specifications. Unauthorized
alterations and unauthorized backcharges will not be
recognized by Greenheck Fan Corporation.
After the unit has been assembled, installed and all
utilities have been hooked up, the unit is now ready for
operation.
Check
Before starting the unit, check the following:
1. Confirm that building supply voltage matches the
voltage for which the unit is wired.
2. Check all piping and wiring penetrations made by
contractors for water tightness. All penetrations
must be made watertight to prevent water damage
to the unit and building.
3. Rotate the fan wheel manually to be sure that it is
free to operate. Remove any dirt or debris that may
have accumulated during installation.
4. Check the fan bearing setscrews for tightness.
5. Check alignment of sheaves and V-belts.
6. Inspect all fasteners to ensure that none have
loosened during shipment.
7. Check all guarding to ensure that it is securely
attached and not interfering with rotating parts.
8. Check all electrical connections for proper
attachment.
9. Check housing and ductwork, if accessible, for
obstructions and foreign material that may damage
the fan wheel.
10. Fill drainage piping trap.
Additional Steps for Initial Start-Up
1. Check for proper wheel rotation by momentarily
energizing the fan. The wheel rotation should be in
the same direction as the rotation decal affixed to the
unit.
One of the most frequently encountered problems
are motors wired which rotate the wheel in the
wrong direction. This is especially true with 3-phase
installations where the motor will run in either
direction, depending on how it has been wired. To
reverse rotation of a 3-phase motor, interchange any
two of the three electrical leads. Single phase motors
can be reversed by changing internal connections as
described on the motor label or wiring diagram.
2. Fans with multi-speed motors should be checked on
low speed during initial start-up.
3. Check for unusual noise, vibration or overheating of
bearings. Refer to the “Troubleshooting” section of
this manual if a problem develops.
4. Grease may be forced out of the bearing seals during
initial start-up. This is a normal self-purging feature
for the type of bearing used on this product.
Tubular Centrifugal Fans10
Page 11
Electrical Connections
Vibration
Before electrical connections are made, the supply
voltage, phase and ampere capacity must be checked
for compatibility with the fan motor. In addition, the
supply wiring must be properly fused and conform to
local and national electrical codes. If the unit is supplied
with a safety disconnect switch, ensure proper wiring
to the fan motor. Be sure the disconnect is switched to
the “OFF” position before connecting supply wires. If
no disconnect is supplied, ensure the supply wire is not
live before connection. Supply wires are then connected
to the optional safety disconnect switch (if supplied) or
wired directly to the motor.
On start-up and during operation, the unit should
operate smoothly with minimal vibration. It is possible
that a higher degree of vibration may be experienced.
Excessive vibration, if left unchecked, can cause
a multitude of problems, including structural and/
or component failure. The most common sources of
vibration are listed.
Common Sources of Vibration
1. Wheel Unbalance
2. Drive Pulley Misalignment
3. Incorrect Belt Tension
4. Bearing Misalignment
5. Mechanical Looseness
6. Faulty Belts
7. Drive Component Unbalance
8. Poor Inlet/Outlet Conditions
9. Foundation Stiffness
Many of these
conditions can be
discovered by careful
observation. Refer to
the troubleshooting
section of this manual
for corrective actions.
If observation cannot
locate the source of
vibration, a qualified
technician using
vibration analysis equipment should be consulted. If
the problem is wheel unbalance, in-place balancing can
be done through the access panel located on the side
of each fan’s tubular housing. Any correction weights
added to the wheel should be welded to either the
wheel back (single-plane balance) or to the wheel back
and wheel cone (two-plane balance).
®
Tubular Centrifugal Fans11
Page 12
®
Routine Maintenance and Operation
WARNING
Disconnect and secure to the “OFF” position all
electrical power to the fan prior to inspection or
servicing. Failure to comply with this safety precaution
could result in serious injury or death.
WARNING
Pour écarter les risques de blessure grave ou de mort,
débrancher et verrouiller l’alimentation électrique en
position « Arrêt » avant tout contrôle ou entretien.
Once the unit has been put into operation, a routine
maintenance schedule should be set up to preserve the
reliability and performance of the fan and accomplish
the following:
1. Lubrication of bearings and motor.
2. Wheel, housing, bolts and set screws on the entire
fan should be checked for tightness.
3. Any dirt accumulation on the wheel or in the housing
should be removed to prevent unbalance and
possible damage.
4. Inspect fan impeller and housing looking for fatigue,
corrosion, or wear.
Fan Operation
All fans should be run every thirty (30) days, or at least
“bumped” every thirty days. It is preferred that each
fan is run as this causes all electrical and mechanical
components to get up to temperature, displacing any
formed condensation, redistributes load on bearings,
and redistributes grease in the bearings (motor and
shaft).
IMPORTANT
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.), consult
manufacturer to determine if the unit can operate
safely at the new condition.
Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper motor cooling. Never
wash-down motor with high pressure spray.
Greasing of motors is only intended when fittings are
provided. Many fractional motors are permanently
lubricated for life and require no further lubrication.
Motors supplied with grease fittings should be
greased in accordance with the manufacturer’s
recommendations. When motor temperature does not
exceed 104ºF (40ºC), the grease should be replaced
after 2000 hours of running time.
Belt Drive Maintenance
V-belt drives must be checked on a regular basis
for wear, tension, alignment and dirt accumulation.
Premature or frequent belt failures can be caused by
improper belt tension (either too loose or too tight)
or misaligned sheaves. Abnormally high belt tension
or drive misalignment will cause excessive bearing
loads and may result in failure of the fan and/or motor
bearings. Conversely, loose belts will cause squealing
on start-up, excessive belt flutter, slippage and
overheated sheaves. Either excessively loose or tight
belts may cause fan vibration.
When replacing V-belts on multiple groove drives all
belts should be changed to provide uniform drive
loading. Use a set of matched belts whenever possible.
Do not pry belts on or off the sheave. Loosen belt
tension until belts can be removed by simply lifting the
belts off the sheaves. After replacing belts, ensure that
slack in each belt is on the same side of the drive. Belt
dressing should never be used.
Do not install new belts on worn sheaves. If the sheaves
have grooves worn in them, they must be replaced
before new belts are installed.
The proper tension for operating a V-belt drive is
the lowest tension at which the belts will not slip at
peak load conditions. Belts are adjusted by raising
or lowering the motor pivot plate. Use the bolts in
the slotted brackets and adjustment rods with bolts
as adjustment points until proper belt tension is
attained. For
initial tensioning,
Deflection =
the proper
belt deflection
halfway between
sheave centers is
1/64-inch for each
inch of belt span.
Belt Span
Check belt tension two times during the first
24hours of operation and periodically thereafter.
Belt Span
64
Tubular Centrifugal Fans12
Page 13
Bearing Lubrication Schedule
Shaft bearings are the most critical moving part of a fan.
Therefore, special attention should be given to keeping
the bearings clean and well lubricated. Proper lubrication
provides for reduction in friction and wear, transmission
and dissipation of heat, extended bearing life and
prevention of rust.
In order for a lubricant to fulfill these tasks, the proper
grease applied at regular intervals is required. See
bearing manufacturer’s instructions or label on the fan
housing for lubrication schedule.
In a clean environment and temperature above 32ºF
(0ºC) and below 200ºF (93ºC), fan shaft bearings with
grease fittings should be lubricated semi-annually using
a high quality lithium based grease. If unusual conditions
exist (temperatures below 32°F or above 200°F),
moisture or contaminants - more frequent lubrication is
required. Lubricate bearings on UL 762 fans with high
temperature grease conforming to NLGI Grade 2,
such as Mobil Mobilith SHC 100 or 200.
With the unit running, add grease very slowly with a
manual grease gun until a slight bead of grease forms
at the seal. Be careful not to unseat the seal by over
lubricating or using excessive pressure. Bearings without
grease fittings are lubricated for life.
Fasteners attaching the bearings to the drive frame
should also be checked.
Wheel, Fasteners and Set Screws
Wheels require very little attention when exhausting clean
air, however, air heavily laden with grease or dirt will tend
to accumulate on the wheel causing unbalance. Wheels
exhausting dirty or grease-laden air require frequent
cleaning to assure smooth and safe operation.
All fasteners, including set screws in the bearing collars,
should be checked for tightness each time maintenance
checks are performed. Particular attention should be paid
to set screws attaching the wheel to the shaft and the
shaft to the bearings. Loose bearing set screws will lead
to premature failure of the fan shaft.
A proper maintenance program will help preserve the
performance and reliability designed into the fan.
Removal of Dust and Dirt
Dirt clogs cooling vents on the motor housing,
contaminates bearing lubricant, and collects on the
impeller causing severe imbalance if left unchecked.
The exterior surface of the motor and impeller should be
thoroughly cleaned periodically. Use caution and do not
allow water or solvents to enter the motor or bearings.
Under no circumstances should motors or bearings be
sprayed with steam or water.
Cleaning Internal Components
Entire wheel should be cleaned during routine duct
cleaning. Partial cleaning may result in an unbalanced
wheel that can cause premature bearing failure or
excessive vibration.
Grease / cleaning solution should drain freely
through the provided drain connection. Remove any
obstructions inhibiting proper drainage.
Only the access door is removed during routine duct
cleaning. The bearing cover is not removed during
routine cleaning. The bearing cover is removed only
when inspecting or changing the bearings, fan shaft or
driven pulley.
Damper Inspection and Service,
Model TCBRU Level 1 or 2
Butterfly dampers should be inspected for proper
operation at each service interval. Check for freedom of
movement and general condition of the damper blades
and hinge rods.
Variable Frequency Drive Operation
For operation with variable frequency drive (VFD),
always check motor amps when adjusting the operating
frequency. Motor may be sized for the original selected
operating speed under 60 Hz. Bypassing the VFD or
increasing the speed from this original selection, even
if less than 60 Hz, may cause motor to overload or fail.
Consult factory with fan serial number, before increasing
the upper limiting frequency.
Always check the fan rpm when adjusting the operating
frequency. Do not exceed maximum class fan rpm of the
wheel.
®
Tubular Centrifugal Fans13
Page 14
®
Parts List
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information, in
addition to the parts list shown, will assist the local Greenheck representative and the factory in providing service
and replacement parts.
Motor Pulley
Belt
Belt Tube
Shaft Pulley
Bearing
Cover
Motor
BearingsShaft
Wheel
Inlet Cone
(Venturi)
Motor Plate
Motor Cover
(optional)
Bearing
Support
Mounting
Brackets
(qty. of 4)
Tubular Centrifugal Fans14
Page 15
Troubleshooting
WARNING
Before taking any corrective action, make certain unit
is not capable of operation during repairs.
Avant d’entreprendre toute action corrective, s’assurer
que l’appareil ne pourra pas fonctionner durant les
AVERTISSEMENT
réparations.
ProblemCauseCorrective Action
Wheel Rubbing Inlet
Adjust wheel and/or inlet cone.
Tighten wheel hub or bearing collars on shaft.
Tighten sheaves on motor/fan shaft. Adjust belt tension.
Excessive Noise
V-Belt Drive
Bearings
Align sheaves properly (see procedure).
Replace worn belts or sheaves.
Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.
Wheel UnbalanceClean all dirt off wheel. Check wheel balance.
Low CFM
High CFM
Static Pressure Wrong
FanCheck wheel for correct rotation.
Duct SystemHigher pressure than design. Filters need replacement.
FanDecrease fan speed.
Duct SystemResize ductwork. Access door, filters, dampers not installed.
Duct system has more
or less restriction than
anticipated
Remove obstructions in system. Use correction factor to
adjust for temperature/altitude. Resize ductwork. Clean filters/
coils. Change fan speed.*
FanCheck rotation of wheel. Reduce fan speed.
High Motor Amp Draw
Fan Doesn’t Operate
Duct System
Electrical Supply
DriveCheck for broken belts. Tighten loose pulleys.
Motor
Resize ductwork. Check proper operation of isolation and
bypass dampers. Check filters and access doors.
Check fuses/circuit breakers. Check for switches turned off or
disconnected. Check for correct supply voltage.
Assure motor is correct horsepower and not tripping overload
protector.
LubricationCheck for excessive or insufficient grease in the bearing.
Overheated Bearing
Excessive Vibration
Mechanical
Belts
System Unbalance
Replace damaged bearing. Relieve excessive belt tension.
Align bearings. Check for bent shaft.
Adjust tightness of belts. Replacement belts should be a
matched set.
Check alignment of shaft, motor and pulleys. Adjustable
pitch pulleys with motors over 15 hp are especially prone to
unbalance. Check wheel balance, rebalance if necessary.
* Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor and
result in motor failure. Do not exceed the maximum cataloged rpm of the fan.
®
Tubular Centrifugal Fans15
Page 16
Maintenance Log
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Date _______________ Time _______________ AM/PM
Notes: __________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck Tubular Centrifugal Inline, Roof Upblast and Roof
Supply catalog provides additional information describing
the equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.