Greenheck TCB-1-10 User Manual

Tubular Centrifugal Fans
Model TCB
Inline - Horizontal or Vertical
Roof Upblast and Roof Supply
March
2007
Tubular Centrifugal Fans
The TCB series of inline centrifugal fans is designed for ducted inline, roof upblast, and roof supply installations. Whether the application is commercial or industrial, Greenheck tubular centrifugal fans provide quiet, efficient, and reliable air performance.
All TCB products are belt driven with motors out of the airstream. Housings are constructed of welded steel or aluminum (optional) and are suitable for indoor or outdoor applications. The backward inclined wheels are manufactured from aluminum and are suitable for clean air or fume exhaust applications. All TCB products meet “Type B” construction as defined by AMCA Standard 99-0401 Classification for Spark Resistant Construction. In addition, the TCB is available with the UL 762 listing for restaurant exhaust applications.
Greenheck Fan Corporation certifies that the model TCB tubular centrifugal inline fans shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
Model TCB — Inline Fan
• Sizes from 09 to 36
• Performance Range: 360 to 24,000 cfm (610 - 40,750 m³/hr)
• Static Pressure: Up to 4.5 in. wg (1,125 Pa)
• Max Operating Temperature: 200°F (90°C)
• Horizontal or Vertical Mounting
• Options: — Easy Access — All Aluminum Construction — UL 762 for Restaurant Exhaust
Model TCB is available with the UL 762 Listing (Power Ventilators for Restaurant Exhaust Appliances).
Models TCB, TCBRU, and TCBRS are Listed for electrical (UL/cUL 705). File no. E40001
Model TCBRS — Roof Supply Fan
• Sizes from 09 to 36
• Performance Range: 360 to 24000 cfm (610 - 40,750 m³/hr)
• Static Pressure: Up to 4 in. wg (1,000 Pa)
• Max Operating Temperature: 200°F (90°C)
• Options: – Insect Screen or Filters – Easy Access – All Aluminum Construction
2
Two Levels of Construction
All TCB inline and roof mounted fans are available in two levels of construction to provide the most efficient and economical selections. Construction differences between level 1 and 2 selections include the impeller, the inlet cone, the shaft size, and the bearings. The housings for both levels are identical in material gauge and overall design.
Level 1 Construction
• Maximum pressure capabilities of 2 in. wg (500 Pa)
• Highest efficiencies at static pressures below 1.5 in. wg (375 Pa)
• Aluminum wheel construction
• Most economical selections
Level 2 Construction
• Maximum pressure capabilities of 4.5 in. wg (1,125 Pa)
• Highest efficiencies at static pressures above 1.5 in. wg (375 Pa)
• Completely welded aluminum wheel
• Increased shaft and bearing diameter
• Increased horsepower and motor frame size capability
Easy Access Feature
All models are available with an optional oversized access door for serviceability of fan components without removing the fan or duct. See page 8 for details.
Model TCBRU — Roof Upblast Fan
• Sizes from 09 to 36
• Performance Range: 425 to 24,000 cfm (722 - 40,750 m³/hr)
• Static Pressure: Up to 4 in. wg (1,000 Pa)
• Max Operating Temperature: 200°F (90°C)
• Options: — Easy Access — All Aluminum Construction
3
Hood Panels
Construction Specifications
Windband
Housing
Housing
Model TCB Model TCBRU
Steel Construction (gauge)
Size Housing Curb Cap Windband
09 12 12 20 22
10 12 12 20 22
12 12 12 20 22
13 12 12 20 22
16 12 12 20 22 1 1 3/16
18 12 12 20 22 1 1 3/16
22 10 12 20 22 1 1 7/16
24 10 12 20 22 1 1 11/16
30 10 12 20 22 11/4 1 15/16
36 10 12 20 22 11/2 1 15/16
Aluminum Construction (thickness in inches)
Curb Cap
Hood
Panels
Model TCBRS
Shaft Diameter (in.)
Level 1 Level 2
3
/4 1
3
/4 1
3
/4 1
3
/4 1
Size Housing Curb Cap Windband
09 0.125 0.125 0.051 0.051
10 0.125 0.125 0.051 0.051
12 0.125 0.125 0.051 0.051
13 0.125 0.125 0.051 0.051
16 0.125 0.125 0.051 0.051 1 1 3/16
18 0.125 0.125 0.051 0.051 1 1 3/16
22 0.125 0.125 0.051 0.051 1 1 7/16
24 0.125 0.125 0.051 0.051 1 1 11/16
30 0.19 0.125 0.051 0.051 11/4 1 15/16
36 0.19 0.125 0.051 0.051 11/2 1 15/16
4
Hood
Panels
Shaft Diameter (in.)
Level 1 Level 2
3
/4 1
3
/4 1
3
/4 1
3
/4 1
TCB Inline Fan - Belt Drive
The Model TCB inline fan is the ideal choice for ducted systems. Greenheck’s standard fan can be mounted in any position from horizontal to vertical, allowing installation in the smallest possible space at the lowest installation cost. The centrifugal wheels used in this design provide higher efficiencies and lower sound levels than propeller type inline fans when used in medium pressure ducted systems. TCB fans are available in either painted steel or aluminum construction.
Typical applications include:
• General exhaust or supply
• Industrial space ventilation
• Fume hood exhaust (special coatings are available)
• Combustion air
• Roof exhaust or supply (with weatherhood)
• Restaurant grease exhaust
Universal Mounting
All TCB fans can be mounted horizontally or vertically. For ease of installation, eight mounting brackets are welded on each fan. The eight brackets along with four mounting supports, provide a universal mounting system.
Fig. 1 Horizontal Base Mount
Each fan is shipped as standard in this arrangement. Motor at 12 o’clock is standard.
Fig. 2 Horizontal Base Mount with Motor at 3 or 9 o’clock
A set of optional mounting rails are required for this installation. This is the base mounting position required with the easy access option.
Fig. 3 Horizontal Ceiling Hung
In this installation the supports can be positioned for mounting the motor at either 6 or 12 o’clock.
Fig. 4 Horizontal Ceiling Hung with Motor at 3 or 9 o’clock
A set of optional mounting rails are required for this installation.
Horizontal Base Mount
Fig. 1
Horizontal Ceiling Hung
Fig. 3
Easy
Access
Option
Horizontal Base Mount
Motor at 3 or 9 o'clock position
Easy
Access
Option
Horizontal Ceiling Hung
Motor at 3 or 9 o'clock position
Vertical Ceiling Hung
Fig. 2
Fig. 4
Optional
Mounting Rails
Optional
Mounting Rails
Fig. 5 Vertical Mount
All TCB fans can be mounted vertically (ceiling hung or base mount) for either upward or downward airflow. Optional mounting rails are recommended.
NOTE: All fans are shown with optional vibration isolators. See the appropriate submittal drawings or installation manual for complete dimensional data.
Vertical Base Mount
Fig. 5
5
TCBRU 16-36
TCBRU 9-13
TCBRU Roof Upblast Fan
The TCBRU is ideal for roof upblast exhaust systems with moderate system static pressures and for applications where quiet operation is essential. Standard features include a necked-down windband section which creates the high outlet velocities necessary to carry contaminated exhausts away from the roof deck. All TCBRU fans include motor covers for weather protection of the motor and drives, gravity operated dampers to prevent backflow into the building, and a welded curb cap for ease in mounting to a roof curb. TCBRU fans are available in either painted steel or aluminum construction.
Typical applications include:
• Low cfm/high velocity exhaust
• General exhaust
• Fume hood exhaust
• Industrial process exhaust
When selecting TCBRU fans, use the TCB inline performance data (pgs. 12 to 31) along with the following system effect curves. The pressure loss determined below must be added to the extended system static pressure to assure accurate selections. Greenheck’s Computer Aided Product Selection (CAPS) software will add these
System Effect Curves
Sizes 9-13 Sizes 16-36
0.8
0.7
0.6
0.5
0.4
0.3
Pressure Loss (inches)
0.2
0.1
0.0 0 1 2 3 4
CFM x 1000
TCBRU fans do not incorporate provisions for internal wiring.
External wiring from the roof to unit must be provided by others
6
09, 10
B
12
13
E
Dimensional Data
Size A B C D E
09 22 211/2 23 45 20 425
10 22 211/2 23 45 20 425
12 22 211/2 23 45 20 1250
13 4 231/2 241/2 501/2 24 1800
D
16 28 251/2 281/2 53 28 2030
C
18 34 281/2 31 571/2 30 2570
22 40 34 351/2 64 34 2740
24 46 361/2 42 741/2 40 4760
1
2
/2"
30 52 421/4 481/2 84 46 6600
36 58 451/2 54 941/2 52 8700
A
All dimensions shown in inches.
system effects automatically.
1.8
1.6
1.4
1.2
1.0
0.8
0.6
Pressure Loss (inches)
0.4
0.2
0.0 0 4 8 12 16 20 24
16
18
22
24
36
CFM x 1000
30
Minimum CFM
Required to Open Dampers
TCBRS
Pressure Loss (inches)
TCBRS Roof Supply Fan
The TCBRS roof mounted supply fan is designed for intake air systems with pressures up to 4 inches of wg and where low sound is required. The TCBRS hood intake is located at a sufficient height above the roof to limit entry of roof debris and snow. In addition, the hood has sufficient intake area to keep velocities low. Filters are available to collect dust and moisture before entering the building. Motor and drive protection is provided with a weatherproof motor cover. For ease of installation, TCBRS fans are shipped assembled and have curb caps for attaching to roof curbs. TCBRS fans are available in either painted steel or aluminum construction.
Typical applications include:
• Ducted supply systems
• Industrial space supply
• Filtered supply
System Effect Curves
0.18
0.16
0.14
0.12
0.10
0.08
0.06
0.04
0.02
0.00
TCBRS fans do not incorporate provisions for internal wiring.
External wiring from the roof to unit must be provided by others
09, 10, 12
0 4 8 12 16 20 24
16
13
22
18
W
Hood End View
B
24
30
CFM x 1000
Hood Side View
A
L
C
21/2 in.
36
TCBRS fan selections can be made using the TCB inline performance data (pgs. 12 to 31) along with the following system effect curves. The pressure loss determined to the left must be added to the external system static pressure to assure accurate selections. Greenheck’s Computer Aided Product Selection (CAPS) software will add these system effects automatically.
Dimensional Data
Size A B C D L W
09 22 211/2 251/2 391/2 39 46
10 22 211/2 251/2 391/2 39 46
12 22 211/2 251/2 391/2 39 46
13 24 231/2 27 431/2 39 54
D
16 28 251/2 31 471/2 51 55
18 34 281/2 331/2 50 63 64
22 40 34 381/2 59 75 73
24 46 361/2 45 671/2 87 82
30 52 421/4 521/2 76 99 88
36 58 451/2 58 851/2 111 88
All dimensions shown in inches.
7
Construction Features
Tubular Centrifugal Belt Drive
TCB - Inline Fan TCBRU - Roof Upblast Fan TCBRS - Roof Supply Fan
Level of Construction
1 or 2
Standard Construction Features
Model Number Code
The model number system is designed to completely identify the fan. A detailed explanation of the model number code for TCB fans is shown below.
TCB - 1 - 24 - 30
Motor Horsepower
1
4 =
/4 30 = 3
1
3 =
/3 50 = 5
1
5 =
Fan Size
09-36
/2 75= 71/2 7 =3/4 100 = 10 10=1 150 = 15
1
15=1
/2 200= 20
20= 2
Inlet & Outlet Flanges
Flanged inlets and outlets with mounting holes are provided for duct connections (TCB only).
Bearings
Standard bearings are grease lubricated, self-aligning, ball type in pillow block mounts. Bearings are selected for a minimum L(10) life in excess of 80,000 hours {L(50)
Housing
Housings are continuously welded steel and coated
average life of 400,000 hours} at maximum cataloged operating speeds.
with Permatector™.
Belt & Bearing Tube
Protective Coating
All steel constructed units are coated with Permatector™, a thermosetting polyester urethane. Aluminum units are uncoated.
Type B Spark Resistance
All fans have aluminum wheels and a nonferrous (aluminum) rub ring which surrounds the fan shaft where it passes through the drive cover. This construction meets Type B spark resistant requirements.
Belts, bearings, and drives are protected from the airstream by heavy gauge belt tubes and bolted bearing covers with shaft seals.
Extended Lube Lines
Lubrication lines with grease fittings allow bearing lubrication without disassembling the fan.
Optional Construction Features
Aluminum Construction
Aluminum construction is available on the TCB, TCBRU and TCBRS. Aluminum fans are an excellent choice for applications involving moisture or coastal installations.
Easy Access Construction
The Easy Access option is highly recommended to allow for inspection, cleaning and service of internal fan components. By removing one access panel, service to the wheel, shaft, and bearing assembly is possible without removing duct connections. In addition, all internal fan components can be removed from the fan through the easy access panel.
Easy Access construction is available on all levels and sizes of TCB, TCBRU, and TCBRS. Easy Access is also available with aluminum fan construction.
Note: The Easy Access panel is located 180° from the motor position.
8
Optional Construction for UL 762 Restaurant Exhaust
Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators are not practical. The TCB with UL 762 grease option is designed to withstand the demands of high temperature kitchen grease exhaust and high-pressure duct washes.
Leak Resistant Construction Features
Continuously welded housing and integral duct flanges
1
4
6
3
provide air and water tight design.
Bearing cover gasketed and includes a labyrinth shaft seal
2
to prevent moisture leakage during normal operation and while cleaning with high pressure solvents.
Continuously welded belt tube keeps the belts and
3
7
bearings clean.
Two threaded drain connections are located 90° from the
4
motor location to allow for removal of grease and moisture.
Mounting and Serviceability Features
Universal mounting brackets allow for rotation of the motor to
5
the 3 or 9 o’clock position at the jobsite.
Duct flanges and access door bolt locations are no more
6
than 4 inches (100 mm) on center per NFPA 96.
“Easy Access Door” provides access for duct cleaning and allows removal of the wheel,
7
5
4
1
2
shaft and bearings for maintenance. Gasket is rated for 400°F (200°C) and prevents leakage during operation [Fan is rated for 300°F (149°C) continous operation].
System Design Guidelines
• Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood.
• Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines. Greenheck’s companion flanges are recommended for ease of installation.
• Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible material. If the ductwork and fan are insulated, the inspection door must be accessible for maintenance.
• A minimum of 10 ft. (3.0 m) of clearance must be kept from the fan outlet to adjacent buildings, property lines, or the closest point of any air intake or operable window at or below the plane of the exhaust termination.
• Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure compliance with NFPA, IMC, and other local codes.
UL 762 is concerned with fans designed for removal of smoke and grease laden vapors with airstream temperatures up to 300°F.
Listed Power Ventilation for Restaurant Exhaust Appliances 13G3 Maximum Operating Temperature 300°F.
• Meets all UL 705 Requirements
• Bolted Access Door
• Drain Connection
• Meets requirements of NFPA 96 Ventilation Control and Fire
Protection of Commercial Cooking Operations
A Tough Package to Beat
The TCB inline grease fan is tough to beat when packaged with our full line of kitchen hoods and grease extraction options. Take advantage of Greenheck’s expertise in providing a total solution in kitchen ventilation equipment.
Duct to heat source
Airow
Roof
Wall and/or ceiling should enclose fan when used for emergency heat and smoke exhaust. Enclosure shall be per NFPA 96 or local building codes.
Ambient temperature not to exceed 120ºF
Minimum duct at discharge
Cooling air for drives and bearings
To building
exterior
9
Accessories
Belt Guard (TCB only)
Belt guards are totally enclosed to provide protection from rotating pulleys and belts. Belt guards meet OSHA guidelines.
Motor Cover (Weatherhood)
Weatherproof motor covers shield the motor and drive components from dust, dirt and moisture when used in outdoor applications. Motor covers also provide protection from rotating pulleys and belts and meet OSHA guidelines. Motor covers are standard on TCBRU and TCBRS models.
Inlet and Outlet Companion Flanges (TCB only)
Companion inlet flanges and outlet flanges with prepunched holes are available for all fan sizes in painted steel construction.
Inlet and Outlet Guards (TCB, TCBRU)
Removable inlet and outlet guards provide protection for personnel and equipment in non-ducted installations. These guards meet OSHA guidelines. TCBRU fans are available with outlet screens to shield the fan discharge and damper from debris.
Inspection Door
Bolted or hinged doors provide access for cleaning or inspection.
Inspection Section (TCB only)
Inspection sections serve as a length of duct that can be easily removed to provide for complete access to the fan for servicing. Each section includes a bolted inspection door.
Mounting Rails (TCB only)
Mounting rails are required for horizontal mounting of TCB fans when the motor is to be located in the 3 or 9 o’clock position. Mounting rails are also recommended for all vertically mounted inline fans. See page 5 for additional details.
Protective Coatings
Greenheck has a wide offering of protective coatings. Consult Greenheck’s Product Application Guide FA/110-04R, Performance Coatings for Ventilation Products for a complete listing of coatings and a relative resistance chart.
Inlet Vane Dampers (TCB only)
Nested inlet vane dampers for controlling air volume are available on model TCB inline fans with Level 2 steel construction in fan sizes 12 through 36.
Birdscreen / Insect Screen (TCBRS only)
TCBRS fans are available with either aluminum insect screen or birdscreen at the hood intake (Birdscreen is standard).
Roof Curbs (TCBRU, TCBRS)
Prefabricated roof curbs are available to reduce installation time and costs by ensuring compatibility between the fan, the curb and the roof opening. All curbs are lined with fiberglass insulation to prevent condensation and reduce sound levels. See Greenheck’s roof curb catalog for complete details.
Washable Aluminum Filters (TCBRS only)
Helps trap dust and dirt before it enters the fan. Filters can be removed for cleaning.
Isolators (TCB only)
Both base mount or hanging isolators are available in either neoprene or spring mounts. The isolators are furnished in sets of four and are sized to match the weight of each fan.
Electrical Accessories
Enclosure Application Toggle Heavy Duty
NEMA-1 Indoor, General Purpose Yes Yes
NEMA-12 Indoor, Dust/Drip Tight Yes Yes
NEMA-3R Indoor/Outdoor, Rainproof Yes Yes
NEMA-4 Indoor/Outdoor, Watertight Yes Yes
NEMA-4X
NEMA-7 & 9 Indoor, Hazardous Locations Yes No
Toggle type and heavy duty disconnect switches are available for positive electrical shut-off and safety in servicing fans. The following switches are available to meet individual electrical requirements.
10
Indoor/Outdoor, Watertight (Corrosion Resistant)
Yes Yes
Accessories (Model TCB shown)
Belt Guard
Outlet Guard
Inspection Section
Motor Cover
Companion Flange (Inlet)
Companion Flange
Mounting Rails
(Outlet)
Neoprene Hanging Isolator
Neoprene Isolator
Inlet Guard
Easy Access
Inspection Door
Spring Base Isolator
Spring Hanging Isolator
11
TCB-1-09
Level 1 Construction
215/8
183/8
213/4
131/4
*
183/8
23
* Maximum w/Motor Cover
17 5/8
Dimensions shown in inches Maximum rpm — 2645 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 2.928 Maximum bhp at a given rpm — (rpm/3114) Max Motor Frame Size - 56
CFM
360 195
420 228
480 260
540 293
600 326
660 358
720 391
780 423
840 456
900 489
960 521
1020 554
1080 586
1140 619
1200 652
OV
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
846 0.02 999 0.03 1260 0.06
5.3 6.0 7.5
941 0.03 1071 0.04 1314 0.07 1526 0.11
5.7 6.3 7.7 9.2
1040 0.04 1155 0.05 1380 0.09 1576 0.12 1758 0.17
6.3 6.8 8.0 9.3 10.6
1144 0.05 1245 0.06 1449 0.10 1635 0.14 1807 0.19 1968 0.23 2115 0.28
7.1 7.4 8.4 9.5 10.7 12.0 13.3
1250 0.06 1341 0.08 1523 0.12 1704 0.16 1865 0.21 2017 0.26 2163 0.31 2298 0.36
7.8 8.1 8.8 9.9 11.0 12.2 13.5 14.7
1357 0.07 1439 0.09 1606 0.14 1774 0.18 1930 0.23 2074 0.29 2212 0.34 2346 0.40 2472 0.46
8.6 8.8 9.3 10.4 11.4 12.6 13.7 14.9 16.2
1465 0.09 1542 0.11 1692 0.16 1845 0.21 1999 0.26 2137 0.32 2270 0.38 2395 0.43 2520 0.50
9.4 9.6 10.0 10.9 12.0 13.1 14.0 15.0 16.3
1576 0.12 1647 0.14 1786 0.18 1928 0.24 2069 0.29 2206 0.35 2331 0.41 2454 0.47 2570 0.54
10.2 10.4 10.8 11.5 12.7 13.6 14.5 15.4 16.5
1688 0.14 1752 0.16 1882 0.21 2012 0.27 2142 0.33 2276 0.39 2400 0.45 2515 0.52 2629 0.59
11.0 11.2 11.7 12.3 13.3 14.2 15.0 16.0 17.0
1801 0.17 1859 0.19 1980 0.25 2100 0.30 2225 0.36 2347 0.43 2469 0.50 2584 0.56
12.0 12.2 12.7 13.3 13.9 14.8 15.7 16.6
1914 0.20 1966 0.23 2081 0.28 2195 0.34 2310 0.40 2424 0.47 2540 0.54
13.0 13.2 14.0 14.2 14.7 15.4 16.4
2028 0.24 2075 0.26 2184 0.32 2292 0.38 2395 0.44 2507 0.52 2612 0.59
14.4 14.9 15.0 15.1 15.5 16.3 17.2
2141 0.28 2186 0.31 2288 0.37 2389 0.43 2490 0.50 2592 0.57
15.9 15.9 16.0 16.2 16.6 17.2
2255 0.33 2298 0.36 2394 0.42 2487 0.49 2585 0.55
16.9 16.9 17.1 17.4 17.8
2370 0.38 2410 0.41 2500 0.47 2590 0.54
17.9 18.0 18.3 18.6
CFM X 100
m³/hr X 100
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
12
TCB-2-09
Level 2 Construction
215/8
183/8
213/4
131/4
*
183/8
23
17 5/8
* Maximum w/Motor Cover
Dimensions shown in inches Maximum rpm — 4050 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 2.75 Maximum bhp at a given rpm — (rpm/3330) Max Motor Frame Size - 145T
CFM OV
400 217
480 260
560 304
640 347
720 391
800 434
880 478
960 521
1040 565
1120 608
1200 652
1280 695
1360 739
1440 782
1520 826
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1198 0.05 1460 0.08 1893 0.18
7.3 8.7 11.9
1332 0.06 1566 0.10 1971 0.20 2309 0.32
8.2 9.6 12.7 15.7
1480 0.09 1686 0.13 2059 0.24 2386 0.36 2671 0.49
9.2 10.6 13.5 16.5 19.1
1635 0.11 1818 0.16 2158 0.27 2469 0.41 2749 0.55 3000 0.70 3228 0.86
10.6 11.7 14.6 17.4 20 23 25
1799 0.15 1958 0.20 2275 0.32 2562 0.45 2830 0.61 3078 0.77 3305 0.94 3514 1.12
12.0 13.0 15.8 18.3 21 23 25 28
1966 0.20 2108 0.25 2397 0.37 2666 0.51 2921 0.67 3158 0.85 3383 1.03 3591 1.21 3786 1.41
13.4 14.5 16.9 18.3 22 24 26 28 31
2135 0.25 2262 0.30 2528 0.43 2784 0.58 3015 0.74 3250 0.93 3464 1.12 3669 1.32 3863 1.52
15.1 16.2 18.2 21 23 25 27 29 32
2308 0.32 2425 0.37 2665 0.50 2905 0.66 3132 0.83 3343 1.01 3555 1.21 3752 1.42 3942 1.64
16.8 17.6 19.6 22 24 26 28 31 33
2482 0.39 2590 0.45 2810 0.59 3033 0.75 3251 0.93 3453 1.11 3648 1.31 3844 1.53 4027 1.76
18.4 19.3 21 23 25 27 29 32 34
2658 0.48 2757 0.54 2960 0.68 3168 0.85 3372 1.03 3571 1.23 3754 1.43 3937 1.65
20 21 23 25 27 29 31 33
2835 0.58 2925 0.65 3113 0.79 3306 0.96 3501 1.15 3691 1.35 3872 1.57 4041 1.79
22 23 24 26 28 30 32 35
3012 0.70 3095 0.76 3271 0.91 3453 1.09 3636 1.28 3813 1.49 3991 1.71
24 25 26 28 29 32 34
3190 0.83 3269 0.90 3434 1.05 3603 1.23 3773 1.43 3945 1.64
26 26 28 29 31 34
3368 0.97 3444 1.05 3599 1.21 3756 1.39 3917 1.59
28 28 30 31 33
3547 1.14 3619 1.21 3765 1.38 3909 1.56
30 30 32 34
CFM X 100
m³/hr X 100
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
13
TCB-1-10
Level 1 Construction
215/8
183/8
213/4
131/4
*
183/8
23
17 5/8
* Maximum w/Motor Cover
Dimensions shown in inches Maximum rpm — 2555 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 2.928 Maximum bhp at a given rpm — (rpm/2760) Max Motor Frame Size - 143T
CFM OV
480 260
560 304
640 347
720 391
800 434
880 478
960 521
1040 565
1120 608
1200 652
1280 695
1360 739
1440 782
1520 826
1600 869
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
858 0.03 1011 0.05 1253 0.09
4.9 5.7 7.3
947 0.04 1089 0.06 1321 0.11 1511 0.15
5.5 6.3 7.7 9.3
1042 0.05 1171 0.08 1394 0.13 1578 0.18 1740 0.23 1892 0.29
6.3 7.0 8.2 9.6 11.2 13.3
1141 0.07 1259 0.09 1470 0.15 1649 0.21 1806 0.27 1949 0.33 2079 0.39
7.2 7.6 8.9 10.0 11.5 13.2 15.0
1239 0.09 1349 0.12 1548 0.18 1723 0.24 1876 0.31 2015 0.37 2144 0.44 2263 0.51
8.0 8.4 9.6 10.7 11.9 13.5 14.8 16.1
1340 0.11 1444 0.14 1630 0.21 1798 0.27 1949 0.34 2084 0.42 2211 0.49 2329 0.57 2440 0.64
8.8 9.2 10.2 11.3 12.5 13.7 15.0 16.2 17.6
1441 0.14 1541 0.17 1716 0.24 1876 0.31 2023 0.39 2157 0.47 2280 0.55 2396 0.63 2506 0.71
9.7 10.1 10.9 12.1 13.3 14.1 15.2 16.5 17.9
1544 0.17 1640 0.21 1805 0.28 1957 0.35 2099 0.44 2231 0.52 2352 0.60 2465 0.69
10.5 10.9 11.7 12.9 13.9 14.8 15.7 16.9
1648 0.21 1739 0.25 1895 0.32 2042 0.40 2178 0.49 2306 0.58 2426 0.67 2538 0.76
11.3 11.7 12.7 13.8 14.6 15.5 16.5 17.7
1752 0.25 1839 0.29 1989 0.37 2129 0.46 2259 0.55 2383 0.64 2501 0.73
12.2 12.6 13.7 14.5 15.3 16.3 17.5
1858 0.30 1940 0.34 2085 0.43 2218 0.52 2343 0.61 2464 0.71
13.2 13.7 14.5 15.2 16.2 17.3
1964 0.35 2041 0.40 2183 0.49 2308 0.58 2430 0.68 2545 0.78
14.5 14.9 15.4 16.2 17.2 18.3
2071 0.41 2144 0.46 2282 0.56 2401 0.66 2519 0.76
15.6 15.8 16.4 17.3 18.3
2177 0.48 2247 0.53 2380 0.64 2497 0.74
16.4 16.7 17.5 18.4
2285 0.56 2351 0.61 2479 0.72
17.3 17.7 18.5
CFM X 100
m³/hr X 100
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
14
TCB-2-10
Level 2 Construction
215/8
183/8
213/4
131/4
*
183/8
23
* Maximum w/Motor Cover
17 5/8
Dimensions shown in inches Maximum rpm — 4050 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 2.75 Maximum bhp at a given rpm — (rpm/3120)
3
Max Motor Frame Size - 145T
Static Pressure in Inches wg
CFM OV
600 326
700 380
800 434
900 489
1000 543
1100 597
1200 652
1300 706
1400 760
1500 815
1600 869
1700 923
1800 978
1900 1032
2000 1086
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1300 0.07 1504 0.11 1875 0.21 2213 0.32
7.3 8.2 10.5 13.2
1453 0.10 1630 0.14 1966 0.24 2273 0.36 2560 0.49
8.4 9.1 11.0 13.3 15.6
1611 0.13 1768 0.18 2070 0.29 2355 0.42 2619 0.55 2872 0.70 3102 0.86
10.0 10.1 11.8 13.7 15.8 18.2 20
1773 0.17 1917 0.23 2188 0.34 2448 0.48 2698 0.62 2932 0.78 3160 0.94 3371 1.11 3568 1.29
11.2 11.3 12.7 14.3 16.2 18.5 20 22 25
1937 0.23 2071 0.29 2319 0.41 2559 0.55 2790 0.70 3011 0.86 3220 1.03 3430 1.22 3626 1.40
12.4 12.7 13.6 15.2 17.0 19.0 21 23 25
2104 0.29 2228 0.35 2457 0.48 2677 0.63 2892 0.79 3103 0.96 3303 1.14 3490 1.32 3685 1.52
13.8 14.3 14.6 16.1 17.9 19.5 21 23 25
2276 0.36 2389 0.43 2601 0.57 2807 0.73 3009 0.89 3199 1.07 3394 1.25 3578 1.45 3751 1.65
15.4 15.4 15.9 17.2 18.9 20 21 23 25
2449 0.45 2552 0.52 2753 0.67 2944 0.83 3128 1.01 3315 1.19 3488 1.38 3670 1.59 3841 1.80
16.4 16.6 17.2 18.3 19.5 21 22 24 25
2623 0.55 2717 0.62 2907 0.79 3083 0.95 3261 1.14 3433 1.33 3603 1.53 3763 1.73 3933 1.96
17.5 17.7 18.5 19.3 20 21 23 24 26
2797 0.66 2883 0.74 3063 0.92 3231 1.09 3398 1.28 3557 1.48 3721 1.69 3878 1.91 4026 2.12
18.6 18.9 19.7 20 21 22 23 25 26
2973 0.79 3052 0.87 3223 1.06 3384 1.25 3537 1.44 3693 1.65 3840 1.86 3995 2.09
19.8 20 21 21 22 23 24 25
3149 0.94 3224 1.03 3384 1.22 3538 1.42 3683 1.62 3831 1.84 3974 2.06
21 21 22 22 23 23 25
3325 1.10 3396 1.19 3546 1.40 3693 1.61 3834 1.82 3970 2.04
22 22 23 23 24 24
3502 1.29 3570 1.38 3710 1.59 3852 1.82 3988 2.04
23 24 24 25 25
3679 1.49 3744 1.59 3875 1.81 4012 2.04
25 25 25 26
CFM X 100
m³/hr X 100
15
TCB-1-12
Level 1 Construction
215/8
183/8
213/4
131/4
*
183/8
23
* Maximum w/Motor Cover
17 5/8
Dimensions shown in inches Maximum rpm — 2490 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 3.436 Maximum bhp at a given rpm — (rpm/2202) Max Motor Frame Size - 145T
CFM OV
700 380
800 434
900 489
1000 543
1100 597
1200 652
1300 706
1400 760
1500 815
1600 869
1700 923
1800 978
1900 1032
2000 1086
2100 1141
0.125 0.25 0.5 00.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
853 0.06 958 0.08 1158 0.14 1345 0.21 1518 0.28
6.2 6.6 7.9 9.4 11.0
943 0.08 1042 0.11 1218 0.17 1386 0.24 1551 0.31 1703 0.40
6.6 7.0 8.3 9.6 11.1 12.5
1037 0.10 1128 0.13 1287 0.20 1442 0.27 1587 0.35 1736 0.44 1873 0.53 2000 0.63
7.1 7.6 8.7 9.9 11.2 12.6 14.2 15.5
1132 0.13 1216 0.17 1363 0.24 1506 0.31 1643 0.40 1771 0.49 1906 0.59 2033 0.69 2151 0.79
7.8 8.3 9.1 10.3 11.5 12.8 14.3 15.6 17.0
1229 0.16 1305 0.20 1447 0.28 1574 0.36 1702 0.45 1827 0.55 1943 0.65 2066 0.75 2183 0.86
8.6 8.9 9.6 10.8 12.0 13.3 14.4 15.7 17.1
1326 0.20 1398 0.25 1532 0.34 1649 0.42 1769 0.51 1884 0.61 1999 0.71 2105 0.82 2216 0.94
9.2 9.5 10.3 11.3 12.6 13.9 14.9 15.9 17.3
1426 0.25 1492 0.30 1619 0.39 1732 0.49 1839 0.58 1950 0.68 2055 0.79 2161 0.90 2260 1.02
9.8 10.2 11.2 12.1 13.4 14.5 15.4 16.4 17.6
1526 0.31 1588 0.36 1707 0.46 1817 0.56 1916 0.66 2019 0.76 2120 0.88 2217 0.99 2316 1.11
10.6 11.2 12.2 13.2 14.2 15.1 16.0 17.0 18.1
1627 0.37 1684 0.42 1796 0.53 1903 0.64 1999 0.75 2089 0.85 2188 0.97 2281 1.09 2372 1.21
11.9 12.5 13.5 14.4 14.9 15.7 16.7 17.6 18.7
1729 0.44 1781 0.50 1886 0.61 1990 0.73 2084 0.85 2170 0.96 2258 1.07 2350 1.20 2436 1.33
13.4 13.9 15.0 15.3 15.7 16.5 17.4 18.3 19.4
1830 0.53 1879 0.58 1980 0.70 2077 0.83 2170 0.95 2254 1.07 2334 1.19 2419 1.32
15.1 15.7 15.9 16.2 16.7 17.3 18.1 19.1
1932 0.62 1978 0.68 2074 0.80 2166 0.93 2256 1.07 2339 1.20 2417 1.32
16.6 16.6 16.8 17.1 17.6 18.2 19.0
2034 0.72 2078 0.78 2169 0.91 2256 1.05 2343 1.19 2425 1.33
17.3 17.3 17.6 18.0 18.5 19.2
2137 0.83 2179 0.90 2265 1.03 2348 1.18 2432 1.33
18.0 18.1 18.4 18.9 19.5
2240 0.96 2280 1.02 2361 1.17 2442 1.32
18.7 18.8 19.2 19.8
CFM X 100
m³/hr X 100
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
16
TCB-2-12
Level 2 Construction
215/8
183/8
213/4
131/4
*
183/8
23
* Maximum w/Motor Cover
17 5/8
Dimensions shown in inches Maximum rpm — 3274 Outlet Velocity = cfm X 0.543 Tip Speed = rpm X 3.21 Maximum bhp at a given rpm — (rpm/2315) Max Motor Frame Size - 182T
CFM OV
750 407
900 489
1050 570
1200 652
1350 733
1500 815
1650 896
1800 978
1950 1059
2100 1141
2250 1222
2400 1304
2550 1385
2700 1467
2850 1548
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
1009 0.08 1226 0.14 1587 0.27
5.5 6.7 9.8
1119 0.11 1315 0.18 1648 0.32 1936 0.49 2182 0.67
6.3 7.6 10.2 13.1 15.9
1238 0.15 1419 0.23 1728 0.39 1995 0.56 2240 0.76 2456 0.96
7.5 8.5 11.0 13.6 16.4 19.0
1363 0.20 1529 0.29 1813 0.46 2070 0.65 2299 0.85 2514 1.08 2710 1.31 2890 1.55
8.9 9.6 12.0 14.2 16.9 19.5 22 24
1495 0.27 1643 0.36 1911 0.55 2151 0.76 2372 0.97 2574 1.20 2768 1.45 2948 1.71 3115 1.97
10.4 11.1 13.2 15.2 17.6 20 22 25 28
1630 0.34 1764 0.44 2018 0.66 2240 0.88 2452 1.11 2647 1.35 2828 1.60 3007 1.87 3174 2.16
12.0 12.9 14.5 16.6 18.6 21 23 26 29
1767 0.44 1887 0.54 2127 0.77 2338 1.01 2534 1.26 2727 1.51 2903 1.78 3067 2.05 3233 2.35
13.9 14.4 15.9 18.4 19.9 22 24 27 30
1908 0.55 2018 0.66 2239 0.90 2445 1.17 2630 1.43 2808 1.70 2983 1.98 3145 2.27
15.9 16.5 18.0 19.9 22 23 25 28
2053 0.68 2151 0.79 2356 1.05 2554 1.34 2731 1.62 2900 1.90 3064 2.20 3225 2.50
18.2 18.8 20 22 23 25 27 29
2198 0.83 2286 0.95 2477 1.22 2664 1.52 2839 1.83 2997 2.13 3154 2.44
21 22 22 23 25 27 29
2344 1.00 2423 1.13 2599 1.41 2777 1.73 2948 2.05 3104 2.38 3250 2.71
24 24 25 26 27 29 32
2490 1.19 2560 1.33 2726 1.63 2896 1.96 3058 2.30 3212 2.65
26 26 27 28 30 32
2637 1.41 2703 1.56 2858 1.87 3016 2.21 3169 2.57
28 29 29 31 32
2785 1.66 2847 1.81 2991 2.14 3138 2.48
31 31 32 34
2933 1.93 2992 2.09 3126 2.43 3262 2.79
34 34 35 37
CFM X 100
m³/hr X 100
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
17
TCB-1-13
Level 1 Construction
23 5/
8
203/8
231/
137/8
*
4
197/8 241/2
* Maximum w/Motor Cover
19
Dimensions shown in inches Maximum rpm — 2355 Outlet Velocity = cfm X 0.442 Tip Speed = rpm X 3.435 Maximum bhp at a given rpm — (rpm/2119)
3
Max Motor Frame Size - 145T
Static Pressure in Inches wg
CFM OV
600 265
750 331
900 398
1050 464
1200 530
1350 597
1500 663
1650 730
1800 796
1950 862
2100 929
2250 995
2400 1061
2550 1128
2700 1194
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
660 0.03 792 0.05 1019 0.10
4.1 5.1 6.9
760 0.05 874 0.07 1073 0.13 1254 0.19
4.8 5.8 7.1 8.4
864 0.07 967 0.10 1146 0.16 1305 0.23 1459 0.30
5.8 6.4 7.5 8.6 10.2
973 0.09 1067 0.13 1230 0.20 1378 0.27 1512 0.36 1646 0.44 1770 0.53
6.6 7.0 8.0 9.1 10.3 12.0 14.0
1085 0.13 1171 0.17 1321 0.24 1457 0.32 1585 0.41 1703 0.51 1820 0.61 1933 0.71 2039 0.81
7.2 7.7 8.6 9.6 10.8 12.0 13.6 15.3 17.2
1199 0.17 1277 0.22 1419 0.30 1545 0.39 1662 0.48 1777 0.58 1883 0.69 1984 0.80 2089 0.91
8.1 8.5 9.4 10.3 11.4 12.5 13.6 15.1 16.7
1316 0.23 1387 0.27 1520 0.37 1637 0.46 1749 0.59 1853 0.67 1957 0.78 2054 0.90 2146 1.02
9.0 9.4 10.2 11.2 12.2 13.2 14.3 15.5 16.9
1434 0.29 1499 0.34 1623 0.44 1736 0.55 1839 0.65 1940 0.77 2034 0.88 2128 1.00 2219 1.13
10.0 10.4 11.3 12.3 13.2 14.3 15.3 16.5 17.8
1552 0.37 1613 0.42 1729 0.54 1836 0.65 1935 0.76 2029 0.88 2121 1.00 2207 1.13 2293 1.26
11.2 11.5 12.5 13.4 14.4 15.4 16.5 17.7 19.0
1672 0.45 1728 0.52 1836 0.64 1939 0.76 2034 0.88 2123 1.00 2209 1.13 2294 1.27
12.4 12.9 13.8 14.7 15.6 16.7 17.8 19.0
1792 0.56 1844 0.62 1947 0.76 2044 0.89 2135 1.02 2221 1.15 2302 1.28
13.8 14.2 15.1 16.1 17.0 18.1 19.2
1913 0.67 1962 0.75 2058 0.89 2150 1.03 2238 1.17 2321 1.31
15.2 15.7 16.7 17.7 18.6 19.6
2034 0.81 2080 0.88 2171 1.04 2258 1.19 2342 1.33
16.9 17.4 18.4 19.4 20
2155 0.95 2199 1.04 2285 1.20
18.7 19.2 20
2277 1.12 2319 1.21
21 21
18
CFM X 100
m³/hr X 100
TCB-2-13
Level 2 Construction
23 5/
8
203/8
231/
137/8
*
4
197/8 241/2
* Maximum w/Motor Cover
19
Dimensions shown in inches Maximum rpm — 2971 Outlet Velocity = cfm X 0.442 Tip Speed = rpm X 3.53 Maximum bhp at a given rpm — (rpm/1933)
3
Max Motor Frame Size - 182T
Static Pressure in Inches wg
CFM
800 353
1000 442
1200 530
1400 619
1600 707
1800 796
2000 884
2200 973
2400 1061
2600 1150
2800 1238
3000 1327
3200 1415
3400 1504
3600 1592
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
OV
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
828 0.08 1026 0.14 1379 0.30
3.8 5.6 10.4
934 0.11 1108 0.18 1418 0.35 1692 0.55
4.4 6.0 10.1 13.5
1048 0.16 1206 0.24 1479 0.42 1731 0.64 1961 0.87
5.8 7.2 10.1 13.0 16.5
1171 0.22 1313 0.31 1562 0.51 1784 0.73 2002 0.99 2201 1.26 2391 1.55
7.5 8.7 10.6 12.8 16.0 18.9 22
1300 0.30 1424 0.40 1657 0.62 1865 0.86 2053 1.12 2247 1.41 2425 1.71 2596 2.03 2759 2.37
9.7 10.0 11.5 13.3 15.6 18.4 21 24 27
1431 0.39 1545 0.51 1759 0.75 1950 1.01 2134 1.29 2300 1.57 2472 1.89 2636 2.23 2790 2.58
11.4 11.3 12.5 14.4 16.0 18.1 21 24 26
1565 0.51 1669 0.63 1868 0.90 2050 1.18 2217 1.48 2381 1.78 2531 2.10 2683 2.44 2836 2.82
12.7 12.7 13.7 15.7 17.0 18.6 21 23 26
1700 0.64 1797 0.78 1979 1.07 2152 1.38 2312 1.69 2464 2.02 2612 2.36 2750 2.70 2883 3.06
14.2 14.5 15.6 16.9 18.3 19.8 21 23 26
1836 0.81 1928 0.96 2097 1.27 2260 1.60 2413 1.94 2556 2.28 2695 2.64 2831 3.01 2959 3.38
16.4 16.9 17.4 18.2 19.7 21 23 24 26
1975 1.00 2060 1.16 2219 1.50 2371 1.85 2517 2.21 2656 2.57 2785 2.95 2914 3.34
19.0 19.2 19.3 19.6 21 23 24 26
2115 1.22 2194 1.40 2343 1.75 2484 2.12 2626 2.51 2758 2.90 2885 3.30
21 21 21 22 23 24 26
2256 1.48 2329 1.66 2470 2.04 2605 2.43 2737 2.84 2864 3.25
24 24 24 24 25 26
2397 1.77 2464 1.96 2600 2.36 2728 2.78 2849 3.20
26 26 26 27 27
2539 2.10 2601 2.30 2731 2.72 2852 3.16 2969 3.61
29 29 30 30 30
2681 2.47 2739 2.67 2863 3.12
33 33 33
CFM X 100
m³/hr X 100
19
TCB-1-16
Level 1 Construction
27 5/
8
243/8
26
161/8
*
237/8 281/2
* Maximum w/Motor Cover
217/8
Dimensions shown in inches Maximum rpm — 2000 Outlet Velocity = cfm X 0.309 Tip Speed = rpm X 4.384 Maximum bhp at a given rpm — (rpm/1378)
3
Max Motor Frame Size - 182T
Static Pressure in Inches wg
CFM OV
1000 308
1250 385
1500 462
1750 540
2000 617
2250 694
2500 771
2750 848
3000 925
3250 1003
3500 1080
3750 1157
4000 1234
4250 1311
4500 1388
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
507 0.05 612 0.09 802 0.17
3.7 4.3 5.9
584 0.08 671 0.12 833 0.21 985 0.32
4.5 4.9 6.2 8.1
668 0.11 743 0.16 884 0.26 1016 0.38 1145 0.52
5.4 5.8 6.9 8.4 10.3
755 0.16 821 0.21 944 0.32 1065 0.45 1176 0.59 1289 0.75 1392 0.91
6.4 6.8 7.9 9.3 10.5 12.0 13.6
844 0.22 904 0.28 1014 0.40 1119 0.54 1225 0.69 1322 0.85 1422 1.02 1517 1.20 1605 1.39
7.6 8.1 9.2 10.4 11.3 12.4 14.0 15.7 17.5
934 0.30 989 0.36 1090 0.49 1185 0.64 1278 0.80 1373 0.97 1460 1.15 1547 1.34 1635 1.54
8.9 9.4 10.7 11.4 12.3 13.3 14.6 16.1 17.9
1026 0.39 1077 0.47 1169 0.61 1257 0.76 1342 0.92 1425 1.10 1511 1.30 1591 1.49 1666 1.70
10.4 11.0 11.9 12.6 13.4 14.4 15.6 16.9 18.4
1118 0.51 1166 0.59 1252 0.74 1334 0.91 1411 1.07 1489 1.26 1564 1.46 1643 1.67 1717 1.88
12.1 12.4 13.1 13.8 14.7 15.7 16.8 18.1 19.4
1210 0.64 1256 0.73 1337 0.90 1412 1.07 1486 1.25 1556 1.44 1627 1.65 1695 1.86 1769 2.09
13.4 13.8 14.5 15.2 16.1 17.1 18.3 19.4 21
1303 0.80 1347 0.90 1423 1.08 1494 1.27 1563 1.46 1630 1.66 1695 1.86 1760 2.09 1823 2.32
14.9 15.3 16.1 16.9 17.7 18.7 19.9 21 22
1397 0.98 1438 1.09 1511 1.28 1578 1.48 1642 1.69 1706 1.90 1768 2.11 1828 2.33 1889 2.58
16.6 17.0 17.9 18.7 19.5 21 22 23 24
1491 1.19 1530 1.30 1599 1.52 1663 1.73 1725 1.94 1784 2.16 1844 2.39 1900 2.62 1956 2.86
18.5 18.9 19.7 21 22 23 24 25 27
1585 1.43 1622 1.55 1689 1.78 1750 2.00 1809 2.23 1865 2.46 1921 2.70 1976 2.95
20 21 22 23 24 25 26 28
1680 1.70 1714 1.83 1779 2.07 1838 2.31 1893 2.55 1948 2.80 1999 3.04
23 23 24 25 26 28 29
1775 2.00 1807 2.14 1869 2.40 1926 2.65 1979 2.91
25 26 27 28 30
20
CFM X 1000
m³/hr X 1000
TCB-2-16
Level 2 Construction
27 5/
8
243/8
26
161/8
*
237/8 281/2
* Maximum w/Motor Cover
217/8
Dimensions shown in inches Maximum rpm — 2431 Outlet Velocity = cfm X 0.309 Tip Speed = rpm X 4.32 Maximum bhp at a given rpm — (rpm/1406)
3
Max Motor Frame Size - 184T
Static Pressure in Inches wg
CFM OV
1200 370
1500 462
1800 555
2100 648
2400 740
2700 833
3000 925
3300 1018
3600 1111
3900 1203
4200 1296
4500 1388
4800 1481
5100 1574
5400 1666
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
668 0.11 842 0.20 1137 0.41
4.6 6.1 10.4
749 0.15 899 0.25 1166 0.49 1395 0.77
5.5 6.8 10.2 13.8
843 0.21 969 0.33 1208 0.59 1424 0.89 1616 1.21
7.1 7.7 10.4 13.5 16.8
944 0.30 1053 0.42 1268 0.71 1461 1.03 1647 1.38 1813 1.75 1972 2.15
8.3 8.8 11.1 13.4 16.6 19.6 22
1047 0.40 1144 0.54 1336 0.85 1518 1.20 1684 1.57 1847 1.97 1996 2.38 2140 2.83 2275 3.29
9.9 10.5 12.0 14.0 16.6 19.5 22 25 27
1152 0.53 1243 0.68 1412 1.01 1579 1.39 1739 1.79 1885 2.21 2033 2.66 2169 3.12 2297 3.59
11.6 12.2 13.2 15.0 17.1 19.5 22 25 28
1260 0.69 1345 0.86 1498 1.21 1651 1.61 1799 2.04 1941 2.48 2070 2.95 2206 3.44 2333 3.94
13.2 13.6 14.4 16.2 18.2 20 23 25 28
1373 0.89 1448 1.07 1588 1.44 1727 1.86 1866 2.31 2001 2.79 2129 3.28 2247 3.79 2370 4.32
14.7 15.1 16.1 17.7 19.5 22 24 26 29
1486 1.12 1553 1.31 1686 1.71 1813 2.15 1939 2.62 2065 3.12 2188 3.65 2306 4.18 2416 4.73
16.6 17.1 18.2 19.3 21 23 25 28 30
1600 1.40 1658 1.59 1786 2.02 1900 2.47 2020 2.97 2138 3.49 2252 4.04 2366 4.61
18.9 19.4 20 21 23 25 27 29
1715 1.72 1766 1.91 1888 2.38 1996 2.85 2106 3.36 2213 3.90 2324 4.48 2430 5.08
21 21 22 23 24 26 29 31
1831 2.08 1878 2.28 1990 2.77 2095 3.28 2193 3.80 2298 4.37 2398 4.96
23 23 24 25 27 28 31
1946 2.50 1992 2.71 2094 3.22 2196 3.76 2289 4.30 2385 4.88
25 26 27 28 29 31
2062 2.96 2105 3.19 2199 3.71 2297 4.29 2388 4.86
28 28 29 30 32
2179 3.49 2219 3.73 2305 4.26 2399 4.87
30 31 32 33
CFM X 1000
m³/hr X 1000
21
TCB-1-18
Level 1 Construction
33 5/8
303/8
291/4
183/8
*
263/8
31
* Maximum w/Motor Cover
261/8
Dimensions shown in inches Maximum rpm — 1645 Outlet Velocity = cfm X 0.199 Tip Speed = rpm X 4.843 Maximum bhp at a given rpm — (rpm/1147)
3
Max Motor Frame Size - 182T
Static Pressure in Inches wg
CFM OV
1500 298
1800 357
2100 417
2400 477
2700 536
3000 596
3300 656
3600 715
3900 775
4200 834
4500 894
4800 954
5100 1013
5400 1073
5700 1133
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
486 0.08 568 0.12 724 0.23
4.3 4.9 6.2
552 0.11 623 0.16 755 0.28 883 0.42
5.4 5.7 6.7 8.1
622 0.16 683 0.21 799 0.34 911 0.48 1022 0.65 1123 0.82
6.7 6.8 7.7 8.5 9.9 11.6
693 0.21 749 0.28 852 0.41 950 0.56 1048 0.73 1147 0.92 1238 1.12 1322 1.33
8.0 8.1 9.0 9.5 10.3 12.0 13.5 14.8
765 0.29 817 0.36 911 0.50 1001 0.66 1088 0.84 1174 1.03 1262 1.24 1346 1.46 1424 1.69
9.1 9.4 10.3 10.5 11.3 12.5 13.8 15.0 16.4
838 0.37 887 0.45 972 0.61 1056 0.78 1136 0.97 1214 1.17 1292 1.38 1369 1.61 1448 1.85
10.2 10.6 11.1 11.5 12.2 13.3 14.2 15.3 16.6
912 0.48 957 0.57 1038 0.74 1115 0.92 1187 1.11 1261 1.32 1331 1.54 1403 1.77 1472 2.02
11.2 11.4 12.0 12.6 13.3 14.1 14.9 15.8 16.8
987 0.61 1029 0.70 1105 0.89 1176 1.08 1246 1.28 1312 1.49 1379 1.72 1443 1.96 1510 2.22
12.1 12.5 13.1 13.8 14.5 15.2 16.0 16.8 17.8
1063 0.75 1102 0.85 1174 1.06 1239 1.26 1305 1.47 1368 1.70 1430 1.93 1491 2.18 1549 2.44
13.3 13.7 14.3 14.9 15.7 16.5 17.3 18.1 18.9
1139 0.92 1175 1.03 1244 1.25 1307 1.47 1366 1.69 1428 1.93 1485 2.17 1542 2.43 1599 2.69
14.6 14.9 15.5 16.3 17.1 17.9 18.7 19.5 20
1215 1.12 1249 1.24 1315 1.47 1375 1.70 1430 1.93 1488 2.18 1544 2.44 1597 2.70
16.0 16.2 16.9 17.6 18.5 19.4 20 21
1292 1.34 1323 1.47 1386 1.72 1444 1.97 1498 2.21 1549 2.46 1604 2.73
17.1 17.4 18.1 19.0 19.9 21 22
1369 1.59 1399 1.72 1458 1.99 1513 2.26 1565 2.52 1615 2.78
18.4 18.7 19.5 20 21 23
1446 1.88 1474 2.01 1530 2.29 1584 2.58 1634 2.85
19.7 20 21 22 23
1523 2.19 1550 2.33 1603 2.63
21 22 22
22
CFM X 1000
m³/hr X 1000
TCB-2-18
Level 2 Construction
33 5/8
303/8
291/4
183/8
*
263/8
31
* Maximum w/Motor Cover
261/8
Dimensions shown in inches Maximum rpm — 2099 Outlet Velocity = cfm X 0.199 Tip Speed = rpm X 4.78 Maximum bhp at a given rpm — (rpm/1224)
3
Max Motor Frame Size - 184T
Static Pressure in Inches wg
CFM OV
1400 278
1750 347
2100 417
2450 487
2800 556
3150 626
3500 695
3850 765
4200 834
4550 904
4900 974
5250 1043
5600 1113
5950 1182
6300 1252
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
588 0.11 725 0.20
5.2 6.2
666 0.16 785 0.26 995 0.50
6.8 7.5 9.4
752 0.23 857 0.34 1045 0.61 1214 0.90 1369 1.22
9.6 8.9 10.1 12.5 15.2
843 0.31 936 0.44 1105 0.73 1259 1.05 1404 1.40 1536 1.76
11.2 10.4 11.3 13.1 15.7 17.9
937 0.42 1021 0.57 1177 0.89 1318 1.23 1450 1.61 1577 2.00 1697 2.41 1812 2.83
12.6 12.1 12.9 14.5 16.7 18.4 20 23
1033 0.55 1110 0.72 1253 1.07 1384 1.44 1508 1.84 1624 2.26 1738 2.70 1847 3.15 1949 3.62
13.9 13.9 14.6 16.3 17.8 19.1 21 23 25
1131 0.71 1202 0.90 1333 1.28 1457 1.69 1571 2.11 1682 2.55 1787 3.02 1889 3.50 1991 4.00
15.7 15.8 16.6 18.5 19.3 20 21 23 26
1230 0.91 1296 1.11 1416 1.52 1532 1.96 1642 2.41 1743 2.88 1845 3.37 1942 3.88 2032 4.40
17.7 18.0 19.1 20 21 22 23 24 26
1331 1.14 1391 1.35 1505 1.80 1612 2.27 1715 2.75 1815 3.25 1906 3.76 2000 4.30 2090 4.85
20 21 21 22 23 24 25 26 28
1433 1.41 1488 1.64 1595 2.12 1694 2.62 1793 3.14 1887 3.67 1977 4.21 2062 4.76
23 23 23 24 24 25 27 28
1535 1.73 1585 1.96 1687 2.48 1781 3.01 1873 3.56 1963 4.12 2050 4.69
25 25 25 26 26 27 29
1638 2.09 1683 2.33 1781 2.89 1871 3.45 1955 4.03 2042 4.62
27 27 27 28 28 30
1741 2.50 1784 2.76 1875 3.34 1961 3.94 2042 4.54
29 29 29 30 31
1844 2.96 1885 3.24 1971 3.84 2053 4.48
31 31 31 33
1948 3.48 1987 3.77 2067 4.40
33 33 34
CFM X 1000
m³/hr X 1000
23
TCB-1-22
Level 1 Construction
39 5/8
363/8
33 3/4
221/2
*
283/8 351/
2
* Maximum w/Motor Cover
301/2
Dimensions shown in inches Maximum rpm — 1375 Outlet Velocity = cfm X 0.139 Tip Speed = rpm X 5.595 Maximum bhp at a given rpm — (rpm/962)
3
Max Motor Frame Size - 182T
Static Pressure in Inches wg
CFM OV
1600 221
2000 277
2400 332
2800 387
3200 443
3600 498
4000 554
4400 609
4800 664
5200 720
5600 775
6000 831
6400 886
6800 941
7200 997
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
388 0.07 477 0.12
3.2 4.5
442 0.10 516 0.15 656 0.30
3.9 5.0 6.7
502 0.14 566 0.20 687 0.36 800 0.54 900 0.73
4.9 5.6 6.9 8.6 10.4
564 0.19 621 0.27 727 0.43 829 0.62 926 0.83 1013 1.05
6.0 6.4 7.6 8.6 10.3 12.1
629 0.26 680 0.34 776 0.52 865 0.72 955 0.95 1039 1.19 1119 1.44 1192 1.69
7.1 7.5 8.3 9.3 10.5 12.3 14.2 16.3
695 0.35 741 0.44 829 0.63 911 0.85 991 1.08 1070 1.34 1145 1.60 1218 1.88 1286 2.16
8.5 8.7 9.2 10.2 11.4 12.7 14.5 16.5 19.0
762 0.46 804 0.56 884 0.76 960 0.99 1033 1.23 1105 1.49 1177 1.78 1244 2.08 1312 2.38
9.7 9.8 10.3 11.4 12.6 14.0 15.1 16.6 18.9
831 0.59 869 0.70 943 0.92 1014 1.16 1082 1.42 1147 1.68 1213 1.97 1278 2.29 1340 2.61
10.9 11.1 11.8 12.9 14.2 15.3 16.3 17.4 18.9
900 0.74 935 0.86 1004 1.10 1068 1.35 1133 1.63 1195 1.91 1254 2.20 1314 2.51
12.4 12.6 13.5 14.6 15.9 16.8 17.7 18.8
969 0.92 1002 1.05 1065 1.31 1127 1.58 1187 1.86 1244 2.16 1302 2.47 1356 2.78
14.0 14.3 15.2 16.6 17.4 18.3 19.3 20
1038 1.13 1069 1.26 1129 1.54 1187 1.83 1242 2.12 1298 2.44 1351 2.77
15.8 16.3 17.3 18.1 19 20 21
1108 1.36 1137 1.51 1193 1.81 1248 2.11 1301 2.42 1352 2.75
17.9 18.2 18.9 19.8 21 22
1178 1.63 1206 1.79 1259 2.10 1309 2.43 1361 2.76
19.3 19.7 21 22 23
1249 1.94 1274 2.10 1325 2.43 1373 2.78
21 21 22 24
1319 2.28 1344 2.45
23 23
24
CFM X 1000
m³/hr X 1000
TCB-2-22
Level 2 Construction
39 5/8
363/8
33 3/4
221/2
*
283/8 351/
2
* Maximum w/Motor Cover
301/2
Dimensions shown in inches Maximum rpm — 1722 Outlet Velocity = cfm X 0.139 Tip Speed = rpm X 5.83 Maximum bhp at a given rpm — (rpm/910)
3
Max Motor Frame Size - 213T
Static Pressure in Inches wg
CFM OV
2000 277
2500 346
3000 415
3500 484
4000 554
4500 623
5000 692
5500 761
6000 831
6500 900
7000 969
7500 1038
8000 1108
8500 1177
9000 1246
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
484 0.15 598 0.27
4.7 5.5
549 0.22 648 0.36 823 0.67
6.4 6.5 9.4
620 0.30 705 0.47 863 0.82 1004 1.21 1127 1.61
7.6 7.8 10.0 12.2 14.6
695 0.42 771 0.60 913 1.00 1040 1.43 1162 1.88 1270 2.35
9.0 9.3 11.0 12.9 15.3 17.1
773 0.56 841 0.77 969 1.21 1089 1.68 1197 2.18 1305 2.69 1403 3.22 1493 3.76
10.8 11.0 12.4 14.2 16.0 17.7 19.7 22
853 0.74 915 0.97 1030 1.45 1141 1.96 1246 2.50 1341 3.07 1438 3.64 1528 4.23 1612 4.83
12.8 12.9 14.0 15.8 17.1 18.4 20 22 25
933 0.96 991 1.21 1098 1.73 1199 2.28 1297 2.87 1390 3.47 1476 4.10 1563 4.73 1646 5.38
14.6 14.8 16.0 17.5 18.4 19.5 21 23 25
1015 1.22 1069 1.49 1167 2.05 1261 2.65 1353 3.27 1440 3.92 1525 4.59 1604 5.27 1682 5.97
16.6 17.0 18.4 19.0 19.7 21 22 24 26
1098 1.52 1148 1.82 1241 2.43 1328 3.06 1411 3.73 1495 4.42 1575 5.13 1653 5.85
18.7 19.3 20 20 21 22 24 25
1181 1.88 1228 2.20 1315 2.85 1396 3.53 1476 4.24 1553 4.97 1630 5.72 1704 6.49
21 21 22 22 23 24 25 27
1265 2.29 1309 2.64 1391 3.34 1468 4.06 1543 4.80 1614 5.57 1687 6.36
23 23 24 24 25 26 27
1349 2.76 1390 3.14 1468 3.88 1542 4.64 1611 5.43 1681 6.24
25 25 26 26 27 28
1433 3.30 1472 3.70 1546 4.49 1617 5.30 1683 6.13
27 28 28 29 29
1518 3.90 1555 4.33 1626 5.17 1692 6.02
30 30 31 32
1603 4.57 1638 5.03 1706 5.92
33 34 34
25
TCB-1-24
Level 1 Construction
45 3/4
421/2
371/4
245/8
*
347/8
42
* Maximum w/Motor Cover
343/4
Dimensions shown in inches Maximum rpm — 1225 Outlet Velocity = cfm X 0.102 Tip Speed = rpm X 6.414 Maximum bhp at a given rpm — (rpm/729)
3
Max Motor Frame Size - 184T
Static Pressure in Inches wg
CFM OV
2500 253
3000 304
3500 355
4000 406
4500 456
5000 507
5500 558
6000 609
6500 659
7000 710
7500 761
8000 812
8500 862
9000 913
9500 964
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
355 0.12 416 0.19 536 0.36
3.3 4.0 6.1
401 0.16 456 0.25 557 0.44 655 0.66
4.3 5.1 6.5 9.1
448 0.23 500 0.32 587 0.52 672 0.76 757 1.02
5.7 6.2 7.9 9.5 10.8
497 0.31 545 0.41 626 0.63 701 0.88 775 1.16 850 1.46
7.0 7.7 9.8 10.3 11.1 13.1
548 0.41 591 0.53 667 0.77 735 1.03 803 1.32 867 1.63 935 1.96 998 2.31
8.4 9.4 10.9 11.5 12.1 13.5 15.2 17.0
599 0.53 639 0.66 711 0.92 774 1.20 833 1.50 896 1.83 953 2.17 1015 2.54 1073 2.92
10.3 11.3 12.2 12.8 13.6 14.5 15.6 17.3 19.0
651 0.68 688 0.82 757 1.11 816 1.40 872 1.72 926 2.05 983 2.41 1035 2.79 1091 3.18
12.1 12.6 13.7 14.4 15.5 16.1 16.8 17.9 19.5
704 0.85 738 1.00 803 1.32 860 1.64 913 1.97 964 2.31 1013 2.68 1065 3.07 1114 3.48
13.6 14.1 15.2 16.6 17.1 17.7 18.3 19.2 20
757 1.05 789 1.22 850 1.55 905 1.90 955 2.25 1004 2.61 1050 2.99 1095 3.39 1144 3.82
15.1 15.7 17.2 18.4 18.8 19.3 20 21 22
811 1.29 840 1.46 897 1.82 951 2.20 1000 2.57 1045 2.95 1090 3.35 1132 3.75 1174 4.18
16.9 17.7 19.0 19.8 20 21 22 23 24
865 1.56 892 1.74 946 2.13 997 2.52 1045 2.92 1089 3.32 1130 3.73 1172 4.16 1212 4.60
19.1 19.7 20 21 22 23 24 25 26
919 1.87 944 2.06 995 2.47 1044 2.88 1091 3.31 1133 3.74 1173 4.17 1213 4.61
21 21 22 23 24 25 25 26
973 2.21 997 2.42 1046 2.85 1092 3.29 1137 3.74 1179 4.19 1218 4.64
22 23 23 24 25 27 28
1028 2.60 1051 2.82 1096 3.27 1140 3.73 1183 4.20 1224 4.69
24 24 25 26 27 29
1082 3.03 1104 3.26 1147 3.73 1189 4.22
25 26 27 28
26
TCB-2-24
Level 2 Construction
45 3/4
421/2
371/4
245/8
*
347/8
42
* Maximum w/Motor Cover
343/4
Dimensions shown in inches Maximum rpm — 1425 Outlet Velocity = cfm X 0.102 Tip Speed = rpm X 6.41 Maximum bhp at a given rpm — (rpm/661)
3
Max Motor Frame Size - 215T
Static Pressure in Inches wg
CFM OV
2800 284
3500 355
4200 426
4900 497
5600 568
6300 639
7000 710
7700 781
8400 852
9100 923
9800 994
10500 1065
11200 1137
11900 1208
12600 1279
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
393 0.21 489 0.39
5.4 6.7
443 0.30 528 0.50 672 0.97
7.0 7.9 10.2
497 0.42 572 0.65 703 1.17 820 1.74
8.5 9.3 11.0 13.8
555 0.57 623 0.83 743 1.41 849 2.04 949 2.71
10.5 11.2 12.5 14.7 17.9
616 0.76 676 1.05 786 1.69 887 2.37 978 3.10 1066 3.87 1146 4.66
12.7 12.9 14.1 16.2 18.5 21 23
679 0.99 733 1.32 834 2.01 928 2.76 1015 3.54 1095 4.36 1175 5.22 1248 6.10
14.7 14.9 16.1 18.2 19.5 21 23 26
742 1.28 792 1.64 886 2.39 973 3.19 1056 4.04 1133 4.92 1204 5.82 1277 6.77 1345 7.73
16.5 16.8 18.2 20 21 22 24 26 29
806 1.62 852 2.01 939 2.83 1021 3.69 1098 4.58 1173 5.52 1243 6.49 1308 7.49 1374 8.52
18.4 18.9 21 22 23 24 25 27 29
871 2.03 914 2.45 994 3.33 1072 4.25 1145 5.20 1214 6.19 1283 7.22 1347 8.28 1407 9.36
21 21 23 23 24 25 27 28 30
937 2.50 977 2.95 1052 3.89 1125 4.87 1194 5.89 1260 6.94 1324 8.02 1387 9.14
23 24 24 25 26 27 29 30
1002 3.04 1040 3.53 1111 4.53 1179 5.57 1246 6.65 1308 7.76 1369 8.90
25 26 27 28 29 30 31
1069 3.66 1105 4.19 1171 5.25 1235 6.35 1298 7.49 1359 8.66 1417 9.86
27 28 29 30 32 33 34
1135 4.36 1169 4.93 1233 6.05 1293 7.22 1352 8.42 1411 9.65
30 31 32 33 35 36
1202 5.15 1234 5.76 1295 6.95 1352 8.18 1408 9.44
33 34 35 36 38
1269 6.04 1299 6.68 1358 7.94 1412 9.23
36 37 38 40
27
TCB-1-30
Level 1 Construction
52 3/
4
481/2
423/4
291/2
*
407/8 481/2
* Maximum w/Motor Cover
42
Dimensions shown in inches Maximum rpm — 955 Outlet Velocity = cfm X 0.078 Tip Speed = rpm X 7.984 Maximum bhp at a given rpm — (rpm/514)
3
Max Motor Frame Size - 213T
Static Pressure in Inches wg
CFM OV
3750 292
4500 350
5250 409
6000 467
6750 526
7500 584
8250 643
9000 701
9750 759
10500 818
11250 876
12000 935
12750 993
13500 1052
14250 1110
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 .75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
293 0.19 343 0.30
4.4 4.9
332 0.27 376 0.39 456 0.69
5.1 5.5 6.6
372 0.37 413 0.51 483 0.83 550 1.21
6.0 6.3 7.6 9.2
413 0.50 451 0.67 516 1.01 576 1.41 634 1.84
7.1 7.6 9.0 10.1 11.3
455 0.67 490 0.85 550 1.22 606 1.64 659 2.10 709 2.59
8.4 9.0 10.5 11.3 12.2 13.6
497 0.87 530 1.08 587 1.48 639 1.92 687 2.39 735 2.91 781 3.46 833 4.03
9.9 11.0 12.0 12.7 13.6 14.6 16.0 18.2
540 1.11 571 1.34 626 1.79 673 2.24 719 2.74 762 3.27 807 3.85 849 4.44 894 5.06
12.3 12.6 13.5 14.3 15.3 16.2 17.6 19.1 21
584 1.39 613 1.64 665 2.13 710 2.62 753 3.13 795 3.70 833 4.27 875 4.90 913 5.55
13.6 14.0 15.0 16.1 16.9 18.1 19.4 21 23
629 1.73 655 1.99 704 2.53 748 3.06 788 3.59 828 4.17 866 4.78 901 5.41 940 6.09
15.0 15.5 16.6 17.7 18.8 20 22 23 25
673 2.11 698 2.39 745 2.97 787 3.55 826 4.12 862 4.70 899 5.34 934 6.00
16.5 17.0 18.1 19.5 21 22 24 26
718 2.56 740 2.85 785 3.48 826 4.09 864 4.70 899 5.31 932 5.95
18.1 18.5 20 22 23 25 27
763 3.06 784 3.37 827 4.03 866 4.69 902 5.35 936 6.00
19.7 20 22 24 26 28
808 3.63 828 3.95 868 4.65 906 5.36 941 6.05
22 23 25 27 29
853 4.27 872 4.61 910 5.34 947 6.10
25 25 28 30
898 4.98 916 5.34 953 6.10
28 29 31
28
TCB-2-30
Level 2 Construction
52 3/
4
481/2
423/4
291/2
*
407/8 481/2
* Maximum w/Motor Cover
42
Dimensions shown in inches Maximum rpm — 1279 Outlet Velocity = cfm X 0.078 Tip Speed = rpm X 7.85 Maximum bhp at a given rpm — (rpm/548)
3
Max Motor Frame Size - 254T
Static Pressure in Inches wg
CFM OV
4000 311
4800 374
5600 436
6400 498
7200 561
8000 623
8800 685
9600 748
10400 810
11200 872
12000 935
12800 997
13600 1060
14400 1122
15200 1184
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
375 0.32 456 0.56 597 1.14
5.9 6.3 9.5
417 0.44 489 0.71 618 1.33
6.8 7.3 9.8
461 0.58 527 0.90 644 1.57 749 2.35 844 3.19
8.0 8.4 10.5 13.6 17.2
509 0.76 569 1.11 675 1.85 772 2.66 863 3.58 945 4.54
9.5 9.8 11.6 13.8 17.6 21
558 0.99 611 1.37 712 2.19 802 3.05 886 3.99 967 5.03 1040 6.10
11.2 11.5 13.0 14.6 17.7 21 23
609 1.26 658 1.68 750 2.57 834 3.48 913 4.48 989 5.55 1062 6.69 1130 7.88 1195 9.11
13.0 13.3 14.4 16.2 18.1 21 23 26 29
660 1.59 705 2.03 792 3.00 871 4.00 945 5.03 1016 6.14 1084 7.32 1152 8.58 1214 9.87
15.1 15.2 16.2 18.0 19.5 21 23 26 29
712 1.97 753 2.45 834 3.49 909 4.58 979 5.66 1047 6.82 1111 8.04 1174 9.32 1237 10.7
16.8 17.0 18.1 19.8 21 22 24 27 29
765 2.42 803 2.93 877 4.04 950 5.20 1017 6.38 1080 7.57 1142 8.85 1201 10.2 1259 11.5
18.6 19.0 20 21 23 24 26 27 30
818 2.95 854 3.48 923 4.65 992 5.89 1055 7.17 1117 8.43 1174 9.72 1233 11.1
21 21 22 23 25 26 28 29
872 3.55 905 4.11 970 5.33 1034 6.67 1096 8.00 1155 9.37 1211 10.7 1265 12.1
23 23 24 25 26 28 30 32
926 4.23 957 4.81 1018 6.09 1078 7.49 1138 8.91 1194 10.4 1248 11.8
25 26 26 27 29 30 32
980 4.99 1009 5.60 1067 6.94 1124 8.40 1181 9.91 1235 11.4
27 28 29 30 31 33
1034 5.85 1062 6.49 1117 7.89 1171 9.40 1223 11.0 1277 12.6
30 31 32 33 34 36
1089 6.80 1115 7.47 1168 8.94 1218 10.5 1269 12.2
33 34 35 36 38
29
TCB-1-36
Level 1 Construction
1
/4
59
55
471/4
313/4
*
463/8
54
3
46
/4
Dimensions shown in inches Maximum rpm — 800 Outlet Velocity = cfm X 0.061 Tip Speed = rpm X 9.424 Maximum bhp at a given rpm — (rpm/397)
3
Max Motor Frame Size - 215T
Static Pressure in Inches wg
CFM OV
5600 339
6400 387
7200 436
8000 484
8800 533
9600 581
10400 630
11200 678
12000 727
12800 775
13600 824
14400 872
15200 921
16000 969
16800 1018
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
0.125 0.25 0.5 0.75 1 1.25 1.5 1.75 2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
273 0.32 311 0.48 379 0.86
5.4 6.5 8.1
301 0.42 336 0.60 398 1.01
6.5 7.7 8.7
330 0.55 362 0.75 420 1.18 473 1.67
8.0 8.5 9.5 10.6
360 0.70 389 0.92 443 1.39 491 1.90 539 2.46
9.2 9.5 10.4 11.6 12.9
390 0.89 417 1.12 468 1.62 514 2.17 557 2.75 599 3.37
10.5 10.8 11.6 12.9 14.4 16.1
420 1.11 446 1.35 493 1.89 537 2.47 577 3.08 617 3.73 655 4.41
12.0 12.3 13.0 14.5 16.1 17.3 17.8
451 1.37 475 1.63 519 2.20 561 2.80 600 3.45 636 4.12 673 4.84 708 5.57
13.8 13.9 14.7 16.4 18.1 18.5 19.0 19.6
482 1.66 505 1.94 547 2.54 586 3.18 623 3.86 659 4.57 692 5.30 727 6.07 759 6.87
15.4 15.7 16.8 18.5 19.3 19.7 20 21 22
513 2.00 535 2.30 575 2.93 612 3.61 647 4.31 681 5.05 714 5.82 745 6.61 777 7.44
17.2 17.5 19 20 21 21 21 22 23
545 2.39 565 2.70 603 3.36 638 4.07 673 4.81 705 5.58 737 6.38 766 7.21 796 8.06
19.1 19.6 21 22 22 22 23 24 25
577 2.83 595 3.15 632 3.84 666 4.59 698 5.36 730 6.16 760 7.00 789 7.85
21 22 23 23 23 24 25 26
608 3.31 626 3.66 661 4.38 694 5.16 725 5.96 755 6.80 784 7.66
24 24 24 25 25 26 27
640 3.86 657 4.22 690 4.98 722 5.78 752 6.62 781 7.49
26 26 26 27 27 28
672 4.46 688 4.84 720 5.63 750 6.46 779 7.34
28 28 28 29 30
704 5.12 720 5.52 750 6.34 779 7.20
30 30 31 32
30
TCB-2-36
Level 2 Construction
1
/4
59
55
471/4
313/4
*
463/8
54
* Maximum w/Motor Cover
3
46
/4
Dimensions shown in inches Maximum rpm — 1051 Outlet Velocity = cfm X 0.061 Tip Speed = rpm X 9.56 Maximum bhp at a given rpm — (rpm/391) Max Motor Frame Size - 256T
CFM OV
7200 436
8400 509
9600 581
10800 654
12000 727
13200 800
14400 872
15600 945
16800 1018
18000 1090
19200 1163
20400 1236
21600 1309
22800 1381
24000 1454
0.25 0.5 1 1.5 2 2.5 3 3.5 4
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Sones Sones Sones Sones Sones Sones Sones Sones Sones
342 0.67 403 1.09 515 2.06
7.3 11.4 11.3
380 0.91 434 1.36 532 2.41 625 3.63
10.8 13 11.7 14.6
420 1.21 467 1.70 556 2.84 640 4.11 721 5.54
14.3 13.7 12.5 14.7 18.3
461 1.59 503 2.12 586 3.34 662 4.69 736 6.17 807 7.79
14.6 14.1 13.5 15.5 18.2 22
504 2.06 542 2.63 617 3.92 688 5.37 756 6.90 822 8.57 886 10.4 945 12.2
15.2 14.7 14.8 16.7 18.7 21 24 28
547 2.61 581 3.23 650 4.59 717 6.13 779 7.75 841 9.46 901 11.3 960 13.3 1015 15.3
16.0 15.6 16.3 18.2 20 22 24 27 31
591 3.26 622 3.93 684 5.35 747 6.97 807 8.70 864 10.5 920 12.4 975 14.4 1030 16.5
17.2 17.4 18.0 19.8 21 23 25 27 31
635 4.02 664 4.74 722 6.25 780 7.94 837 9.76 890 11.7 943 13.6 994 15.6 1045 17.8
19.1 19.4 20 22 23 25 26 28 30
679 4.88 707 5.67 761 7.28 814 9.02 868 10.9 920 12.9 968 15.0 1018 17.1
21 22 23 24 25 27 28 30
724 5.87 750 6.73 800 8.43 849 10.2 901 12.2 950 14.3 998 16.5 1042 18.7
24 24 25 26 27 29 31 32
769 6.98 793 7.93 840 9.72 887 11.6 935 13.6 982 15.8 1028 18.1
26 27 27 29 30 32 33
814 8.24 837 9.27 881 11.2 926 13.1 969 15.2 1015 17.5
29 29 30 32 33 34
859 9.65 881 10.8 923 12.8 965 14.8 1006 16.9 1049 19.3
32 32 33 35 36 38
905 11.2 925 12.4 966 14.5 1005 16.7 1045 18.9
35 36 37 38 40
950 12.9 970 14.2 1008 16.5 1046 18.7
39 39 41 42
3
Static Pressure in Inches wg
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories) in the airstream.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet fan sone levels.
31
Centrifugal Inline Guide
Models SQ and BSQ centrifugal backward inclined belt or direct drive fans are designed for clean air applications (intake, exhaust, return, or make-up air systems) where space is a prime consideration. Capacities range from 62 cfm (105 m3/hr) to 26,600 (45,000 m3/hr) cfm and up to 3.5 in. wg (869 Pa) of static pressure. Maximum operating temperature is 180ºF (82ºC).
Model TCB centrifugal backward inclined belt drive fans for higher pressures. Capacities range from 360 cfm (612 m3/hr) to 24,000 cfm (40,800 m3/hr) and up to 4.5 in. wg (1118 Pa) of static pressure. Maximum operating temperature is 200ºF (93ºC). Model TCB is available with UL 762 for restaurant exhaust.
Mixed flow models QEI (belt drive) or QEID (direct drive) are designed for a wide range of applications including clean air (intake, exhaust, return, or make-up air systems) and specialized UL Listed applications such as emergency smoke exhaust or restaurant grease exhaust. Capacities range from 1,000 cfm (1,700 m3/hr) to 96,000 cfm (163,000 m3/hr) and up to 9.5 in. wg (2370 Pa) of static pressure. Maximum continuous operating temperature for standard construction is 200ºF (93ºC).
Model TCF centrifugal backward inclined airfoil fans are designed for high volume clean air applications. Best suited for high volume clean air or UL Listed emergency smoke exhaust applications. The TCF is also available in an optional arrangement 3 design that results in reduced unit length. Maximum capacity of 150,000 cfm (255,000 m3/hr) or up to 9 in. wg (2200 Pa) of static pressure. Maximum continuous operating temperature for standard construction is 200ºF (93ºC).
Building Value in Air
Greenheck delivers value to mechanical engineers by helping them solve virtually any air quality challenges their clients face with a comprehensive selection of
top quality, innovative air­related equipment. We offer extra value to contractors by providing easy-to-install, competitively priced, reliable products that arrive on time.
And building owners and occupants value the energy efficiency, low maintenance and quiet dependable operation they experience long after the construction project ends.
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.