Greenheck Support Mullions User Manual

Document number 462105
®
FABRICATION AND FIELD
INSTALLATION INSTRUCTIONS
Support Mullions for use in Oversize Openings
These installation instructions apply to the fabrication and construction of generic support mullions. Support mullions are necessary whenever static fire dampers are installed into a vertical opening that is larger than the largest UL rated size for that damper. The mullions allow construction of a fire barrier that is larger than the maximum available size.
The opening must not exceed 120 in. (3048mm) high, but can be any width provided a vertical support mullion is used a maximum of every 120 inches (3048mm). To properly use support mullions they must be fabricated and installed according to the following instructions.
Application
Generic steel mullions can be used to separate vertically mounted galvanized steel fire dampers in wall openings larger than the UL permitted multiple damper assembly size. Mullions can either be used vertically, horizontally or both to split up a vertical wall opening requiring use of a damper having a 1 mullion span is 120 in. (3048mm) plus expansion allowance when used either horizontally or vertically.
Sleeves are to be around each damper assembly. Mullions are not intended to be in the airstream, (i.e. exposed to flow) or to be a part of the ductwork.
1
/2 hour fire resistance rating. Maximum
Wall Opening
Steel mullions are intended for use in a concrete block or solid concrete wall.
Hollow concrete blocks are to be filled with concrete (minimum 3500 psi) to permit proper mullion anchoring.
Wall thickness is to be 7 in. (178mm) minimum, 12 in. (305mm) maximum.
Retaining Angles (Typical)
Sleeve (Typical)
Wall Mullion Cap B-B (Typical)
Mullion Assembly A-A (Typical)
Horz. to Vert. Mullion Cap C-C (Typical)
G
G
G
E
G
F
E
F
SPECIAL NOTE: Support
mullions may only be used
D
with static-rated fire damper assemblies; they cannot be used to install combination fire-smoke dampers in wall openings that exceed the maximum UL-approved size for the fire-smoke damper model being installed.
Support mullion assemblies consist of three basic parts:
Formed Section View (2 req’d)
the wall mullion cap, the horizontal to vertical mullion cap and the mullion sections. Determine the quantity of each piece required to complete the installation.
Dimensional Information shown in inches (mm).
Table 1
Opening Width/Height D H
12 (305) 11½ (292) 3¼ (83)
24 (610) 23½ (597) 3 3/8 (86)
36 (914) 33 3/8 (847) 3½ (89)
48 (1219) 47¼ (1200) 3 5/8 (92)
60 (1524) 59 1/8 (1501) 3¾ (95)
72 (1829) 71 (1803) 3 7/8 (98)
84 (2134) 82 7/8 (2105) 4 (102)
96 (2438) 94¾ (2406) 4 1/8 (105)
108 (2743) 106¾ (2711) 4 ¼ (108)
120 (3048) 118¾ (3016) 4 3/8 (111)
E = Wall Thickness - 1/2 in. (13mm) F = Wall Thickness +
1
/4 in. (6mm)
Fabrication of Wall Mullion Caps
Wall mullion caps must be constructed from 12 ga. steel with a minimum yield strength of 42,000 psi.
1. Fabricate the formed section as shown to right.
2. Shear the cap end plate to required dimensions.
3. Weld the cap end plates to the formed section with 1/8 in. (3mm) fillet welds completely around the top edges of the formed section.
4. Drill and countersink 8 holes ( 4 on each side) for ¼-20 flat head machine screws.
Fabrication of Mullion Sections
Mullions must be constructed from 16 ga. (1.5mm) steel with a minimum yield strength of 42,000 psi.
Important: The “D” dimension shown has been calculated to include the necessary clearances required for thermal expansion in the mullions. The values can be found using the wall opening dimensions and tables on this page.
1. Form two identical pieces of mullion section as
shown.
2. Connect the two mullion sections together. Use 3/16
in (4.7mm) steel blind rivets of 3/4 in. (19mm) long intermittent welds 12 in. (305mm) on center and a 6 in. (152mm) maximum from both ends.
Important: Both sides of the mullion piece should be fastened using the method described above.
8
33/
7
8
/
3/16 in. typical rivet location
2 2C-4
C= Wall Thickness
2
31/
D
3/16 in. blind rivet (stl) or 3/4 in. long intermittent welds 12 in. on center, 6 in. maximum from both ends, both sides of assembly.
3
4
/
Assembled View
Detail A-A Mullion Assembly
All dimensions shown are in inches.
13
2 2
16
/
1
H
H
Formed Section
End View
Weld
E/8
E/4
Detail B-B
E/4
E
E/4
E/8
4
31/
Cap End Plate
(2 req’d)
Wall Mullion Cap Assembled View
1
/4
3
H
Wall Mullion Cap
All dimensions shown are in inches.
Fabrication of Horizontal to Vertical Mullion Caps
Horizontal to vertical mullion caps must be constructed from 12 ga. (2.7mm) steel with a minimum yield strength of 42,000 psi.
Important: The H, E and F dimensions shown have been calculated to provide the correct performance. The values can be found by using the wall opening dimensions and Table 1.
1. Form the horizontal mullion channel as shown.
3
2. Drill 12, mullion channel using the dimensions shown.
3. Form the center channel as shown.
/16 in. (4.7mm) dia. holes into the horizontal
Loading...
+ 1 hidden pages