Greenheck SSFSDR Installation Manual

Refer to:
steel deck
steel deck
Concrete floor
Concrete floor
retaining plate
retaining plate
RRL, RRL/OCI, TOR
RRL, RRL/OCI, TOR
For dimension information-see submittals
For dimension information-see submittals
‘Installation Instructions for FDR, SSFDR, DFDR, SSDFDR, SEDFDR Series Round Fire Dampers’ (Part #452721) or ‘Installation Instructions for FSDR, SEFSDR, SSFDSR Series Round Combination Fire Smoke Dampers’ (Part #453562)
Part # 469129
Installation Instruction Supplement for
FDR, SSFDR, DFDR, SEDFDR,
SSDFDR Series
Fire Dampers and
FSDR, SEFSDR, SSFSDR, Series
Combination Fire Smoke Dampers
Installed in Concrete Floor with Steel Deck
Application
Horizontal installation of FDR, SSFDR, DFDR, SEDFDR,
SSDFDR, FSDR, SEFSDR, SSFSDR models in concrete floors utilizing a steel deck. The hole opening made through the concrete floor may not allow the bottom plate to be placed against the steel deck on an even plane. This installation details how to properly install the required retaining plates next to the steel deck.
1. Damper assemblies must be installed in wall/floor
openings using a single retaining plate on either side of the wall/floor. The use of a second retaining plate is allowed, but is not necessary. A single retaining plate is provided with the dampers. A second retaining plate can be ordered as an option.
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 Standard 555S
(Listing #R13317)
(Listing #R13447)
Figure 1: Damper installed in concrete floor with steel
deck with actuator above the floor
Figure 2: Damper installed in concrete floor with steel
deck with actuator below the floor.
Copyright© 2006 Greenheck Fan Corporation Concrete Floor w/Steel Supp Round Damper
Rev. 1 May 2006
Loading...