Greenheck PVe-20 User Manual

Heat Recovery Ventilator
Model PVe
• Light Industrial • Commercial • Institutional
• 1,000 - 6,000 cfm
• 2.0 in. wg External Static Pressure
• Aluminum Plate Heat Exchanger
October
2009
Model PVe
Greenheck’s model PVe is a sensible idea for your fresh outdoor air needs. This aluminum plate air-to-air, heat recovery unit transfers sensible (heat) energy from the exhaust airstream to the supply airstream. This provides pretempered fresh outdoor air to your building, allowing you to reduce the size of your heating and cooling equipment, resulting in lower utility bills, year round.
Additionally, the plate heat exchanger has no moving parts, requiring less maintenance to provide healthy outdoor air to the building occupants. Light industrial applications, as well as bathroom and locker room exhaust, are great places to use Greenheck’s model PVe in addition to clean air applications. Typical plate heat exchanger ventilator applications are listed below.
Animal Shelters Bars and Clubs Churches Dormitories
Locker Rooms Nursing Homes Office Buildings Printing Shops
Restaurants Schools Function Halls Casinos
Veterinary Hospitals Bus Garages Maintenance Shops Auto Repair Facilities
Design Features:
Aluminum Heat Exchanger
1
• AHRI Standard 1060 Certified Performance
• High Heat Transfer
up to 70%
• Corrosion-Resistant
• Cross Airflow Pattern
• Low Static Pressure
1-inch double-wall construction
2
with 18 gauge outer and 24 gauge inner galvanized steel panels, alternative coatings available as an option. Double-wall construction protects insulation from moisture and prevents insulation fibers from entering the airstream. Insulation is 1.5 lbs/ft³density.
Downturned hood design lowers supply air intake
3
velocities to prevent rain and snow from being pulled into the unit. Each hood has washable aluminum mesh prefilters blocking debris orleaves.
Integral Filter Rack Design
4
• 2-inch (51mm) MERV 8 filters included as a standardoffering
Fork-able base and lifting locations cut into the
5
base for quick and easy jobsite off-loading and unitsetting.
3
8
1
4
6
5
Solid integral base with ½-inch upturned lips
6
around bottom openings, perimeter, and joints prevent water from leaking through the base into the building.
Integral stainless steel drain pan that is double-
7
pitched for true condensate drainage.
Reliable frost control protection with an optional
8
electric preheater.
7
5
2
Additional Features:
• Quiet running, forward-curved blowers
• Adjustable motor pulleys for final systembalancing
• Factory provided motor starters and disconnectionswitch in a sealed control center
• Neoprene isolation on blower assembly to minimize sound and vibration transmission
• Door seals utilize a superior bulb-design with four blades to provide a tight seal to prevent water penetration. The durable and flexible design offer years of service
• Liftoff door design with hinges for easier inspection and dual door handles to provide a secure and tight seal for gasketing
Standard Operation
How does the Plate Heat Exchanger work?
Improving building indoor air quality, requires fresh outdoor air be provided to the building. Therefore, by code, most buildings must have a certain amount of exhaust and outdoor air always moving in and out of the building. A plate heat exchanger ventilator combines both airstreams into one unit, and transfers energy between the airstreams, while keeping the air separated. All year long the plate heat exchanger is working to reduce energy consumption while meeting the air supply requirements of your building.
Winter Operation
On cold winter days, the unit significantly helps heat the outdoor air coming into the building. The warm exhaust air (return air) heats up the plate heat exchanger on the way out of the building. When the cold outdoor air hits the warm plate heat exchanger, it gets conditioned up to 70% of the way to the return air temperature. In this example, if your space is heated to 72°F(22°C) during the winter, on a 0°F (-18°C) day, the air coming off of the plate heat exchanger (supply air) would be 50°F(10°C). The heating equipment now only needs to heat from 50 to 72°F (10 to 22°C), rather than 0 to 72°F (-18 to 22°C) saving significant amounts of energy all winterlong.
Outdoor Air
0°F
-18°C
Return Air
72°F
22°C
Heat Recovery Technology
PVe Plate heat exchanger
Exhaust Air
22°F
-6°C
Supply Air
50°F
10°C
Summer Operation
On hot summer days, the unit takes cool conditioned air from the space and passes it through the plate heat exchanger on the way out of the building. When the hot summer outdoor air hits the cool plate heat exchanger, it gets conditioned down almost 70% of the way to the space temperature. In this example, if your space is air-conditioned to 75°F (24°C) during the summer, on a 105°F (41°C) day, the air coming off of the plate heat exchanger (supply air) would be 84°F (29°C). The cooling equipment now only needs to cool from 84°F (29°C) to 75°F (24°C) saving significant energy throughout the summer.
Outdoor Air
105°F
41°C
Return Air
75°F
24°C
Heat Recovery Technology
PVe Plate heat exchanger
Certifications
PVe’s construction is matched with extensive in-house testing and third-party verification of performanceandsafety.
Greenheck Fan Corporation certifies that the PVe models shown herein are licensed to bear the AMCA
Licensed to bear the AMCA seal for AirPerformance
seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified RatingsProgram.
Exhaust Air
96°F
36°C
Supply Air
84°F
29°C
Unit is ETL Listed — all internal electrical components are factory wired to a single-point power connection
AHRI Standard 1060 certified plate heat exchanger performance assures the PVe model will function as required in demandingenvironments
Every unit is tested at the factory before it is shipped to the jobsite.
®
Heat recovery plate exchangers are certified by the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with AHRI Standard 1060. Actual performance in packaged equipment may vary. Certified ratings are available in the Certified Product Directory at http://www.
ahridirectory.org/ahridirectory/pages/home.aspx
What is the Benefit of Greenheck Energy Recovery?
For the Building Owner
• Improved Indoor Air Quality
Introducing fresh, outdoor air to a building is a key component to sustaining excellent indoor air quality.
Outdoor air can be very expensive to heat and cool, but the PVe unit can provide an economical approach to delivering outdoor air into a building.
• Energy Savings = Quick Payback
The energy recovery unit provides energy savings throughout the year. In the summer, the energy recovery
unit removes heat out of the outdoor air and in the winter, heat is added back into the fresh airstream. When you combine the energy savings from summer and winter operation, they lead to a very fast payback period.
For the Maintenance Personnel
• Low Maintenance Equipment
Heat Transfer Plate Exchanger: The aluminum plate heat exchanger is a major
component in the PVe and will require some minimal maintenance. The plate heat exchanger is removable, making the cleaning quick and easy. To clean the plate heat exchanger, wash it with water mixed with a light detergent, rinse with water and let dry. This should be done as often as needed for the particular application, however, most applications will only need cleaning once every 5-10 years. Occasionally vacuuming off the face of the plate heat exchanger is suggested for optimum air performance, which should be done more frequently depending on the air quality in your location.
Fans: The blowers that are used in the PVe are centrifugal, forward-curved-
type fans. These fans come with easy to adjust pulleys, belt tension bolts and permanently sealed bearings.
Filters: The 2-inch, 30% efficient MERV 8 filters that are included with the unit are designed for easy access
andremoval.
• Quality Construction
Greenheck has focused on the manufacturing and unit designs
to create well-constructed equipment. Investments in automated manufacturing processes provide accurate and repeatable results, giving excellent part fit and unit strength. Incorporation of innovative designs add to the quality while keeping maintenance work simple to perform.
• Long-Lasting Equipment
Because of our high-quality construction, the equipment that goes
to the field is made to last. As reassurance to the customer, each PVe unit carries a one year warranty from the ship date.
What is the Benefit of Greenheck Energy Recovery?
For the Design Engineer
• Adhering to ASHRAE Guidelines
ASHRAE Standard 90.1 ASHRAE 90.1 provides design guidelines regarding when it is most beneficial to use energy recovery.
Depending upon your geographic location and the percentage of outdoor air required for the application, ASHRAE recommends when to use energy recovery. An important part of this guideline is that when energy recovery is recommended, the device should be AHRI 1060 Certified.
ASHRAE Standard 62 ASHRAE 62 allows certain amounts of leakage from airstream to airstream when using energy recovery equipment
depending on the quality of the air being exhausted from the building. Plate heat exchangers have a low leakage design, allowing up to Class 3 air to be exhausted through the AHRI Certified device.
• LEED Certification Credits
For Green Building designs, the PVe offers an excellent way to acquire credits in both Energy
and Atmosphere (EA) and indoor Environmental Quality (EQ) categories towards a LEED certification.
Prepared to Support
• CAPS Program
CAPS is Greenheck’s comprehensive product selection program. The CAPS program was
developed with ease of use and fast selections in mind. There is also useful information available for making selections and educating people who are new to energy recovery technology. CAPS also provides submittals which include unit overviews, electrical information, fan charts, arrangements, engineering drawings, payback information, and psychrometric processes.
Green Building Efforts
• Industry Certification
To ensure performance on the jobsite, Greenheck emphasizes the need for the three major industry
certifications for energy recovery units: AMCA Licensed for Air Performance, ETL Listed for safety, and AHRI Certification on the plate heat exchanger.
• CSI Specifications
After a unit has been selected in CAPS, an accurate unit specification is available for use in the job
specification. These specifications have been recently updated to the CSI format.
For the Contractor
• Easy Installation
- Fork-able Base
- Integrated Lifting Holes
- Single-Point Power
These are just a few of the built-in features to make the installation process quick and easy. Also, our
comprehensive Installation, Operation, and Maintenance Manual is available online, so the information you need is quick and easy to obtain.
• Product Approval
Form, fit and function, the PVe was designed to operate in nearly every commercial and institutional
application. With over 12 years in the energy recovery market, our energy recovery ventilation product line is well known and accepted throughout the industry.
Fork-able Base
• One Year Warranty
Our one year unit warranty lets you to rest easy knowing that we stand behind our product. With the aluminum
plate heat exchanger design, there are no moving parts on the heat transfer device, which means there’s nothing to wear or break over time.
Accessories
Low-Leakage Dampers — Internally mounted for both supply and exhaust
Where code requires low-leakage dampers they can be provided to keep the cold weather out in the winter, or hot and humid weather out during the summer. Since the dampers are wired to a single-point power source, a simple run command sent to the unit, powers the dampers open. When your unit is off during unoccupied hours, the dampers close to keep the outdoor air out.
Air Filtration — High-Efficiency Filters
The PVe comes standard with 2-inch (51mm) MERV 8, 30% efficient filters. Optional MERV 13, 85% efficient filters are available to help meet additional LEED requirements or to simply improve the quality of your indoor air.
Painted Exterior
For added aesthetics combined with a long-lasting finish, Greenheck offers many different paint options. In addition to prepainted Permatector™ many additional baked enamel paint colors are available to customize your unit.
Roof Curbs
For a cohesive fit between the PVe and your building, Greenheck offers a pre­engineered curb design. They are available with duct adaptors to simplify field duct installation and get the unit up and running morequickly.
Remote Panel
With the optional remote panel, you have control and the information you want. Monitoring lights, on/off time-clock control, or on/off/auto switch are a few of the available options. So whether you want to control the unit operation via a 7-day time clock or simply want to monitor unit performance, the remote panel is the option that provides valuable information.
Dirty Filter Sensors
Filters require scheduled maintenance to improve air quality and system efficiency. A dirty filter sensor allows you to minimize maintenance frequency to only when it is needed. The dirty filter kit senses when the filters are dirty and sends a signal to our built-in control center. Greenheck offers an optional remote control panel and a “clogged filter” light to tie the signal into.
PERMATECTOR™
Factory Mounted Sensors
Amp Draw, Pressure, Temperature: To get the information you need to know and where you need to measure it, Greenheck offers factory mounted sensors that are tied to the unit’s control center. These sensors can be used to simply monitor unit operation or to actively control the unit with controls provided byothers.
Amp Monitor Blower amp draw can be monitored
through the use of an amperage sensor. These sensors allow for either an analog or digital output based on
your system needs. Plate Heat Exchanger Pressure Sensors In each airstream, a pressure sensor
is available to monitor where the
plate heat exchanger is operating.
Plate heat exchanger pressure can
be used as a CFM gauge as the
aluminum plate heat exchanger is
a laminar flow device (i.e. a specific
pressure equals a specificCFM). Temperature Sensors Plate heat exchanger performance
can be determined with factory
mounted temperature sensors. Every
compartment can be monitored to
determine how your unit is operating.
CO2 Sensor
A good indicator for building health is low levels of carbon dioxide (CO2 ). Greenheck offers a CO2 sensor, that can be used to engage the unit based on CO2 levels, or it can increase or decrease airflow through the use of a variable frequency drive (VFD) on the blowers. The CO can be unit mounted or space mounted depending on your application.
Service Outlet
While performing minimal maintenance on your PVe, a service outlet can provide power when and where it’s needed. Shipped loose, the outlet can be mounted in the correct location for your building.
Vapor-Tight Lights
Access doors provide natural lighting during the day, but there may be times when more light is needed to see properly inside the unit. To increase bulb life and to protect the bulb, Greenheck offers a vapor-tight glass bulb cover.
Blower Variable Frequency Drives
VFD’s are a great tool to control airflow to the space or to maintain duct pressures. With this optional feature, two VFD’s are utilized, one per fan for independent and flexiblecontrol.
sensor
2
Accessories
Economizer Control (Free Cooling)
Take advantage of cool outdoor air to handle space loads. A call for cool air is sent to the unit’s control center which triggers the optional plate heat exchanger bypass economizer sequence.
Plate Heat Exchanger Bypass - Open/Closed
Integral face and bypass dampers allow cool air to bypass the plate heat exchanger when it’s in the free cooling range (temperature or enthalpy). When the conditions are too warm or cold, the dampers cycle back to allow heat recovery.
Frost Protection
Cold climates, in combination with higher indoor humidity levels, may cause frost to form on the heat recovery plate heat exchanger. To protect against frost, the leaving air temperature of the plate heat exchanger is measured in the exhaust airstream to ensure the plate heat exchanger is not frosting. If the temperature of the plate heat exchanger falls below 32ºF (0ºC) (field adjustable) signaling a frosting condition, the unit enters into frost control mode. One of three frost control methods described below are available depending on your application.
Timed Exhaust Frost Control
The supply blower cycles on and off based on a factory provided timer. With the supply blower off, the warm exhaust air melts the frost. Once the adjustable timer completes its cycle, the supply blower returns to normal operation. Minimum on and off times can be programmed to avoid short cycling.
Plate Heat Exchanger Bypass - Open/Closed
When the temperature of the exhaust air leaving the exchanger drops below the adjustable set-point, the face and bypass dampers allow air to bypass the plate heat exchanger, allowing warm exhaust air to melt the frost. Once the exhaust air temperature rises above the adjustable set-point, the unit returns to normal operation.
Preheat Frost Control
An electric preheater is built into the PVe outdoor air intake. When the temperature of the exhaust air leaving the plate heat exchanger drops below the adjustable set-point, the preheater engages. Once the exhaust air temperature increases, the preheater shuts off.
Dimensional Data
Filters
Filters
Face/Bypass Damper
Plate Ventilator
Outdoor Air Hood
B
AD
CLEARANCE
C
D
D
CLEARANCE
C
D
D
Quick Select Chart
Model PVe-20 PVe-35 PVe-45 PVe-55
CFM
Unit Range
3
m
/hr
Motor HP
External Static Pressures (in. wg)
**Weight
** The weights shown are a worst case scenario based on the sheet metal and component weights for the unit. These weights include sheet metal weights added together with the largest motors, blowers and accessories for the units.
Minimum 1000 2000 3100 4000
Maximum 2200 3400 4500 6000
Minimum 1699 3398 5267 6796
Maximum 3738 5777 7646 10194
Minimum 0.25 0.50 1.00 1.50
Maximum 2.00 3.00 5.00 5.00
Minimum 0
Maximum 2.00 (496 Pa)
lbs 1300 1600 2100 2700
kg 590 726 953 1225
Overall Unit Dimensions
Unit Size A B C D E
PVe-20 104.1 (2650) 59.7 (1520) 41.5 (1060) 20.3 (520) 20.7 (530)
PVe-35 104.1 (2650) 59.7 (1520) 49.2 (1250) 25.2 (640) 17.7 (450)
PVe-45 110.6 (2810) 59.7 (1520) 61.1 (1560) 25.2 (640) 19.0 (490)
PVe-55 116.5 (2960) 59.7 (1520) 76.1 (1940) 25.2 (640) 23.8 (610)
All dimensions are shown in inches (millimeters). Door handles, hinges and other protrusions are not included in the dimensions above. Dimensions are rounded up to the nearest .1 inch (2.54 millimeters).
Outdoor Air Hood
Outdoor Air Hood
Filters
Face/Bypass Damper
Filters
Bypass Damper
Face Damper
Filters Filters
AD
Plate Ventilator
Plate Ventilator
Exhaust Air Hood
Control Center
B
E
C
Dimensional Data
CLEARANCE
B
C
A
D
Intake and Discharge Options
Option Bottom Top Side End
OA Intake X
SA Discharge X X
RA Intake X
EA Discharge X
OA - Outdoor Air SA - Supply Air (to the space) RA - Return Air (from the space) EA - Exhaust Air
OA Intake
RA Intake
EA Discharge
B
A
SA Discharge
D
C
E
F
Duct Dimensions
Model A B C D E F
PVe-20 10.7 (280) 12.2 (310) 10.3 (270) 11.8 (300) 22.0 (570) 14.0 (360)
PVe-35 11.9 (310) 13.7 (350) 11.4 (290) 13.1 (340) 34.0 (870) 14.0 (360)
PVe-45 14.1 (360) 16.0 (410) 13.3 (340) 14.5 (370) 46.0 (1170) 14.0 (360)
PVe-55 16.4 (420) 19.2 (490) 15.9 (450) 18.6 (480) 60.0 (1530) 14.0 (360)
All dimensions are shown in inches (millimeters).
Clearances
Unit Size A B C D
PVe-20
36 (920) 36 (920) 36 (920)
PVe-35 48 (1220) 36 (920) 36 (920) 60 (1530)
PVe-45 60 (1530) 36 (920) 36 (920) 60 (1530)
PVe-55 72 (1830) 36 (920) 36 (920) 60 (1530)
All dimensions are shown in inches (millimeters). The weatherhoods include 2-inch aluminum mesh filters that are removed out of the end of the hood as shown in this drawing and require extra clearance for removal.
60 (1530)
C
CLEARANCE
A
D
D
B
CLEARANCE
Performance Data
The AMCA seal for Air Performance is vitally important for ensuring the proper amount of fresh, outdoor air is being delivered to the building. Performance as cataloged is assured. All PVe sizes are tested in our AMCA Accredited Laboratory and all models are licensed to bear the AMCA Air Performance seal.
CFM OV
1000 1205
1600 1928
2200 2651
Model PVe-20
CFM OV
2200 2157
2800 2745
3400 3333
Model PVe-35
FRPM 692 879 1037
BHP 0.12 0.19 0.25
FRPM 881 1034 1165 1284 1394 1494 1592 1690
BHP 0.35 0.45 0.55 0.65 0.75 0.85 0.95 1.06
FRPM 1115 1222 1343 1443 1538 1631 1718
BHP 0.81 0.92 1.07 1.21 1.34 1.48 1.61
FRPM 841 959 1068 1168 1262 1353 1436 1514
BHP 0.54 0.66 0.78 0.91 1.04 1.17 1.31 1.43
FRPM 1011 1105 1199 1288 1371 1451 1525 1599
BHP 1.02 1.17 1.32 1.47 1.63 1.79 1.95 2.12
FRPM 1188 1269 1346 1424 1498 1571 1639
BHP 1.75 1.92 2.10 2.28 2.47 2.66 2.84
0.250 0.500 0.750 1.000 1.250 1.500 1.750 2.000
0.250 0.500 0.750 1.000 1.250 1.500 1.750 2.000
Greenheck Fan Corporation certifies that the PVe models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings Program.
NOTE:
1. Performance tables show EXTERNAL static pressurecapabilities.
2. Bhp values are shown for one blower motor only.
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
CFM OV
3400 2361
3950 2743
4500 3125
Model PVe-45
CFM OV
4500 2239
5250 2612
6000 2985
Model PVe-55
Gross supply air performance ratings (airflow, pressure and power) are at port 2 with port 1, port 3 and port 4 at 0.0 in. wg. Gross exhaust performance ratings (airflow, pressure and power) are to port 3 with port 1, port 2 and port 4 at 0.0in.wg. Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
Model CFM
PVe-20
PVe-35
PVe-45
PVe-55
The air performance data accounts for the pressure drop across the heat recovery plate heat exchanger and the internal housing losses, but does not include pressure drop for filters or weatherhoods. Add filter and/or weatherhood pressure drop to the external static pressure to determine correct RPM and horsepower.
1000 0.04 0.05 0.02
2200 0.20 0.25 0.10
2200 0.10 0.10 0.07
3400 0.25 0.25 0.17
3400 0.15 0.18 0.08
4500 0.26 0.32 0.14
4500 0.19 0.18 0.07
6000 0.34 0.32 0.13
30% Efficient Filter
Pressure Drop (in. wg)
FRPM 796 888 977 1055 1130 1198 1268 1336
BHP 1.08 1.27 1.48 1.66 1.87 2.07 2.30 2.53
FRPM 898 976 1056 1132 1200 1265 1328 1387
BHP 1.63 1.84 2.07 2.30 2.52 2.75 3.00 3.23
FRPM 1002 1071 1138 1211 1277 1338 1396 1453
BHP 2.33 2.57 2.81 3.09 3.35 3.61 3.85 4.13
FRPM 613 691 764 833 898 961 1019 1074
BHP 1.27 1.51 1.76 2.01 2.26 2.53 2.81 3.07
FRPM 690 758 823 886 946 1004 1058 1112
BHP 1.91 2.19 2.47 2.77 3.06 3.36 3.64 3.97
FRPM 771 831 890 945 1000 1053 1105
BHP 2.76 3.08 3.40 3.71 4.06 4.38 4.73
0.250 0.500 0.750 1.000 1.250 1.500 1.750 2.000
0.250 0.500 0.750 1.000 1.250 1.500 1.750 2.000
Supply Weatherhood
Pressure Drop (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
EXTERNAL STATIC PRESSURE (in. wg)
Exhaust Weatherhood
Pressure Drop (in. wg)
10
Typical Applications
OUTDOOR
AIR
OUTDOOR
AIR
The PVe unit can add to the benefit of a building design anywhere that outdoor air is required and the exhaust air is Class 3 or lower per standard ASHRAE 62-2004. Class 3 air is defined as significant contaminant concentration, significant sensory-irritation intensity, or offensive odors. With the aluminum plate heat exchanger’s minimal cross-leakage design, Greenheck has targeted light industrial applications in addition to commercial and institutional comfort applications.
With Ducted Air Handlers
The PVe unit may be combined with ducted air handling units or fan coil boxes. A single heat recovery ventilator provides fresh outdoor air for multiple air handling units or in a one-to-one ratio where a single heat recovery ventilator and air handler serves only one space.
AIR HANDLING
UNIT (AHU)
Heating
Coil
Cooling
Coil
72°F 50% 72°F 50%
ZONE 1 ZONE 2
Heating
Cooling
SUPPLY AIR
AHU
Coil
Coil
RELIEF AIR
OUTDOOR AIR UNIT (OA unit)
WITH HEAT RECOVERY
OUTDOOR
AIR
RESTROOM
Exhaust
Plate
Heat
Exchanger
EXHAUST AIR
Fan
RETURN DUCT
SIDE VIEW
SUPPLY DUCT
With Packaged Rooftop Equipment
This diagram illustrates how heat recovery ventilators may be used in conjunction with packaged rooftop equipment. Fresh, outdoor air enters the heat recovery ventilator and is pretreated before entering the heating/ cooling equipment. This pretreating occurs because the heat recovery plate heat exchanger is transferring sensible energy between the outdoor air and the building exhaust air.
Exhaust
Fan
EXHAUST
AIR
SUPPLY DUCT
RESTROOM
Heat Plate
Exchanger
PLATE HEAT RECOVERY VENTILATOR (PVe)
SIDE VIEW
72°F
Heating
Coil
RETURN DUCT
ZONE 1
50%
AIR HANDLING UNIT (AHU)
Cooling
Coil
SUPPLY AIR
11
Greenheck’s Energy Recovery Models
Model MiniVent - Energy Recovery Ventilator
The MiniVent-450 & 750 are energy recovery ventilators used for commercial and institutional applications that require 300 to 800 cfm of ventilation air. The compact design provides an economical solution for individual spaces, such as school classrooms and small offices.
Model ERV/ERVe - Energy Recovery Ventilator
Low first-cost and maximum energy savings combine to yield an extremely attractive payback on Greenheck Energy Recovery Ventilators. By incorporating ERV’s into the HVAC system, air conditioning and heating equipment can be downsized. Energy recovery ventilators are perfectly suited to help control humidity. In the summer, when outdoor humidity is high, the energy wheel dehumidifies the outdoor air. This greatly reduces the latent load on the air conditioning equipment and also eliminates rising indoor humidity levels that can occur in hot, humid climates. In the winter, when outdoor air is dry, the energy wheel humidifies the air. This increases comfort and reduces the amount of humidification required. Capacities for model ERV range from 400 to 12,000 cfm with external static pressure capabilities to 1.5 in. wg. Capacities for model ERVe range from 1,000 to 6,000 cfm with external static pressure capabilities to 1.0 in. wg.
Model ERCH - Energy Recovery with Cooling and Heating
The model ERCH combines the benefits of the total energy wheel with supplemental cooling and heating. The result is a product that is specifically designed to process 100% outdoor air to desired supply conditions. Four housing sizes provide airflow capacities from 1,000 to 10,000 cfm with external static pressures to 1.5 in. wg. A variety of tempering options are available. The coil section of the ERCH accommodates a cooling coil, a heating coil, or both.
Model VER - Versatile Energy Recovery
The Model VER is a fully featured, versatile energy recovery unit with a wide range of heating and cooling options available. The unit includes an energy wheel to pretemper the outdoor air which reduces the heating and cooling equipment needed, while also lowering operational costs. In addition to the standard heating and cooling options, the VersiVent has options such as environmentally friendly R410a refrigerant, a wrap-around heat pipe for additional dehumidification and reheat capacity, and a quiet, efficient, plenum supply fan. Capacities range from 2,000 to 10,000 cfm with external static pressure capabilities to 3 in. wg.
Model APEX - Affordable, Practical, Energy Exchanger
The APEX combines high airflow capacities with cost-saving energy recovery ventilation by providing centralized outdoor air distribution and reducing the need for multiple unit installations. Fresh outdoor air is preconditioned by the total enthalpy wheel, which recovers a majority of the energy from the exhaust air. It saves 3-4 tons of cooling per 1,000 cfm and saves 50-60 MBH of heating per 1,000 cfm. Easy to install and operate with airflow capacities that range from 10,000 to 20,000 cfm and external static pressures to 2.5 in. wg.
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Prepared to Support
Green Building Efforts
Greenheck P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Copyright © 2009 Greenheck Fan Corp. • Catalog PVe Rev. 2 October 2009 IP
Loading...