Greenheck’s Series L, low silhouette, models LD, LB, LDP, and LBP centrifugal roof exhaust fans
provide the industry’s best performance and durability for general clean air applications.
• Broadest performance in the industry, up to 1.25 in. wg (311 Pa) and 37,500 cfm (63,713 m
• Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory,
and all models are licensed to bear the AMCA sound and air performance seals.
• UL Listed for electrical.*
• Greenheck subjects these products to extensive life testing, assuring you the fans will provide
years of reliable performance.
Greenheck Fan Corporation certifies the
models LD, LDP, LB, and LBP shown
herein are licensed to bear the AMCA
seal. The ratings shown are based on
tests and procedures performed in
accordance with AMCA Publication 211
and AMCA Publication 311 and comply
with the requirements of the AMCA
Certified Ratings Program.
*UL is optional and must be specified.
Models LD, LDP, LB, and LBP are
listed for electrical (UL/cUL 705)
File no. E40001.
3
/hr).
Leading Edge Technical Support
When you need extensive product or installation and operating manual (IOM)
information, our products are supported by the industry’s best product literature,
electronic media and computer aided product selection (CAPS) program. You’ll
also find this information on our website at www.greenheck.com
You can always count on personal service and expertise from our national and
international representative organization. To locate your nearest Greenheck
representative, call 715-359-6171 or visit our website at www.greenheck.com
Quick Build Programs
Our Quick Build (QB) Program ensures rapid response time when your needs
require a fast turnaround. Select from more than 40 configurations of the
Series L, low silhouette model fan and we will manufacture and ship them
within ten days. We have strategically located many warehouses across the
United States and internationally to fill your request at a moments notice.
World Class Manufacturing
Greenheck’s skilled production workers use cost-effective machines and
unique dies designed and built by our own engineers to add innovative
features and greater strength to our centrifugal roof exhaust fans. Our
advanced manufacturing processes and quality control procedures
always ensure the highest product quality. And just to be sure you
get the peace-of-mind you expect when you specify Greenheck, our
assembly inspectors test run and monitor every fan before it leaves the
factory. Results of these tests are kept in permanent records for future
reference.
2
Unique Construction Features
Louvered Penthouse Style
• Hinged Cover - All sizes feature an
aluminum cover which may be hinged to provide quick access to the motor and drive assembly. Covers are fastened down with a quick release hood latch.
• Large Interior Dimensions - All sizes allow
complete accessibility from above. Interior dimensions offer clearance for inspection, cleaning, or maintenance of the motor, wheel, belt(s), and drives.
• Strength & Weather Resistant - Each unit
features storm resistant aluminum louver blades with mitered corners. For decades, our storm resistant blades have proven highly effective. Each sturdy extruded aluminum louver blade has a material thickness of 0.080 inches.
Greenheck’s louvered penthouse hoods feature heavy gauge extruded aluminum louvers with mitered corners for a clean, finished appearance and weather resistant construction.
The interior vertical edge of the curb cap forms the throat and weathershield. Each corner is also shielded to prevent leakage.
Penthouses are available in aluminum for lasting durability and appearance.
Fabra Hood Style
• Hinged Hood - All sizes feature a hood
which may be hinged to provide quick access to the motor and drive assembly. Access may be gained by simply removing two of the four hood fasteners or all fasteners for complete removal.
• Large Interior Dimensions - All sizes allow
complete accessibility. Interior dimensions offer clearance for inspection, cleaning, or maintenance of the motor, wheel, belt(s), and drives.
• Strength & Weather Resistance - The
hood is designed with arched panels manufactured of heavy gauge, precision roll formed steel with interlocking edges. Each interlocking rib creates a tight, weather resistant seal. Heavy gauge steel support members provide structural strength. The first hood was put into service over 30years ago.
Greenheck’s interlocking rib design combines four material thicknesses with I-beam design principles producing a hood far superior in strength to conventional designs (an important feature in high wind and snow load regions).
Formed channels adjacent to the ribs provide water drainage to ensure weather tightness.
Hoods are available in galvanized steel, coated steel, or aluminum construction.
3
1
6
10
5
12
2
9
15
13
13
11
14
LB/LD
8
4
6
10
11
7
Fabra Hood Style
5
9
3
LBP/LDP
Louvered Penthouse Style
4
Unique Construction Features
Recommended
Duct and
Damper Size
Recommended
Roof Opening
1 1/4 in.
(32 mm)
3/4 in.
(19 mm)
Damper
8 to 12 in.
(203 to 305 mm)
1 1/4 in.
(32 mm)
1
FABRA HOOD STYLE - Models LD and LB have
a rib-lock galvanized housing. Hood panels are
interlocked and attached to sturdy galvanized
rails. (Aluminum housings are optional).
HINGED ACCESS - The entire hood assembly
2
on models LD and LB can be hinged open for
access to the internal fan components.
LOUVERED PENTHOUSE - Models LDP and
3
LBP penthouse style housings are constructed
of heavy extruded aluminum louvers with
mitered and welded corners.
HOOD COVER - Models LDP and LBP
4
aluminum hood covers are hinged and
removable for access.
DRIVE FRAME - Constructed from heavy
5
gauge galvanized steel. Belt adjustment is
accomplished by loosening fasteners, sliding
the motor plate, and retightening fasteners.
FAN SHAFT - Precisely sized, ground, and
6
polished so the first critical speed is at least
25% over the maximum operating speed. Close
tolerances between the shaft and bearing result
in longer bearing life.
BEARINGS - 100% factory tested and designed
7
specifically for air handling applications with
a minimum L10 life in excess of 100,000 hours
(L50 average life of 500,000 hours).
CURB CAP - Curb cap has prepunched
8
mounting holes to ensure correct attachment to
the curb.
9
MOTOR - All motors are carefully matched to
the fan load to provide years of trouble free
operation.
DRIVE ASSEMBLY - Drives are oversized 150%
10
of driven horsepower. Machined cast iron
pulleys are factory set to the required RPM and
are adjustable for final system balancing. Belts
are static free and oil resistant.
11
WHEEL - An aluminum, backward inclined,
non-overloading, centrifugal wheel is utilized
to deliver maximum efficiency. Each wheel is
statically and dynamically balanced.
VIBRATION ISOLATORS - Support the drive
12
assembly and wheel without steel to steel
contact providing long life and quiet operation.
BIRDSCREEN - Galvanized rigid wire protects
13
the fan’s discharge from birds or small objects.
(Aluminum birdscreen is optional).
WINDBAND - Lower windband assembly
14
ensures weathertight and rigid unit
construction.
DISCONNECT SWITCH - NEMA-1 switch is
15
factory mounted. Wiring from the motor to the
disconnect enclosure is provided as standard.
All wiring and electrical components comply
with the National Electric Codes (NEC) and are
UL Listed or Recognized.
CONDUIT CHASE - A large diameter conduit for
16
installing electrical wiring through the curb cap
into the motor compartment. (Not shown)
Standard Installation
Models LB, LD, LBP, and LDP exhaust fans are designed
to meet the needs of general clean air applications. Tests
have been conducted to ensure safe and reliable fans
capable of withstanding normal exhaust conditions.
When roofing materials extend to the top of the curb,
roof curbs should be 11⁄2 in. (38 mm) (3/4 in. (19 mm) on
a side) less than the unit curb cap to allow for roofing
and flashing.
For recommended duct size, damper size, and
roof opening dimensions, refer to CAPS or the
performance data pages.
Installation must include a means for inspecting,
cleaning, and servicing the exhaust fan.
Due to the varying airstreams encountered in
commercial ventilation, system designers must
be aware of national, state, and local codes and
guidelines governing these installations. Local code
authorities should be consulted before proceeding
with any ventilation project.
5
Options and Accessories
BIRDSCREEN - Galvanized mesh is standard.
Optional aluminum or stainless steel rigid wire are
also available.
HOOD INSULATION - Hood insulation is dual-
density to minimize condensation, reduce thermal
transfer, and enhance sound absorption at high and
low frequencies.
LIFTING LUGS - Four heavy gauge steel brackets
are available to provide lifting points when raising
the fan to the roof.
TIE DOWN POINTS - Four heavy gauge steel
brackets are available to secure the fan in heavy
wind applications. Cables and anchors by others.
COATINGS - All Greenheck coatings and resistance
charts can be found in the performance coatings
catalog. A wide variety of coatings and colors are
available in two categories:
Decorative coatings – Sixteen standard colors
are available.
Protective coatings – Five electrostatic applied
powder coatings are available to protect against
most environments.
DAMPERS - Designed to
prevent outside air from
entering back into the building
when fan is off. Options include
gravity and motorized dampers.
Damper sizes are shown on
each performance data page.
CURB SEAL - Rubber seal between fan and curb
to ensure proper sealing when attached to a curb.
DISCONNECT SWITCHES -
A wide selection of NEMA
rated switches are available
for positive electrical shutoff
and safety, including: dusttight, rainproof, and corrosionresistant. Switches may be
internally or externally mounted.
SPEED CONTROLLERS - Available for use with
shaded pole and permanent split capacitor (PSC)
open motors on models LD and LDP fans. They
provide an economical means of system balancing
with direct drive fans.
CURB EXTENSIONS - Extensions raise the fan
discharge above the roof line and provide an
accessible mounting location for dampers.
Insect screen bases
constructed with
a removable
fine mesh are
recommended for
applications where insect
entry must be prevented. Curb
extensions are not available with LDP and
LBP severe duty construction models.
ROOF CURBS - Prefabricated roof curbs reduce
installation time and costs by ensuring compatibility
between the fan, curb and roof opening. All curbs
are insulated with fiberglass.
A wide variety of roof curbs
are available including
flanged, pitched and
sound-absorbing.
6
Severe Duty Option
OUTSIDE CURB DIMENSION
ROOF OPENING
12, 18 OR 24 INCHES
(305, 457, 610 MM)
THROAT DIMENSION
(ROOF OPENING)
1 INCH (25 MM) INSULATION
6 INCH x 3 INCH
(152 MM x 76 MM)
STEEL MOUNTING ANGLE
(12 GAUGE MINIMUM)
RECOMMENDED
DUCT & DAMPER SIZE
1-1/4 INCH
(32 MM)
4 IN.
(102 MM)
1-3/4 INCH (44 MM)
3/4 INCH (19 MM)
4 IN.
(102 MM)
4 IN.
(102 MM)
4 IN
(102 MM)
1-3/4 INCH
(44 MM)
2-1/2 INCH (64 MM)
2-1/2 INCH
(64 MM)
1-3/4 INCH (44 MM)
CONCRETE
ROOF TRUSS
CORRUGATED
ROOF DECK
SEVERE DUTY - Specifically designed for applications with extremely
high structural design load requirements. The severe duty models LDP
and LBP are far superior to any centrifugal roof exhaust fan currently
in the market. Designed with structural steel supports and ESD-603D
louver blades, the severe duty louver enclosure (SDLE) may be used
in any application which requires a fan to endure high winds with the
potential of wind blown debris. The louvered housing has been tested
in accordance with the following Miami-Dade test protocols:
• Large Missile Impact Test - TAS-201-94
• Uniform Static Air Pressure - TAS-202-94
• Uniform Cyclic Wind Loading - TAS-203-94
To meet the above protocols, the severe duty fan must be mounted
on a severe duty roof curb, which is attached directly to the building
structure. Maximum design load is 140 psf.
Available on sizes
• LDP - 60 though 120
• LBP - 10 through 30
Weights and dimensions will vary from standard LDP and LBP construction.
NOTICE OF ACCEPTANCE
NUMBER 08-0429.05
Severe Duty Installation
Models LDP and LBP severe duty exhaust fans are designed to meet the needs of general clean
air applications. Tests have been conducted to ensure safe, rugged and reliable fans capable of
withstanding severe exhaust conditions.
The severe duty roof curb model SD is
supplied with this product and is designed
with 12 gauge welded steel construction.
Greenheck recommends the severe duty curb
to be anchored to the structure of the building.
Dependent upon roofing material it shall be
bolted and welded. For recommended duct
size, refer to CAPS or installation manual.
Installation must include a means for
inspecting, cleaning, and servicing the
exhaust fan.
Due to the varying airstreams encountered
in commercial ventilation, system designers
must be aware of national, state, and local
codes and guidelines governing these
installations. Local code authorities should
be consulted before proceeding with any
ventilation project.
7
Severe Duty Dimensions
LDP - SEVERE DUTY DIMENSIONS
B
C
D
E
A
A
LBP - SEVERE DUTY DIMENSIONS
CB
D
E
AA
Model
Number
ABCDE
Damper
Size
(square)
60
65
17
70
(432)
347⁄8
(886)
347⁄8
(886)
175⁄8
(448)
13⁄4
(44)
8
(203)
75
LDP
80
85
90
19
(483)
367⁄8
(934)
367⁄8
(934)
175⁄8
(448)
13⁄4
(44)
10
(254)
95
LBP
100
120
10
14
18
21
24
30
(559)
(559)
(660)
(762)
(864)
(1016)
22
22
26
30
34
40
397⁄8
(1013)
397⁄8
(1013)
437⁄8
(1114)
477⁄8
(1216)
517⁄8
(1318)
577⁄8
(1470)
397⁄8
(1013)
503⁄8
(1280)
517⁄8
(1318)
577⁄8
(1470)
617⁄8
(1572)
697⁄8
(1775)
195⁄8
(498)
181⁄8
(460)
181⁄8
(460)
245⁄8
(625)
245⁄8
(625)
271⁄4
(692)
13⁄4
(44)
13⁄4
(44)
13⁄4
(44)
13⁄4
(44)
13⁄4
(44)
13⁄4
(44)
12
(305)
12
(305)
16
(406)
18
(457)
24
(610)
30
(762)
All dimensions are in inches (millimeters). Weight in pounds (kilograms). *Weight shown is the largest cataloged Open Drip Proof motor.
Roof
Opening
(square)
101⁄2
(267)
121⁄2
(318)
141⁄2
(368)
101⁄2
(267)
101⁄2
(267)
101⁄2
(267)
1
⁄2
10
(267)
101⁄2
(267)
101⁄2
(267)
Weight*
375
(170)
400
(181)
425
(193)
550
(249)
550
(249)
550
(249)
700
(318)
800
(363)
950
(431)
Cover
Thickness
0.100
(0.045)
aluminum
0.100
(0.045)
aluminum
Louver
Thickness
0.125
(0.056)
aluminum
0.125
(0.056)
aluminum
Curb Cap
Thickness
0.25
(0.113)
steel
0.25
(0.113)
steel
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.