4
SYSTEM STARTUP
For proper unit function and safety, follow everything in this startup procedure in the order presented. This to be
done after the electrical (see base unit IOM GFC #456856) and gas connections are complete.
• Voltage meter
• Incline manometer or equivalent
Special Tools Required • Tachometer
• Thermometer
• Amperage meter
See IOM GFC #456856 (TSU) or GFC #457831 (VSU) before completing these steps.
1. Check Gas Pressure
Check the gas pressure with the unit’s nameplate pressure requirements.
2. Burner Air Pressure Differential
Proper air velocity over the burner is critical on a direct fired gas unit. If the air velocity is not within
specifications, the unit will not operate efficiently, can produce excess carbon
monoxide (CO) or other gases, and may have sporadic shutdowns. Proper air
velocity is determined by measuring the static pressure drop across the burner.
To measure the static pressure drop, the fan should be running and be
discharging 70° air. Using an incline manometer or equivalent, insert one sensor
into the entering air access opening (plugged test port) and the other on the
downstream side, through the view port (see page 12 for locations). The proper
static pressure reading should be from .625 in. to .675 in.
If this reading is higher or lower and the air quantity (cfm) delivered to the building
is acceptable, then the burner baffles will need to be adjusted (see diagram).
Open the burner access door. Using a wrench loosen the 4 screws to adjust the
baffles. To increase the static pressure loss, decrease the opening size and to
decrease the loss, increase the opening size. The top and bottom baffles should
be of equal distance from the burner. Tighten the baffle fasteners, replace the
door, turn unit on, and recheck the loss. This process may need to be repeated
until the proper pressure reading is attained. This adjustment will change the air
quantity delivered by the unit and therefore should be rechecked (see start up in Base Unit IOM).
3. Pilot Pressure
The pilot pressure is preset at the factory and should not require adjustment. Pilot pressure will vary by unit
size.
4. Set Maximum Discharge Temperature
Do not set the burner based on gas pressure. The burner's maximum fire rate needs to be set or the unit will
over fire at startup causing unit shutdowns. To do this, the inlet air and outlet air temperatures of the unit need
to be measured with the burner on high fire.
a. Determine Required Temperature Rise
Based on the geographical area, determine the winter design temperature. Subtract the winter design
temperature from the desired output temperature to get the required temperature rise.
Desired output temperature - winter design temperature = temperature rise.
( Example: for Schofield, WI 70° - (-15°) = 85°F)
b. Set unit to Run at high fire.
1. On Maxitrol Series 14 systems remove and isolate the wire attached to terminal #4 of the A1014 amplifier.
2. On Maxitrol Series 44 systems remove and isolate the wire attached to terminal #3 of the A1044 amplifier.