Greenheck KFCC Installation, Operation And Maintenance Manual

Page 1
Kitchen Fan Control Center
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
Table of Contents
General Description .............................2
Receiving and Handling ..........................2
Installation
Control Box ...................................3
Switch Mounting ...............................3
Temperature Sensor(s) - Hood Mounting .......... 3-4
Duct Collar Mounting ........4
Thermostat - Hood Mounting .....................4
General Safety Information
Only qualified personal should install this product. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock and other potential hazards.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC) and latest edition of the National Fire Protection Agency Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations (NFPA 96). Follow the Canadian Electrical Code (CEC) and ULC-S650 if installing this product in Canada.
2. Do not allow the electrical components of this product to come in contact with oil, grease, hot surfaces, water, or chemicals.
3. Verify the site can supply the necessary power for each fan and for the control panel.
WARNING
Electrical shock hazard. Can cause equipment damage, personal injury or death. Service must only be performed by personal that are knowledgeable in the operation of the equipment being controlled.
CAUTION
Always disconnect power before working on or near the product. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
It is the responsibility of the installer to make sure both electrical and gas appliances shut down in the event of a fire or in the event of a power loss to the building when this sequence is required by the authority having jurisdiction.
Duct Collar Mounting .................5
Electrical Connections
Power for KFCC ...............................6
Power for Hood Lights ..........................6
Power for Starters and Fans ......................7
Fire System Integration ..........................7
Spare Fire Contacts .............................8
Switches - Fan, 1-Speed ........................8
Fan, 2-Speed ........................8
Lights ..............................8
Tempered Supply, Heat Only ............9
Tempered Supply, Cool Only ............9
Tempered Supply, Heat and Cool ........9
Combination Fan/Light Switch ...................9
Make-Up Air Interface .........................9
Power for Shunt Trip ...........................9
Audible Alarm ................................9
Lights Out in Fire ............................10
Additional Fire Contacts .......................10
Additional Exhaust Contacts ...................10
Additional Supply Contacts ....................11
Exhaust Fan Failure Indicator ...................11
Supply Fan Failure Indicator ...................11
Status Lights ................................11
Temperature Interlock, Digital ...................12
Temperature Interlock, Thermostat ..............12
Digital Temperature Interlock Configuration ...... 13-14
Thermostat Style Temperature
Interlock Configuration .........................15
KFCC Field Connection Checklist .................16
General Wiring Diagram .........................17
Testing .......................................18
Operation ....................................19
Troubleshooting ...............................19
Maintenance ..................................20
Frequently Asked Questions .....................20
Replacement Parts .............................21
Codes and Standards ..........................21
Maintenance Log ........................... 22-23
Our Commitment ..............................24
®
Kitchen Fan Control Center
1
Page 2
General Description
Receiving and Handling
Description
The kitchen fan control center, or KFCC, is a pre-engineered package designed to control the operation of fans in a constant volume kitchen. The package consists of a cabinet encasing one or more fan motor starters interlocked together for on/off operation. Different fan, light and thermal switch combinations may be provided to operate the kitchen hood fan(s), light(s), and heating/cooling capabilities of the supply air. The control center as a standard is equipped with additional relays prewired to the fan starter(s). These additional relays are capable of turning on the kitchen exhaust and shutting down supply regardless of the present state of the fans via integration of a fire system microswitch with factory terminals. The control center can be equipped with temperature interlock, designed to automatically start kitchen fans and keep them running while heat is being generated from the cooking appliances. Hood systems should always be manually started before the cooking equipment is turned on, but if forgotten the interlock will safely trigger the fans to start once heat is detected. Other options are available.
Purpose
The purpose of the KFCC is to provide a complete control center equipped with fan motor starters. The control center provides a common connection point to interlock kitchen exhaust, supply, and hood lights with the hood’s fire suppression system. The cabinet is pre-engineered with terminal blocks for most field wiring connections. The control center can also be equipped with interlock between the exhaust fans and cooking equipment, as to meet International Mechanical Code (IMC) 2015 Section 507.1.1. In this case, the system will utilize a temperature sensor in the exhaust duct collar or capture area in the hood to detect heat generated from cooking operations and automatically activate the exhaust fans if not already running.
Product Application
The KFCC is designed for both Type I and Type II (grease and non-grease) constant volume hood systems, where starters are needed to activate fans. The control center can operate both single and three phase fans. Greenheck recommends using one KFCC per hood system (activates all fans simultaneously). When temperature interlock is provided in this package, it is not to be used in conjunction with exhaust fire dampers.
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all of the copies of the bill of lading which is countersigned by the delivering carrier. If damaged upon arrival, file a claim with the carrier. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts.
Storage
If this product must be stored prior to installation, it must be protected from dirt and moisture. Indoor storage is highly recommended.
NOTE
Improper storage which results in damage to the unit will void the warranty.
Handling
Make sure the equipment does not suffer any heavy vibration or knocks.
Kitchen Fan Control Center
2
®
Page 3
Installation
2 inch typical
(50.8 mm)
3 inch air space
(76.2 mm)
Sensor Install
(cutout area)
Exhaust Area
Supply Area
(optional)
P.O.BOX 410 SCHOFIELD
TITLE
Control Box Mounting
NOTE
Control box may be factory mounted. If so, continue to the next section.
Locate an area with enough space to mount the control box and fasten to the wall. Use appropriate type fasteners depending on the mounting location. Avoid installing the control box in environments with high magnetic and/or radio frequency interference.
Switch Mounting
NOTE
If the switches were NOT shipped loose, provided in a separate junction box, continue to the next section.
Locate an area with enough space to mount the switches junction box and fasten to the wall.
Temperature Sensor(s) - Hood Mounting
NOTE
Temperature sensor(s) will be provided only if the
digital temperature interlock option was configured/
ordered with the unit. If it wasn’t, continue to the next
section.
Temperature sensor(s) may be factory installed. If so,
continue to the next section.
1. Locate flat area(s) at the top interior of the hood in
front of the filters, towards the front of the hood.
19.525 inches
(495.9 mm)
Top View of Exhaust Hood
2. Find a spot for the sensor in the flat space that will
not interfere with the fire suppression nozzles and that is not within 12inches (304.8 mm) of any light fixtures. Cut a 3/4 to 7/8-inch (19.0 to 22.2mm) diameter hole in the flat spot of the capture tank.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
Hood Surface
®
Kitchen Fan Control Center
3
Page 4
Temperature Sensor(s) - Hood Mounting, continued
3. Place the J-box plate inside of the octagon extension ring and place over the hole.
4. Disassemble the compression seal and place through hole and J-box plate as shown. Tighten the nut inside the octagon extension ring.
Compression Seal PN 463570
Gasket
Octagon Extension PN 830125
J-Box Plate PN 732396
Lock Washer
Temperature Sensor(s) - Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. Find a spot to mount the sensor where it will not interfere with fire suppression nozzles or other items installed in the ducts. If an exhaust fire damper is present in the hood exhaust collar, it must be removed prior to temperature sensor installation. A 3/4 to 7/8-inch (19.0 to 22.2 mm) diameter hole must be cut into the duct 2 inches (50.8 mm) above the hood top.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
2 inches
(50.8 mm)
Nut
Exploded View (Components)
5. Place the temperature sensor through the compression seal and tighten the compression fitting to 35 ft.-lbs. (47.5 Nm).
Temperature Sensor PN 384925
Additional Octagon Extension (Optional) PN 830125
Octagon Cover PN 380926
6. Wire the sensor. Refer to Electrical Connections section for instructions on wiring the temperature sensor.
7. Place octagon cover onto J-box and fasten it.
Hood Exhaust Collar Front Side
2. Place the J-box plate inside of the octagon extension ring and place over the hole in the exhaust collar.
3. Disassemble the compression seal and place through hole in duct collar and J-box plate as shown. Tighten the nut inside the octagon extension ring.
1/4-inch Compression Seal PN 463570
Octagon Extension
Quik Seal Gasket
PN 830125
J-Box Plate PN 732396
Lock Washer
Nut
Exploded View (Components)
4. Place the temperature sensor through the compression seal and tighten the compression fitting to 35 ft.-lbs. (47.5 Nm).
Kitchen Fan Control Center
4
Octagon Cover PN 380926
Additional Octagon Extension (Optional) PN 830125
Sensor PN 384925
5. Wire the sensor. Refer to Electrical Connections section for instructions on wiring the temperature sensor.
6. Place octagon cover onto J-box and fasten it.
®
Page 5
Thermostat(s) - Hood Mounting
19.525 inches
(495.9 mm)
3 inch air space
(76.2 mm)
2 inch typical
(50.8 mm)
Exhaust Area
Supply Area
(optional)
Sensor Install
(cut out area)
NOTE
The thermostat(s) will be provided only if the thermostat style temperature interlock option was configured/ordered with the unit. If it wasn’t, continue to the next section.
The thermostat(s) may be factory installed. If so, continue to the next section.
1. Locate the flat area(s) at the top interior of the hood in front of the filters, towards the front of the hood.
Hood Plan View
2. Find a suitable location for the sensor in the flat space that will not interfere with the fire suppression nozzles and that is not within 12inches light fixtures. Cut a 11⁄8 to 1¼ inch (28.6 to 31.8mm) diameter hole in the flat spot of the capture tank.
(28.6 to 31.8 mm)
(304.8 mm) of any
Thermostat(s) – Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. Find a spot to mount the thermostat where it will not interfere with fire suppression nozzles or other items installed in the ducts. If an exhaust fire damper is present in the hood exhaust collar, it must be removed prior to temperature sensor installation. A
1
1
8 to 1¼ inch (28.6 to 31.8 mm) diameter hole must be cut into the duct 2 inches (50.8 mm) above the hood top.
(28.6 to 31.8 mm)
Hood Exhaust Collar (front side)
2. Place the J-box plate inside the octagon extension ring and place over the hole in the exhaust collar.
3. Disassemble the Quik-Seal fitting and place through hole in duct collar and J-box plate as shown. Tighten the nut inside the octagon extension ring.
Gasket
1/2 inch Quik-Seal
PN 451168
2 inches
(50.8 mm)
Hood Surface
3. Place the J-box plate inside the octagon extension ring and place over the hole.
4. Disassemble the compression seal and place through hole and J-box plate as shown. Tighten the nut inside the octagon extension ring.
Compression Seal
PN 452614
Gasket
Exploded View (Components)
Octagon Extension
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
5. Place the thermostat through compression seal and tighten the compression fitting to 35 ft.-lbs. (47.5Nm).
6. Wire the thermostat. Refer to Electrical Connections section for instructions on wiring the thermostat.
7. Place octagon cover onto J-box and fasten it.
Octagon Extension
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
Exploded View (Components)
4. Thread the thermostat into the Quik-Seal fitting until secure.
5. Wire the thermostat. Refer to Electrical Connections section for instructions on wiring the thermostat.
6. Place octagon cover onto J-box and fasten it.
®
Kitchen Fan Control Center
5
Page 6
Electrical Connections
NOTE
All wiring of electrical equipment must be done to meet NEC and local codes.
NOTE
All field wire must be high temperature rated. All 115VAC field wiring (or higher) must be routed through hard or flex conduit. All low voltage field wiring should be plenum rated if not routed through conduit. Field wiring should not come in contact with the surface of the hood. To reduce the likelihood of electromagnetic disturbance, avoid routing high and low voltage cables in the same cable conduit.
The extent of field wiring required will depend on the options and general configuration of the KFCC. Each option is broken out in the next portion of this manual. Each option will either be factory wired or will require field wiring. Use 14 AWG, 60°C copper wire unless otherwise specified.
Power for KFCC
The KFCC needs a power source to operate all inner components. This power source cannot be on a shunt trip breaker; the power must remain constant to the panel, even in the event of a kitchen fire.
Power for KFCC
• 115 VAC, 15 amp circuit to terminals H1 and N1
L1
H1
CONTROL INPUT:
115 VAC, 15 AMPS FROM BREAKER
N1
G
N
Power for Hood Lights (Optional)
If the KFCC is configured for hood light control, a separate power source for each light circuit will need to be run to the panel as well to power the lights. The KFCC can provide up to three light circuits.
Power for Hood Lights
• 115 VAC, 15 amp circuit to terminals H2 and N2 (first light circuit)
• 115 VAC, 15 amp circuit to terminals H3 and N3 (second light circuit)
• 115 VAC, 15 amp circuit to terminals H4 and N4 (third light circuit)
Hood Lights
• To terminals B2 and W2 (first light circuit)
• To terminals B3 and W3 (second light circuit)
• To terminals B4 and W4 (third light circuit)
L1
BK
H2
Each light circuit must not exceed 1400W maximum. If panel is configured for lights out in fire, each light circuit must not exceed 900W maximum.
Hood lights may be directly wired to light switch, creating unoccupied terminals B2, B3 and B4. Please refer to the wiring diagram specifically created for the panel on the inside door of the control center.
LIGHT INPUT: 115 VAC,
15 AMPS FROM BREAKER
S-1
B2
LT
1400W max.
LT
NOTE
W2
WH
N2
N
Kitchen Fan Control Center
6
®
Page 7
Power for Starters and Fans
The KFCC is equipped with contactors that may have thermal overloads attached to them. Each fan should have a designated power source. The breaker size (amps), wire gauge, phase, and voltage for each fan is specified on the KFCC wiring diagram.
115 VAC Single Phase Fan(s) Power Wiring
• LINE - from breaker to terminals L1 and L2
• LOAD, 115 VAC - from terminal block L2 and T3 on the bottom of contactor/overload to fan disconnect
OL1 ST1
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1
T2
T3
OL2 ST2
T1
T2
T3
OL3 ST3
T1
T2
T3
Exh
FAN 1
Exh
FAN 2
Exh
FAN 3
INPUT POWER
2 wire
115/1 phase
from breaker
L1
N
L2
L1
L2
L3
Single phase, 115 VAC
Wiring Connection Example
200/208/230/277 VAC Single Phase Fan(s) Power Wiring
• LINE - from breaker to terminals L1 and L2
• LOAD, 200/208/230/277 VAC - from T1 and T3 on the bottom of contactor/overload to fan disconnect
INPUT POWER
2 wire 208/1 phase from breaker
L1
L2
Single phase, 200/208/230/277 VAC
Wiring Connection Example
L1
L2
L3
Three Phase Fan(s) Power Wiring
• LINE - from breaker to terminals L1, L2 and L3
• LOAD - from T1, T2 and T3 on the bottom of contactor/overload to fan disconnect
INPUT POWER
3 wire
208/3 phase
from breaker
L1
L2
L3
L1
L2
L3
Fire System Integration
A dedicated fire system microswitch needs to be wired into the KFCC for all Type I hood systems. During a fire, this will disengage supply starters, and therefore turn off corresponding supply fans. If KFCC is configured with “Exhaust in Fire” option, the KFCC will also engage the exhaust starters, therefore turning on exhaust fans in the event of a fire.
Dedicated Fire System Microswitch
• Common to terminal C1
• Normally-closed to terminal NC1
• Normally-open to terminal NO1
G
C1
RD(RD)
FS1
C
BR(BK)
BK(YW)
NO
NC1
NO1
NOTE
C2, NC2, and NO2 terminals are provided for a second fire system microswitch. These terminals are not wired to any components; they are simply provided for a connection point only.
Wiring Multiple Fire Systems into KFCC
If wiring in multiple fire systems into one KFCC, a series connection of normally-closed contacts (a dedicated microswitch in each fire system) should be connected
G
between terminals C1 and NC1. All normally-open wires from the microswitches used for the series connection between C1 and NC1 should be connected to terminal NO1.
• Common of first fire system switch to terminal C1
• Normally-closed of first fire system switch to common of second fire system switch
• Normally-closed of second fire system switch to terminal NC1
• Normally-open on both switches tie to terminal NO1
FS1
RD(RD)
G
C1 NC1
BR(BK)
NC
C
BK(YW)
NO
FS2
C
BR(BK)
NC
BK(YW)
NO
ANSUL®AMEREX
COM RD (RD)
N.C. BR (BK) N.O. BK (YW)
NO1
®
Three phase, Wiring Connection Example
200V, 208V, 230V, 460V, and 575V also available
®
Kitchen Fan Control Center
7
Page 8
Spare Fire Contacts
The KFCC includes additional fire relay contacts standard for shunt trips, alarms, or additional utilities that need control signals to be sent in the event of a kitchen fire. The additional relay’s state will only be changed if the dedicated fire system is wired into the KFCC. Wiring from added relays to terminals will be done in the factory.
Fire Relay
• Power to terminal C3
• From terminal NO3 (normally open; closes in fire) to device
• From terminal NC3 (normally closed; opens in fire) to device
• Power to terminal C4
• From terminal NO4 (normally open; closes in fire) to device
• From terminal NC4 (normally closed; opens in fire) to device
RD
C3
NO3
NC3
BK
BR
12
14
A
R2
11
B
A
B
NOTE
Relay contacts will be dry unless otherwise noted on the panel’s specific wiring diagram.
Do not use additional relay contacts for power interruption to appliances. Contacts are rated up to 250 VAC and 8amps maximum.
Relay contacts will also switch state in the event power is lost to the control panel (terminals H1 and N1).
C4
NO4
NC4
RD
BL
BR
22
24
21
R2
Switches (Optional)
A switch panel may be supplied to operate lights, fans, heating/cooling capabilities of a tempered supply, a damper, or another component of the kitchen exhaust system. If selected, the switch(es) will be provided one of four ways:
1. Shipped loose for remote mounting
2. Mounted on the hood
3. Mounted on the hood utility cabinet
4. Mounted on a wall utility cabinet If the switches and the KFCC are both mounted on the
same hood, wiring to the fan switches will be done in the factory.
Fan, 1-Speed
• To terminals S1H and S1* (first fan switch)
• To terminals S2H and S2* (second fan switch)
• To terminals S3H and S3* (third fan switch) *S1N, S2N and S3N used if lighted toggle switches are
utilized.
S1
Ship Loose
Fan Switch Example
S1
Factory Wired, Control Cabinet Mounted
Fan Switch Example
S1S1H S1S1H
LT1
R
S1NS1S1H S1
Fan, 2-Speed
• To terminals S1F, S1, and S1S (first 2-speed fan switch)
HI
S1
S1
Ship Loose, 2-Speed
Fan Switch Example
LO
S1F
S1S
Lights
• To terminals H2 and B2 (first light switch)
• To terminals H3 and B3 (second light switch)
• To terminals H4 and B4 (third light switch)
S-1
B2H2
Kitchen Fan Control Center
8
®
Page 9
Tempered Supply, Heat Only
• To terminals R and W1
Tempered Supply, Cool Only
• To terminals R and Y1
Tempered Supply, Heat and Cool
• To terminals R (common), W1 (heat), and Y1 (cool)
R
R
Switch Mounting - Ship Loose for Remote Mounting
S3-1
CONNECTIONS TO
TEMPERED MUA FAN
HEAT
OFF
COOL
W1
W1
Y1
Y1
Make-Up Air (MUA) Interface (Optional)
When the KFCC is interfaced with another Greenheck supply air unit, this option may omit the redundant starter in the KFCC, as the supply air unit may already be provided with one. This will be 24VAC voltage; so 18 AWG, shielded control wire can be utilized.
Make-Up Air Unit
• From terminal R in MUA control center to terminal R in KFCC
• From terminal G in MUA control center to terminal G in KFCC
R
R
EXHAUST STARTERS
BL
CONNECTIONS TO
TEMPERED MUA FAN
TYP. THRU ALL
13 14
13 14
R12
11 14
G
G
BL
Make-Up Air Tempering Switch Example
R
R
Switch Mounting - On Control Package
S3-1
BL
Mounted on Control Package
Make-Up Air Tempering Switch Example
Shipped Loose
CONNECTIONS TO
TEMPERED MUA FAN
HEAT
OFF
COOL
BL
BL
W1
Y1
W1
Y1
Connections from these terminals will have to be made to the respective supply fan terminals R, W1 (if used), and Y1 (if used). Use proper gauge wire for field wiring depending on the voltage used.
When connecting to Greenheck’s tempered Make-Up Air unit, connect R, W1 (if used), and Y1 (if used) up to the supply unit and land on R, W1 (if used), and Y1 (if used). This will be 24 VAC power, so 18 AWG shielded wire should be utilized.
Power for Shunt Trip (Optional)
If the KFCC is configured with the power for shunt trip option, the KFCC will have terminals to connect an externally provided shunt trip breaker coil to allow the breakers to be tripped in the event of a fire. Connections include:
(Externally Provided) Shunt Trip Breakers
• To terminals STH and STN
STH
STB1
STB2
STN
Audible Alarm (Optional)
With this option, an alarm will be provided and mounted on the panel that will sound in the event of a kitchen fire. This option will be factory-mounted and wired if selected.
Combination Fan/Light Switch
• To terminals S1H and S1
S1
S1S1H
NOTE
For combination light/fans option, light circuit must not exceed 900W maximum.
®
Kitchen Fan Control Center
9
Page 10
Lights Out In Fire (Optional)
This option will turn off the kitchen hood lights in the event of a fire without the use of a shunt trip breaker. If provided, this option will be factory wired. Normal light circuit wiring should be followed. Please see either Switches (Optional), Lights on page8 or Combination Light/Fan Switch on page 9 for additional wiring information.
NOTE
For lights out in fire option, light circuit must not exceed 900W maximum.
Additional Fire Contacts (Optional)
The KFCC can include additional fire relays for shunt trips, alarms, or additional utilities that need control signals to be sent in the event of a kitchen fire. The additional relay’s state will only be changed if the dedicated fire system is wired into the KFCC. Wiring from additional relays to terminals will be done at the factory.
Additional Fire Relay
• Power to terminal C9
• From terminal NO9 (normally open; closes in fire) to device
• From terminal NC9 (normally closed; opens in fire) to device
• Power to terminal C10
• From terminal NO10 (normally open; closes in fire) to device
• From terminal NC10 (normally closed; opens in fire) to device
RD
C9
A
B
A
B
NO9
NC9
C10
NO10
NC10
BK
BR
RD
BK
BR
12
14
22
24
11
21
R5
R5
Additional Exhaust Contacts (Optional)
The KFCC can include additional relays for devices that activate when the exhaust fan is running. Wiring from additional relays to terminals will be done at the factory.
Additional Exhaust Relay
• Power to terminal C7
• From terminal NO7 (normally open; closes with exhaust) to device
• From terminal NC7 (normally closed; opens with exhaust) to device
• Power to terminal C8
• From terminal NO8 (normally open; closes with exhaust) to device
• From terminal NC8 (normally closed; opens with exhaust) to device
RD
C7
NO7
NC7
C8
NO8
NC8
BK
BR
RD
BK
BR
14
12
24
22
NOTE
11
21
R4
R4
A B
A B
Relay contacts will be dry. Power will need to be provided to the common terminal on each set.
Contacts are rated up to 250 VAC and 8 amps maximum.
NOTE
Relay contacts will be dry. Power will need to be provided to the common terminal on each set.
Do not use additional relay contacts for power interruption to appliances. Contacts are rated up to 250 VAC and 8 amps maximum.
Relay contacts will also switch state in the event power is lost to the control panel (terminals H1 and N1).
Kitchen Fan Control Center
10
®
Page 11
Additional Supply Contacts (Optional)
The KFCC can include additional relays for devices that activate when the supply fan is running. Wiring from added relays to terminals will be done at the factory.
Additional Supply Relay
• Power to terminal C5
• From terminal NO5 (normally open; closes in fire) to device
• From terminal NC5 (normally closed; opens in fire) to device
• Power to terminal C6
• From terminal NO6 (normally open; closes in fire) to device
• From terminal NC6 (normally closed; opens in fire) to device
RD
C5
NO5
NC5
C6
NO6
NC6
BK
BR
RD
BK
BR
14
12
24
22
R3
11
R3
21
NOTE
A
B
A
B
Relay contacts will be dry. Power will need to be provided to the common terminal on each set.
Contacts are rated up to 250 VAC and 8 amps maximum.
Exhaust Fan Failure Indicator (Optional)
This option will provide a small indicator light on the front panel of the KFCC. A field provided air proving switch in the exhaust duct or current sensor on the exhaust fan power feed needs to be wired to a set of terminals, which will illuminate this light and provide a visual if the exhaust fan is not operating when the fans are turned on.
Air Flow Switch (field provided)
• To terminals AF1 and AF2
EXHAUST AIR FLOW SWITCH FIELD WIRED
PR
AF1
AF1 AF2
LT2
G
EF Failure Light
WH
Supply Fan Failure Indicator (Optional)
This option will provide a small indicator light on the front panel of the KFCC. A field provided air proving switch in the supply duct or current sensor on the supply fan power feed needs to be wired to a set of terminals, which will illuminate this light and provide a visual if the supply fan is not operating when the fans are turned on.
Air Flow Switch (field provided)
• To terminals AF3 and AF4
SUPPLY AIR FLOW SWITCH FIELD WIRED
AF2
AF3 AF4
LT3PRWH
G
SF Failure Light
Status Lights (Optional)
The option adds status lights to the face of the KFCC. Power will have to be provided for each light in the field.
Status light(s)
• Bring 115 VAC power to SL1 and a neutral to SL2 (1st status light)
• Bring 115 VAC power to SL3 and a neutral to SL4 (2nd status light)
SL1 SL2
115V STATUS LIGHT
LT
Example of two 115 VAC Status Lights
SL3
115V STATUS LIGHT
LT
SL4
®
Kitchen Fan Control Center
11
Page 12
Temperature Interlock – Digital (Optional)
When configured with digital temperature interlock, the KFCC will include sensor(s) (located in the hood or shipped loose) and digital controllers. Unless already done by the factory, wire the two leads of each sensor to the control panel as shown below using low voltage, 18 AWG stranded wire. The two wires of each sensor are not polarity sensitive.
Digital Temperature Sensors
Choose the final connection option based on the table.
Sensor Terminals
First Sensor T1-A and T1-B Others
(if applicable)
T2-A and T2-B T3-A and T3-B T4-A and T4-B T5-A and T5-B T6-A and T6-B T7-A and T7-B T8-A and T8-B T9-A and T9-B T10-A and T10-B T11-A and T11-B T12-A and T12-B
Temperature Interlock – Thermostat (Optional)
When configured with thermostat style, temperature interlock, the KFCC will include thermostat(s) (mounted in hood or shipped loose) and a time delay relay. Unless already done by the factory, wire all thermostats in parallel back to terminal blocks T1-A and T1-B in control panel using 14 gauge 90°C minimum conductors.
Thermostat(s)
• To terminals T1-A and T1-B
TYP. 1 SENSOR PER
TS1
T1-A
6
R9
12
NOC
T1-B
(Off Delay: 1-100 minutes)
S1S1H S1S1H
TS2
NOTE
Wire thermostats in parallel if multiple thermostats are utilized. Do not connect thermostats in series with each other.
EXHAUST COLLAR
WIRED IN PARALLEL
TS1
T1-B T1-A
2
11
Digital Temperature Interlock Sensors
T3-A T3-B
T2-A T2-B
1
TC1
Wiring Example of Three
TS2
TS3
3
4
12
NOTE
Do not connect temperature sensors in series. Separate as much as possible the probe and digital input cables from inductive loads and power cables, to avoid any electromagnetic disturbances. Never lay power and probe cables in the same cable conduits (including those for the electrical panel). Loosen every screw and insert the cable end. Next, tighten the screws and gently pull the cables to check their tightness.
Kitchen Fan Control Center
12
®
Page 13
Digital Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured with digital temperature interlock option.
Pre-programmed, digital temperature controller(s) will be provided to monitor temperatures detected by sensor(s) and engage fan(s).
The fan(s) will start running when a temperature exceeds the set point (defaulted at 90°F) plus differential (defaulted at 25°F). Once the temperature drops back below the set point AND the fan(s) have been running for a minimum run time (defaulted at 5 minutes), the fan(s) will shut off.
OUTPUT
DIRECT OUTPUT 1
ON
OFF
TEMPERATURE
DIFFERENTIAL
(DEFAULT = 25°F)
Calibration
Each controller is capable of monitoring up to three individual sensors. There will be an individual set point for each sensor input. The temperature set point may need to be adjusted slightly depending on both ambient and cooking conditions. To adjust the set points on the controller, follow these instructions:
1. Press
Set
button. ‘St1” will appear.
2. Press or button to navigate to set point that
you wish to adjust (St1, St2, or St3).
3. Press
or button to adjust and press
Set
button to view current set point. Press
Set
button to store
value.
4. Press
Set
+ buttons together to exit set point
menu or wait 1 minute.
Show Sensor Values
Press value, and press these two buttons together again to see additional sensors connected. “Sd1” represents sensor input one, “Sd2”represents sensor input two, and “Sd3” represents sensor input three (respective to each controller). After 1 minute of no button presses, the controller will go back to displaying the first programmed input (see parameters P31, P32, P33).
Set
+ buttons together to show sensor and
SET POINT
(DEFAULT = 90°F)
®
Kitchen Fan Control Center
13
Page 14
Factory Parameters
NOTE
The controller is pre-programmed at the factory to operate based on how many sensors were selected. Adjustments (outside of the set point temperatures discussed in calibration section) should only be made under factory instruction. The list provided is for reference only.
To access/adjust all factory parameters, follow these instructions:
1. Press and hold appears.
Set
button for 30 seconds or until ‘0’
2. Press
3. With or button navigate to the desired parameter on the list of parameters.
4. Press
5. Press either value.
6. Press parameter list.
7. Press programming menu or wait 1 minute (keypad timeout).
Temperature Controller Parameters
Description Units 1 Sensor Program 2 Sensor Program 3 Sensor Program St1 Setpoint Value Sensor 1 Degrees 90.0 90.0 90.0 St2 Setpoint Value Sensor 2 Degrees 3.0 90.0 90.0 St3 Setpoint Value Sensor 3 Degrees 3.0 3.0 90.0 r01 Differential Sensor 1 Degrees 25.0 25.0 25.0 r02 Differential Sensor 2 Degrees 1.0 25.0 25.0 r03 Differential Sensor 3 Degrees 1.0 1.0 25.0
r4 Minimum Setpoint Value Degrees -50.0 -50.0 -50.0
r5 Maximum Setpoint Value Degrees 150.0 150.0 150.0 c01 Mode Sensor 1 Range dir dir dir c02 Mode Sensor 2 Range inu dir dir c03 Mode Sensor 3 Range inu inu dir c11 Minimum Output 1 Stop Time Minutes 5.0 5.0 5.0 c12 Minimum Output 2 Stop Time Minutes 0.0 5.0 5.0 c13 Minimum Output 3 Stop time Minutes 0.0 0.0 5.0 c21 Minimum Output 1 On Time Minutes 0.0 0.0 0.0 c22 Minimum Output 2 On Time Minutes 0.0 0.0 0.0 c23 Minimum Output 3 On Time Minutes 0.0 0.0 0.0 c31 On Time Fault Sensor 1 Cycle Minutes 10.0 10.0 10.0 c32 On Time Fault Sensor 2 Cycle Minutes 0.0 10.0 10.0 c33 On Time Fault Sensor 3 Cycle Minutes 0.0 0.0 10.0 c41 Off Time Fault Sensor 1 Cycle Minutes 0.0 0.0 0.0 c42 Off Time Fault Sensor 2 Cycle Minutes 0.0 0.0 0.0 c43 Off Time Fault Sensor 3 Cycle Minutes 0.0 0.0 0.0
P0 Temp Scale Option F F F P11 Sensor 1 Calibration Degrees 0.0 0.0 0.0 P12 Sensor 2 Calibration Degrees 0.0 0.0 0.0 P13 Sensor 3 Calibration Degrees 0.0 0.0 0.0
P2 Decimal Point Option YES YES YES P31 Sensor 1 Present Option YES YES YES P32 Sensor 2 Present Option NO YES YES P33 Sensor 3 Present Option NO NO YES
H2 Keypad Protection Option NO NO NO
H4 Serial Communications Address Range 0 0 0
H5 Keypad Code Range 0 0 0
H6 Type of Sensor Option Pt1 Pt1 Pt1
Shaded values are changed by the factory
Set
button to enter parameter list.
Set
button to see the current set value.
or button to set the desired new
Set
button to confirm it and exit to the
Set
+ buttons together to exit the
Kitchen Fan Control Center
14
®
Page 15
Thermostat Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured with thermostat style temperature interlock.
Calibration
Thermostat is preset by factory to 95°F (35°C) and has a slow make and break contact. It will make contact on a temperature rise and break contact on temperature fall. The temperature set point may have to be adjusted slightly depending of both ambient and cooking conditions. The adjustment knob is located on the back of the thermostat. Use a small blade screwdriver to make the adjustments.
1. Turn counterclockwise to increase the temperature set point, turn clockwise to decrease the temperature set point.
2. Quarter revolution in either direction corresponds to a 22.5°F (12.5°C) adjustment. Be sure to make small adjustments, about 1/16 of a turn (≈6°F) or less at one time.
3. Do not exceed more than one-half revolution in either direction.
4. Check system operation before making additional adjustments.
Adjustment Screw
®
Kitchen Fan Control Center
15
Page 16
KFCC Field Connection Checklist
Power to KFCC Cabinet and Lights
115 VAC power for controls (terminals H1, N1) 115 VAC power for hood lights, one per light circuit
(terminals H2, N2 | H3, N3 | H4, N4)
Connect lights, one per light circuit
(terminals B2, W2 | B3, W3 | B4, W4) (Lights may be directly wired to switch)
Power for Fans
115/200/208/230/277 VAC power, single phase fans
from breaker (terminals L1, L2)
208/230/277/460/575 VAC power, three phase fans
from breaker (terminals L1, L2, L3)
115 VAC power for single phase to fan (contactor/
overload T3, terminal L2 is neutral)
208/230/277/460 VAC power to single phase fan
(contactor/overload T1, T3)
208/460/575 VAC power to three phase fan
(contactor/overload T1, T2, T3)
Fire System
Microswitch C, N.O., and N.C. (terminals C1, NO1,
NC1)
Spare Fire Contacts
Spare, dry relay contact (terminals C3, NO3, NC3) Spare, dry relay contact (terminals C4, NO4, NC4)
Switches - if equipped
Fan, 1-Speed (terminals S_H, S_; S_N is neutral if
lighted)
Fan, 2-Speed (terminals S_F, S_S, S_) Light (terminals H2, B2 or H3, B3 or H4, B4; may be
directly wired to hood lights)
Thermal, heat only (terminals R, W1) Thermal, cool only (terminals R, Y1) Thermal, heat and cool (terminals R, W1, Y1)
MUA Interface - if equipped
To MUA Control Center (terminals R, G)
Power for Shunt Trip - if equipped
Shunt trip breaker coil (terminals STH, STN)
Additional Fire Contacts - if equipped
Spare, dry relay contact (terminals C9, NO9, NC9) Spare, dry relay contact (terminals C10, NO10, NC10)
Additional Exhaust Contacts - if equipped
Spare, dry relay contact (terminals C7, NO7, NC7) Spare, dry relay contact (terminals C8, NO8, NC8)
Additional Supply Contacts - if equipped
Spare, dry relay contact (terminals C5, NO5, NC5) Spare, dry relay contact (terminals C6, NO6, NC6)
Exhaust Fan Failure Indicator - if equipped
Field provided airflow switch or current sensor
(terminals AF1, AF2)
Supply Fan Failure Indicator - if equipped
Field provided airflow switch or current sensor
(terminals AF3, AF4)
Status Lights (115 VAC) - if equipped
Status light one (terminals SL1, SL2) Status light two (terminals SL3, SL4)
Digital Style Temperature Interlock - if equipped
Sensor(s) (terminals T_-A, T_-B)
Thermostat Style Temperature Interlock - if equipped
Thermostat(s) (wired in parallel between terminals
T1-A, T1-B)
Kitchen Fan Control Center
16
®
Page 17
General Wiring Diagram
This is an example of a generic wiring diagram of a KFCC. The KFCC is configured with
two exhaust fans and one supply fan, as well as three digital interlock sensors.
To see your job specific drawing, look on the inside panel of the KFCC.
L1
H1
RD
S1H
TC1
TC1
OR
R1
R1
RD
YW
11
14
12
11
D3 D1
TS1
T1-B T1-A
2
RD
11
RD
RD(RD)
C1
CONTROL INPUT: 115VAC, 15AMPS FROM BREAKER
FACTORY MOUNTED SWITCH
FACTORY WIRING TO SWITCH
S1
2423
1715
T3-A T3-B
1
TC1
2220
T2-A T2-B
TC1
FS1
BR(BK)
NC
C
BK(YW)
NO
OR
OR
S1
S1
TS3
TS2
3
4
BR
NC1
NO1
BK
12
R
ST1
A1ORA2
ST2
A1ORA2
ST3
A1YWA2
A1R1A2
LT1
S1N
OL1
96
OL2
96
OL3
96
Panel Mark:
N
G
N1
12.0
COOL
LI G
H T S
O F
F FA N
HEAT
WH
WH
95
WH
95
INPUT POWER
2 WIRE
115/1 PHASE
FROM BREAKER
INPUT POWER
WH
95
208/3 PHASE
FROM BREAKER
D2
INPUT POWER
230/1 PHASE
FROM BREAKER
3 WIRE
2 WIRE
6.0
L1
N
L2
L1 L2 L3
L1 L2
CONTROL PANEL
Installation Location:
20.0
"LIGHTS" SWITCH
"FAN" SWITCH
"HEAT/COOL" SWITCH
OL1 ST1
T1
L1
T1
T2
L2
T2
T3
T3
L3
OL2 ST2
T1
T1
L1
T2
L2
T2
T3
T3
L3
OL3 ST3
T1
T1
L1
T2
L2
T2
T3
T3
L3
Ship Loose
Exh
FAN 1
Exh
FAN 2
Supply FAN 3
Hood Mark(s):
F1-E EF-1 1 115 1 16.0 12 ga 20 amp F2-E EF-2 0.5 208 3 2.4 14 ga 15 amp F3-S SF-1 0.75 230 1 6.9 14 ga 15 amp
Qty. Fan Switches (0-3)
1
Qty. Light Switches (0-3)
1
Qty. Temp. Switches (0-1)
1
One Switch for L & F Digitial Temperature Interlock
X
Mounted Sensors - Factory
0
Mounted Sensors - Field
3
Heat Switch
X
Cool Switch
X
G
AD Switch Remote Switches Audible Alarm Gas Reset Power for Gas Solenoid Power for Shunt Trip
X
G
Spare Fire Switch Contact
(dry contacts for building alarm)
G
Spare Relay Contacts
WH
A B
open w/power at H1/N1 & fire system armed
A
WH
closed on fire or no power closed w/power at H1/N1 & fire system armed
B
open on fire or no power
Controls
Tempering SW
Gas Off w/Fans
RD/RD BR/BK BK/YW
RD BK
22
BR
24
NO
NC
21
Volt
C
R1
WirePH FLA Breaker
Exhaust in Fire
X
MUA Interface Lights Out in Fire Fire Relay (#1)
X
Extra Fire Relay (#2) Extra Fire Relay (#3) DPDT Relay w/SF DPDT Relay w/EF Off Delay Relay SF Failure Light EF Failure Light Fan Failure Light (Appl.) Aux. Supply Contact SDR
Ansul / Amerex
RD/RD BR/BK
FS2
BK/YW
(activated by FS1)
RD
C4
BK
NO4
A B
NC4
32
BR
34
Fan MarkMotor HP
C2 NC2 NO2
(can be used for shunt trip, alarms, etc.)
C3 NO3 NC3
R1
31
STH
STB1
STN
TEMPERATURE INTERLOCK CALIBRATION
1. PRESS SET BUTTON. 'St1' WILL APPEAR.
2. PRESS UP OR DOWN BUTTON TO NAVIGATE TO SET POINT THAT YOU WISH TO ADJUST ('St1', 'St2', OR 'St3').
3. PRESS SET BUTTON TO VIEW CURRENT SET POINT. PRESS UP OR DOWN BUTTON TO ADJUST AND PRESS SET BUTTON TO STORE VALUE.
4. PRESS SET + DOWN BUTTONS TOGETHER TO EXIT OR WAIT 1 MINUTE.
5. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS.
WH
Switches Mounting - On Control Package
L1
BK
H2
R
R
Switch Mounting - On Control Package
BL
LIGHT INPUT: 115VAC,
15AMPS FROM BREAKER
S2
CONNECTIONS TO
TEMPERED MUA FAN
S3
HEAT
OFF
COOL
B2
1400W max.
N
WH
N2
W2
LT
LT
W1
Y1
BL
W1
BL
Y1
TORQUE:
TERMINAL BLOCKS = 8 LB.IN
GROUNDING BLOCKS = 8 LB.IN
LABEL DESCRIPTION
Exhaust Fan
EF
Supply Fan
SF
Starter
ST
OverLoad
OL
Contactor
C
Ground
G
Switch
S
Light
LT
Fire Switch
FS
Relay
R
Air Flow Switch
AF
Gas Solenoid
SV
Shunt Trip Breaker
STB
Damper
D
PushButton
PB
Evap Cooler
EC
Temperature Sensor
TCTSTemperature Controller
DRAWING SHOWN DE-ENERGIZED AT L1 (TERM. #H1), W/ FIRE SYSTEM ARMED (NON-FIRE MODE). (NORMAL OPERATION, R1 & R2 ARE ENERGIZED) IF WALL MOUNTED PREWIRE, OR FIELD INSTALLED FIRE SYSTEM, THE FIRE SYSTEM MICROSWITCHES MUST BE FIELD WIRED.
COMMERCIAL APPLIANCE OUTLET CENTER
LISTED
ELECTRICAL RATINGS: 120V, 1PHASE, 60HZ, 15A
43BM
Wiring Diagram Code:
NOTES:
FILE #E313951
FIELD WIRING:
USE MINIMUM
60° Copper Wire
FACTORY WIRING FIELD WIRING
ALL WIRING 90°C 14 GA.
UNLESS SPECIFIED
WIRE COLOR
BK - black BL - blue BR - brown OR - orange PR - purple RD - red YW - yellow WH - white
®
Kitchen Fan Control Center
17
Page 18
Testing
1. Turn the fan switch(es) on, then off to ensure proper fan operation before cooking equipment is started. Once this is verified, testing can proceed.
2. If applicable, turn the light switch(es) on, then off to ensure proper light operation in the hood. Once this is verified, testing can proceed.
3. Press and hold down the fire suppression switch connected to the KFCC and verify that the corresponding exhaust and/or supply fan(s) react appropriately when in the fire state. Verify all shunt trip breakers, alarms, and other components utilizing any of the spare relay contacts in the KFCC are activated properly.
4. If the KFCC is configured with thermostat style
temperature interlock, please follow steps 5 through 9 below. If the KFCC is configured with digital temperature interlock, please follow steps 10 through 12.
5. For testing only, locate the time delay relay. Turn the time adjustment knob counterclockwise to the first mark in order to expedite the testing process. Make a note as to where the timed relay was originally set.
6. Heat up cooking equipment with fans off. Once the temperature reaches the set point of the thermostat the fans will start, preferably within 5 to 10 minutes. If the fans take more than 15 minutes to start, decrease the temperature set point by turning the adjustment screw 1/16 turn clockwise. Do not apply direct flame to the thermostat.
7. If an adjustment was made in Step 6, repeat now.
8. After verification of fan start-up, shut down cooking equipment. The fan switch should still be in the off position. Once cooking equipment has cooled, the thermostat will open triggering the timer function in the time delay relay to begin. Once time has expired, the fans will shut down. Thermostat operation can be verified by checking voltage (115VAC) between terminal blocks T1-B and N1 on the control panel. 115 VAC will be present when the thermostat senses heat.
9. Once proper operation has been verified, set the dial on the timed relay to its original setting (approximately 20 minute delay).
10. With the fans turned off by the fan switch, turn on at least one piece of cooking equipment under the hood. The fans should automatically start within 5 to 10 minutes. If the fans take more than 15 minutes to start, decrease the temperature set point(s) on the temperature controller (see Digital Style Temperature Interlock Configuration, page 13).
11. If an adjustment was made in Step 10, repeat now.
12. After verification of fan start-up, shut down cooking equipment. The fan switch should still be in the off position. Once cooking equipment has cooled below the set point, the fans will shut down.
CAUTION
If provided with temperature interlock, the sensors/ thermostats should never be exposed to direct flame. Exposing a sensor/thermostat to direct flame may render the sensor/thermostat inoperable and will void the warranty.
NOTE
During testing, if the KFCC is configured with temperature interlock and fans do not start automatically in the first 15 minutes of cooking equipment activation, manually start fans to avoid accidental fire system dump due to heat build-up.
Kitchen Fan Control Center
18
®
Page 19
Operation
Troubleshooting
1. Turn fans on and off using the fan switch.
2. If KFCC is configured to control hood lights, turn
hood lights on and off using the light switch.
3. If KFCC is configured with digital style
temperature interlock, it is normal for the fan(s) to remain running after the switch is turned off. The exhaust temperature controller will shut down fans after heat is no longer present under the hood and the temperature is below the set point. In the event that the cooking equipment is started without turning the fans on manually, the fans will turn on automatically and remain running with the presence of heat under the hood. Once the temperature is below the set point, the fans will shut down.
4. If KFCC is configured with thermostat style
temperature interlock, it is normal for the fan(s) to remain running after the fan switch is turned off. The exhaust thermostat will open after heat is no longer present under the hood which will activate the timed relay to begin its countdown. Once time has expired, fans will shut down. The timed relay is adjustable from 1-100 minutes. The recommended time delay setting is approximately 20 minutes.
1. Fan(s) do not turn on automatically upon cooking equipment activation
• Confirm that the KFCC has been configured with temperature interlock, either thermostat style or digital style.
• Check wiring to control panel. With thermostat style interlock, thermostats must be wired in parallel. With digital style interlock, sensors must be wired to the control panel separately.
• Temperature set point is too high, decrease set point.
• No power to fan(s), check breakers/starters/relays.
2. Controller(s) in KFCC display EP1 or EP2 and EP3
fan(s) will not shut off.
• EP1, EP2 and EP3 represent sensor errors.
• Disconnect the sensor from the system, and check resistance between the two wires on the sensor. At room temperature (77°F or 25°C), the sensor should read 1097.4 ohms.
• Check wiring connections between the sensor and control cabinet.
3. Fan(s) do not shut off.
• Fan switch must be in the off position.
• If the KFCC is configured with digital style temperature interlock, check the controller to determine if there is a sensor error of EP1, EP2 and/ or EP3. If yes, refer to the controller display error message, item2 above.
• Cooking equipment is still hot, and the KFCC is configured with temperature interlock. Wait for the equipment to cool.
• Temperature set point for temperature interlock is set too low, increase set point.
• Check control circuit (fan starter) wiring.
4. Exhaust fan(s) will not shut off, and supply fan(s)
will not turn on.
• Check hood for fire system dump.
• If no fire system dump has occurred, check fire system wiring between fire system microswitch and control panel.
®
5. Fan(s) do not turn on quick enough.
• Decrease temperature set point
Kitchen Fan Control Center
19
Page 20
Maintenance
Daily
If KFCC is configured with temperature interlock, clean thermostat or sensor with cloth and degreaser. Keep clean for best performance; can clean weekly depending upon grease accumulation.
Weekly
Depending on grease production and grease filter type in the hood, temperature thermostats or sensors can be cleaned weekly.
Seasonal
If KFCC is configured with temperature interlock, may have to change temperature settings if ambient kitchen temperatures fluctuate between summer and winter seasons.
Whom to call
Contact your local manufacturer’s representative.
What to have ready for the call
Sales order, serial number and description of product. Sales Order Number ________________________ Serial Number ______________________________
Frequently Asked Questions Regarding Temperature Interlock
What temperature is the thermostat/temperature interlock set from the factory?
Thermostat style: 95ºF
Digital style: 95ºF set point + 25ºF hysteresis
How do I determine if the KFCC is configured with thermostat style or digital style temperature interlock?
Thermostat style interlock uses 5/8-inch diameter
sensor(s) mounted in either the hood capture area or exhaust collar(s). The KFCC will include a solid­state relay with a 1-100 minute off-delay dial. Inspect the sensor diameter or look inside the KFCC for this solid-state relay.
Digital style interlock uses 1/4-inch diameter sensor(s)
mounted in either the hood capture area or exhaust collar(s). The KFCC will include a controller with a digital read out, capable of displaying different temperature values. Inspect the sensor diameter or look inside the KFCC for this digital-displaying controller.
Will the temperature interlock automatically start/ stop the fans?
When connected properly to the fan starters the
temperature interlock will automatically control the fans without input from the user. However, the intended use of the temperature interlock is as a back-up to manual control.
With thermostat style interlock, what is the purpose of the timer in the KFCC?
The timer is used to delay the shut down of the fans,
to prevent fan on/off cycling while the temperature in the exhaust duct can reach steady state. Without the delay, cycling could occur both on startup or shutdown of cooking equipment. The delay is typically set at 20minutes.
How many individual breakers does the KFCC require?
The number of individual breakers depends the
number of fans controlled and options included in the KFCC. Each individual fan typically requires its own breaker. The KFCC main power requires its own breaker. Each light circuit is typically put on individual breakers.
Kitchen Fan Control Center
20
Can I still turn my fan on and off?
Yes, the temperature interlock is designed to operate
with a typical on/off switch. The fan may not turn off immediately after turning the fan switch off, it will sense when the cooking operations have cooled and then turn off.
®
Page 21
Replacement Parts
Codes and Standards Compliance
Part
Number
384905
384908
383559
383560
Terminal Block, Single Pole, DIN-RAIL MT, ABB ZS6
Jumper, DIN-RAIL Terminal Block 2 Pole ABB JB6-2
DPDT Relay Base Finder 95853
DPDT Relay Finder 40528120000 115 VAC DPDT Relay
Description
Digital Style Temperature Interlock
384925
Temperature Sensor (RTD) Dwyer TE-IBN-E0448-00
Temperature Controller
880601
Programmed for 1 sensor Dwyer TSDIN-013-G
Temperature Controller
880602
Programmed for 2 sensors Dwyer TSDIN-013-G
Temperature Controller
880603
Programmed for 3 sensors Dwyer TSDIN-013-G
830125
Extension, Octagon (drilled) SC55151-1/2 (380928)
732396 J-Box Plate
380926
463570
Cover, Octagon Box SC#54-C-1RACO 722
Evergreen Compression Seal 1/4-inch, #302
Thermostat Style Temperature Interlock
383923
451168
830125
380926
383271
452614
Thermostat, Vulcan 1C2B9 5/8-inch Type C
Evergreen Quik-Seal, 1/2-inch #171 (1-1/8 inch hole size)
Extension, Octagon (drilled) SC55151-1/2 (380928)
Cover, Octagon Box SC#54-C-1RACO 722
Timer SSAC #KRDB424 SPST 1-100 min.
Evergreen Compression Seal, 5/8-inch, #302
732396 J-Box Plate
• UL 710 and UL 891
• National Fire Protection Association (NFPA 96)
• National Electrical Code (NEC)
• Canadian Electrical Code (CEC)
With Temperature Interlock Option Included:
• International Mechanical Code (IMC) 2015 Section
507.1.1
®
Kitchen Fan Control Center
21
Page 22
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Kitchen Fan Control Center
22
®
Page 23
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
®
Kitchen Fan Control Center
23
Page 24
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
Greenheck’s Kitchen Ventilation Systems, Controls and Energy Management catalog, provides additional information describing the equipment, fan performance, available accessories, and specification data.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
482413 • Kitchen Fan Control Center, Rev. 1, March 2017 Copyright 2017 © Greenheck Fan Corporation
24
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
Loading...