Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
Table of Contents
General Description .............................2
Receiving and Handling ..........................2
Installation
Control Box ...................................3
Switch Mounting ...............................3
Temperature Sensor(s) - Hood Mounting .......... 3-4
Duct Collar Mounting ........4
Thermostat - Hood Mounting .....................4
General Safety Information
Only qualified personal should install this product.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock and other potential hazards.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC) and latest edition
of the National Fire Protection Agency Standard for
Ventilation Control and Fire Protection of Commercial
Cooking Operations (NFPA 96). Follow the Canadian
Electrical Code (CEC) and ULC-S650 if installing this
product in Canada.
2. Do not allow the electrical components of this
product to come in contact with oil, grease, hot
surfaces, water, or chemicals.
3. Verify the site can supply the necessary power for
each fan and for the control panel.
WARNING
Electrical shock hazard. Can cause equipment
damage, personal injury or death. Service must only
be performed by personal that are knowledgeable in
the operation of the equipment being controlled.
CAUTION
Always disconnect power before working on or near
the product. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
It is the responsibility of the installer to make sure both
electrical and gas appliances shut down in the event
of a fire or in the event of a power loss to the building
when this sequence is required by the authority having
jurisdiction.
Duct Collar Mounting .................5
Electrical Connections
Power for KFCC ...............................6
Power for Hood Lights ..........................6
Power for Starters and Fans ......................7
Fire System Integration ..........................7
Spare Fire Contacts .............................8
Switches - Fan, 1-Speed ........................8
Fan, 2-Speed ........................8
Lights ..............................8
Tempered Supply, Heat Only ............9
Tempered Supply, Cool Only ............9
Tempered Supply, Heat and Cool ........9
Combination Fan/Light Switch ...................9
Make-Up Air Interface .........................9
Power for Shunt Trip ...........................9
Audible Alarm ................................9
Lights Out in Fire ............................10
Additional Fire Contacts .......................10
Additional Exhaust Contacts ...................10
Additional Supply Contacts ....................11
Exhaust Fan Failure Indicator ...................11
Supply Fan Failure Indicator ...................11
Status Lights ................................11
Temperature Interlock, Digital ...................12
Temperature Interlock, Thermostat ..............12
Digital Temperature Interlock Configuration ...... 13-14
The kitchen fan control center, or KFCC, is a
pre-engineered package designed to control the
operation of fans in a constant volume kitchen. The
package consists of a cabinet encasing one or more fan
motor starters interlocked together for on/off operation.
Different fan, light and thermal switch combinations may
be provided to operate the kitchen hood fan(s), light(s),
and heating/cooling capabilities of the supply air. The
control center as a standard is equipped with additional
relays prewired to the fan starter(s). These additional
relays are capable of turning on the kitchen exhaust and
shutting down supply regardless of the present state of
the fans via integration of a fire system microswitch with
factory terminals. The control center can be equipped
with temperature interlock, designed to automatically
start kitchen fans and keep them running while heat is
being generated from the cooking appliances. Hood
systems should always be manually started before the
cooking equipment is turned on, but if forgotten the
interlock will safely trigger the fans to start once heat is
detected. Other options are available.
Purpose
The purpose of the KFCC is to provide a complete
control center equipped with fan motor starters. The
control center provides a common connection point
to interlock kitchen exhaust, supply, and hood lights
with the hood’s fire suppression system. The cabinet is
pre-engineered with terminal blocks for most field wiring
connections. The control center can also be equipped
with interlock between the exhaust fans and cooking
equipment, as to meet International Mechanical Code
(IMC) 2015 Section 507.1.1. In this case, the system will
utilize a temperature sensor in the exhaust duct collar
or capture area in the hood to detect heat generated
from cooking operations and automatically activate the
exhaust fans if not already running.
Product Application
The KFCC is designed for both Type I and Type II
(grease and non-grease) constant volume hood
systems, where starters are needed to activate fans.
The control center can operate both single and three
phase fans. Greenheck recommends using one KFCC
per hood system (activates all fans simultaneously).
When temperature interlock is provided in this package,
it is not to be used in conjunction with exhaust fire
dampers.
Receiving
Upon receiving the product, check to make sure all
items are accounted for by referencing the bill of lading
to ensure all items were received. Notify the carrier if
any damage is noticed. The carrier will make notification
on the delivery receipt acknowledging any damage to
the product. All damage should be noted on all of the
copies of the bill of lading which is countersigned by the
delivering carrier. If damaged upon arrival, file a claim
with the carrier. Any physical damage to the unit after
acceptance is not the responsibility of the manufacturer.
Unpacking
Verify that all required parts and the correct quantity of
each item have been received. If any items are missing,
report shortages to your local representative to arrange
for obtaining missing parts.
Storage
If this product must be stored prior to installation,
it must be protected from dirt and moisture. Indoor
storage is highly recommended.
NOTE
Improper storage which results in damage to the unit
will void the warranty.
Handling
Make sure the equipment does not suffer any heavy
vibration or knocks.
Kitchen Fan Control Center
2
®
Page 3
Installation
2 inch typical
(50.8 mm)
3 inch air space
(76.2 mm)
Sensor Install
(cutout area)
Exhaust Area
Supply Area
(optional)
P.O.BOX 410 SCHOFIELD
TITLE
Control Box Mounting
NOTE
Control box may be factory mounted. If so, continue
to the next section.
Locate an area with enough space to mount the control
box and fasten to the wall. Use appropriate type
fasteners depending on the mounting location. Avoid
installing the control box in environments with high
magnetic and/or radio frequency interference.
Switch Mounting
NOTE
If the switches were NOT shipped loose, provided in a
separate junction box, continue to the next section.
Locate an area with enough space to mount the
switches junction box and fasten to the wall.
Temperature Sensor(s) - Hood Mounting
NOTE
Temperature sensor(s) will be provided only if the
digital temperature interlock option was configured/
ordered with the unit. If it wasn’t, continue to the next
section.
Temperature sensor(s) may be factory installed. If so,
continue to the next section.
1. Locate flat area(s) at the top interior of the hood in
front of the filters, towards the front of the hood.
19.525 inches
(495.9 mm)
Top View of Exhaust Hood
2. Find a spot for the sensor in the flat space that will
not interfere with the fire suppression nozzles and
that is not within 12inches (304.8 mm) of any light
fixtures. Cut a 3/4 to 7/8-inch (19.0 to 22.2mm)
diameter hole in the flat spot of the capture tank.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
Hood Surface
®
Kitchen Fan Control Center
3
Page 4
Temperature Sensor(s) - Hood Mounting, continued
3. Place the J-box plate inside of the octagon extension
ring and place over the hole.
4. Disassemble the compression seal and place through
hole and J-box plate as shown. Tighten the nut inside
the octagon extension ring.
Compression Seal
PN 463570
Gasket
Octagon Extension
PN 830125
J-Box Plate
PN 732396
Lock Washer
Temperature Sensor(s) - Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. Find a
spot to mount the sensor where it will not interfere
with fire suppression nozzles or other items installed
in the ducts. If an exhaust fire damper is present in
the hood exhaust collar, it must be removed prior
to temperature sensor installation. A 3/4 to 7/8-inch
(19.0 to 22.2 mm) diameter hole must be cut into the
duct 2 inches (50.8 mm) above the hood top.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
2 inches
(50.8 mm)
Nut
Exploded View (Components)
5. Place the temperature sensor through the
compression seal and tighten the compression fitting
to 35 ft.-lbs. (47.5 Nm).
Temperature Sensor
PN 384925
Additional Octagon Extension
(Optional)
PN 830125
Octagon Cover
PN 380926
6. Wire the sensor. Refer to Electrical Connections
section for instructions on wiring the temperature
sensor.
7. Place octagon cover onto J-box and fasten it.
Hood Exhaust Collar
Front Side
2. Place the J-box plate inside of the octagon extension
ring and place over the hole in the exhaust collar.
3. Disassemble the compression seal and place through
hole in duct collar and J-box plate as shown. Tighten
the nut inside the octagon extension ring.
1/4-inch Compression Seal
PN 463570
Octagon Extension
Quik Seal
Gasket
PN 830125
J-Box Plate
PN 732396
Lock Washer
Nut
Exploded View (Components)
4. Place the temperature sensor through the
compression seal and tighten the compression fitting
to 35 ft.-lbs. (47.5 Nm).
Kitchen Fan Control Center
4
Octagon Cover
PN 380926
Additional Octagon
Extension
(Optional)
PN 830125
Sensor
PN 384925
5. Wire the sensor. Refer to Electrical Connections
section for instructions on wiring the temperature
sensor.
6. Place octagon cover onto J-box and fasten it.
®
Page 5
Thermostat(s) - Hood Mounting
19.525 inches
(495.9 mm)
3 inch air space
(76.2 mm)
2 inch typical
(50.8 mm)
Exhaust Area
Supply Area
(optional)
Sensor Install
(cut out area)
NOTE
The thermostat(s) will be provided only if the thermostat
style temperature interlock option was configured/ordered
with the unit. If it wasn’t, continue to the next section.
The thermostat(s) may be factory installed. If so,
continue to the next section.
1. Locate the flat area(s) at the top interior of the hood in
front of the filters, towards the front of the hood.
Hood Plan View
2. Find a suitable location for the sensor in the flat space
that will not interfere with the fire suppression nozzles
and that is not within 12inches
light fixtures. Cut a 11⁄8 to 1¼ inch (28.6 to 31.8mm)
diameter hole in the flat spot of the capture tank.
(28.6 to 31.8 mm)
(304.8 mm) of any
Thermostat(s) – Duct Collar Mounting
1. Locate the exhaust duct on top of the hood. Find
a spot to mount the thermostat where it will not
interfere with fire suppression nozzles or other items
installed in the ducts. If an exhaust fire damper
is present in the hood exhaust collar, it must be
removed prior to temperature sensor installation. A
1
1
⁄8 to 1¼ inch (28.6 to 31.8 mm) diameter hole must
be cut into the duct 2 inches (50.8 mm) above the
hood top.
(28.6 to 31.8 mm)
Hood Exhaust Collar
(front side)
2. Place the J-box plate inside the octagon extension
ring and place over the hole in the exhaust collar.
3. Disassemble the Quik-Seal fitting and place through
hole in duct collar and J-box plate as shown. Tighten
the nut inside the octagon extension ring.
Gasket
1/2 inch Quik-Seal
PN 451168
2 inches
(50.8 mm)
Hood Surface
3. Place the J-box plate inside the octagon extension
ring and place over the hole.
4. Disassemble the compression seal and place through
hole and J-box plate as shown. Tighten the nut inside
the octagon extension ring.
Compression Seal
PN 452614
Gasket
Exploded View (Components)
Octagon Extension
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
5. Place the thermostat through compression seal and
tighten the compression fitting to 35 ft.-lbs. (47.5Nm).
6. Wire the thermostat. Refer to Electrical Connections
section for instructions on wiring the thermostat.
7. Place octagon cover onto J-box and fasten it.
Octagon Extension
PN 830125
Junction Box Plate
PN 732396
Lock Washer
Nut
Exploded View (Components)
4. Thread the thermostat into the Quik-Seal fitting until
secure.
5. Wire the thermostat. Refer to Electrical Connections
section for instructions on wiring the thermostat.
6. Place octagon cover onto J-box and fasten it.
®
Kitchen Fan Control Center
5
Page 6
Electrical Connections
NOTE
All wiring of electrical equipment must be done to
meet NEC and local codes.
NOTE
All field wire must be high temperature rated. All
115VAC field wiring (or higher) must be routed
through hard or flex conduit. All low voltage field
wiring should be plenum rated if not routed through
conduit. Field wiring should not come in contact with
the surface of the hood. To reduce the likelihood of
electromagnetic disturbance, avoid routing high and
low voltage cables in the same cable conduit.
The extent of field wiring required will depend on the
options and general configuration of the KFCC. Each
option is broken out in the next portion of this manual.
Each option will either be factory wired or will require
field wiring. Use 14 AWG, 60°C copper wire unless
otherwise specified.
Power for KFCC
The KFCC needs a power source to operate all inner
components. This power source cannot be on a shunt
trip breaker; the power must remain constant to the
panel, even in the event of a kitchen fire.
Power for KFCC
• 115 VAC, 15 amp circuit to terminals H1 and N1
L1
H1
CONTROL INPUT:
115 VAC, 15 AMPS FROM BREAKER
N1
G
N
Power for Hood Lights (Optional)
If the KFCC is configured for hood light control, a
separate power source for each light circuit will need
to be run to the panel as well to power the lights. The
KFCC can provide up to three light circuits.
Power for Hood Lights
• 115 VAC, 15 amp circuit to terminals H2 and N2
(first light circuit)
• 115 VAC, 15 amp circuit to terminals H3 and N3
(second light circuit)
• 115 VAC, 15 amp circuit to terminals H4 and N4
(third light circuit)
Hood Lights
• To terminals B2 and W2 (first light circuit)
• To terminals B3 and W3 (second light circuit)
• To terminals B4 and W4 (third light circuit)
L1
BK
H2
Each light circuit must not exceed 1400W maximum.
If panel is configured for lights out in fire, each light
circuit must not exceed 900W maximum.
Hood lights may be directly wired to light switch,
creating unoccupied terminals B2, B3 and B4. Please
refer to the wiring diagram specifically created for the
panel on the inside door of the control center.
LIGHT INPUT: 115 VAC,
15 AMPS FROM BREAKER
S-1
B2
LT
1400W max.
LT
NOTE
W2
WH
N2
N
Kitchen Fan Control Center
6
®
Page 7
Power for Starters and Fans
The KFCC is equipped with contactors that may have
thermal overloads attached to them. Each fan should
have a designated power source. The breaker size
(amps), wire gauge, phase, and voltage for each fan is
specified on the KFCC wiring diagram.
115 VAC Single Phase Fan(s) Power Wiring
• LINE - from breaker to terminals L1 and L2
• LOAD, 115 VAC - from terminal block L2 and T3 on
the bottom of contactor/overload to fan disconnect
OL1 ST1
T1
T2
T3
T1
T2
T3
T1
T2
T3
T1
T2
T3
OL2 ST2
T1
T2
T3
OL3 ST3
T1
T2
T3
Exh
FAN 1
Exh
FAN 2
Exh
FAN 3
INPUT POWER
2 wire
115/1 phase
from breaker
L1
N
L2
L1
L2
L3
Single phase, 115 VAC
Wiring Connection Example
200/208/230/277 VAC Single Phase Fan(s) Power
Wiring
• LINE - from breaker to terminals L1 and L2
• LOAD, 200/208/230/277 VAC - from T1 and T3 on
the bottom of contactor/overload to fan disconnect
INPUT POWER
2 wire
208/1 phase
from breaker
L1
L2
Single phase, 200/208/230/277 VAC
Wiring Connection Example
L1
L2
L3
Three Phase Fan(s) Power Wiring
• LINE - from breaker to terminals L1, L2 and L3
• LOAD - from T1, T2 and T3 on the bottom of
contactor/overload to fan disconnect
INPUT POWER
3 wire
208/3 phase
from breaker
L1
L2
L3
L1
L2
L3
Fire System Integration
A dedicated fire system microswitch needs to be wired
into the KFCC for all Type I hood systems. During a fire,
this will disengage supply starters, and therefore turn off
corresponding supply fans. If KFCC is configured with
“Exhaust in Fire” option, the KFCC will also engage the
exhaust starters, therefore turning on exhaust fans in
the event of a fire.
Dedicated Fire System Microswitch
• Common to terminal C1
• Normally-closed to terminal NC1
• Normally-open to terminal NO1
G
C1
RD(RD)
FS1
C
BR(BK)
BK(YW)
NO
NC1
NO1
NOTE
C2, NC2, and NO2 terminals are provided for a
second fire system microswitch. These terminals
are not wired to any components; they are simply
provided for a connection point only.
Wiring Multiple Fire Systems into KFCC
If wiring in multiple fire systems into one KFCC, a series
connection of normally-closed contacts (a dedicated
microswitch in each fire system) should be connected
G
between terminals C1 and NC1. All normally-open
wires from the microswitches used for the series
connection between C1 and NC1 should be connected
to terminal NO1.
• Common of first fire system switch to terminal C1
• Normally-closed of first fire system switch to
common of second fire system switch
• Normally-closed of second fire system switch to
terminal NC1
• Normally-open on both switches tie to terminal NO1
FS1
RD(RD)
G
C1NC1
BR(BK)
NC
C
BK(YW)
NO
FS2
C
BR(BK)
NC
BK(YW)
NO
ANSUL®AMEREX
COMRD(RD)
N.C.BR(BK)
N.O.BK(YW)
NO1
®
Three phase, Wiring Connection Example
200V, 208V, 230V, 460V, and 575V also available
®
Kitchen Fan Control Center
7
Page 8
Spare Fire Contacts
The KFCC includes additional fire relay contacts
standard for shunt trips, alarms, or additional utilities
that need control signals to be sent in the event of a
kitchen fire. The additional relay’s state will only be
changed if the dedicated fire system is wired into the
KFCC. Wiring from added relays to terminals will be
done in the factory.
Fire Relay
• Power to terminal C3
• From terminal NO3 (normally open; closes in fire) to
device
• From terminal NC3 (normally closed; opens in fire)
to device
• Power to terminal C4
• From terminal NO4 (normally open; closes in fire) to
device
• From terminal NC4 (normally closed; opens in fire)
to device
RD
C3
NO3
NC3
BK
BR
12
14
A
R2
11
B
A
B
NOTE
Relay contacts will be dry unless otherwise noted on
the panel’s specific wiring diagram.
Do not use additional relay contacts for power
interruption to appliances. Contacts are rated up to
250 VAC and 8amps maximum.
Relay contacts will also switch state in the event
power is lost to the control panel (terminals H1 and
N1).
C4
NO4
NC4
RD
BL
BR
22
24
21
R2
Switches (Optional)
A switch panel may be supplied to operate lights, fans,
heating/cooling capabilities of a tempered supply, a
damper, or another component of the kitchen exhaust
system. If selected, the switch(es) will be provided one
of four ways:
1. Shipped loose for remote mounting
2. Mounted on the hood
3. Mounted on the hood utility cabinet
4. Mounted on a wall utility cabinet
If the switches and the KFCC are both mounted on the
same hood, wiring to the fan switches will be done in
the factory.
Fan, 1-Speed
• To terminals S1H and S1* (first fan switch)
• To terminals S2H and S2* (second fan switch)
• To terminals S3H and S3* (third fan switch)
*S1N, S2N and S3N used if lighted toggle switches are
utilized.
S1
Ship Loose
Fan Switch Example
S1
Factory Wired, Control Cabinet Mounted
Fan Switch Example
S1S1HS1S1H
LT1
R
S1NS1S1HS1
Fan, 2-Speed
• To terminals S1F, S1, and S1S (first 2-speed fan
switch)
HI
S1
S1
Ship Loose, 2-Speed
Fan Switch Example
LO
S1F
S1S
Lights
• To terminals H2 and B2 (first light switch)
• To terminals H3 and B3 (second light switch)
• To terminals H4 and B4 (third light switch)
S-1
B2H2
Kitchen Fan Control Center
8
®
Page 9
Tempered Supply, Heat Only
• To terminals R and W1
Tempered Supply, Cool Only
• To terminals R and Y1
Tempered Supply, Heat and Cool
• To terminals R (common), W1 (heat), and Y1 (cool)
R
R
Switch Mounting - Ship Loose for Remote Mounting
S3-1
CONNECTIONS TO
TEMPERED MUA FAN
HEAT
OFF
COOL
W1
W1
Y1
Y1
Make-Up Air (MUA) Interface (Optional)
When the KFCC is interfaced with another Greenheck
supply air unit, this option may omit the redundant
starter in the KFCC, as the supply air unit may already
be provided with one. This will be 24VAC voltage; so 18
AWG, shielded control wire can be utilized.
Make-Up Air Unit
• From terminal R in MUA control center to terminal R
in KFCC
• From terminal G in MUA control center to
terminal G in KFCC
R
R
EXHAUST STARTERS
BL
CONNECTIONS TO
TEMPERED MUA FAN
TYP. THRU ALL
13 14
13 14
R12
11 14
G
G
BL
Make-Up Air Tempering Switch Example
R
R
Switch Mounting - On Control Package
S3-1
BL
Mounted on Control Package
Make-Up Air Tempering Switch Example
Shipped Loose
CONNECTIONS TO
TEMPERED MUA FAN
HEAT
OFF
COOL
BL
BL
W1
Y1
W1
Y1
Connections from these terminals will have to be made
to the respective supply fan terminals R, W1 (if used),
and Y1 (if used). Use proper gauge wire for field wiring
depending on the voltage used.
When connecting to Greenheck’s tempered Make-Up
Air unit, connect R, W1 (if used), and Y1 (if used) up to
the supply unit and land on R, W1 (if used), and Y1 (if
used). This will be 24 VAC power, so 18 AWG shielded
wire should be utilized.
Power for Shunt Trip (Optional)
If the KFCC is configured with the power for shunt
trip option, the KFCC will have terminals to connect
an externally provided shunt trip breaker coil to
allow the breakers to be tripped in the event of a fire.
Connections include:
(Externally Provided) Shunt Trip Breakers
• To terminals STH and STN
STH
STB1
STB2
STN
Audible Alarm (Optional)
With this option, an alarm will be provided and mounted
on the panel that will sound in the event of a kitchen
fire. This option will be factory-mounted and wired if
selected.
Combination Fan/Light Switch
• To terminals S1H and S1
S1
S1S1H
NOTE
For combination light/fans option, light circuit must
not exceed 900W maximum.
®
Kitchen Fan Control Center
9
Page 10
Lights Out In Fire (Optional)
This option will turn off the kitchen hood lights in
the event of a fire without the use of a shunt trip
breaker. If provided, this option will be factory wired.
Normal light circuit wiring should be followed. Please
see either Switches (Optional), Lights on page8
or Combination Light/Fan Switch on page 9 for
additional wiring information.
NOTE
For lights out in fire option, light circuit must not
exceed 900W maximum.
Additional Fire Contacts (Optional)
The KFCC can include additional fire relays for shunt
trips, alarms, or additional utilities that need control
signals to be sent in the event of a kitchen fire. The
additional relay’s state will only be changed if the
dedicated fire system is wired into the KFCC. Wiring
from additional relays to terminals will be done at the
factory.
Additional Fire Relay
• Power to terminal C9
• From terminal NO9 (normally open; closes in fire) to
device
• From terminal NC9 (normally closed; opens in fire)
to device
• Power to terminal C10
• From terminal NO10 (normally open; closes in fire)
to device
• From terminal NC10 (normally closed; opens in fire)
to device
RD
C9
A
B
A
B
NO9
NC9
C10
NO10
NC10
BK
BR
RD
BK
BR
12
14
22
24
11
21
R5
R5
Additional Exhaust Contacts (Optional)
The KFCC can include additional relays for devices that
activate when the exhaust fan is running. Wiring from
additional relays to terminals will be done at the factory.
Additional Exhaust Relay
• Power to terminal C7
• From terminal NO7 (normally open; closes with
exhaust) to device
• From terminal NC7 (normally closed; opens with
exhaust) to device
• Power to terminal C8
• From terminal NO8 (normally open; closes with
exhaust) to device
• From terminal NC8 (normally closed; opens with
exhaust) to device
RD
C7
NO7
NC7
C8
NO8
NC8
BK
BR
RD
BK
BR
14
12
24
22
NOTE
11
21
R4
R4
A
B
A
B
Relay contacts will be dry. Power will need to be
provided to the common terminal on each set.
Contacts are rated up to 250 VAC and 8 amps
maximum.
NOTE
Relay contacts will be dry. Power will need to be
provided to the common terminal on each set.
Do not use additional relay contacts for power
interruption to appliances. Contacts are rated up to
250 VAC and 8 amps maximum.
Relay contacts will also switch state in the event
power is lost to the control panel (terminals H1 and
N1).
Kitchen Fan Control Center
10
®
Page 11
Additional Supply Contacts (Optional)
The KFCC can include additional relays for devices that
activate when the supply fan is running. Wiring from
added relays to terminals will be done at the factory.
Additional Supply Relay
• Power to terminal C5
• From terminal NO5 (normally open; closes in fire) to
device
• From terminal NC5 (normally closed; opens in fire)
to device
• Power to terminal C6
• From terminal NO6 (normally open; closes in fire) to
device
• From terminal NC6 (normally closed; opens in fire)
to device
RD
C5
NO5
NC5
C6
NO6
NC6
BK
BR
RD
BK
BR
14
12
24
22
R3
11
R3
21
NOTE
A
B
A
B
Relay contacts will be dry. Power will need to be
provided to the common terminal on each set.
Contacts are rated up to 250 VAC and 8 amps
maximum.
Exhaust Fan Failure Indicator (Optional)
This option will provide a small indicator light on the
front panel of the KFCC. A field provided air proving
switch in the exhaust duct or current sensor on the
exhaust fan power feed needs to be wired to a set of
terminals, which will illuminate this light and provide a
visual if the exhaust fan is not operating when the fans
are turned on.
Air Flow Switch (field provided)
• To terminals AF1 and AF2
EXHAUST AIR FLOW SWITCH FIELD WIRED
PR
AF1
AF1AF2
LT2
G
EF Failure Light
WH
Supply Fan Failure Indicator (Optional)
This option will provide a small indicator light on the
front panel of the KFCC. A field provided air proving
switch in the supply duct or current sensor on the
supply fan power feed needs to be wired to a set of
terminals, which will illuminate this light and provide a
visual if the supply fan is not operating when the fans
are turned on.
Air Flow Switch (field provided)
• To terminals AF3 and AF4
SUPPLY AIR FLOW SWITCH FIELD WIRED
AF2
AF3AF4
LT3PRWH
G
SF Failure Light
Status Lights (Optional)
The option adds status lights to the face of the KFCC.
Power will have to be provided for each light in the field.
Status light(s)
• Bring 115 VAC power to SL1 and a neutral to SL2
(1st status light)
• Bring 115 VAC power to SL3 and a neutral to SL4
(2nd status light)
SL1SL2
115V STATUS LIGHT
LT
Example of two 115 VAC Status Lights
SL3
115V STATUS LIGHT
LT
SL4
®
Kitchen Fan Control Center
11
Page 12
Temperature Interlock – Digital (Optional)
When configured with digital temperature interlock,
the KFCC will include sensor(s) (located in the hood or
shipped loose) and digital controllers. Unless already
done by the factory, wire the two leads of each sensor
to the control panel as shown below using low voltage,
18 AWG stranded wire. The two wires of each sensor
are not polarity sensitive.
Digital Temperature Sensors
Choose the final connection option based on the table.
SensorTerminals
First SensorT1-A and T1-B
Others
(if applicable)
T2-A and T2-B
T3-A and T3-B
T4-A and T4-B
T5-A and T5-B
T6-A and T6-B
T7-A and T7-B
T8-A and T8-B
T9-A and T9-B
T10-A and T10-B
T11-A and T11-B
T12-A and T12-B
Temperature Interlock – Thermostat (Optional)
When configured with thermostat style, temperature
interlock, the KFCC will include thermostat(s) (mounted
in hood or shipped loose) and a time delay relay. Unless
already done by the factory, wire all thermostats in
parallel back to terminal blocks T1-A and T1-B in control
panel using 14 gauge 90°C minimum conductors.
Thermostat(s)
• To terminals T1-A and T1-B
TYP. 1 SENSOR PER
TS1
T1-A
6
R9
12
NOC
T1-B
(Off Delay: 1-100 minutes)
S1S1HS1S1H
TS2
NOTE
Wire thermostats in parallel if multiple thermostats
are utilized. Do not connect thermostats in series with
each other.
EXHAUST COLLAR
WIRED IN PARALLEL
TS1
T1-BT1-A
2
11
Digital Temperature Interlock Sensors
T3-AT3-B
T2-AT2-B
1
TC1
Wiring Example of Three
TS2
TS3
3
4
12
NOTE
Do not connect temperature sensors in series.
Separate as much as possible the probe and digital
input cables from inductive loads and power cables,
to avoid any electromagnetic disturbances. Never
lay power and probe cables in the same cable
conduits (including those for the electrical panel).
Loosen every screw and insert the cable end. Next,
tighten the screws and gently pull the cables to
check their tightness.
Kitchen Fan Control Center
12
®
Page 13
Digital Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured
with digital temperature interlock option.
Pre-programmed, digital temperature controller(s) will be
provided to monitor temperatures detected by sensor(s)
and engage fan(s).
The fan(s) will start running when a temperature
exceeds the set point (defaulted at 90°F) plus differential
(defaulted at 25°F). Once the temperature drops back
below the set point AND the fan(s) have been running
for a minimum run time (defaulted at 5 minutes), the
fan(s) will shut off.
OUTPUT
DIRECT OUTPUT 1
ON
OFF
TEMPERATURE
DIFFERENTIAL
(DEFAULT = 25°F)
Calibration
Each controller is capable of monitoring up to three
individual sensors. There will be an individual set point
for each sensor input. The temperature set point may
need to be adjusted slightly depending on both ambient
and cooking conditions. To adjust the set points on the
controller, follow these instructions:
1. Press
Set
button. ‘St1” will appear.
2. Press or button to navigate to set point that
you wish to adjust (St1, St2, or St3).
3. Press
or button to adjust and press
Set
button to view current set point. Press
Set
button to store
value.
4. Press
Set
+ buttons together to exit set point
menu or wait 1 minute.
Show Sensor Values
Press
value, and press these two buttons together again to
see additional sensors connected. “Sd1” represents
sensor input one, “Sd2”represents sensor input two,
and “Sd3” represents sensor input three (respective to
each controller). After 1 minute of no button presses, the
controller will go back to displaying the first
programmed input (see parameters P31, P32, P33).
Set
+ buttons together to show sensor and
SET POINT
(DEFAULT = 90°F)
®
Kitchen Fan Control Center
13
Page 14
Factory Parameters
NOTE
The controller is pre-programmed at the factory to
operate based on how many sensors were selected.
Adjustments (outside of the set point temperatures
discussed in calibration section) should only be made
under factory instruction. The list provided is for
reference only.
To access/adjust all factory parameters, follow these
instructions:
1. Press and hold
appears.
Set
button for 30 seconds or until ‘0’
2. Press
3. With or button navigate to the desired
parameter on the list of parameters.
4. Press
5. Press either
value.
6. Press
parameter list.
7. Press
programming menu or wait 1 minute (keypad
timeout).
Temperature Controller Parameters
DescriptionUnits1 Sensor Program2 Sensor Program3 Sensor Program
St1Setpoint Value Sensor 1Degrees90.090.090.0
St2Setpoint Value Sensor 2Degrees3.090.090.0
St3Setpoint Value Sensor 3Degrees3.03.090.0
r01Differential Sensor 1Degrees25.025.025.0
r02Differential Sensor 2Degrees1.025.025.0
r03Differential Sensor 3Degrees1.01.025.0
r4Minimum Setpoint ValueDegrees-50.0-50.0-50.0
r5Maximum Setpoint ValueDegrees150.0150.0150.0
c01Mode Sensor 1Rangedirdirdir
c02Mode Sensor 2Rangeinudirdir
c03Mode Sensor 3Rangeinuinudir
c11Minimum Output 1 Stop TimeMinutes5.05.05.0
c12Minimum Output 2 Stop TimeMinutes0.05.05.0
c13Minimum Output 3 Stop timeMinutes0.00.05.0
c21Minimum Output 1 On TimeMinutes0.00.00.0
c22Minimum Output 2 On TimeMinutes0.00.00.0
c23Minimum Output 3 On TimeMinutes0.00.00.0
c31On Time Fault Sensor 1 CycleMinutes10.010.010.0
c32On Time Fault Sensor 2 CycleMinutes0.010.010.0
c33On Time Fault Sensor 3 CycleMinutes0.00.010.0
c41Off Time Fault Sensor 1 Cycle Minutes0.00.00.0
c42Off Time Fault Sensor 2 Cycle Minutes0.00.00.0
c43Off Time Fault Sensor 3 Cycle Minutes0.00.00.0
Thermostat Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured
with thermostat style temperature interlock.
Calibration
Thermostat is preset by factory to
95°F (35°C) and has a slow make
and break contact. It will make
contact on a temperature rise and
break contact on temperature
fall. The temperature set point
may have to be adjusted slightly
depending of both ambient
and cooking conditions. The
adjustment knob is located on
the back of the thermostat. Use a
small blade screwdriver to make
the adjustments.
1. Turn counterclockwise to increase the temperature
set point, turn clockwise to decrease the temperature
set point.
2. Quarter revolution in either direction corresponds to
a 22.5°F (12.5°C) adjustment. Be sure to make small
adjustments, about 1/16 of a turn (≈6°F) or less at one
time.
3. Do not exceed more than one-half revolution in either
direction.
4. Check system operation before making additional
adjustments.
Adjustment
Screw
®
Kitchen Fan Control Center
15
Page 16
KFCC Field Connection Checklist
Power to KFCC Cabinet and Lights
115 VAC power for controls (terminals H1, N1)
115 VAC power for hood lights, one per light circuit
(terminals H2, N2 | H3, N3 | H4, N4)
Connect lights, one per light circuit
(terminals B2, W2 | B3, W3 | B4, W4)
(Lights may be directly wired to switch)
Power for Fans
115/200/208/230/277 VAC power, single phase fans
from breaker (terminals L1, L2)
208/230/277/460/575 VAC power, three phase fans
from breaker (terminals L1, L2, L3)
115 VAC power for single phase to fan (contactor/
overload T3, terminal L2 is neutral)
208/230/277/460 VAC power to single phase fan
(contactor/overload T1, T3)
208/460/575 VAC power to three phase fan
(contactor/overload T1, T2, T3)
Fire System
Microswitch C, N.O., and N.C. (terminals C1, NO1,
Status light one (terminals SL1, SL2)
Status light two (terminals SL3, SL4)
Digital Style Temperature Interlock - if equipped
Sensor(s) (terminals T_-A, T_-B)
Thermostat Style Temperature Interlock - if equipped
Thermostat(s) (wired in parallel between terminals
T1-A, T1-B)
Kitchen Fan Control Center
16
®
Page 17
General Wiring Diagram
This is an example of a generic wiring diagram of a KFCC. The KFCC is configured with
two exhaust fans and one supply fan, as well as three digital interlock sensors.
To see your job specific drawing, look on the inside panel of the KFCC.
L1
H1
RD
S1H
TC1
TC1
OR
R1
R1
RD
YW
11
14
12
11
D3D1
TS1
T1-BT1-A
2
RD
11
RD
RD(RD)
C1
CONTROL INPUT: 115VAC, 15AMPS FROM BREAKER
FACTORY MOUNTED SWITCH
FACTORY WIRING TO SWITCH
S1
2423
1715
T3-AT3-B
1
TC1
2220
T2-AT2-B
TC1
FS1
BR(BK)
NC
C
BK(YW)
NO
OR
OR
S1
S1
TS3
TS2
3
4
BR
NC1
NO1
BK
12
R
ST1
A1ORA2
ST2
A1ORA2
ST3
A1YWA2
A1R1A2
LT1
S1N
OL1
96
OL2
96
OL3
96
Panel Mark:
N
G
N1
12.0
COOL
LI
G
H
T
S
O
F
F
FA
N
HEAT
WH
WH
95
WH
95
INPUT POWER
2 WIRE
115/1 PHASE
FROM BREAKER
INPUT POWER
WH
95
208/3 PHASE
FROM BREAKER
D2
INPUT POWER
230/1 PHASE
FROM BREAKER
3 WIRE
2 WIRE
6.0
L1
N
L2
L1
L2
L3
L1
L2
CONTROL PANEL
Installation Location:
20.0
"LIGHTS" SWITCH
"FAN" SWITCH
"HEAT/COOL" SWITCH
OL1 ST1
T1
L1
T1
T2
L2
T2
T3
T3
L3
OL2 ST2
T1
T1
L1
T2
L2
T2
T3
T3
L3
OL3 ST3
T1
T1
L1
T2
L2
T2
T3
T3
L3
Ship Loose
Exh
FAN 1
Exh
FAN 2
Supply
FAN 3
Hood Mark(s):
F1-EEF-11 115 1 16.0 12 ga 20 amp
F2-EEF-20.5 208 3 2.4 14 ga 15 amp
F3-SSF-1 0.75 230 1 6.9 14 ga 15 amp
Qty. Fan Switches (0-3)
1
Qty. Light Switches (0-3)
1
Qty. Temp. Switches (0-1)
1
One Switch for L & F
Digitial Temperature Interlock
X
Mounted Sensors - Factory
0
Mounted Sensors - Field
3
Heat Switch
X
Cool Switch
X
G
AD Switch
Remote Switches
Audible Alarm
Gas Reset
Power for Gas Solenoid
Power for Shunt Trip
X
G
Spare Fire Switch Contact
(dry contacts for building alarm)
G
Spare Relay Contacts
WH
A
B
open w/power at H1/N1 & fire system armed
A
WH
closed on fire or no power
closed w/power at H1/N1 & fire system armed
B
open on fire or no power
Controls
Tempering SW
Gas Off w/Fans
RD/RD
BR/BK
BK/YW
RD
BK
22
BR
24
NO
NC
21
Volt
C
R1
WirePH FLABreaker
Exhaust in Fire
X
MUA Interface
Lights Out in Fire
Fire Relay (#1)
X
Extra Fire Relay (#2)
Extra Fire Relay (#3)
DPDT Relay w/SF
DPDT Relay w/EF
Off Delay Relay
SF Failure Light
EF Failure Light
Fan Failure Light (Appl.)
Aux. Supply Contact
SDR
Ansul / Amerex
RD/RD
BR/BK
FS2
BK/YW
(activated by FS1)
RD
C4
BK
NO4
A
B
NC4
32
BR
34
Fan MarkMotorHP
C2
NC2
NO2
(can be used for shunt trip, alarms, etc.)
C3
NO3
NC3
R1
31
STH
STB1
STN
TEMPERATURE INTERLOCK CALIBRATION
1. PRESS SET BUTTON. 'St1' WILL APPEAR.
2. PRESS UP OR DOWN BUTTON TO NAVIGATE TO SET POINT THAT YOU WISH
TO ADJUST ('St1', 'St2', OR 'St3').
3. PRESS SET BUTTON TO VIEW CURRENT SET POINT. PRESS UP OR DOWN
BUTTON TO ADJUST AND PRESS SET BUTTON TO STORE VALUE.
4. PRESS SET + DOWN BUTTONS TOGETHER TO EXIT OR WAIT 1 MINUTE.
5. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS.
WH
Switches Mounting - On Control Package
L1
BK
H2
R
R
Switch Mounting - On Control Package
BL
LIGHT INPUT: 115VAC,
15AMPS FROM BREAKER
S2
CONNECTIONS TO
TEMPERED MUA FAN
S3
HEAT
OFF
COOL
B2
1400W max.
N
WH
N2
W2
LT
LT
W1
Y1
BL
W1
BL
Y1
TORQUE:
TERMINAL BLOCKS = 8 LB.IN
GROUNDING BLOCKS = 8 LB.IN
LABEL DESCRIPTION
Exhaust Fan
EF
Supply Fan
SF
Starter
ST
OverLoad
OL
Contactor
C
Ground
G
Switch
S
Light
LT
Fire Switch
FS
Relay
R
Air Flow Switch
AF
Gas Solenoid
SV
Shunt Trip Breaker
STB
Damper
D
PushButton
PB
Evap Cooler
EC
Temperature Sensor
TCTSTemperature Controller
DRAWING SHOWN DE-ENERGIZED AT L1 (TERM. #H1),
W/ FIRE SYSTEM ARMED (NON-FIRE MODE). (NORMAL
OPERATION, R1 & R2 ARE ENERGIZED) IF WALL
MOUNTED PREWIRE, OR FIELD INSTALLED FIRE
SYSTEM, THE FIRE SYSTEM MICROSWITCHES MUST
BE FIELD WIRED.
COMMERCIAL APPLIANCE OUTLET CENTER
LISTED
ELECTRICAL RATINGS: 120V, 1PHASE, 60HZ, 15A
43BM
Wiring Diagram Code:
NOTES:
FILE #E313951
FIELD WIRING:
USE MINIMUM
60° Copper Wire
FACTORY WIRING
FIELD WIRING
ALL WIRING 90°C 14 GA.
UNLESS SPECIFIED
WIRE COLOR
BK - black
BL - blue
BR - brown
OR - orange
PR - purple
RD - red
YW - yellow
WH - white
®
Kitchen Fan Control Center
17
Page 18
Testing
1. Turn the fan switch(es) on, then off to ensure proper
fan operation before cooking equipment is started.
Once this is verified, testing can proceed.
2. If applicable, turn the light switch(es) on, then off to
ensure proper light operation in the hood. Once this
is verified, testing can proceed.
3. Press and hold down the fire suppression switch
connected to the KFCC and verify that the
corresponding exhaust and/or supply fan(s) react
appropriately when in the fire state. Verify all shunt
trip breakers, alarms, and other components
utilizing any of the spare relay contacts in the KFCC
are activated properly.
4. If the KFCC is configured with thermostat style
temperature interlock, please follow steps 5
through 9 below. If the KFCC is configured with
digital temperature interlock, please follow steps
10 through 12.
5. For testing only, locate the time delay relay. Turn the
time adjustment knob counterclockwise to the first
mark in order to expedite the testing process. Make
a note as to where the timed relay was originally set.
6. Heat up cooking equipment with fans off. Once the
temperature reaches the set point of the thermostat
the fans will start, preferably within 5 to 10 minutes.
If the fans take more than 15 minutes to start,
decrease the temperature set point by turning the
adjustment screw 1/16 turn clockwise. Do not apply
direct flame to the thermostat.
7. If an adjustment was made in Step 6, repeat now.
8. After verification of fan start-up, shut down cooking
equipment. The fan switch should still be in the off
position. Once cooking equipment has cooled, the
thermostat will open triggering the timer function
in the time delay relay to begin. Once time has
expired, the fans will shut down. Thermostat
operation can be verified by checking voltage
(115VAC) between terminal blocks T1-B and N1 on
the control panel. 115 VAC will be present when the
thermostat senses heat.
9. Once proper operation has been verified, set
the dial on the timed relay to its original setting
(approximately 20 minute delay).
10. With the fans turned off by the fan switch, turn on
at least one piece of cooking equipment under
the hood. The fans should automatically start
within 5 to 10 minutes. If the fans take more than
15 minutes to start, decrease the temperature set
point(s) on the temperature controller (see Digital
Style Temperature Interlock Configuration, page 13).
11. If an adjustment was made in Step 10, repeat now.
12. After verification of fan start-up, shut down cooking
equipment. The fan switch should still be in the
off position. Once cooking equipment has cooled
below the set point, the fans will shut down.
CAUTION
If provided with temperature interlock, the sensors/
thermostats should never be exposed to direct flame.
Exposing a sensor/thermostat to direct flame may
render the sensor/thermostat inoperable and will void
the warranty.
NOTE
During testing, if the KFCC is configured with
temperature interlock and fans do not start
automatically in the first 15 minutes of cooking
equipment activation, manually start fans to avoid
accidental fire system dump due to heat build-up.
Kitchen Fan Control Center
18
®
Page 19
Operation
Troubleshooting
1. Turn fans on and off using the fan switch.
2. If KFCC is configured to control hood lights, turn
hood lights on and off using the light switch.
3. If KFCC is configured with digital style
temperature interlock, it is normal for the fan(s) to
remain running after the switch is turned off. The
exhaust temperature controller will shut down fans
after heat is no longer present under the hood and the
temperature is below the set point. In the event that
the cooking equipment is started without turning the
fans on manually, the fans will turn on automatically
and remain running with the presence of heat under
the hood. Once the temperature is below the set
point, the fans will shut down.
4. If KFCC is configured with thermostat style
temperature interlock, it is normal for the fan(s) to
remain running after the fan switch is turned off. The
exhaust thermostat will open after heat is no longer
present under the hood which will activate the timed
relay to begin its countdown. Once time has expired,
fans will shut down. The timed relay is adjustable
from 1-100 minutes. The recommended time delay
setting is approximately 20 minutes.
1. Fan(s) do not turn on automatically upon cooking
equipment activation
• Confirm that the KFCC has been configured with
temperature interlock, either thermostat style or
digital style.
• Check wiring to control panel. With thermostat style
interlock, thermostats must be wired in parallel. With
digital style interlock, sensors must be wired to the
control panel separately.
• Temperature set point is too high, decrease set point.
• No power to fan(s), check breakers/starters/relays.
2. Controller(s) in KFCC display EP1 or EP2 and EP3
fan(s) will not shut off.
• EP1, EP2 and EP3 represent sensor errors.
• Disconnect the sensor from the system, and check
resistance between the two wires on the sensor. At
room temperature (77°F or 25°C), the sensor should
read 1097.4 ohms.
• Check wiring connections between the sensor and
control cabinet.
3. Fan(s) do not shut off.
• Fan switch must be in the off position.
• If the KFCC is configured with digital style
temperature interlock, check the controller to
determine if there is a sensor error of EP1, EP2 and/
or EP3. If yes, refer to the controller display error
message, item2 above.
• Cooking equipment is still hot, and the KFCC is
configured with temperature interlock. Wait for the
equipment to cool.
• Temperature set point for temperature interlock is set
too low, increase set point.
• Check control circuit (fan starter) wiring.
4. Exhaust fan(s) will not shut off, and supply fan(s)
will not turn on.
• Check hood for fire system dump.
• If no fire system dump has occurred, check fire
system wiring between fire system microswitch and
control panel.
®
5. Fan(s) do not turn on quick enough.
• Decrease temperature set point
Kitchen Fan Control Center
19
Page 20
Maintenance
Daily
If KFCC is configured with temperature interlock,
clean thermostat or sensor with cloth and degreaser.
Keep clean for best performance; can clean weekly
depending upon grease accumulation.
Weekly
Depending on grease production and grease filter type
in the hood, temperature thermostats or sensors can be
cleaned weekly.
Seasonal
If KFCC is configured with temperature interlock, may
have to change temperature settings if ambient kitchen
temperatures fluctuate between summer and winter
seasons.
Whom to call
Contact your local manufacturer’s representative.
What to have ready for the call
Sales order, serial number and description of product.
Sales Order Number ________________________
Serial Number ______________________________
Frequently Asked Questions
Regarding Temperature Interlock
What temperature is the thermostat/temperature
interlock set from the factory?
Thermostat style: 95ºF
Digital style: 95ºF set point + 25ºF hysteresis
How do I determine if the KFCC is configured
with thermostat style or digital style temperature
interlock?
Thermostat style interlock uses 5/8-inch diameter
sensor(s) mounted in either the hood capture area
or exhaust collar(s). The KFCC will include a solidstate relay with a 1-100 minute off-delay dial. Inspect
the sensor diameter or look inside the KFCC for this
solid-state relay.
Digital style interlock uses 1/4-inch diameter sensor(s)
mounted in either the hood capture area or exhaust
collar(s). The KFCC will include a controller with
a digital read out, capable of displaying different
temperature values. Inspect the sensor diameter
or look inside the KFCC for this digital-displaying
controller.
Will the temperature interlock automatically start/
stop the fans?
When connected properly to the fan starters the
temperature interlock will automatically control
the fans without input from the user. However, the
intended use of the temperature interlock is as a
back-up to manual control.
With thermostat style interlock, what is the purpose
of the timer in the KFCC?
The timer is used to delay the shut down of the fans,
to prevent fan on/off cycling while the temperature
in the exhaust duct can reach steady state. Without
the delay, cycling could occur both on startup
or shutdown of cooking equipment. The delay is
typically set at 20minutes.
How many individual breakers does the KFCC
require?
The number of individual breakers depends the
number of fans controlled and options included in
the KFCC. Each individual fan typically requires its
own breaker. The KFCC main power requires its own
breaker. Each light circuit is typically put on individual
breakers.
Kitchen Fan Control Center
20
Can I still turn my fan on and off?
Yes, the temperature interlock is designed to operate
with a typical on/off switch. The fan may not turn off
immediately after turning the fan switch off, it will
sense when the cooking operations have cooled and
then turn off.
®
Page 21
Replacement Parts
Codes and Standards Compliance
Part
Number
384905
384908
383559
383560
Terminal Block, Single Pole,
DIN-RAIL MT, ABB ZS6
Jumper, DIN-RAIL
Terminal Block 2 Pole ABB JB6-2
DPDT Relay Base
Finder 95853
DPDT Relay
Finder 40528120000 115 VAC DPDT Relay
Description
Digital Style Temperature Interlock
384925
Temperature Sensor (RTD)
Dwyer TE-IBN-E0448-00
Temperature Controller
880601
Programmed for 1 sensor
Dwyer TSDIN-013-G
Temperature Controller
880602
Programmed for 2 sensors
Dwyer TSDIN-013-G
Temperature Controller
880603
Programmed for 3 sensors
Dwyer TSDIN-013-G
830125
Extension, Octagon (drilled)
SC55151-1/2 (380928)
732396J-Box Plate
380926
463570
Cover, Octagon Box
SC#54-C-1RACO 722
Evergreen Compression Seal
1/4-inch, #302
Thermostat Style Temperature Interlock
383923
451168
830125
380926
383271
452614
Thermostat, Vulcan
1C2B9 5/8-inch Type C
Evergreen Quik-Seal, 1/2-inch
#171 (1-1/8 inch hole size)
Extension, Octagon (drilled)
SC55151-1/2 (380928)
Cover, Octagon Box
SC#54-C-1RACO 722
Timer SSAC
#KRDB424 SPST 1-100 min.
Evergreen Compression Seal,
5/8-inch, #302
732396J-Box Plate
• UL 710 and UL 891
• National Fire Protection Association (NFPA 96)
• National Electrical Code (NEC)
• Canadian Electrical Code (CEC)
With Temperature Interlock Option Included:
• International Mechanical Code (IMC) 2015 Section
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Kitchen Ventilation Systems, Controls and
Energy Management catalog, provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.