Greenheck IGX-HV-109 User Manual

Modular Heating & Ventilating Unit
Model IGX-HV
• Indirect Gas-Fired Heating
• Evaporative • Chilled Water • DX Cooling
October
2008
PRODUCT FEATURES
Model IGX-HV
Indirect Gas-Fired Heating and Ventilating Unit Indoor/Outdoor Installations
A modular design concept enables the flexibility to customize each product for its application. Modules are then factory assembled and wired to minimize field installation labor. The result is a semi-custom product at an attractive cost.
IGX-HV shown with horizontal discharge.
Reliable Fan Performance
Air performance ratings from Greenheck’s AMCA registered test chamber ensure accurate data.
Indirect Gas-Fired Furnaces
The Greenheck furnace is designed for top-notch performance and long life, combining quality components with expert craftsmanship. Unique to our furnace is a post purge cycle, which runs the combustion fan after the unit is shut down to vent hot air and moisture out of the heat exchanger. The elimination of these corrosion catalysts adds years to the life of the heat exchanger.
Other key features of our furnace are listed below:
• Power vented
• 80% thermal efficiency
• Seamless tubes
• Electronic staged gas controls
• Electronic modulating gas controls
• Aluminized steel or stainless steel heat exchanger
• Direct spark ignition system
• Easy access burner controls
• ETL listed to ANSI Standard Z83.8
• Solid state automatic ignition module
Fans are constructed of heavy gauge steel and designed for high efficiency and low sound levels. Wheels are statically and dynamically balanced to ensure vibration free operation.
Control Center
The control center includes the following standard components:
• Magnetic motor starter with solid state overload
protection
• Control transformer
• Disconnect switch
• Separately fused motor
• Distribution terminal strip
Premium grade control components are selected for reliable operation. All electrical components are UL Listed, recognized or classified. Control centers are factory prewired for single point power connection.
Vibration Isolators
The entire fan and motor assembly is mounted on vibration isolators to minimize noise transmission into the building. Neoprene isolators are standard on all units, spring isolators are optional.
2
Factory Wired and Tested
All units are tested prior to shipment. Units are checked for vibration and proper operation.
CONTROL OPTIONS
Suppl
y
Return Ai
r
70% - 100
%
Outdoor Air
0% - 30%
Suppl
y
Return Ai
r
70% - 100
%
Outdoor Air
0% - 30%
Suppl
y
Return Ai
r
25% - 100
%
Outdoor Air 30% - 75%
Suppl
y
Return Ai
r
70% - 100
%
Suppl
y
Return Ai
r
25% - 100
%
Suppl
y
Return Ai
r
100
%
Heating and Ventilating Control
Three heating and ventilating options are available to provide proper tempering and fulfill varying requirements for fresh outdoor air. In all cases, heating and cooling functions are controlled by a Greenheck room thermostat or a DDC system (by others).
HV1: 0%-30% Minimum Outdoor Air
HV1 is the most common among heating and ventilating units, allowing you to set the minimum outdoor air volume between 0 and 30% of the total supply air volume. With the relatively low percentage of outdoor air, mixed air temperatures are mild and stable.
1-stage heating and/or cooling is recommended. (2-stage or electronic
modulation is optional).
Thermostat Options
HV2: 30%-75% Minimum Outdoor Air
The HV2 option is required when the minimum outdoor air volume exceeds 30% of the total supply air volume. With higher outdoor air volumes, mixed air temperatures can vary greatly. Accordingly,
2-stage heating and/or cooling is recommended. Also, an airstream
override thermostat is standard with HV2 to prevent cold air discharge (below 55˚ F) when the thermostat is satisfied. (electronic modulation is optional).
HV3: 100% Return Air
The HV3 option is available when no outdoor air is needed. With relatively stable return air conditions, 1-stage
heating and/or cooling is strongly recommended. (2-stage or electronic
modulation is optional).
Basic bimetal thermostats with mercury switches or fully programmable electronic thermostats are available as part of your IGX-HV system. Match your heating, cooling, staging, and operational requirements to the appropriate thermostat.
TC1: 1-Stage Heating / Cooling
TC1 is a coiled bimetal thermostat used for single-stage heating, cooling or heating-cooling systems.
TC4: Programmable
TC4 has full seven-day program capability. The thermostat can be set for four times and eight temperature settings each day of the week. It can control up to two stages of heating and two stages
TC2: 2-Stage Heating
of cooling.
TC2 is a coiled bimetal thermostat used for 2-stage heating systems.
TC5: Deluxe Programmable
TC5 has full seven-day program capability. The thermostat can be set for two occupied and two
TC3: 2-Stage Heating / 2-Stage Cooling
TC3 is a coiled bimetal thermostat used for 2-stage heating, cooling or heating­cooling systems. It includes an adjustable heat anticipator, stops, and a locking cover.
unoccupied times with adjustable temperature settings for each day of the week. It can control up to three stages of heating and two stages of cooling. The Intelligent Fan™ feature energizes the fan continuously during occupied mode and intermittently with a call for heating or cooling in unoccupied mode.
3
MIXING BOX CONTROLS
Suppl
y
Return Ai
r
Outdoor Air
The mixing box (shown at right) includes outdoor air and return air low leakage control dampers in a face and bypass configuration. Either two inch pleated or aluminum mesh filters are available within the mixing box section. Double wall construction is optional.
A mixing box control option must be specified for every IGX-HV unit. Greenheck offers eight mixing box control options that accommodate a wide variety of applications. The four EC and four MB options are described below. Specify only one control box option per unit.
Mixing Box Controls with Economizer Cooling
The economizer controls package enables free cooling using outdoor air. All EC options include a modulating actuator for controlling outdoor and return air dampers, and a minimum outdoor air positioner. During a call for heating the economizer is locked out and the outdoor air damper holds at the minimum position.
EC1: Outdoor Temperature Reference
The economizer controller positions the mixing box dampers to achieve 55° F mixed temperature when the thermostat calls for cooling AND the outdoor air temperature is below the economizer setpoint. If outdoor air temperature is between 55° F and the economizer setpoint, the dampers will modulate to the 100% outdoor air position. Above the setpoint, the outdoor air damper is held at the minimum position. The setpoint is field adjustable and the outdoor air sensor is factory mounted.
EC3: Airstream Temperature Reference
The economizer controller compares the temperatures of the outdoor air and return air when the thermostat calls for cooling. The mixing box dampers are then
positioned to maximize the airflow of the cooler airstream. When outdoor air temperature is sufficiently cool, the mixing box dampers will modulate to provide 55° F mixed air. The outdoor air sensor is factory mounted. The return air sensors are field installed.
EC2: Outdoor Enthalpy Reference
Same as EC1, except economizer setpoint is based on outdoor air enthalpy.
EC4: Airstream Enthalpy Reference
Same as EC3, except airstream enthalpy values are compared.
Mixing Box Controls (no economizer)
In addition to the EC options described above, Greenheck offers four MB mixing box control options for applications where a factory provided economizer package is not desired.
MB1: Minimum Outdoor Air Positioner
The MB1 option includes a modulating actuator and potentiometer that control the outdoor air and return air damper positions. When the unit is energized, the dampers will travel to the position corresponding to the potentiometer setting, providing the desired amount of outdoor air. When the unit is powered off, the outdoor air damper closes to prevent backdrafting. To adjust the damper settings, simply dial the potentiometer (shown above) to desired operating position of the outdoor air damper.
MB2: 2-10 Volt External Signal
The MB2 option includes a modulating actuator that is controlled by an external 2-10 volt signal. This option is appropriate for applications that call for a building
4
automation system that will control the mixing box dampers.
MB3: 4-20 mA External Signal
The MB3 option includes a modulating actuator that is controlled by an external 4-20 mA signal. Like the MB2 option, this option is appropriate for applications that call for a building automation system that will control the mixing box dampers.
MB4: Manual Quadrant
The MB4 option consists of a manual quadrant that enables the outdoor air and return air dampers to be secured into a single position. The primary function is to introduce the specified minimum outdoor air volume during operation. Dampers remain in the same position when the unit is powered off.
Evaporative Cooling
COOLING OPTIONS
An evaporative cooling section includes a galvanized steel housing with a louvered intake, two inch aluminum mesh filters and a stainless steel evaporative cooling media housing. The evaporative cooling media is Munters CELdek or GLASdek and has a depth of 12 inches for 90% cooling effectiveness.
Drain and overflow lines are conveniently stubbed through the side of the cooling section. The supply line connection is field located where convenient.
IGX-HV airflow capacity for evaporative cooling is up to 14,000 cfm. Below 9,000 cfm, evaporative cooling modules ship attached and factory wired. Field attachment is required for airflow above 9,000 cfm.
Mixing Box Controls:
Mixing box control option EC1 is recommended for use
Cooling Coils
Model IGX-HV boasts the flexibility of Chilled Water or Direct Expansion (DX) cooling with capacity to 11,000 CFM. The cooling section includes the cooling coil, stainless steel drain pan and insulated double wall construction. Drain and coil connections are stubbed through the wall for convenience.
For proper coil sizing, use Greenheck’s Computer Aided Product Selection (CAPS) program or contact your local representative. Four and six row coils are available.
Cooling coil sections are installed downstream of the mixing box section for a draw through arrangement. This provides a streamlined transition to adjacent IGX-HV sections. DX coils require remote condensing units.
Mixing Box Controls:
All MB and EC mixing box control options are available with chilled water or DX cooling coils.
with evaporative cooling. On a call for cooling when the outdoor air temperature is below the economizer setpoint, the dampers modulate to provide cool mixed temperatures down to 55° F. When the outdoor air is above the economizer setpoint, the evaporative cooling section is energized and the dampers travel to the 100% outdoor air position.
The MB mixing box options are NOT recommended in conjunction with evaporative cooling.
For economizer climates, the EC1 option is recommended. Mixing box options operate as described on page 4.
Thermostats:
The cooling coil and MB mixing box control options may use a 1-stage (chilled water or single stage DX) or 2-stage (dual stage DX) cooling thermostat.
The cooling coil and EC mixing box control options require a 2-stage cooling thermostat. Economizer represents the first stage of cooling and a single DX stage or chilled water coil represents the second stage of cooling.
Mixing Box Selection Guide
EC Options MB Options
EC1 EC2 EC3 EC4 MB1 MB2 MB3 MB4
No Cooling Yes Yes Yes Yes Yes Yes Yes Yes
Evaporative Cooling
Chilled Water or DX Cooling
*Two-stage cooling thermostat required. Boldface type indicates factory recommended options.
Yes
Yes* Yes* Yes* Yes* Yes Yes Yes Yes
Yes
Not
Recommended
Not
Recommended
No No No No
5
AIR PERFORMANCE
Housing Size 12
MODEL CFM
800
IGX-HV-108
IGX-HV-109
IGX-HV-110
1,000
1,200
1,500
2,000
2,500
2,000
2,500
3,000
Housing Size 22
MODEL CFM
2,600
IGX-HV-112
IGX-HV-115
3,500
4,400
5,000
6,000
7,000
TOTAL STATIC PRESSURE in inches of WG
0.50 0.75 1.00 1.25 1.50 1.75
RPM 993 1109 1216 1311 1399 BHP .21 .26 .31 .35 .40 RPM 1112 1228 1325 1415 1500 1579 BHP .34 .41 .47 .53 .59 .65 RPM 1238 1347 1445 1530 BHP .51 .59 .68 .75 RPM 880 1014 1140 1255 1361 1460 BHP .36 .45 .54 .63 .73 .84 RPM 1004 1113 1219 1321 1417 1510 BHP .65 .77 .90 1.0 1.1 1.3 RPM 1154 1244 1329 1419 1503 1587 BHP 1.1 1.2 1.4 1.6 1.7 1.9 RPM 805 912 1013 1110 1199 BHP .48 .59 .71 .84 .96 RPM 906 995 1082 1166 1247 1325 BPH .79 .93 1.07 1.21 1.36 1.51 RPM 1014 1097 1172 1244 1315 1386 BHP 1.22 1.39 1.55 1.72 1.88 2.05
TOTAL STATIC PRESSURE in inches of WG
0.50 0.75 1.00 1.25 1.50 1.75
RPM 662 761 853 934 1009 BHP .58 .72 .86 1.0 1.2 RPM 756 839 920 993 1065 1133 BHP 1.0 1.3 1.5 1.7 1.9 2.1 RPM 871 939 1006 1073 1137 1197 BHP 1.8 2.1 2.4 2.6 2.9 3.1 RPM 671 741 808 871 931 986 BHP 1.7 2.0 2.3 2.6 2.9 3.2 RPM 749 812 870 929 982 1035 BHP 2.6 2.9 3.3 3.7 4.0 4.4 RPM 833 889 943 994 1044 1093 BHP 3.7 4.2 4.6 5.0 5.5 5.9
Maximum
Furnace Size
(Input MBH)
100
150
150
200
250
250
250
250
250
Maximum
Furnace Size
(Input MBH)
350
500
600
600
600
600
Housing Size 32
MODEL CFM
TOTAL STATIC PRESSURE in inches of WG
0.50 0.75 1.00 1.25 1.50 1.75
RPM 566 627 685 738 790 839 BHP 2.1 2.5 2.8 3.2 3.6 4.0 RPM 636 690 740 790 836 880 BHP 3.3 3.8 4.2 4.7 5.1 5.6 RPM 712 759 805 849 891 933 BHP 5.0 5.5 6.1 6.6 7.1 7.7 RPM 542 590 634 678 723 765 BHP 3.6 4.0 4.5 5.0 5.6 6.1 RPM 633 672 711 748 784 820 BHP 6.3 6.9 7.5 8.1 8.7 9.3 RPM 731 763 795 829 861 892 BHP 10.2 10.9 11.6 12.3 13.1 13.8
IGX-HV-118
IGX-HV-120
7,000
8,500
10,000
10,000
12,500
15,000
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers and furnaces. For exact air performance data based on specific unit configuration, use the Greenheck CAPS selection program.
6
Maximum
Furnace Size
(Input MBH)
1,050
1,200
1,200
1,200
1,200
1,200
ACCESSORIES
Air Filter Gauge
Indicates when filters become dirty. An indicator light may be wall/beam mounted or provided with a remote control panel.
Motorized Dampers
Discharge dampers are available to prevent backdrafts when the fan is not in operation. Mixing box dampers are factory mounted and wired.
Fan Spring Vibration Isolation
Spring vibration isolators are available in lieu of neoprene isolators for housing sizes H22 and H32 (fan sizes 112 and larger).
115 Volt Service Receptacle
A 115 volt GFCI outlet is mounted externally in a NEMA 3R box for the convenience of field service personnel. A separate 115 volt power source is required.
Roof Curbs
Factory provided roof curbs are available to ensure compatibility between make-up air unit and roof curb. Standard construction is
galvanized steel.
G90
Propane Gas Conversion Kit
Greenheck’s indirect gas furnaces are ETL listed for both Natural Gas or LP.
Duct Adapter
Duct adapters are optional with factory supplied curbs and provide an easy method for attaching ductwork to the curb.
Double Wall Construction
An interior metal liner is available to isolate insulation from the airstream. One-inch thick insulation is included with this option.
Gas Pressure Regulator
Required if building gas line pressure exceeds IGX-HV maximum inlet gas pressure of 14 in. wg.
Smoke Detector
A 12/24 VDC Photoelectric smoke detector is available for duct mounting. Typical operating temperature range is 32°F to 131°F (0°C to 55°C).
Discharge Diffuser
Available as either 3-way diffuser for horizontal discharge or 4-way diffuser for downblast
discharge.
Special Coatings
Greenheck’s Permatector powder paint is available if a painted look is desired and recommended for outdoor installations near salt water shorelines. Decorative baked enamel paints are also available in a variety of colors to match existing building fixtures. Consult your Greenheck representative for paint selections.
Weatherhood
A galvanized steel mist eliminating intake hood is standard on outdoor IGX-HV models. The mist eliminating intake hood provides a double layer of protection against moisture entering the mixing box section.
3-Way Diffuser
Airstream Override
This option prevents the discharge air temperature from dropping below 55°F after the call for heating has ended.
Warm-Up Control
Available with the TC5 thermostat. The thermostat may be programmed to provide a warm-up cycle prior to the occupied start time. This ensures immediate comfort and proper air quality as people enter the occupied areas.
7
Specifications
General: Heating and Ventilating unit shall be as
manufactured by Greenheck or approved equal provided all specifications are met. Greenheck Model IGX-HV is used as the basis of design. Performance shall be as scheduled on plans.
Furnace: Indirect gas fired furnace shall be 80% efficient,
ETL Listed and have a blow through fan design. Furnace shall be capable of operation with Natural or LP gas and have a power venting system with post purge cycle. The heat exchanger shall be constructed of aluminized steel or stainless steel. Standard furnace features shall include main gas pressure regulator, main gas valve, electronic staged controls, direct spark ignition system, high limit and a 24 volt control transformer. Furnace shall be insulated and have double wall construction.
Temperature Control: Heating and cooling output shall
be controlled by a room thermostat to maintain desired room temperature. Economizer control shall provide the first stage of cooling, where specified. Furnaces shall provide one or two stages of heat output control.
Unit Casing and Frames: All frames and panels shall
be G90 galvanized steel. Where top panels are joined there shall be a standing seam to insure positive weather protection. All metal-to-metal surfaces exposed to the weather shall be sealed, requiring no caulking at job site. All components shall be easily accessible through removable doors.
Insulation: Models provided with a mixing box shall be
insulated from the return section through to the supply discharge. Insulation shall be in accordance with NFPA 90A and tested to meet UL 181 erosion requirements. Double wall shall be provided if specified.
Fan Section: Centrifugal fans shall be double width,
double inlet. Fan and motor shall be mounted on a common base and shall be internally isolated. All blower wheels shall be statically and dynamically balanced. Ground and polished steel fan shafts shall be mounted in permanently lubricated ball bearings (up to size 118) or ball bearing pillow blocks (size 120 and larger). Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged speeds.
Motors and Drives: Motors shall be energy efficient,
complying with EPACT standards, for single speed ODP and TE enclosures. Motors shall be permanently lubricated, heavy duty type, matched to the fan load and furnished at the specified voltage, phase and enclosure. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be cast and have machined surfaces, 10 horsepower and less shall be supplied with an adjustable drive pulley.
Electrical: All internal electrical
components shall be prewired for single point power connection. All electrical components shall be UL listed, recognized or classified where applicable and wired in compliance with the National Electrical Code. Control center shall include motor starter, control circuit fusing, control transformer for 24 VAC circuit, integral disconnect switch with separate motor fusing and terminal strip. Contactors, Class 20 adjustable overload protection and single phase protection shall be standard.
Filter Section: Filters shall be
mounted in a V-bank arrangement such that velocities across the filters do not exceed 550 feet per minute. Filters shall be easily accessible through a removable access panel.
Weatherhood: Weatherhood shall be mist eliminating
type, constructed of G90 galvanized steel. The weatherhood shall contain drainable blade louvers, backed by mist eliminating filters to prevent moisture intake.
Mixing Box: Mixing box shall contain outside air and
return air dampers with low leak, pressure activated, extruded vinyl blade seals, aluminum jamb seals, Belimo actuator and 30% efficient pleated filters in a V-bank arrangement. The mixing box shall modulate the amount of outdoor and return air by use of dampers. Input signal for return damper shall be from potentiometer, 2-10 volt signal, 4-20 mA signal or manual quadrant controller.
Evaporative Cooling Section: Evaporative cooling
section shall include a galvanized steel housing with louvered intake, two inch aluminum mesh filters and a stainless steel evaporative cooling module all provided by the make-up air unit manufacturer. The louver shall be stationary type with drainable blades, designed to withstand wind loads of 25 PSF and bear the AMCA seal. Evaporative cooling media shall be Munters CELdek with a depth of 12 inches for a cooling effectiveness of 90%. Drain and overflow connections shall be piped through the side of the evaporative cooling section.
Cooling Coil: Direct expansion (DX) or chilled water
coil shall be factory tested and rated in accordance with ARI 410. Coils shall have copper tubes with permanently expanded aluminum fins, 12 fpi or less. DX coils shall be equipped with distributors to receive expansion valves at the liquid connections. Drain pans shall extend at least 12 inches downstream of coil and be sloped to drain connection.
Copyright © 2008 Greenheck Fan Corp. • IGX-HV Rev. 2 October 2008 SN
Loading...