IGX Typical Specification
General: Make-up air unit shall be as manufactured by
Greenheck or approved equal provided all
specifications are
met. Greenheck Model IGX is used as
the basis of design. Performance shall be as scheduled
on plans.
Furnace: Indirect fired gas furnace shall be 80% efficient,
ETL Listed and have a blow through fan design. Furnace
shall be capable of operation with natural or LP gas and
have a power venting system. The heat exchanger shall be
constructed of aluminized steel or stainless steel. Standard
furnace features shall include main gas pressure regulator,
main gas valve, electronic staged or electronic modulating
controls, direct spark ignition system, high limit and a 24
volt control transformer. Furnace shall be insulated and have
double wall construction.
Temperature Control: Furnace heat output shall be
controlled based on a field adjustable discharge
temperature set point. Discharge temperature sensor shall
be factory mounted and wired to the unit control center.
Furnace(s) shall have electronic modulation or at least 2
stages of control.
Unit Casing and Frames: Unit shall be of internal frame
type construction of galvanized steel. All frames and panels
shall be G90 galvanized steel. Where top panels are joined
there shall be a standing seam to insure positive weather
protection. All metal-to-metal surfaces exposed to the
weather shall be sealed, requiring no caulking at job site. All
components shall be easily accessible through removable
doors.
Insulation: Models provided with a mixing box shall be
insulated from the return section through to the supply
discharge. Insulation shall be in accordance with NFPA 90A
and tested to meet UL 181 erosion requirements. Double
wall shall be provided if specified.
Fan Section: Centrifugal fans shall be double width,
double inlet. Fan and motor shall be mounted on a common
base and shall be internally isolated. All blower wheels shall
be statically and dynamically balanced. Ground and
polished steel fan shafts shall be mounted in permanently
lubricated ball bearings (up to size 118) or ball bearing
pillow blocks (size 120). Bearings shall be selected for a
minimum (L10) life in excess of 100,000 hours at maximum
cataloged speeds.
Motors and Drives: Motors shall be energy efficient,
complying with EPACT standards, for single speed ODP and
TE enclosures. Motors shall be permanently lubricated,
heavy duty type, matched to the fan load and furnished at
the specified voltage, phase and enclosure. Drives shall be
sized for a minimum of 150% of driven horsepower. Pulleys
shall be cast and have machined surfaces, 10 horse power
and less shall be supplied with an adjustable drive pulley.
Electrical: All internal electrical components shall be
prewired for single point power connection. All electrical
components shall be UL listed, recognized or classified
where applicable and wired in compliance with the National
Electrical Code. Control center shall include motor starter,
control circuit short circuit protection, control transformer
for 24 VAC circuit, integral disconnect switch and terminal
strip. Contactors, Class 20 adjustable overload protection
and single phase protection shall be standard.
Filter Section: Filters shall be mounted in a V-bank
arrangement such that velocities across the filters do not
exceed 550 feet per minute. Filters shall be easily accessible
through a removable access panel.
Weatherhood: Weatherhood shall be constructed of G90
galvanized steel with birdscreen mounted at the intake.
Mixing
Box
(Night
Setback): Mixing box
shall provide 100% make-up air
during occupied hours and 100% recirculation air during
unoccupied hours. Furnace(s) shall be multi-stage and
operate based on discharge temperature control on
occupied setting and space temperature control on
unoccupied setting. The system shall allow for separate field
adjustable temperature set points for occupied and
unoccupied modes of operation.
Mixing Box (2-Position): Damper shall be either fully open
or fully closed. Damper position shall be controlled by a
remotely mounted switch. Mixing box shall provide 100%
make-up air when the damper is closed and recirculate
100% return air when the damper is open.
Mixing Box (Building Pressure): Mixing box shall
modulate outdoor and return air volumes to maintain
desired building pressure. A remote control panel shall be
provided by the make-up air unit manufacturer and include a
photohelic gauge. Furnace(s) shall multi-stage and operate
based on discharge temperature control.
Mixing Box (Potentiometer): Mixing box shall enable
manual modulation of outdoor air and return air volumes
from a remote potentiometer. The potentiometer shall be
mounted on a control panel provided by the make-up air
unit manufacturer. Furnace(s) shall multi-stage and operate
based on discharge temperature control.
Mixing Box (Building Pressure): Mixing box shall
modulate outdoor and return air volumes to maintain
desired building pressure. A remote control panel shall be
provided by the make-up air unit manufacturer and include a
photohelic gauge. Furnace shall be multi-stage or
modulating and operate based on discharge temp control.
Mixing Box (External Signal): Mixing box shall enable
modulation of outdoor and return air volumes from external
signal 4-20 mA or 0-10 VDC signal supplied by others.
Damper actuator control will be factory wired to terminal
block in unit control center to receive modulation signal field
wired to unit by others for easy BMS/DDC interface.
Cooling Coil: Direct expansion (DX) or chilled water coil
shall be factory tested and rated in accordance with ARI
410. Coils shall have copper tubes with permanently
expanded aluminum fins, 12 fpi or less. DX coils shall be
equipped with distributors to receive expansion valves at
the liquid connections. Drain pans shall extend at least 12
inches downstream of coil and sloped to drain connection.
Evaporative Cooling Section: Evaporative cooling section
shall include a galvanized steel housing with louvered intake,
2 inch aluminum mesh filters and a stainless steel
evaporative cooling module all provided by the make-up air
unit manufacturer. Evaporative cooling media shall be
cellulose or fiberglass with a depth of 12 inches for a cooling
effectiveness of 90%. Drain and overflow connections shall
be piped through the side of the evaporative cooling section.