Greenheck ERV-10 Installation Manual

Energy Recovery Ventilators
®
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Models:
ERV-10 ERV-20 ERV-45 ERV-55 ERV-90 ERV-120
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to the unit while it is running.
®
Energy Recovery Ventilator
1
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
®
506 (Ashland Inc.) or
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle each piece in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
Inspection and Maintenance during Storage
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate all moving components by hand ten to fifteen revolutions to distribute lubricant on motor and bearings. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Energy Recovery Ventilator
2
Table of Contents
Product Overview
Product Overview . . . . . . . . . . . . . 3
Supplemental Installation, Operation and
Maintenance Manuals . . . . . . . . . . . 3
Optional Subassemblies . . . . . . . . . . 3
Installation
Dimensional Data . . . . . . . . . . . . 4-5
Recommended Roof Openings & Weights . . . 6
Service Clearances . . . . . . . . . . . . 7
Access Panel Locations . . . . . . . . . 8-9
Handling . . . . . . . . . . . . . . . . . 9
Lifting . . . . . . . . . . . . . . . . . . 9
Roof Curb Mounting . . . . . . . . . . . . 10
Curb Outside Dimensions and Weights . . . . 10
Ductwork Connections . . . . . . . . . . . 10
Rail Mounting / Layout . . . . . . . . . . . 11
Outdoor Air Weatherhood . . . . . . . . . . 11
Exhaust Weatherhood . . . . . . . . . . . 11
Dampers. . . . . . . . . . . . . . . . . 11
Electrical Information
General Electrical Information . . . . . . . . 12
Control Center Components . . . . . . . . . 13
Optional Accessory Wiring Schematics . . . . 14
Unit Overview . . . . . . . . . . . . . . . 15
Optional Component Overview
Economizer . . . . . . . . . . . . . . . 15
Frost Control . . . . . . . . . . . . . . . 16
Variable Frequency Drive . . . . . . . . . . 16
CO
Sensor . . . . . . . . . . . . . . . 16
2
Rotation Sensor . . . . . . . . . . . . . . 16
Dirty Filter Switch . . . . . . . . . . . . . 16
Service Outlet . . . . . . . . . . . . . . 16
Start-Up
General . . . . . . . . . . . . . . . . . 17
Pre Start-Up Checklist . . . . . . . . . . . 17
Special Tools Required . . . . . . . . . . . 17
Start-Up Checklist. . . . . . . . . . . . . 17
Optional Accessories Checklists . . . . . . . 18
Start-Up Components
Fans . . . . . . . . . . . . . . . . . . 19
Vibration . . . . . . . . . . . . . . . . . 20
Energy Recovery Wheel . . . . . . . . . . 20
Drive Belt . . . . . . . . . . . . . . . . 20
Air Seals . . . . . . . . . . . . . . . . . 20
Optional Start-Up Components
Dirty Filter Switch . . . . . . . . . . . . . 20
Economizer . . . . . . . . . . . . . . . 21
Frost Control . . . . . . . . . . . . . . . 22
Variable Frequency Drives . . . . . . . .22-24
Routine Maintenance. . . . . . . . . . 25-28
Troubleshooting
Economizer Alarms . . . . . . . . . . . . 28
Airflow. . . . . . . . . . . . . . . . . . 29
Unit . . . . . . . . . . . . . . . . . 30-31
Maintenance Log . . . . . . . . . Backcover
Our Commitment . . . . . . . . . Backcover
The ERV brings in fresh, outdoor air and removes stale, exhaust air. Prior to discharging the exhaust air, the energy recovery wheel transfers energy from the exhaust air to the outdoor air at an efficiency of 70-80%. Simply put, this unit preconditions the outdoor air to save money on heating and cooling costs.
Supplemental IOMs
Refer to the following Installation, Operation and Maintenance (IOM) Manuals for additional details:
• ERV-90 and ERV-120 Curbs
• ERV Exhaust Weatherhood
Optional Subassemblies
Electric Heater Application/Operation
Factory installed electric heaters can be provided for preheat frost control. An electric preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. Electric heaters are available in 208, 230, or 460 VAC (refer to heater nameplate for voltage).
Preheaters: Preheaters are standard as single-stage on/off control. Preheaters are single point wired at the factory. A thermodisc temperature sensor (with a 5°F set point) is mounted in the outdoor airstream after the preheater to turn the preheater on. See Frost Control Application/Operation for typical set points. If the temperature falls below the set point and the wheel pressure drop sensor is triggered, the preheater will turn on.
Access to the preheater control panel is through the outdoor air filter door.
Energy Recovery Ventilator
3
Installation
g
a
Dimensional Data
ERV-10, 20, 45 and 55
Unit Size
ERV-10 46 34 27 10 16 6
ERV-20 62 51 34 18 18 8
ERV-45 67 67 44 24 24 10
Exterior Dimensions Unit Opening Dimensions
ABCFGKLQP
3
4 71016
3
8 111⁄2 19 18
3
4 131⁄2 26 26
ERV-55 75 70 67 22 27 16 18
All dimensions are in inches.
Outdoor Air Discharge
LxK
Exhaust Air Intake
FxG
Outdoor Air Intake
Q x P
C
3
4 28 48
Outdoor Air Discharge
LxK
B
C
A
A
Exhaust Air Discharge
Outdoor Air Discharge
LxK
B
C
FxG
B
Exhaust Air Intake
FxG
Exhaust Air Discharge
Arrangement A Arrangement B
Outdoor Air Discharge
LxK
Exhaust Air Discharge
A
C
Outdoor Air IntakeExhaust Air Intake
Exhaust Air Intake
B
FxG
Outdoor Air Int
A
Outdoor Air Intake
Energy Recovery Ventilator
4
Arrangement C Arrangement D
Installation
Dimensional Data
ERV-90 and 120
Unit Size
ABCDEFGK LQP
ERV-90L 124 84 64 16 19 48 25 16 18
Exterior Dimensions Unit Opening Dimensions
5
8 60 25
ERV-90H 124 84 64 16 19 48 25 19 22 60 25
ERV-120H 146 97 77 17
1
2 263⁄4 60 28 23 25 70 30
All dimensions are in inches.
Outdoor Air Discharge
L x K
E
A
Exhaust
Hood
Outdoor Air Inlet
Q x P
C
Exhaust Air Discharge
L x K
Outdoor Air Discharge
L x K
Exhaust Air Inlet
F x G
C
B
A
Intake
Hood
Exhaust Air Inlet
H x J
D
B
C
Intake Hood
Arrangement A Arrangement B
Exhaust Air Inlet
H x J
D
B
Outdoor Air Discharge
L x K
E
A
Exhaust
Hood
C
Intake Hood
D
B
Arrangement C Arrangement D
Outdoor Air Discharge
L x K
Exhaust Air Inlet
E
A
Exhaust
Hood
F x G
Energy Recovery Ventilator
5
Recommended Roof Openings & Weights
Position the unit roof opening such that the supply discharge and exhaust inlet of the unit will line up with the corresponding ductwork. Be sure to allow for the recommended service clearances when positioning opening (see Service Clearances). Do not face the outdoor air intake of the unit into prevailing wind and keep the intake away from any other exhaust fans. Likewise, position the exhaust discharge opening away from outdoor air intakes of any other equipment.
When cutting only duct openings, cut opening 1 inch (25 mm) larger than duct size to allow clearance for installation. Area enclosed by roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R” value of at least 5. If area within curb is open, higher radiated sound levels may result.
Where the supply or warm air duct passes thru a combustible roof, a clearance of one inch must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A.
EXHAUST
INLET
ERV-90 and 120
V
EXHAUST
INTAKE
SUPPLY
DISCHARGE
0.50
U
V
SUPPLY
DISCHARGE
U
0.50
ERV-10, 20, 45 and 55
Unit Size U V
Approx.
Weight (lbs.)
ERV-10 26.5 20 340
ERV-20 43 26 860
ERV-45 58 35 1290
ERV-55 60 30 1470
ERV-90 62 36 3230
ERV-120 77 38 3700
All dimensions are in inches. *Weight assumes outdoor unit with filters, weatherhoods and outdoor air intake damper.
Energy Recovery Ventilator
6
Service Clearances
ERV-10, 20, 45 and 55 units require minimum clearances to perform routine maintenance, such as filter replacement, energy wheel cassette inspection, and fan belt adjustment. Blower and motor assemblies, energy recovery wheel cassette and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances, refer to
drawings below for these dimensions.
ERV-10, ERV-20, ERV-45, ERV-55 ERV-90, ERV-120
Access Panels
T
Exhaust
Side
Outdoor
Air Side
R
Cassette slides out*
S
*ERV-10, 20, and 45 only.
Arrangement A
Recommended Service Clearances
Unit Size R S T X
ERV-10 32 30 42
ERV-20
ERV-45
ERV-55
(30 for maintenance)
(39 for maintenance)
(32 for maintenance)
44
60
65
ERV-90 42
ERV-120 42
All dimensions are in inches.
30 42
40 42
40 42
Access Panels
X
Access PanelAccess Panel
Cassette
X
Access PanelAccess Panel
X
Cassette
Access Panel
X
Access Panel
X
Arrangement A
X
Cassette
Access PanelAccess Panel
X
Cassette
Supply Weatherhood
Arrangement B, C or D
Energy Recovery Ventilator
Access Panel
Exhaust Weatherhood
X
7
Access Panel Locations
g
ERV-10, ERV-20, ERV-45, ERV-55 ERV-90
Outdoor Air
Discharge
Exhaust Air
Inlet
3
1
2
Interior
3
Outdoor Air
Discharge
5
2
6
Exhaust Air
Inlet
3
4
Arrangement A
1
3
Exhaust Air
Dischar
e
Arrangement B, C or D
Exhaust Air
Discharge
4
Outdoor Ai
2
Intake
Outdoor Air
Intake
Outdoor Air Inlet
Exhaust Air Discharge
Rooftop
3
4
1
Arrangement A
5
2
6
4
Intake Hood
1
Exhaust Hood
Arrangement B, C or D
3
1
Outdoor air blower and motor
Energy wheel cassette
Energy wheel cassette
Internal filters
2
Outdoor air intake damper
Frost control
Outdoor air sensors
Main disconnect
3
Electrical control center
Internal filters
4
Energy Recovery Ventilator
8
Exhaust air blower and motor
1
2
Exhaust blower and motor
Electric control center
Main Disconnect
Energy wheel cassette
3
Internal filters
Frost control
Outdoor air sensors
4
5
6
Preheater controls
Outdoor air intake damper
Supply blower and motor
Exhaust air intake damper
Access Panel Locations continued
ERV-120
Outdoor Air
Discharge
2
3
Exhaust Air
Intake
3
Handling
While this unit was constructed with quality and dependability in mind, damage still may occur during handling of the unit for installation. Exercise extreme caution to prevent any damage from occurring to the refrigerant system.
The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook. Adequate space should be left around the unit for filter replacement and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.
Outdoor Air Intake
Exhaust Air Discharge
3
4
1
Arrangement A
2
4
Outdoor
Weatherhood
Arrangement B, C or D
Exhaust Hood
Lifting
WARNING
All factory provided lifting lugs must be used when lifting the unit. Failure to comply with this safety precaution could result in property damage, serious injury or death.
1. Before lifting, be sure that all shipping material has been removed from unit.
2. To assist in determining rigging requirements, weights are shown below.
3. Unit must be lifted by all lifting lugs provided on
3
1
base structure.
4. Rigger to use suitable mating hardware to attach to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent damage to the cabinet by the lift cables.
1
2
3
4
Exhaust blower and motor
Electric control center
Main disconnect
Supply blower and motor
Exhaust air intake damper
Energy wheel cassette
Internal filters
Frost control
Outdoor air sensor
Preheater controls
Outdoor air intake damper
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by others) has been applied to the curb prior to lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
Energy Recovery Ventilator
9
Roof Curb Mounting
R
o
t
a
t
i
o
n
POOR
Roof curb details including duct location dimensions, are available on ERV-90 & 120 Roof Curb Assembly Instructions.
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory Supplied Roof Curbs: Roof curbs are Model GPI or GPNS for the ERV-10, 20, 45, 55. The GPI or GPNS ships assembled and includes a duct adapter.
Roof curbs are Model GKD for the ERV-90 and
120. The GKD ships in a knockdown kit (includes duct adapter) and requires field assembly (by others). Assembly instructions are included with the GKD curbs.
2. Install Curb: Locate curb over roof opening and fasten in place. (Refer to Recommended Roof Openings). Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper unit operation, it is important that the installation be level. Shim as required to level.
3. Install Ductwork: Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.
Curb Outside Dimensions and Weights
Side of Unit
B
C
D
Roof Curb
E
Base
A
1-inch Insulation
Curb Cap Details for Factory Supplied Roof Curbs
Unit Size A
BCDE
ERV-10 1.75 2.00 1.00 1.125 0.750
ERV-20 1.75 2.00 1.00 1.200 0.875
ERV-45 1.75 2.00 1.00 0.813 0.875
ERV-55 1.75 2.00 1.00 0.813 0.750
ERV-90 1.813 4.00 1.75 1.000 0.750
ERV-120 1.938 4.125 1.938 1.125 0.625
All dimensions are in inches.
Ductwork Connections
Examples of poor and good fan-to-duct connections are shown. Airflow out of the fan should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result in low airflow and other system effects.
n
o
i
t
a
t
o
R
Length of Straight Duct
W
L
ERV-90 and 120
Unit Size L W Curb Weight (lbs.)
ERV-10 42.5 30.5 60
ERV-20 58.5 47.5 115
ERV-45 63.5 63.5 160
ERV-55 71.8 66 185
ERV-90 120.5 80.5 520
ERV-120 142.25 93 700
All dimensions are in inches. Weights are for 12-inch high GPI type curbs.
Energy Recovery Ventilator
10
GOOD
Recommended Discharge Duct Size and Length
Model Blower Size Duct Size Straight Duct Length
ERV-10 10 9 x 9 36
ERV-20 10 14 x 14 36
ERV-45 12 20 x 20 36
ERV-55 15 28 x 28 60
ERV-90L 15 28 x 28 60
ERV-90H 18 32 x 32 60
ERV-120 20 34 x 34 72
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.
• Straight duct lengths were calculated based on 100% effective duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
Loading...
+ 22 hidden pages