Greenheck ERT User Manual

REMOTE PANELS
Two Position
• Unit On/Off: Controls start and stop of the entire unit.
Three Position
• Hand/Off/Automatic: Three way switch operates as an override to allow the unit to be turned on, off, or operated automatically by the building controls.
Time Delay Override
The time delay override is used in conjunction with the 7-day time clock. This option allows the operator to override the 7-day time clock when it has turned the ERV off. The override period is manually set for up to two hours.
Greenheck remote panels offer a convenient and attractive option for controlling and monitoring energy recovery ventilators. A variety of indicator lights, switches and time devices are available to be mounted to a stainless steel face plate.
Field wiring is only required from the remote panel to a low voltage terminal strip in the control center of the energy recovery ventilator. A junction box is included with the remote panel.
Two of the many remote panel configurations are shown. Customize your remote panel with the options listed below.
Lights
• Dirty Supply Filter
• Dirty Exhaust Filter
• Unit On/Off
• Economizer *: Indicates when “free cooling” conditions are present.
• Rotation Sensor: Indicates when the energy wheel is not rotating.
• Frost Control **: Indicates when frost control is activated.
Switches
Time Devices
7-Day Time Clock
A programmable digital 7-day time clock automates start/stop control of the energy recovery ventilators. It is easily programmed to energize the ERV when the space is occupied and shut down the unit when the space is unoccupied.
* Refer to the ERV catalog for details on the outdoor air sensors to be used in conjunction with the economizer indicator light. An enthalpy sensor or temperature sensor must be selected with the economizer indicator light.
** Consult the ERV catalog for details on preheat, timed exhaust, and modulating frost control options.
Ventilation Control Options
Greenheck offers two methods of controlling the ventilation rates. Each method controls outdoor air and exhaust air fans simultaneously.
• Set Point Control
The CO2sensor controls high and low speeds (1/2 or 1/3 reduction) via inputs to factory installed and programmed variable frequency drive (VFD). When the CO2levels in the space are below the field adjustable set point, the VFDs will switch to low speed. When the CO2levels in the space are above the set point, the VFDs will switch to high speed.
• Proportional Control
Using a 0-10V signal, the CO2sensor modulates VFDs that continuously vary the speed of the supply and exhaust fans. Outdoor air volumes are controlled to maintain CO2levels within the desired range.
Demand Control Ventilation
Demand control ventilation practices may be desirable for applications with widely varying outdoor air requirements such as, auditoriums, theaters and gymnasiums. The ventilation system must be sized for the maximum occupancy, however, there may be a considerable number of operating hours when less outdoor air is required.
In these cases, the Greenheck demand control ventilation option is a simple, reliable and cost effective solution that helps reduce energy bills and provides a better indoor climate.
CO2 Sensor
The heart of the demand control ventilation system is a CO2sensor which monitors the carbon dioxide levels in the building. The sensor may be factory installed in the exhaust air stream or shipped loose for field mounting in the occupied space.
The sensor displays the CO2 content in parts per million. The CO2setpoint is field adjustable.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
DEMAND CONTROL
Greenheck P.O.Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Copyright © 2005 Greenheck Fan Corp. • Remote Control Panels RG Rev. 3 May 2005
Model APEX
The Model APEX is designed for energy recovery applications requiring up to 20,000 cfm. Supplemental heating and cooling is available.