Ventilation Control Options
Greenheck offers two methods of controlling the
ventilation rates. Each method controls outdoor
air and exhaust air fans simultaneously.
• Set Point Control
The CO2sensor controls high and low speeds
(1/2 or 1/3 reduction) via inputs to factory
installed and programmed variable frequency
drive (VFD). When the CO2levels in the space are
below the field adjustable set point, the VFDs will
switch to low speed. When the CO2levels in the
space are above the set point, the VFDs will
switch to high speed.
• Proportional Control
Using a 0-10V signal, the CO2sensor modulates
VFDs that continuously vary the speed of the
supply and exhaust fans. Outdoor air volumes are
controlled to maintain CO2levels within the
desired range.
Demand Control Ventilation
Demand control ventilation practices may be desirable for applications with widely varying outdoor air
requirements such as, auditoriums, theaters and gymnasiums. The ventilation system must be sized for the
maximum occupancy, however, there may be a considerable number of operating hours when less outdoor air
is required.
In these cases, the Greenheck demand control ventilation option is a simple, reliable and cost effective
solution that helps reduce energy bills and provides a better indoor climate.
CO2 Sensor
The heart of the demand
control ventilation
system is a CO2sensor
which monitors the
carbon dioxide levels in
the building. The sensor
may be factory installed
in the exhaust air stream
or shipped loose for field
mounting in the
occupied space.
The sensor displays the
CO2 content in parts per
million. The CO2setpoint
is field adjustable.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
DEMAND CONTROL
Greenheck P.O.Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Copyright © 2005 Greenheck Fan Corp. • Remote Control Panels RG Rev. 3 May 2005
Model APEX
The Model APEX is designed
for energy recovery
applications requiring up to
20,000 cfm. Supplemental
heating and cooling is
available.
MiniVent
The MiniVent energy recovery
ventilator is designed for
applications requiring 300-750
cfm. The unit is designed for
floor mount, wall mount or
hanging from the ceiling.
Model ERT
Combines the benefits of
the energy wheel and a
wrap around heatpipe with
supplemental heating and
cooling
.
Additional Energy Recovery Products offered by Greenheck