Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards,
including environmental. Other considerations may be
required if high winds or seismic activity are present.
If more information is needed, contact a licensed
professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CE) in Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affect motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Verify that the power source is compatible with the
equipment.
6. Never open access doors to the unit while it is
running.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
Upon receiving the product, check to ensure all items
are accounted for by referencing the delivery receipt or
packing list. Inspect each crate or carton for shipping
damage before accepting delivery. Alert the carrier
of any damage detected. The customer will make
a notation of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading which
is countersigned by the delivering carrier. If damaged,
immediately contact your Greenheck Representative.
Any physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C)
and 110°F (43°C) (wide temperature swings may
cause condensation and “sweating” of metal parts).
All accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all unit parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl
hard to reach internal surfaces or for occasional use,
consider using Tectyl
or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
®
511M Rust Preventive or WD-40®
Energy Recovery Ventilator with Tempering
3
Page 4
Product Overview
The model ERT combines the benefits of energy
recovery, wrap-around heat pipe, cooling coil and
optional heating sources. Heating sources include
electric, hot water. Cooling sources include split direct
expansion and chilled water. This product is specifically
designed to process 100% outdoor air to desired
supply conditions. Three housing sizes provide airflow
capacities from 2,000 to 10,000 cfm with external static
pressures up to 1.75 in. wg.
Optional Subassemblies
Dampers
There are four locations where dampers can be
installed. Low leakage or insulated low leakage
motorized dampers can be added in the outdoor
airstream and/or return airstream. An unoccupied
recirculating air damper is also available. A backdraft
damper is standard in the exhaust hood.
BACKDRAFT
EXHAUST DAMPER
TWO-INCH THICK MERV 8
PLEATED FILTERS
MOTORIZED RETURN
COIL
HEATPIPE
AIR DAMPER
INTAKE DAMPER
COIL
HEATING
CONTROL
CENTER
RETURN AIR
PERMANENT
ALUMINUM
MESH FILTERS
OUTDOOR AIR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
DAMPER
WHEEL CASSETTE
SUPPLY FILTERS
EXHAUST FILTERS
HEATPIPE
COOLING
Split DX
The unit is equipped with an evaporator coil that
will be connected to a separate condensing unit
(provided by others). Depending on controlling options,
the condensing unit will be controlled by others or
an integral unit microprocessor controller. Piping
components such as thermostatic expansion valve, filter
drier, sight glass, etc., shall be field-provided.
Electric Post-Heaters
The optional post-heater is used as a heat source for
the building and is integrated into the supply airstream.
A temperature sensor (with a field-adjustable set point)
is mounted in the supply airstream after the post-heater
to turn the post-heater on. A SCR heater allows for
an infinite amount of modulating control of the heat to
provide an accurate discharge temperature during the
call for heat.
As standard, the post-heater control panel is not single
point wired to the unit control center. Separate power
must be supplied to the post-heater disconnect (located
in unit control center). Electric heaters are available in
208, 230, 460, or 575 VAC (refer to heater nameplate for
voltage).
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory-mounted.
Exhaust Air Weatherhood
The exhaust weatherhood is shipped separately as a
kit with its own instructions. Backdraft dampers are
always included as an integral part of the exhaust hood
assemblies.
MOTORIZED RECIRCULATING
MOTORIZED OUTDOOR
AIR DAMPER
TWO-INCH THICK MERV 8 OR MERV
AIR DAMPER
8 AND 13 PLEATED FILTERS
Filters
There is the option of either two-inch thick MERV 8
or MERV 8 and 13 pre-filters in the outdoor airstream
and MERV 8 filters in the exhaust airstream. There are
also permanent washable aluminum mesh filters in the
optional weatherhood.
Hot Water / Chilled Water Coils
Water coils can be used for a single purpose such
as heating or cooling, or their function can be
alternated between heating and cooling by changing
the temperature of the water flowing through the coil.
Depending on the application, it may be necessary to
use a glycol mixture to prevent the liquid from freezing.
The water coils are engineered to operate at pressures
up to 250 PSIG and temperatures up to 300°F, but
ancillary equipment such as valves and pumps will often
dictate lower operating temperatures. All water coils
are pressure tested at the factory with 450 PSIG of dry
nitrogen.
Energy Recovery Ventilator with Tempering
4
Page 5
Installation
Unit Dimensions and Weights
ModelLengthWidthHeight
Exhaust
Hood
ERT-45119.364.470.220.721.73100
ERT-55133.575.27123.621.73625
ERT-90151.594.58925.526.75800
All dimensions are in inches. Unit weights assume rooftop configuration with weatherhood, filters, outdoor air
damper, cooling options, including but not limited to a six row dx coil, and heating options (where applicable).
The approximate weight (lbs) is assuming all possible accessories are added per housing and may vary by 10%
depending on unit.
Curb Outside Dimensions, Recommended Roof Openings and Curb Weights
Outdoor Air
Hood
Approximate Weight
(lbs)
Curb Weight
with Piping
Vestibule
Model
Outside
Curb
Dimensions
Recommended
Roof
Openings
Optional
Piping
Vestibule
Length WidthABCD
12 inch
Curb
Weight
12 inch Curb
Weight
with Piping
Vestibule
Curb weight
only
Adder per inch
ERT-45114.96031.854.848.132.8195228+9.5+11.4
ERT-55129.170.838.363.554.832.8228260+10.9+12.7
ERT-90147.190.139.179.464.132.8291323+13.1+14.9
All dimensions are in inches. All weights are in pounds.
Various curb heights are available; use the adder per inch column to determine the weights above 12 inches.
L
W
RETURN AIR
INTAKE
SUPPLY AIR
DISCHARGE
A
B
1-inch Foam Insulation
Curb Duct
Adaptor
1.9 inches
1/2 inch
Curb
Unit Base
1.63
inches
1 inch
Curb
Height
Roof Curb Detail
Energy Recovery Ventilator with Tempering
5
Page 6
Service Clearances / Access Panel
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
ModelA (in.)B (in.)
ERT-454836
ERT-556442
ERT-904242
CENTER
B
B
ACCESS DOOR
EXHAUST AIR
WEATHERHOOD
ACCESS DOOR
CASSETTE REMOVAL
WHEEL CASSETTE
A
ACCESS DOOR
EXHAUST FILTERS
ACCESS DOOR
CONTROL
RETURN AIR
INTAKE
OUTDOOR AIR
WEATHERHOOD
DAMPER
SUPPLY FILTERS
HEATPIPE
ACCESS PANEL
ACCESS DOOR
COIL
COOLING
HEATPIPE
COIL
HEATING
B
ACCESS DOOR
Handling
While this unit was constructed with quality and dependability in mind, damage still may occur during handling of the
unit for installation.
The system design and installation should follow accepted industry practice, such as described in the ASHRAE
Handbook. Adequate space should be left around the unit for piping coils and drains, filter replacement, and
maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal
should that become necessary.
Energy Recovery Ventilator with Tempering
6
Page 7
Lifting
WARNING
All factory-provided lifting lugs must be used when
lifting the units. Failure to comply with this safety
precaution could result in property damage, serious
injury, or death.
1. Before lifting, be sure that all shipping material has
been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Installation, Unit
Dimensions and Weights section of this manual.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach to
unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to lifting
the unit and setting on curb.
11. Do not use fork lifts for handling unit.
NOTE
Install and caulk covers over lift points after unit is
installed to ensure weatherization.
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening.
Do not face the outdoor air intake of the unit into
prevailing wind and keep the intake away from any other
exhaust fans. Likewise, position the exhaust discharge
opening away from outdoor air intakes of any other
equipment.
1. Factory-Supplied Roof Curbs Roof curbs are
Model GKD, which are shipped in a knockdown kit
(includes duct adapter) and require field assembly
(by others). Assembly instructions are included with
the curb.
2. Install Curb Locate curb over
roof opening and fasten
in place. Reference
Installation, Curb
Outside Dimensions,
Recommended
Roof Openings
and Weights in this
manual. Check
that the diagonal
dimensions are within
±1/8 inch of each
other and adjust as
necessary. For proper
coil drainage and
unit operation, it is
important that the
installation be level.
Shim as required to
level.
3. Install Ductwork Installation of all ducts should
be done in accordance with SMACNA and AMCA
guidelines. Duct adapter provided to support ducts
prior to setting the unit.
4. Set the Unit Lift unit to a point directly above the
curb and duct openings. Guide unit while lowering
to align with duct openings. Roof curbs fit inside the
unit base. Make sure the unit is properly seated on
the curb and is level. Gasketing (by others) needs
to be installed to curb creating a seal between the
ductwork and the base of the unit.
Energy Recovery Ventilator with Tempering
7
Page 8
Optional Piping Vestibule
Insulated enclosure that is mounted externally to the
unit in order to protect the water supply and return
piping. Not available in models with water-source heat
pump or evaporative cooling.
Supply Blower
Access Door
Drain Pan
Connection
Exhaust Blower
Access Door
Outdoor Air
Weatherhood
Cassette/Filter
Access Door
Piping
Vestibule
Rail Mounting / Layout
1. Rails designed to handle the weight of the unit
should be positioned as shown on the diagram (rails
by others).
2. Make sure that rail positioning does not interfere with
the supply air discharge opening or the exhaust air
intake opening on the unit. Avoid area dimensioned
“B” below.
3. Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
4. Set unit on rails.
Cooling Coil (with or without heating)
Exhaust Blower
Access Door
Outdoor Air
Weatherhood
Heating Only
Unit SizeWeight
ERT-45235
ERT-55235
ERT-90280
All weights are in pounds.
Cassette/Filter
Access Door
Supply Blower
Access Door
Piping
Vestibule
BA
Rail Mounting
Unit SizeAB
ERT-457.041.9
ERT-555.553.0
ERT-906.059.0
All dimensions are in inches.
Energy Recovery Ventilator with Tempering
8
Page 9
Ductwork Connections
R
o
t
a
t
i
o
n
POOR
Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.
n
o
i
t
a
t
o
R
Length of Straight Duct
GOOD
Inlet/Outlet Descriptions
Code DescriptionCode Description
OIEOutdoor Air Intake EndSDTSupply Discharge Top
OITOutdoor Air Intake TopSDT/IG Supply Discharge Top w/IG
RIEReturn Air Intake EndSDSSupply Discharge Side
RISReturn Air Intake SideSDBSupply Discharge Bottom
RIBReturn Air Intake BottomEDEExhaust Discharge End
RITReturn Air Intake TopEDTExhaust Discharge Top
SDESupply Discharge EndEDSExhaust Discharge Side
ERT-45
Recommended
Duct Size
IntakeDuct SizeDischarge12-12 Blower
OIE28 x 36SDE20 x 20
OIT34 x 24SDS20 x 20
RIE24 x 40SDT20 x 20
RIS26 x 32SDT/IG28 x 28
RIB20 x 48SDB16 x 18
RIT28 x 30EDE20 x 20
EDT20 x 20
EDS20 x 20
ERT-55
Recommended
Duct Size
IntakeDuct SizeDischarge15-15 Blower
OIE32 x 52SDE28 x 28
OIT40 x 28SDS28 x 28
RIE30 x 40SDT28 x 28
RIS30 x 38SDT/IG38 x 30
RIB20 x 54SDB18 x 20
RIT30 x 40EDE28 x 28
EDT28 x 28
EDS28 x 28
ERT-90
Recommended
Duct Size
IntakeDuct SizeDischarge18-18 Blower
OIE34 x 64SDE32 x 32
OIT34 x 50SDS32 x 32
RIE32 x 60SDT32 x 32
RIS40 x 40SDT/IG34 x 33
RIB22 x 74SDB20 x 24
RIT40 x 40EDE32 x 32
EDT32 x 32
EDS32 x 32
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM) at
minimum airflow and up to 1600 fpm at maximum airflow.
• Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
Energy Recovery Ventilator with Tempering
9
Page 10
Electrical Installation
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest
edition of the National Electrical Code ANSI/NFPA70
and any local codes that may apply. In Canada, wiring
should be done in accordance with the Canadian
Electrical Code.
IMPORTANT
The equipment must be properly grounded and
bonded. Any wiring running through the unit in the
airstream must be protected by metal conduit, metal
clad cable or raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105°C, except for an
energy cut-off or sensor lead wire which must be rated
to 150°C.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
WARNING
If unit is equipped with a microprocessor, terminals Y1,
Y2 and W1 cannot be wired to a thermostat. Wiring to
these terminals will bypass unit’s internal safeties.
1. Determine the Size of the Main Power Lines
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.
2. Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate
power supply. The power connection should
be made to the factory-provided electric heater
disconnect and must be compatible with the ratings
on the nameplate, supply power voltage, phase and
amperage. Consult ANSI/NFPA 70 and CSA C22.1
for proper conductor sizing.
3. Provide the Opening(s) for the Electrical
Connections
Electrical openings vary by unit size and arrangement
and are field-supplied.
4. Connect the Power Supplies
Connect the main power lines and electric heater
power lines to the disconnect switches or terminal
blocks and main grounding lug(s). Torque field
connections to manufacturer’s recommendations.
5. Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V
power supply circuit. The circuit must include short
circuit protection which may need to be supplied by
others.
6. Connect Field-Wired Low Voltage Components
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field-wiring, refer to the unitspecific wiring diagram located on the inside of the
control center access door.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that
field-supplied conduit does not interfere with access
panel operation. All low voltage wiring should be run in
conduit wherever it may be exposed to the weather.
The low voltage control circuit is 24 VAC and control
wiring should not exceed 0.75 ohms. If wire resistance
exceeds 0.75 ohms, an isolation relay should be added
to the unit control center and wired in place of the
remote switch (typically between terminal blocks R
and G on the terminal strip. The relay must be rated
for at least 5 amps and have a 24 VAC coil. Failure to
comply with these guidelines may cause motor starters
to “chatter” or not pull in which can cause contactor
failures and/or motor failures.
Energy Recovery Ventilator with Tempering
10
Page 11
Field-Provided Disconnect
If field-installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
Discharge Air Temperature Sensor
The discharge air temperature
sensor is factory-mounted in the
blower discharge section of the unit
behind the blower cut off plate.
Typical Control Center Components with
Microprocessor Control
8
1
9
5
7
4
17
2
3
10
6
1114
13
16
15
Individual components and locations will vary.
1. Main disconnect (non-fusible, lockable)
2. Motor starter - outdoor air fan
3. Motor starter - exhaust air fan
4. Motor contactor - energy wheel
5. 24 VAC control transformer
6. 24 VAC terminal strip
7. Fuses for blower motors
8. Grounding lug
9. Distribution block
10. Terminal block
Optional Components
11. Microprocessor controller
12. Dirty filter pressure switches
13. Economizer module
14. Thermostats for
• Economizer module
• Energy recovery wheel frost control
15. GreenTrol®
16. Frost control pressure switch
17. Energy recovery wheel VFD
12
Energy Recovery Ventilator with Tempering
11
Page 12
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of different
alarm lights and switches to control the unit. The remote
panel ships loose and requires mounting and wiring in
the field. The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
• Wheel rotation sensor light
Unit Interfacing Terminals
Heating/Cooling Switches and Night Setback Switch/
Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
UNIT ON/OFF
S1
COOL STAGE 1 / ECONOMIZER
S6
COOL STAGE 2
S7
HEAT
S4
C
G
Y1
Y2
W1
6
7
12
7-Day Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
BLACKBLUE
RED
(CAPPED)
TIMER
C
G
Y1
Y2
W1
6
7
12
On/Off/Auto Switch & Indictor Light Wiring
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
UNIT ON/OFF
FROST CONTROL
ECONOMIZER
WHEEL ROTATION
ON
OFF
AUTO
* -- BMS, TIMECLOCK,
TSTAT, RTU, ETC.
*
R
C
G
Y1
Y2
W1
6
7
12
UNOCCUPIED RECIRCULATION
S5
Dirty Filter Indicator
(Powered by others)
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
NC
NC
HOTCOMMON
C
C
A
NO
NO
DIRTY FILTER
C
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
ON/OFF/AUTO SWITCH ALLOWS THREE MODES OF OPERATION
"ON" - UNIT IS TURNED ON MANUALLY
"OFF" - UNIT IS TURNED OFF MANUALLY
"AUTO" - UNIT IS CONTROLLED VIA SCHEDULER OF BMS, TIMECLOCK, TSAT, ETC.
Energy Recovery Ventilator with Tempering
12
NC
NC
NO
C
NO
DIRTY FILTER
Page 13
Piping Installation
Optional Coil Piping
Factory-installed cooling and heating components are
mounted in the coil section of the unit. The coil section
is downstream of the energy wheel on the supply air
side of the unit. Note the coil connection locations on
the picture. Coil connections are located external to the
unit as shown.
Note: DX coil liquid connection is internal to units.
Water coil
connections
Water Coils
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. When installing couplings,
do not apply undue stress to the connection
extending through the unit. Use a backup pipe
wrench to avoid breaking the weld between coil
connection and header.
2. Connect the water supply to the bottom connection
on the air leaving side and the water return to the
top connection on the air entering side. Connecting
the supply and/or return in any other manner will
result in very poor performance. Be sure to replace
factory-installed grommets around coil connections
if removed for piping. Failure to replace grommets
will result in water leakage into the unit and altered
performance.
3. Water coils are not normally recommended for
use with entering air temperatures below 40°F. No
control system can be depended on to be 100% safe
against freeze-up with water coils. Glycol solutions
or brines are the only safe media for operation of
water coils with low entering air conditions. If glycol
or brine solutions are not used, coils must be drained
when freezing conditions are expected. If required,
vent and drain connections must be fieldpiped, external to the unit.
4. Pipe sizes for the system must be selected on
the basis of the head (pressure) available from the
circulation pump. The velocity should not exceed
6 feet per second and the friction loss should be
approximately 3 feet of water column per 100 feet
of pipe.
5. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. Refer to Condensate
Drain Trap section.
DX coil
liquid
connection
access
door
Direct Expansion (DX) Coils (Split DX)
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should not
be applied at the connection to coil headers.
2. The condensate drain pipe should be sized
adequately to ensure the condensate drains properly.
Refer to Condensate Drain Trap section.
3. When connecting suction and liquid connections
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage. Be
sure to replace factory-installed grommets around
coil connections if removed for piping.
4. Manufacturer does not supply compressor or
condensing units with standard models. For further
instruction on DX coil installation and operation
contact your compressor and/or condenser
manufacturer.
Condensate Drain Trap
This unit is equipped with a stainless steel condensate
pan with a 1-inch MPT stainless steel drain connection.
It is important that the drain connection be fitted with a
P trap to ensure proper drainage of condensate while
maintaining internal static pressures.
A P trap assembly (kit) is supplied with each unit and
is to be assembled and installed as local conditions
require and according to the
assembly instructions provided
with the P trap. If local and area
codes permit, the condensate
may be drained back onto the
roof, but a drip pad should be
provided beneath the outlet. If
local and area codes require a
permanent drain line, it should
be fabricated and installed in
accordance with Best Practices and all codes.
In some climates, it will be necessary to provide freeze
protection for the P trap and drain line. The P trap
should be kept filled with water or glycol solution at
all times and it should be protected from freezing to
protect the P trap from damage. If severe weather
conditions occur, it may be necessary to fabricate a P
trap and drain line of metal and install a heat tape to
prevent freezing.
Energy Recovery Ventilator with Tempering
13
Page 14
Unit Overview
Optional Component Overview
Basic Unit
The unit is pre-wired such that when a call for outside
air is made (via field-supplied 24 VAC control signal
wired to unit control center), the supply fan, exhaust fan,
and energy wheel are energized and optional motorized
dampers open.
The unit can be supplied with or without heating and
cooling coils. For units with coils, controls can be
supplied by manufacturer or by the controls contractor.
If supplied by the controls contractor, they would
provide, mount, and wire any temperature controllers
and temperature or relative humidity sensors required
for the unit to discharge air at the desired conditions.
However, temperature, pressure, and current sensors
can be provided by manufacturer for purposes of
monitoring via the BMS.
Summer Operation
Outdoor air is preconditioned (temperature and moisture
levels are decreased) by the transfer of energy from the
cooler, drier exhaust air via the energy recovery wheel.
Units supplied with cooling coils can further cool the
air coming off the wheel and strip out moisture to levels
at or below room design. A heating coil downstream of
the cooling coil can reheat the air to a more comfortable
discharge temperature to the space.
Return Air
75°F
50% RH
Exhaust Air
Supply Air
Outdoor Air
95°F
117 grains/lb.
79°F
75 grains/lb.
Winter Operation
Outdoor air is preconditioned (temperature and moisture
levels are increased) by the transfer of energy from the
warmer, more humid exhaust air via the energy recovery
wheel. Units supplied with heating coils can further heat
the air coming off the wheel to levels at or above room
design.
Economizer
The energy wheel operation can be altered to take
advantage of economizer operation (free cooling).
Two modes are available:
1. Stopping the wheel
2. Modulating the wheel
Stopping the wheel: A field-supplied call for cool (Y1)
is required. De-energizing the wheel is accomplished in
one of three ways:
1. The outdoor air temperature is less than the
outdoor dry bulb set point (DRYBLB SET)
2. The outdoor air temperature is less than the return
air temperature
3. The outdoor air enthalpy is within the preset
enthalpy curve
A low temperature lock out (LOW T LOCK) is also set
to deactivate mechanical cooling when it exceeds
the outdoor air temperature (factory default 32°F).
Effectively, the two sensors create a deadband where
the energy recovery wheel will not operate and free
cooling from the outside can be brought into the
building unconditioned.
Modulating the wheel (factory): A variable frequency
drive is fully programmed at the factory. A “call for cool”
must be field-wired to the unit. (Terminals provided
in unit. Refer to wiring diagram in unit control center).
to allow for initiation of economizer mode. The unit
recognizes economizer conditions based on one of the
previously mention sensors and set points. The unit will
then modulate the wheel speed to maintain the mixed
air temperature set point (MAT SET).
Modulating the wheel (by others): A variable
frequency drive is fully programmed at the factory.
A field-supplied 0-10 VDC signal will be required for
operation of the energy wheel. The field will be required
to have full control of the energy wheel speed at all
times. If no 0-10 VDC signal is provided, the energy
wheel will run at the factory default of 3 Hz and no
energy transfer will be captured.
Exhaust Air
Outdoor Air
10°F
5 grains/lb.
Energy Recovery Ventilator with Tempering
14
Return Air
72°F
40% RH
Supply Air
60°F
39 grains/lb.
Page 15
Frost Control
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the energy
recovery wheel. Frost control is an optional feature that
will prevent/control wheel frosting. Three options are
available:
1. Timed exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control
All of these options are provided with a thermodisc
mounted in the outdoor air intake compartment and a
pressure sensor to monitor pressure drop across the
energy wheel.
An outdoor air temperature of below 5°F and an
increase in pressure drop would indicate that frost is
occurring. Both the pressure sensor and the outdoor air
thermodisc must trigger in order to initiate frost control.
The two sensors together ensure that frost control is
only initiated during a real frost condition.
Timed exhaust frost control includes a timer in
addition to the thermodisc and wheel pressure sensor.
When timed exhaust frost control is initiated, the timer
will turn the supply blower off. Timed exhaust, using
default timer setting, will shut down the supply fan for
5 minutes every 30 minutes to allow exhaust to defrost
energy wheel. Use the test procedure in the Optional
Start-Up Accessories section for troubleshooting.
Electric preheat frost control includes an electric
heater (at outdoor air intake) in addition to the
thermodisc and pressure sensor on wheel. When
electric preheat frost control is initiated, the electric
preheater will turn on and warm the air entering the
energy wheel to avoid frosting. Use the test procedure
in the Optional Start-Up Accessories section for
troubleshooting.
Modulating wheel frost control includes a variable
frequency drive (VFD) in addition to the thermodisc and
pressure sensor. When modulating wheel frost control
is initiated, the VFD will reduce the speed of the wheel.
Reducing the speed of the energy wheel reduces its
effectiveness, which keeps the exhaust air condition
from reaching saturation, thus, eliminating condensation
and frosting. If the outdoor air temperature is greater
than the frost threshold temperature OR the pressure
differential is less than the set point, the wheel will run
at full speed. If the outdoor air temperature is less than
5°F AND the pressure differential is greater than the
set point, the wheel will run at reduced speed until the
pressure differential falls below the set point. The VFD
will be fully programmed at the factory.
Variable Frequency Drives (VFD)
Variable frequency drives are used to control the speed
of the fan as either multi-speed or modulating control.
Multi-speed VFDs reference a contact which can be
made by a switch or a sensor with a satisfied set point.
Modulating control references a 2-10 VDC signal to the
VFD which will vary the fan speed from a minimum 50%
to full 100% rpm. An optional CO
provide both a set point contact or a modulating 2-10
VDC signal.
sensor is available to
2
CO2 Sensor
This accessory is often used in Demand Control
Ventilation (DCV) applications. The factory-provided
sensors can either be set to reference a set point
for multi-speed operation, or output a 2-10 VDC
signal to modulate the fan speed. These can either
be shipped loose to mount in the ductwork, or can
be factory-mounted in the return air intake. Follow
instructions supplied with sensor for installation and
wiring details.
Rotation Sensor
The rotation sensor monitors energy wheel rotation. If
the wheel should stop rotating, the sensor will close a
set of contacts in the unit control center. Field-wiring of
a light (or other alarm) between terminals R and 12 in
the unit control center will notify maintenance personnel
when a failure has occurred.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit control
center. Field-wiring of a light (or other alarm) to these
contacts will notify maintenance personnel when
filters need to be replaced. The switch has not been
set at the factory due to external system losses that
will affect the switch. This switch will need minor field
adjustments after the unit has been installed with all
ductwork complete. The dirty filter switch is mounted in
the exhaust inlet compartment next to the unit control
center or in unit control center.
Energy Recovery Ventilator with Tempering
15
Page 16
Microprocessor Control
The microprocessor
controller is specifically
designed and
programmed to optimize
the performance of
the unit with supplemental heating and cooling. This
option ensures that the outdoor air is conditioned to
the desired discharge conditions. The controller and
accompanying sensors are factory-mounted, wired and
programmed. Default settings are pre-programmed, but
are easily field-adjustable.
The microprocessor controller can be interfaced with
a Building Management System through LonWorks®,
BACnet®, or ModBus.
Please refer to the DDC Controller for Energy Recovery
Installation, Operation and Maintenance manual for
detailed information.
Unoccupied Recirculation Damper
(not offered with electric heat units)
The unoccupied recirculation option provides a
recirculation damper from the return air intake to the
supply airstream to reduce heating and cooling loads
when less ventilation is required. During the unoccupied
mode, the exhaust fan will remain off and the supply
air fan will operate with mode of tempering to maintain
unoccupied temperature set point.
Service Outlet
120 VAC GFCI service outlet ships loose for field
installation. Requires separate power source so power
is available when unit main disconnect is turned off for
servicing.
Vapor Tight Lights
Vapor tight lights provide light to each of the
compartments in the energy recovery unit. The lights
are wired to a junction box mounted on the outside of
the unit. The switch to turn the lights on is located in
the unit control center. The switch requires a separate
power source to allow for power to the lights when the
unit main disconnect is off for servicing.
Outdoor Airflow Monitor
A factory-wired, mounted and powered airflow
monitoring system is provided. The airflow control
system offers the following functionality:
• Display of outdoor airflow rate in actual cubic feet
per minute (CFM) or actual liters per second (LPS) on
a 16 character LCD display.
• Two configurable analog outputs for transmitting
outdoor airflow rate, outdoor air temperature, or a
proportional-integral-derivative (PID) control signal
based on an outdoor airflow set point.
• A configurable digital output that operates based on
an airflow set point or range.
Operation: Outdoor airflow monitoring is accomplished
using two thermal dispersion sensors that accurately
measure airflow velocity down to zero feet per
minute (fpm). The airflow controller takes the average
measurement for two sensor configurations, and
determines the outdoor airflow rate based on the
effective intake area. Field calibration of the outdoor
airflow monitoring device determines the effective intake
area of the unit.
Refer to GreenTrol® Automation Inc. GF-2200A
technical data sheet for further detail.
IMPORTANT
For the outdoor airflow monitoring device to perform
as intended, field calibration is required. Calibration of
the airflow monitoring device requires an independent
measurement of airflow and should be performed
when the system undergoes test and balance.
Smoke Detector
The Hochiki America DH-98 duct smoke detector
provides early detection of smoke and
products of combustion present in air
moving through HVAC duct systems.
The DH-98-P is designed to prevent
the recirculation of smoke in areas
by the air handling systems, fans,
and blowers. Complete systems may
be shut down in the event of smoke
detection. The Hochiki America
DH-98-P operate on 115 VAC, 24 VAC and 24 VDC.
The DH-98-P is designed and built to meet all local
requirements, as well as the NFPA regulations regarding
duct smoke detectors. Output terminals are provided
for remote accessories such as a horn, strobe, remote
status indicators and reset key switches or push
buttons.
Refer to Hochiki America DH-98-P installation
instructions for further detail.
Energy Recovery Ventilator with Tempering
16
Page 17
Start-Up Unit
SPECIAL TOOLS REQUIRED
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
CAUTION
Do not operate without the filters and birdscreen
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers and fans are
set-up to run correctly when supplied power. If
any one fan is running backwards or making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect. This
will ensure proper operation of the unit. Failure to
comply may void the warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
• Voltage Meter (with wire probes)
• Amperage Meter
• Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
• U-tube manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running. In order to measure
volts and amps, the control center door needs to be
open and the unit energized.
• Make sure Pre-Start-Up checklist is complete.
• Jumper R to G to enable unit. Jumper R to Y1 and R
to Y2 to enable cooling and R to W1 to enable heat
for units without microprocessor.
• Turn the disconnect on. Make sure all fans are
rotating the correct direction.
• Allow the unit to run until the refrigerant system
stabilizes. Approximately 10-15 minutes.
Voltage Imbalance
In a three-phase system, excessive voltage imbalance
between phases will cause motors to overheat and
eventually fail. Maximum allowable imbalance is 2%.
To determine voltage imbalance, use recorded voltage
measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA
Energy Recovery Ventilator with Tempering
17
Page 18
Pre Start-Up
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model No. __________________________________
Unit Serial No. ____________________________________
Energy Wheel Serial Number _______________________
Start-Up Date ____________________________________
Start-Up Personnel Name _________________________
Start-Up Company ________________________________
Phone Number ___________________________________
Pre Start-Up Checklist
Disconnect and lock-out all power switches.
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
Check fan rotation.
Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
Check the fan belt drives for proper alignment and
tension.
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
Verify that non-motorized dampers open and close
properly.
Check the tightness of all electrical wiring
connections.
Verify control wire gauge.
Verify diameter seal settings on the energy recovery
wheel.
Verify proper drain trap installation.
Inspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully
straighten fins with a fin comb.
Start-Up Checklist
Line Voltage. Check at unit disconnect.
L1-L2VoltsL2-L3VoltsL1-L3Volts
Motor Amp Draw
Supply Motor AmpsL1AmpsL2AmpsL3Amps
Exhaust Motor AmpsL1AmpsL2AmpsL3Amps
Fan RPM
Supply Fan RPMSupply FanYes / No
Measured AirflowCFM
Exhaust FanRPMExhaust FanYes / No
Measured AirflowCFM
Energy Wheel Motor
L1AmpsL2AmpsL3Amps
Heating System / Electric Heat
Pre-HeaterL1-L2VoltsL2-L3VoltsL1-L3Volts
L1AmpsL2AmpsL3Amps
Temp. Rise
Correct fan rotation direction?
Post-HeaterL1-L2VoltsL2-L3VoltsL1-L3Volts
L1AmpsL2AmpsL3Amps
Temp. Rise
Energy Recovery Ventilator with Tempering
18
Page 19
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Frost Control Application / Operation Section:SettingFactory Default
YesNoFrost Control set point5°F
Differential2°F
TimerRefer to IOM
YesNoFrost Control ModulatingRefer to IOM
Economizer Application / Operation Section:
YesNoEconomizer (temperature)
Set point65°F
Offset20°F
Differential2°F
YesNoEconomizer (enthalpy)
Set pointB
YesNoEconomizer (modulating)Refer to IOM
Optional Accessories Section:Operational
YesNo Wheel Rotation Sensor
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesNo CO2 SensorYes No N/A
YesNo Service OutletYes No N/A
YesNo Vapor Tight LightsYes No N/A
YesNo Remote Control PanelYes No N/A
1
(
⁄8 in. from wheel)
Yes No N/A
Variable Frequency Drives Section:Operational
YesNo Blower VFDsYes No N/A
YesNo Wheel VFDYes No N/A
Damper Section:Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
YesNo Night Setback DamperYes No N/A
Outdoor Air Monitoring:
YesNoField calibrated.
Energy Recovery Ventilator with Tempering
19
Page 20
Start-Up Components
R
ing
Scr
Scr
ews
ews
Energy Wheel
The energy wheel is installed in the unit’s airstream with
one half of the wheel in the intake airstream and one
half in the return airstream. Air leakage between the two
airstreams has to be kept to a minimum and the wheel
has air seals that must be adjusted for that purpose.
The seals must be adjusted at time of start-up.
Drive Belt
Inspect the drive belt. Make sure the belt rides smoothly
in the pulley and around the outside of the wheel. Note
the directional arrow and data information shown in the
image.
Bearing Support
Push the wheel cassette back into the unit and plug
in the power connector. Turn the main power supply
back on and then observe the operation of the wheel by
opening the wheel access door slightly. Remove filters if
necessary to observe the wheel.
Fans
The unit contains a double inlet airfoil fan andshould be
checked for free rotation. If any binding occurs, check
for concealed damage and foreign objects in the fan
housing. Be sure to check the belt drives per the startup recommendations in the Fan Belt Drive section.
Centering of the fan wheel can be accomplished by
loosening the wheel hub set screw and moving the
wheel to the desired position.
Fan Performance Modifications
Adjustable
Air Seals
Label showing
cassette serial number
and date code
Drive Belt
Drive Pulley
Adjust the Air Seals
The first step in wheel seal adjustment is to make sure
the unit power supply is locked out. Disconnect the
wiring to the wheel module and pull the wheel cassette
out of the cabinet on its tracks. Large cassettes are
not removable. Then slowly
rotate the wheel by hand to
make sure there is no binding
or misalignment. The wheel
should rotate smoothly and
should not bind.
There is a perimeter seal
located around the outside
of the wheel and a diameter
etain
seal across the face of the
wheel on both sides. Check to
make sure that all air seals are
secure and in good condition.
Adjust the air seals by
loosening all the air seal
retaining screws on the
bearing support (see image for
reference). Using a piece of
paper as a feeler gauge, adjust
the seals so they almost touch
Bearing Support Bar
Showing air seal assembly
the face of the wheel while
tugging slightly on the paper. When the wheel is rotated,
there should be a slight tug on the paper. Tighten the
screws, repeat the steps on the other set of seals.
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.), consult
manufacturer to determine if the unit can operate
safely at the new conditions.
Due to job specification revisions, it may be necessary
to adjust or change the sheave or pulley to obtain the
desired airflow at the time of installation. The start-up
technician must check blower amperage to ensure that
the amperage listed on the motor nameplate is not
exceeded. Amperage to be tested with access doors
closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by
manufacturer, have been carefully selected for the
unit’s specific operating condition. Utilizing different
components than those supplied could result in unsafe
operating conditions which may cause personal injury or
failure of the following components:
• Fan Shaft • Bearings • Motor
• Fan Wheel • Belt
Tighten all fasteners and set screws securely and realign
drive pulleys after adjustment. Check pulleys and belts
for proper alignment to avoid unnecessary belt wear,
noise, vibration and power loss. Motor and drive shafts
must be parallel and pulleys in line (see diagrams in Belt
Drive Installation section).
Energy Recovery Ventilator with Tempering
20
Page 21
Belt Drive Installation
1. Remove the protective coating from the
end of the fan shaft and assure that it is
free of nicks and burrs.
2. Check fan and motor shafts for parallel
and angular alignment.
3. Slide sheaves on shafts. Do not drive
sheaves on as this may result in bearing
damage.
4. Align fan and motor sheaves with a
straightedge to centerline.
5. Place belts over sheaves. Do not pry
or force belts, as this could result in
damage to the cords in the belts.
6. With the fan off, adjust the belt tension
by moving the motor base. (See belt
tensioning procedures in the Routine
Maintenance section of this manual).
When in operation, the tight side of the belts should
be in a straight line from sheave to sheave with a
slight bow on the slack side.
WRONGWRONG
WRONGCORRECT
Proper alignment of motor and drive shaft.
0.25 in.
1.5 in.
centerline
straightedge
2 in.
Pulley
alignment
example
Direction of Fan Wheel Rotation
Blower access is labeled on unit. Check for proper
wheel rotation by momentarily energizing the fan.
Rotation is determined by viewing the wheel from the
drive side and should match the rotation decal affixed to
the fan housing.
If the wheel is rotating the wrong way, direction can be
reversed by interchanging any two of the three electrical
leads.
Check for unusual noise, vibration, or overheating
of bearings. Refer to the Troubleshooting section of this
manual if a problem develops.
Fan RPM
Supply fan and exhaust fan will have an adjustable
motor pulley (on 15 HP and below) preset at the factory
to the customer-specified RPM. Fan speed can be
increased or decreased by adjusting the pitch diameter
of the motor pulley. Multi-groove variable pitch pulleys
must be adjusted an equal number of turns open
or closed. Any increase in fan speed represents a
substantial increase in load on the motor. Always check
the motor amperage reading and compare it to the
amperage rating shown on the motor nameplate when
changing fan RPM. All access doors must be installed
except the control center door.
WARNING
Do not operate units with access doors open or
without proper ductwork in place as the fan motors
will overload.
Blower Diameter
Model
ERT-4512 x 123700
ERT-5515 x 152900
ERT-9018 x 182450
x Width
(inches)
Maximum RPM for
Backward-Curved
Blowers
Vibration
Excessive vibration may be experienced during initial
start-up and can cause a multitude of problems,
including structural and/or component failure.
Vibration Causes
Off axis or loose components
Drive component unbalance
Poor inlet / outlet conditions
Foundation stiffness
If observation cannot locate the source of vibration, a
qualified technician using vibration analysis equipment
should be consulted. If the problem is wheel unbalance,
in-place balancing can be done.
Generally, fan vibration and noise is transmitted to other
parts of the building by the ductwork. To eliminate this
undesirable effect, the use of heavy canvas connectors
is recommended.
Many of these conditions
can be discovered by
careful observation. Refer
to the Troubleshooting
section of this manual
for corrective actions.
Energy Recovery Ventilator with Tempering
21
Page 22
Optional Start-Up Components
Dirty Filter Switch
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch.
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (Senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’
of the switch. (Senses pressure at air inlet side of filters)
1. Open the filter compartment and place a sheet of
plastic or cardboard over 50% of the filter media.
2. Replace the filter compartment door.
3. Check to see if there is power at the alert signal
leads (refer to electrical diagram).
4. Whether there is power or not, turn the adjustment
screw on the dirty filter gauge (clockwise if you did
not have power, counterclockwise if you did have
power) until the power comes on or just before the
power goes off.
5. Open the filter compartment and remove the
obstructing material.
6. Replace the door and check to make sure that you
do not have power at the alert signal leads. The unit
is now ready for operation.
Economizer
Relevant Set Points
1. MAT SET The mixed air temperature set point after
the energy wheel. The control will modulate the
energy wheel to maintain temperature as best as it
can (Set point menu, default 53°F)
2. LOW T LOCK The set point for the low temperature
mechanical cooling lockout. (Set point menu, default
32°F)
3. DRYBLB SET The outdoor air set point to call for
economizer. (Set point menu, default 63°F)
4. MIN POS The minimum signal voltage sent to the
energy wheel. This must be set to 2 VDC. (Set point
menu, default 2.8 VDC)
5. AUX1 O The controllers operating sequence
structure. (Set point menu, default ‘None’)
6. ERV OAT SP The set point for low temperature
economizer lockout. This is the low temperature set
point when AUX1 O is set to ERV. (Set point menu,
default 32°F)
7. STG3 DLY Time delay after second cooling stage is
enabled (Advanced setup menu, default 2 hrs.)
Using the Keypad with Settings and Parameters
To use the keypad when working with Set Points,
System and Advanced Settings, Checkout Tests, and
Alarms:
1. Navigate to the desired menu.
2. Press
currently displayed menu.
3. Use the
parameter.
4. Press (enter) to display the value of the currently
displayed item.
5. Press the
displayed parameter value.a
6. Press the
displayed parameter value.
7. Press (enter) to accept the displayed value and
store it in non-volatile RAM.
8. CHANGE STORED displays.
9. Press
parameter.
10. Press
parameter.
a
When values are displayed, pressing and holding the
or button causes the display to automatically
increment.
The table shows which set points are relevant to the
given sequences. Refer to the wiring diagram for the
units’ sequence.
DRYBLB SETXX
MAT SETXXXXXX
LOW T LOCKXXXXXX
ERV OAT SPXXX
MIN POSXXX
AUX1 OUTERVERVERV
STG3 DLYXXXXXX
(enter) to display the first item in the
and buttons to scroll to the desired
button to increase (change) the
button to increase (change) the
a
(enter) to return the current menu
(escape) to return to the current menu
MODULATE WHEELSTOP WHEEL
OA
Temp
OA
Enthalpy
OA/RA
Temp
Differential
OA
Temp
OA
Enthalpy
Differential
OA/RA
Temp
Energy Recovery Ventilator with Tempering
22
Page 23
Stop Wheel
1. Navigate to the Checkout menu and press (enter).
2. The energy wheel and cooling should stop.
3. Navigate to Connect ERV and press
(enter) twice
to run the test.
4. Voltage between AUX1-O and C should be 24 VAC.
The energy wheel should activate.
Modulate Wheel
1. Navigate to the Checkout menu and press (Enter).
2. The cooling should turn off and the wheel should be
rotating at full speed.
3. Navigate to Damper Open and press
to run the test.
4. Voltage between terminals ACT 2-10 and ACT COM
should be 10 VDC. This will slow the wheel down to
minimum speed.
5. Press
(escape), navigate to Damper Close and
press (enter) twice to run the test.
6. Voltage between terminal ACT 2-10 and ACT COM
should be 2 VDC. This will speed the wheel up to
maximum speed.
(enter) twice
Frost Control
Timed Exhaust
1. Remove power from unit.
2. Jumper the frost indicating wheel pressure switch in
the unit control center.
3. Jumper the temperature indicating thermodisc in
the unit control center. Thermodisc has a pre-set
temperature of 5°F.
4. Set the frost control timer scale for T1 and T2 to 1m.
Set the timer settings for T1 and T2 to 10.
5. Add power to the unit. Blower should cycle on for
one minute, then turn off for one minute.
6. Remove power from unit and remove jumpers that
were placed. Reset timer settings.
• T1 timer setting
set to 5 and
timer scale
set to 10m for
5 minutes of
wheel off time.
• T2 timer setting
set to 5 and
timer scale
set to 1h for
30 minutes of
wheel on time.
Timer
Scale
Timer
Settings
Timer
Scale
T1
Settings
T2
Settings
Electric Preheat
1. Remove power from unit.
2. Jumper the frost indicating wheel pressure switch in
the preheat control center.
3. Jumper the temperature indicating thermodisc in
the preheat control center. Thermodisc has a pre-set
temperature of 5° F.
4. Apply power to unit. Preheater should turn on.
Energy Recovery Ventilator with Tempering
23
Page 24
Outdoor Airflow Monitor
For additional information on how to navigate through
the airflow controller menus, refer to the technical
manuals GF-2200A from GreenTrol® Automation Inc.
at www.greentrol.com.
Field calibration procedure:
1. Turn off power to the unit using the power
disconnect(s).
2. Remove the cover from the GreenTrol airflow
monitoring controller.
3. Install a jumper wire between terminals R and G on
the unit’s terminal board if one isn’t present.
4. When safe, turn the power back on to the unit
using the power disconnect(s).
If no microprocessor controller, skip to step 8.
Steps 5 thru 7 are for microprocessor only.
5. Look at the unit’s microprocessor controller screen
and view the status of the unit. If the displayed
status is “System Off” continue with step 6,
otherwise go to step 7.
6. Adjust the unit on/off priorities on the unit’s
microprocessor controller so the unit will run for
calibration.
a. Push the “Prg” button on the microprocessor
controller.
b. Use the up and down arrows to get to the “On/
Off Unit” menu.
c. Push the Enter button to view the current unit on/
off priorities.
d. Push the down arrow to display the Unit ON/OFF
Control screen.
e. Record the settings so they can be changed
back when calibration is complete:
By digit input: ___________
By BMS: ___________
By Scheduler: ___________
f. Use the Enter button to navigate between the
different settings on the page, use the up and
down arrows to change the values so that “By
digit input” is the only setting with “Yes”.
7. Enter the service override menu to control the
damper position.
a. At the Home Screen push the “Prg” button. (If
you’re not at the home screen, push the Escape
button until you get there).
b. Use the up and down arrows to get to the
“Service” menu, then push the Enter button.
c. If you’re asked for a password, enter “1000” for
the password and push Enter.
d. Use the up and down arrows to get to the
“Overrides” screen, then push Enter.
e. Use the arrow buttons to get the supply override.
8. Measure the supply airflow rate of the unit using an
approved test and balance method.
9. Without making any changes to the system,
calibrate the airflow monitoring controller so it
reads the airflow measured in step 8 by using the
Field Calibration Wizard.
a. The field calibration lasts for two minutes. Any
significant changes in airflow will affect the
accuracy of the reading.
b. To enter the Field Calibration Wizard, hold the
Down and Enter buttons simultaneously on the
airflow controller, then release the buttons.
c. Push the Enter button to access Wizard 1
d. Push the Enter button twice and change Wiz1
Enable to YES.
e. When asked for the number of calibration points
(Cal Points), set the value to 1.
f. Push the Enter button when the display says
“Set Flow 1”.
g. After completing the steps above, set the
FLOW1 value to the airflow measured in step 8,
then push the Enter button to begin calibration.
10. After the calibration is completed, measure the
supply airflow rate again and compare with the
value on the airflow controller’s display
a. If the values are within 5% of each other the
device has been successfully calibrated.
b. If the values are not within 5% of each other
repeat the field calibration process.
11. If you had to change the On/Off priorities on the
microprocessor unit controller, change them back
to the values that were written down in step 6.
12. Turn off power to the unit using the power
disconnect(s) and wait one minute for the variable
frequency drive(s) to lose backup power.
13. Replace the cover to the GreenTrol airflow
monitoring station.
14. If you added a jumper between terminals R and
G in step 3, remove it at this time. If a jumper was
already in place, leave it in place.
15. When safe, turn the power back on to the unit
using the power disconnect(s).
Recycling of the power resets the manual override
values that were set during the calibration.
Energy Recovery Ventilator with Tempering
24
Page 25
Variable Frequency Drives
Optional factory-installed, wired, and programmed
variable frequency drives (VFDs) may have been
provided for modulating or multi-speed control of the
blowers and energy recovery wheel for economizer and
frost control modes. One VFD, either Yaskawa model
V1000 or J1000, is provided for each blower (supply air
and exhaust) and one Yaskawa model J1000 is provided
for the energy recovery wheel.
Refer to the tables in this section for factory settings
and field wiring requirements. Refer to the unit control
center for unit specific wiring diagram. When making
adjustments outside of the factory set points, refer to
Yaskawa VFD instruction manual, which can be found
online at www.drives.com. For technical support,
contact Yaskawa direct at 1-800-927-5292.
IGS-S+R-R+
MPACAMAC+VA2A1PCP2P1
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
J1000
V1000
A1 AC
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
USER TO PROVIDE CONTACTS AND ISOLATION
AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER A1-01 CHANGE TO 2
PARAMETER d1-01 FOR NEW 60Hz SETTING
PARAMETER d1-02 FOR NEW 40Hz SETTING
PARAMETER d1-03 FOR NEW 30Hz SETTING
PARAMETER A1-01 CHANGE TO 0
0-10 VDC CONTROL SIGNAL (BY OTHERS)
WIRED TO A1 (+) AND AC (COMMON)
0 VDC=30 Hz
10 VDC=60 Hz
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4SC
NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 40 Hz.
S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.
MA MB MCACAMAC+VA1SCS5S4S3S2S1
Factory Set Points
Variable frequency drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:
• Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30
and 60Hz
• Multi-Speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
- Open - Drive runs at 60Hz
- SC to S4 - Drive runs at 40Hz
- SC to S5 - Drive runs at 30Hz
• CO
Sensor:
2
Set Point Control: A carbon dioxide sensor is
provided from the factory for field-mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with two preset speeds of 700
PPM or less CO2 = 50% fan speed and 800 PPM
or greater CO2 = 100% fan speed.
Proportional Control: A carbon dioxide sensor is
provided from the factory for field-mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with default factory settings
of 500 PPM or less CO2 = 50% fan speed and
1000 PPM or greater CO2 = 100% fan speed.
Modulation of VFD occurs proportional to CO
2
between 500 and 1000 PPM.
The terminal locations for Modulating and Multi-speed
are shown on the previous page. Most of the set points
in the VFDs are Yaskawa factory defaults. However, a
few set points are changed at Greenheck and are shown
in the tables. These settings are based on the VFD
mode selected.
Change Set Points
To gain access to change set points on the V1000 and
J1000 drives, parameter A1-01 needs to be set at “2”.
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.
• Drive Operation
- SC to S1 contact for On/Off
- A1 (0-10 VDC) referenced to AC
Can use +15 VDC from +V
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”. Then
go to A1-03 and change it to “1110” and press enter.
The drive is now reset back to the settings programmed
at Greenheck. This option is not available on the J1000.
Energy Recovery Ventilator with Tempering
25
Page 26
Modulating Control for Fan Speed
(0-10 VDC)
Parameter
Setting
V1000J1000
A1-01Access Level22
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
Motor
FLA
Motor
FLA
H2-01Terminal MA, MC Function55
H3-04Terminal A1 Bias50%50%
L4-01H2-01 Frequency Detection1515
L5-01Auto Restart Attempt55
A1-01Access Level00
CO2 Proportional Control
Parameter
Setting
V1000J1000
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLAFLAFLA
H3-03
H3-04
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
150%150%
25%25%
L2-01Ride Thru Power Loss22
L4-05Frequency Ref Loss0NA
L5-01Auto Restart Attempt55
A1-01Access Level00
CO2 Sensor Control for Fan Speed
(1/2 speed when CO2 drops below 700 PPM)
(Full speed when CO2 rises above 800 PPM)
Multi-Speed Control for Fan Speed
(1/3 or 1/2 speed reduction)
Parameter
Setting
V1000J1000
A1-01Access Level22
B1-01Reference Source (Frequency)00
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D1-01Frequency Reference 160 Hz60 Hz
D1-02Frequency Reference 240 Hz40 Hz
D1-03Frequency Reference 330 Hz30 Hz
D1-04Frequency Reference 460 Hz60 Hz
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H1-04
H1-05
H1-06
Multi-Function Input Sel 4
(Terminal S4)
Multi-Function Input Sel 5
(Terminal S5)
Multi-Function Input Sel 6
(Terminal S6)
Motor
FLA
33
44
5NA
Motor
FLA
H2-01Terminal MA, MC Function55
H3-10A2 Not UsedFNA
L4-01H2-01 Frequency Detection1515
L5-01Auto Restart Attempt55
A1-01Access Level00
Variable Frequency Drives for
Energy Recovery Wheel
ParameterSetting – J1000
A1-01Access Level2
B1-17VFD Auto Start1
C1-04Decel Time600
*C4-01Torque Gain0.6
C6-02Carrier Frequency2
D2-01Ref Upper Limit40 or 50*
D2-02Ref Lower Limit5%
E2-01Motor Rated FLAMotor FLA
E2-03Motor No-Load Current
H1-02
H2-01
H1-04
Multi-Function Input
(Terminal S2)
Multi-Function Output
(MA, MB, MC)
Multi-Function Input Sel 4
(Terminal S4)
Economizer Signal Source
(0-10 VDC)
H3-03
H3-04
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
Must be less than
FLA
6
4
7
Setting
Honeywell
Module
Controller
0
40 or
50**
L1-01Elect Thermal Overload2
L2-01Ride Thru Power Loss2
L4-01Frequency Detection Level15
L5-01Auto Restart Attempt5
A1-01Access Level0
* 208/230 volt only
**36 through 52 inch wheels are 40 (24 Hz)
58 or 74 inch wheel is 50 (30 Hz)
Carel
40 or
50*
0
Energy Recovery Ventilator with Tempering
26
Page 27
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to the unit to
OFF at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and serious
injury may occur.
This unit requires minimal maintenance to operate
properly. Maintenance requirements for this model
vary for each installation and depend greatly on how
much the system is used and the cleanliness of the air.
Proper maintenance will both increase the life of the
system and maintain its efficiency. Maintenance must
be performed by experienced technicians and in the
case of refrigeration systems, must be done by an EPA
certified technician.
Maintenance frequency is based on a presumed
nominal use of the system. If the system is being
run constantly, the frequency should be adjusted
accordingly. If there is seasonal debris in the air which
can be drawn into the filters and the coils, they should
be checked more frequently. If the system is being
used for only a few hours per day, the frequency may
be reduced. Use the maintenance log at the end of
this manual to record each maintenance session
and observations and then establish a maintenance
schedule that is appropriate for the installation. The
following is provided as a guideline:
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit startup checklist provided in the manual to ensure the
refrigeration system operates in the intended matter.
1. Lubrication
Apply lubricant where required
2. Dampers
Check for unobstructed operation
3. Blower Wheel and Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
4. Door Seal
Check if intact and pliable
5. Wiring Connections
Check all connections for tightness
6. Cabinet
Check entire cabinet, inside and out, for dirt
buildup or corrosion. Remove accumulated dirt,
remove any surface corrosion and coat the area
with appropriate finish.
Adjust replacement schedule for MERV 13 or
other filters as inspection requires.
Semiannually
1. Check motor and motor bearings
Check for excessive heat, vibration or noise.
Lubricate bearings in accordance with the motor
manufacturer’s recommendations.
2. Condensate Drain (if applicable)
Inspect and clean – refill with water
3. Wrap-Around Heat Pipe
Inspect for cleanliness – clean as required
Energy Recovery Ventilator with Tempering
27
Page 28
Maintenance Procedures
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate this unit without the filters and
birdscreen installed. They prevent the entry of foreign
objects such as leaves, birds, etc. Do not remove
access panels or other unit components while
standing on a ladder or other unsteady base. Access
panels and unit components are heavy and serious
injury may occur.
Lubrication
Check all moving components for proper lubrication.
Apply lubricant where required. Any components
showing excessive wear should be replaced to maintain
the integrity of the unit and ensure proper operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Fan Belts
Belts must be checked on a regular basis for wear,
tension, alignment, and dirt accumulation. Premature
or frequent belt failures can be caused by improper
belt tension (either too loose or too tight) or misaligned
sheaves. Abnormally high belt tension or drive
misalignment will cause excessive bearing loads and
may result in failure of the fan and/or motor bearings.
Conversely, loose belts will cause squealing on start-up,
excessive belt flutter, slippage, and overheated sheaves.
Both loose and tight belts can cause fan vibration.
When replacing belts on multiple groove drives, all belts
should be changed to provide uniform drive loading. Do
not pry belts on or off the sheave. Loosen belt tension
until belts can be removed by simply lifting the belts off
the sheaves. After replacing belts, ensure that slack in
each belt is on the same side of the drive. Belt dressing
should never be used.
Do not install new belts on worn sheaves. If the sheaves
have grooves worn in them, they must be replaced
before new belts are installed.
The proper belt setting is the lowest tension at which the
belts will not slip under
Deflection =
peak load operation.
For initial tensioning,
set the belt deflection at
1/64-inch for each inch
of belt span (measured
half-way between sheave
Belt Span
centers). For example, if
the belt span is 64 inches, the belt deflection should be
one inch (using moderate thumb pressure at mid-point
of the drive). Check belt tension two times during the
first 24 hours of operation and periodically thereafter.
Belt Span
64
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper cooling. Never washdown the motor with high pressure spray. Greasing
of motors is only intended when fittings are provided.
Fan motors typically have two grease fittings. Each
motor manufacturer has different lubrication schedules
for different models. Go to the motor manufacturer’s
website and download their maintenance requirements.
Do not over-lubricate motors or use an incompatible
grease. Many fractional motors are permanently
lubricated for life and require no further lubrication.
Fan Wheel and Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs, the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion, or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20° to 120°F and in a relatively clean
environment. Some bearings are relubricatable and will
need to be regreased depending on fan use. Check your
bearings for grease zerk fittings to find out what type
of bearing you have. If your fan is not being operated
under normal use, bearings should be checked monthly
for lubrication.
Shaft bearings are the most critical moving part of a
fan. Therefore, special attention should be given to
keeping the bearings clean and well lubricated. Proper
lubrication provides for reduction in friction and wear,
transmission and dissipation of heat, extended bearing
life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper
grease applied at regular intervals is required.
If unusual conditions exist—temperatures below 32°F or
above 200°F, moisture or contaminants—more frequent
lubrication is required.
With the unit running, add grease very slowly with a
manual grease gun until a slight bead of grease forms at
the seal.
Be careful not to unseat the seal by over lubricating
or using excessive pressure. A guide to the amount
of grease to be used is to fill 30% to 60% of available
space in the bearing and housing.
A high quality lithium based grease conforming to NLGI
Grade 2 consistency should be used.
Energy Recovery Ventilator with Tempering
28
Page 29
Internal Filter
The unit will typically be provided with 2-inch thick
pleated paper filters in the airstream. These filters
should be checked according to a routine maintenance
schedule and replaced as necessary to ensure proper
airflow through the unit. Replacement filters shall be of
same performance and quality as factory-installed filters.
Filters upstream of the coil should be checked regularly.
If the filters are dirty, they should be cleaned or
replaced. It is important the filters stay clean to maintain
desired airflow.
Internal Filter Size and Quantities
Model
ERT-4520 x 2533
ERT-5516 x 2066
ERT-9020 x 2088
Filter Size
(inches)
Quantity
Supply
Quantity
Exhaust
External Filter
Aluminum mesh, 2-inch thick filters are located in
the supply weatherhood (if
the weatherhood option was
purchased). These filters should
be checked and cleaned on a
regular basis for best efficiency.
The frequency of cleaning
depends upon the cleanliness
of the incoming air. These filters
should be cleaned by rinsing
with a mild detergent in warm
water prior to start-up.
External Filter Size and Quantities
Model
ERT-4516 x 204
ERT-5516 x 206
ERT-9016 x 208
Filter Size
(inches)
Filter
External Filter
Access
Quantity
Coils
Coils must be cleaned to maintain maximum
performance. Check coils once per year under normal
operating conditions and if dirty, brush or vacuum clean.
Soiled fins reduce the capacity of the coil, demand
more energy from the fan and create an environment
for odor and bacteria to grow and spread through the
conditioned zone.
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Care must
be taken not to damage the coils, including the fins,
while cleaning. Caution: Fin edges are sharp!
WARNING
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel only.
Drain pans in any air conditioning unit will have some
moisture in them, therefore, algae and other organisms
will grow due to airborne spores and bacteria. Periodic
cleaning is necessary to prevent this buildup from
plugging the drain and causing the drain pan to
overflow. Inspect twice a year to avoid the possibility
of overflow. Also, drain pans should be kept clean to
prevent the spread of disease.
Winterizing Coils
Coil freeze-up can be caused by such things as air
stratification and failure of outdoor air dampers and/
or preheat coils. Routine draining of water cooling coils
for winter shutdown cannot be depended upon as
insurance against freeze-up. Severe coil damage may
result. It is recommended that all coils be drained as
thoroughly as possible and then treated in the following
manner.
WARNING
Carefully read instructions for mixing antifreeze
solution used. Some products will have a higher
freezing point in their natural state than when mixed
with water.
Fill each coil independently with an antifreeze solution
using a small circulating pump and again thoroughly
drain. Check freezing point of antifreeze before
proceeding to next coil. Due to a small amount of water
always remaining in each coil, there will be diluting
effect. The small amount of antifreeze solution remaining
in the coil must always be concentrated enough to
prevent freeze-up.
Door Seals
An EPDM foam rubber bulb seal backed with a high
strength acrylic adhesive is installed on the door frame
of the unit. This creates and air tight seal between the
rubber seal and the door. Inspect at least annually to
ensure that the seal is damage free and still intact.
Energy Recovery Ventilator with Tempering
29
Page 30
Energy Wheel Maintenance
WARNING
Whenever performing maintenance or inspections,
always disconnect the power source.
Inspection
The wheel should be inspected semiannually
in accordance with the maintenance schedule.
Maintenance of the wheel consists
mainly of inspecting the wheel
for cleanliness and then checking
the drive motor, belt, and pulley
for wear. If the wheel layers
appear dirty, the wheel should be
disassembled and cleaned.
The wheel rotates through the two
airstreams which are moving in
opposite directions, the wheel is
self-cleaning, up to a point. If the
wheel media becomes blocked by
dirt or dust, or if the media collects
Energy Wheel
Cassette
a layer of smoke residue or an oily
film, the energy transfer efficiency drops.
The main factor in the frequency of cleaning is the
cleanliness of the air. If air filters are not changed
frequently, the wheel will collect contaminants and will
then have to be cleaned.
Wheel Disassembly
Wheels are part of a cassette that may be pulled from
the unit for easy access. There may be a small damper
assembly or other component that blocks removal of
the cassette. Before sliding out the cassette or any other
component, disconnect any power supply cord and
secure it so it cannot jam or otherwise get damaged.
Each wheel has removable segments that hold the
coated layers of media and each segment is held in
place with two retaining
clips located on the outer
rim of the wheel. When
removing more than one
segment, remove them in
sequence from opposite
sides of the wheel (180 degrees apart) to reduce the
imbalance. Secure the wheel against rotation. Carefully
release the two retaining clips and swing them fully
open. The segment can now be removed by pushing the
face of the segment close to the outer rim of the wheel.
Wheel segments are built to close tolerances and the
segment may have to be jiggled to remove it. Do not
use a hammer or otherwise force the segment because
these are high value items and are not built to withstand
abuse.
Whenever retaining clips are opened, they should be
closed as soon as possible. If the wheel should rotate
when a clip is open, the clip will jam against the bearing
support bar and could cause damage.
Segment Retaining Clip
Cleaning
Maintenance or cleaning of the wheel segments
should be done with the segments removed from
the wheel cassette to avoid splashing liquids or
cleaning agents inside the cabinet. If the energy wheel
appears excessively dirty, it should be cleaned to
ensure maximum operating efficiency. Only excessive
buildup of foreign materials needs to be removed.
DISCOLORATION AND STAINING OF ENERGY
RECOVERY WHEEL DOES NOT AFFECT ITS
PERFORMANCE.
Thoroughly spray the wheel matrix with a household
cleaner such as Fantastik™ or the equivalent. Gently
rinse with warm water and use a soft brush to remove
any heavy accumulations. A detergent/water solution
can also be used. Avoid aggressive organic solvents,
such as acetone. Wheel segments can be soaked in the
above solution overnight for removal of stubborn dirt or
accumulations.
After cleaning is complete, shake excess water from the
wheel or segments. Dry the wheel or segments before
putting them back into the cassette.
Reassembly
When reinstalling the segments, be sure to install them
with the correct face toward the motor side of the
cassette. Note that one face of each segment is smooth
and the other face has a reinforcing channel or support
cut into the surface.
Wheel Segment
(Pulley Side)
Wheel Segment
(Motor Side)
Wheel Belt
Inspect belts each time filters are replaced. Belts
that look chewed up or are leaving belt dust near the
motor pulley may indicate a problem with the wheel.
Be sure to inspect wheel for smooth and unrestricted
rotation. If a belt requires replacement, contact the
local manufacturer representative. Instructions for
replacement will ship with the new belt.
Wheel Bearing
In the unlikely event that a wheel bearing fails, the
bearing is behind a removable plate on the wheel
support beam (slide cassette halfway out of cabinet to
access). Contact the local manufacturer representative
for detailed instructions on how to replace the bearing.
Energy Recovery Ventilator with Tempering
30
Page 31
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.Replace fuse or reset circuit breaker and check amps.
Blower fails to
operate
Motor starters
“chatter” or do
not pull in
Motor over
amps
Defective motor or capacitor.Replace.
Motor overloaded.Reset VFD and check amps.
Electrical.
Control power (24 VAC) wiring run is too
long. (Resistance should not
exceed 0.75 ohms).
Incoming supply power is less than
anticipated. Voltage supplied to starter coil
must be within +10% / -15% of nominal
voltage stated on the coil.
Static pressures are higher than design.Check for dirty filters. Improve ductwork.
Motor voltage incorrect.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Check for On/Off switches. Check for correct supply voltage.
Check Control wiring.
Shorten wiring run to mechanical room or install a relay to turn
unit on/off. Consult factory for relay information. Increase wire
gauge size so that resistance is 0.75 ohms or less.
Need to increase supply power or use a special control
transformer which is sized for the actual supply power.
Check motor wiring. Check motor nameplate versus supplied
voltage.
See specifications and catalog for fan curves to determine if
horsepower is sufficient.
Improve ductwork to eliminate losses using good duct
practices.
Check maximum motor RPM and compare with catalog data.
Verify that external control wiring is in place if required.
Low airflow
(cfm)
High airflow
(cfm)
Excessive
noise or
vibration
Fan wheels are operating backwards.
Dirty filter.
Leaks in ductwork.Repair.
Elbows or other obstructions may be
obstructing fan outlet.
Motor base or blower loose.Tighten mounting bolts.
Noise being transmitted by duct.
For 3-phase, see Direction of Fan Wheel Rotation in Start-Up
Components section.
Replace filters or follow cleaning procedures in Routine
Maintenance section of this manual.
Correct or improve ductwork.
Check for correct maximum fan RPM. Decrease maximum fan
speed if necessary in the VFD.
Induce Ps into system ductwork. Make sure grilles and access
doors are installed. Decrease fan speed if necessary.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing
collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten
collars and fasteners.
Make sure ductwork is supported properly. Make sure ductwork
metal thickness is sized for proper stiffness. Check duct size at
discharge to ensure that air velocities are not too high.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
Energy Recovery Ventilator with Tempering
31
Page 32
Troubleshooting - Energy Wheel
SymptomPossible CauseCorrective Action
Energy wheel
does NOT turn
Energy wheel
runs intermittently
Air seals are too tight.
Broken belt.Replace.
No power to wheel motor.
Wheel motor overloads are tripping due to
rubbing between wheel and air seals.
See Air Seals in the Start-Up Components, Energy Wheel
section.
Make sure wheel drive is plugged in. Verify power is
available.
Recheck air seals, make sure they are not too tight. See
Adjust the Air Seals in the Start-Up Components, Energy
Wheel section.
Energy Recovery Ventilator with Tempering
32
Page 33
Troubleshooting - Controller Alarms
The first step in troubleshooting the unit is to check
the on-board alarm indicators. Several of the electronic
controls in the unit monitor the system for faults and will
go into alarm, shutting down the unit or a single function
within the unit.
Microprocessor Controller
Check the screen on the
microprocessor for an
alarm condition. If it is in
alarm condition, a message
will show on the screen.
The microprocessor controller is located in the main
control center. If it is in alarm condition, the alarm button
will blink red. Press the alarm button to see the specific
condition or to reset the microprocessor. Refer to the
DDC Installation Operations and Maintenance manual
for detailed information on fault codes and see the unitspecific wiring diagram.
Variable Frequency Drive (VFD)
VFDs have a display screen that will
show an alarm condition. If a fault such
as a voltage spike occurs, the VFD will
go into alarm and will not reset until a
hard restart is performed. See the unitspecific manufacturer’s manual supplied
with the unit. VFDs are located in the
main control center.
Troubleshooting - Economizer
Alarms
Addressing Alarms
Alarms will signify a faulty sensor. When this occurs,
verify all connections to the sensor and controller are
secure. Press enter twice to clear the alarm. If the issue
persists, consult the factory.
Clearing Alarms
Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the
3. ERASE? displays.
4. Press
5. ALARM ERASED displays.
6. Press (escape) to complete the action and return
to the previous menu.
If an alarm still exists after you clear it, it redisplays
within 5 seconds.
(enter).
(enter).
NOTE
Troubleshooting - Rotation Sensor
When the unit is first turned on, the LED on the back of
the sensor should turn on and stay on with the wheel
running.
1. When the wheel is spinning, the contact in the
rotation sensor is closed and the small LED light on
the sensor is ON.
2. When the wheel is stopped, there is a 10-20 second
delay before the sensor will indicate no rotation.
When the sensor indicates no rotation, it opens the
internal contact and the LED light is OFF.
3. If the LED comes on and then shuts off after
5 seconds or less, the sensor is NOT properly
set. Contact manufacturer for adjustment
procedure.
4. If the LED comes on and then shuts off after 10-20
seconds, the sensor is properly set although it is
either to close to the wheel or not close enough.
It should be 4 mm from the wheel. Verify that the
sensor depth was set using the appropriate gauge.
When the wheel is unplugged and the unit is still
powered on:
1. The LED should stay on for 10-20 seconds and then
turn off.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck catalog Energy Recovery Ventilator Model ERT,
provides additional information describing the equipment, fan
performance, available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at: www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.