CAPS 4.18.1634G:\JOBS\TEEN CENTER - LOS ALAMOS.gfcjPage 1 of 2
Page 2
Product IOMs
Mark NameModel Name
ERV-1ERCH
EF-1 ALT. 1GB
EF-4, EF-2, EF-3SP
TEEN CENTER - LOS ALAMOS
CAPS 4.18.1634G:\JOBS\TEEN CENTER - LOS ALAMOS.gfcjPage 2 of 2
Page 3
Document 476054
Model ERCH
®
Energy Recovery Ventilator
with Heating and Cooling
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards,
including environmental. Other considerations may be
required if high winds or seismic activity are present.
If more information is needed, contact a licensed
professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CE) in Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affect motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Verify that the power source is compatible with the
equipment.
6. Never open access doors to the unit while it is
running.
DANGER
• Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
• If this unit is equipped with optional gas
accessories, turn off gas supply whenever power is
disconnected.
CAUTION
This unit may be equipped with a compressed
refrigerant system. If a leak in the system should
occur, immediately evacuate and ventilate the area.
An EPA Certified Technician must be engaged to
make repairs or corrections. Refrigerant leaks may
also cause bodily harm.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
WARNING
The roof lining contains high voltage wiring. To
prevent electrocution, do not puncture the interior or
exterior panels of the roof.
®
Energy Recovery Ventilator with Heating and Cooling1
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
2
®
Page 5
Receiving
Upon receiving the product check to make sure all items
are accounted for by referencing the bill of lading to
ensure all items were received. Inspect each crate for
shipping damage before accepting delivery. Notify the
carrier if any damage is noticed. The carrier will make
notification on the delivery receipt acknowledging any
damage to the product. All damage should be noted on
all the copies of the bill of lading which is countersigned
by the delivering carrier. A Carrier Inspection Report
should be filled out by the carrier upon arrival and
reported to the Traffic Department. If damaged upon
arrival, file claim with carrier. Any physical damage to
the unit after acceptance is not the responsibility of
manufacturer.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C)
and 110°F (43°C) (wide temperature swings may
cause condensation and “sweating” of metal parts).
All accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all unit parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lintfree cloths. Polish any remaining rust from surface
with crocus cloth or fine emery paper and oil. Do not
destroy the continuity of the surfaces. Wipe thoroughly
clean with Tectyl® 506 (Ashland Inc.) or the equivalent.
For hard to reach internal surfaces or for occasional
use, consider using Tectyl® 511M Rust Preventive or
WD-40
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
2. Rotate the fan wheel(s) by hand and assure no parts
® or the equivalent.
bearings, drive, motor base, and accessories for
tightness.
are rubbing.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®3
Page 6
Product Overview
The model ERCH combines the benefits of energy
recovery and many combinations of supplemental
heating and cooling. Heating sources include indirect
gas, electric, hot water, and water-source heat pump.
Cooling sources include, packaged direct expansion,
split direct expansion, chilled water, and water-source
heat pump. Indirect evaporative and indirect/direct
evaporative cooling is also available in this platform.
This product is specifically designed to process 100%
outdoor air to desired supply conditions. Four housing
sizes provide air flow capacities from 1,000 CFM to
10,000 CFM with external static pressures up to
1.75in.wg.
Tons
Model
ERCH-204, 5, 6, single stage4, 5, 6, 7 single stage
ERCH-458, 10, 12.5, 158, 10, 11, 12.5, 14
ERCH-5515, 17.5, 2015, 16, 19
ERCH-9020, 25, 3020, 22, 24, 27, 30
Water-Source
Heat Pump
Packaged Direct
Expansion
Optional Subassemblies
Dampers
There are four locations where dampers can be
installed. Low leakage or insulated low leakage
motorized dampers can be added in the outdoor
airstream and/or return airstream. An unoccupied
recirculating air damper is also available. A backdraft
damper is standard in the exhaust hood.
Filters
There is the option of either two-inch thick MERV 8
or MERV 8 and 13 pre-filters in the outdoor airstream
and MERV 8 filters in the exhaust airstream. There are
also permanent washable aluminum mesh filters in the
optional weatherhood.
Backdraft
Permanent
Aluminum
Mesh Filters
Motorized Outdoor
Exhaust Damper
Exhaust
Weatherhood
Ooutdoor Air
Weatherhood
Air Damper
Two-inch thick MERV 8 or MERV
8 and 13 pleated filters
Two-inch thick MERV 8
pleated filters
Wheel Cassette
Filters
Motorized Return Air
Damper
Electrical Box
Return Air
Filters
Coil Section
Motorized Recirculating Air Damper
Intake
Hot Water / Chilled Water Coils
Water coils can be used for a single purpose such
as heating or cooling, or their function can be
alternated between heating and cooling by changing
the temperature of the water flowing through the coil.
Depending on the application, it may be necessary to
use a glycol mixture to prevent the liquid from freezing.
The water coils are engineered to operate at pressures
up to 250 PSIG and temperatures up to 300°F, but
ancillary equipment such as valves and pumps will often
dictate lower operating temperatures. All water coils
are pressure tested at the factory with 450 PSIG of dry
nitrogen.
Steam Coils
Steam coils are used for heating applications and are
built to operate at pressures of up to 125 PSIG with
a maximum temperature of 353°F. They are pressure
tested with 600 PSIG of dry nitrogen. The most frequent
use of steam coils is for retrofitting or modifying existing
steam heat systems.
Evaporative Cooler
Evaporative cooling modules
include Munters® CELdek®
media (GLASdek® optional)
and a stainless steel frame.
Evaporative cooling media is
12 inches in depth and capable
of 90% cooling effectiveness.
A cooling module in the
exhaust airstream for indirect
evaporative cooling is
standard. For combination
indirect and direct evaporative cooling, an evaporative
section may also be added to the outdoor air stream.
Optional features include an automatic drain and fill with
freeze protection.
Packaged Direct Expansion (PDX)
The DX system comes fully charged from the factory
with refrigerant and is ready for installation upon arrival.
The smaller tonnage units (4-7 tons) contain a single
compressor, allowing for one stage of cooling. Larger
units (8-30 tons) come standard with two compressors
This allows for staging of compressors to meet a wider
range of outdoor air loads with reducing the amount of
cycles per compressor.
Integral Components
All units are provided with an expansion valve, hermetic
scroll compressor(s), liquid line filter drier, high pressure
manual reset cutout, low pressure auto-reset cutout,
time delays for compressor protection, service/charging
Indirect Gas Heater
valves, moisture indicating sight glass, and optional hot
gas bypass. The compressors also come standard with
a crankcase heater for additional protection.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
4
®
Page 7
Split DX
The unit is equipped with an evaporator coil that
will be connected to a separate condensing unit
(provided by others). Depending on controlling options,
the condensing unit will be controlled by others or
an integral unit microprocessor controller. Piping
components such as thermostatic expansion valve, filter
drier, sight glass, etc., shall be field-provided.
Heat Pump Module
Units with an optional, integral heat pump module
contains hermetic scroll-type compressor(s), a coaxial
refrigerant-to-water heat exchanger(s), refrigerant flow
reversing valve(s), expansion valve(s), liquid line filter
drier, high pressure manual reset cutout, crankcase
heater(s) and various sensors, service ports and safety
devices. The heat pump is intended to be connected to
an external water source such as a water cooling tower,
boiler, or a geothermal source. The module is piped
to the airside coil located in the supply airstream and
optionally to a reheat coil that will control humidity. The location of components in the module will vary.
Control circuitry and the
Unit Protection Module
(UPM) for the heat pump
will be provided by the
factory. The UPM is a
printed circuit board and
has LED fault indicator
lights to indicate various
alarm conditions and also
power status. A unitspecific schematic for
electrical circuits is located in the control center and
another unit-specific schematic for heat pump circuitry
and UPM are located in the heat pump module.
Unit Protection Module
(UPM)
Electric Post-Heaters
The optional post-heater is used as a heat source for
the building and is integrated into the supply airstream.
A temperature sensor (with a field-adjustable set point)
is mounted in the supply airstream after the post-heater
to turn the post-heater on. A SCR heater allows for
an infinite amount of modulating control of the heat to
provide an accurate discharge temperature during the
call for heat.
As standard, the post-heater control panel is not single
point wired to the unit control center. Separate power
must be supplied to the post-heater disconnect (located
in unit control center). Electric heaters are available in
208, 230, 460, or 575 VAC (refer to heater nameplate for
voltage).
Indirect Gas Furnace
An optional indirect gas
furnace may be installed and
provides supplementary heat
to the building. Refer to the
PVF/PVG Indirect Gas-Fired
Heat manuals provided with
the unit. A unit-specific wiring
diagram is located inside the
furnace housing access door.
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory-mounted.
Exhaust Air Weatherhood
The exhaust weatherhood is shipped separately as a
kit with its own instructions. Backdraft dampers are
always included as an integral part of the exhaust hood
assemblies.
High Efficiency
Scroll Type
Compressors
Coaxial
Refrigerant-
to-Water Heat
Exchangers
Heat Pump Module
Refrigerant
Reversing
Valves
Water Intake
and Discharge
Connections
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®5
Page 8
Installation
Unit Dimensions and Weights
Model
ERCH-20
ERCH-45
ERCH-55
ERCH-90
Overall Exterior Dimensions
ConfigurationLengthWidthHeight
Heating Only76.2
Exhaust
Hood
Outdoor Air
Hood
Approximate
Weight
(lbs)
1550
Cooling Coil*96.21825
PDX
WSHP2375
108.2
54.354.220.817.7
2350
Evap Cooling1800
Heating Only84.3
2325
Cooling Coil*104.32725
PDX
WSHP3775
119.3
64.470.220.721.7
3675
Evap Cooling2900
Heating Only97.5
3000
Cooling Coil*116.53475
PDX
WSHP4725
133.5
75.27123.621.7
4125
Evap Cooling3325
Heating Only109.5
4300
Cooling Coil*129.55050
PDX
WSHP6450
151.5
94.58925.526.7
6325
Evap Cooling5400
*With or without heat.
PDX = Packaged Direct Expansion
WSHP = Water-Source Heat Pump
All dimensions are in inches. Unit weights assume rooftop configuration with weatherhood, filters, outdoor air damper and
heating or cooling options (where applicable) including but not limited to: a six row dx coil, integral condensing section and
an indirect gas-fired furnace. The approximate weight (lbs) is assuming all possible accessories are added per housing and
may vary by 10% depending on unit.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
6
®
Page 9
Installation
Curb Outside Dimensions, Recommended Roof Openings and Curb Weights
ModelConfiguration
Heating Only71.849.9
Cooling Coil*91.849.9
ERCH-20
PDX
WSHP
Evap Cooling28.3
Heating Only79.960
Cooling Coil*99.960
ERCH-45
PDX
WSHP
Evap Cooling31.8
Heating Only93.170.8
Cooling Coil*112.170.8
ERCH-55
PDX
WSHP
Evap Cooling38.3
Heating Only105.190.1
Cooling Coil*112.170.8
ERCH-90
PDX
WSHP
Evap Cooling39.1
Outside
Curb
Dimensions
Recommended
Roof
Openings
Optional
Piping
Vestibule
Length WidthABCD
12.3134157+6.9+8.3
32.8
NANANA
12.3157180+8.0+9.4
32.8
NANANA
12.3184207+9.3+10.7
32.8
NANANA
12.3231254+11.2+12.6
32.8
NANANA
103.849.9
114.960
129.170.8
147.190.1
28.3
42.5
31.8
43.8
38.3
57.8
39.1
61.4
43.530
54.835.1
63.541.8
79.451.1
12 inch
Curb
Weight
12 inch
Curb
Weight
with Piping
Vestibule
Curb
weight
only
Adder per inch
Curb Weight
with Piping
Vestibule
147179+7.7+9.5
166
199
+8.3
+10.1
170202+8.8+10.6
195
228
+9.5
+11.4
196228+10.1+11.9
228
260
+10.9
+12.7
196228+12+13.8
291
323
+13.1
+14.9
*With or without heating.
PDX = Packaged Direct Expansion
WSHP = Water-Source Heat Pump
All dimensions are in inches. All weights are in pounds. Various curb heights are available, use the adder per inch column to
determine the weights above 12 inches.
L
A
RETURN AIR INTAKE
W
SUPPLY AIR
DISCHARGE
OPTIONAL
PIPING VESTIBULE
CD
26.1 inches
B
1-inch Foam Insulation
Curb Duct
Adaptor
1.9 inches
1/2 inch
Curb
Unit Base
1.63
inches
1 inch
Curb
Height
Curb Cap Details for Factory-Supplied Roof Curbs
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®7
Page 10
Service Clearances / Access Panel - Heating Only
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
OUTDOOR AIR FILTERS
*CASSETTE REMOVAL
WHEEL CASSETTE
ACCESS DOOR
EXHAUST FILTERS
HEATING COIL
ACCESS DOOR
ELECTRICAL BOX
ModelA (in.)B (in.)
ERCH-204836
ERCH-456442
ERCH-554242
ERCH-904248
A
52 inches
CLEARANCE WITH
IG HEATER
0 inches
CLEARANCE WITHOUT
IG HEATER
INDIRECT GAS FURNACE
36 inches
ACCESS DOOR
PIPING VESTIBULE
(OPTIONAL)
ACCESS DOOR
Drawing shows both heating coil and indirect gas furnace options. Electric heat is also available. Only one can
be selected.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
8
®
Page 11
Service Clearances / Access Panel - Cooling Coil (with or without heating)
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
OUTDOOR AIR FILTERS
*CASSETTE REMOVAL
WHEEL CASSETTE
ACCESS DOOR
EXHAUST FILTERS
COOLING COIL
ACCESS PANEL
A
HEATING COIL
ACCESS DOOR
ELECTRICAL BOX
ModelA (in.)B (in.)
ERCH-204836
ERCH-456442
ERCH-554242
ERCH-904248
52 inches
CLEARANCE WITH
IG HEATER
0 inches
CLEARANCE WITHOUT
IG HEATER
INDIRECT GAS FURNACE
ACCESS DOOR
48 inches
CLEARANCE
WITH
VESTIBULE
36 inches
CLEARANCE
WITHOUT
VESTIBULE
ACCESS DOOR
PIPING VESTIBULE
(OPTIONAL)
Drawing shows both heating coil and indirect gas furnace options. Only one can be selected.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®9
Page 12
Service Clearances / Access Panel - Integral Air-Cooled Packaged DX
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
EXHAUST AIR
WEATHERHOOD
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
OUTDOOR AIR FILTERS
*CASSETTE REMOVAL
WHEEL CASSETTE
ACCESS DOOR
ACCESS DOORS
ELECTRICAL BOX
EXHAUST FILTERS
COOLING COIL
ACCESS PANEL
HEATING COIL
HGRH COIL
A
ACCESS DOOR
ACCESS PANEL
ACCESS PANEL
COMPRESSORS
ACCESS PANEL
ModelA (in.)B (in.)
ERCH-204836
ERCH-456442
ERCH-554242
ERCH-904248
42 inches
MINIMUM
CONDENSING SECTION
36 inches
CLEARANCE
WITHOUT
VESTIBULE
PIPING VESTIBULE
(OPTIONAL)
48 inches
CLEARANCE
WITH
VESTIBULE
Drawing shows both heating coil and indirect gas furnace options. Electric heat is also available. Only one can
be selected. Optional hot gas reheat coil also shown, available with split or packaged DX.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
10
®
Page 13
Service Clearances / Access Panel - Water-Source Heat Pump
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
OUTDOOR AIR FILTERS
*CASSETTE REMOVAL
WHEEL CASSETTE
ACCESS DOORS
ELECTRICAL BOX
EXHAUST FILTERS
HEATING AND
COOLING COIL
ACCESS PANEL
ModelA (in.)B (in.)
ERCH-204836
ERCH-456442
ERCH-554242
ERCH-904248
A
ACCESS PANEL
ACCESS DOOR
HEAT PUMP
42 inches
HGRH COIL
ACCESS DOOR
Drawing shows optional hot gas reheat coil.
ACCESS DOOR
36 inches
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®11
Page 14
Service Clearances / Access Panel - Evaporative Cooling
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
EXHAUST AIR
WEATHERHOOD
OUTDOOR AIR FILTERS
*CASSETTE REMOVAL
WHEEL CASSETTE
ACCESS DOORS
INDIRECT
EVAP
DIRECT
EVAP
ModelA (in.)B (in.)
ERCH-204836
ERCH-456442
A
ACCESS DOOR
ELECTRICAL BOX
EXHAUST FILTERS
ERCH-554242
ERCH-904248
52 inches
CLEARANCE WITH
IG HEATER
0 inches
CLEARANCE WITHOUT
IG HEATER
INDIRECT GAS FURNACE
ACCESS DOOR
ACCESS DOOR
ACCESS DOOR
36 inches
Drawing shows optional indirect gas furnace. Electric heat is also available. Only one can be selected.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
12
®
Page 15
Handling
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation. Exercise extreme
caution to prevent any damage from occurring to the
refrigerant system. This unit could contain a system
pressurized with refrigerant that, if damaged, could
leak into the atmosphere or cause bodily harm due to
the extreme cold nature of expanding refrigerant. Use
protective equipment such as gloves and safety glasses
to minimize or prevent injury in case of a system leak
during installation.
The system design and installation should follow
accepted industry practice, such as described in
the ASHRAE Handbook. Adequate space should be
left around the unit for piping coils and drains, filter
replacement, and maintenance. Sufficient space should
be provided on the side of the unit for routine service
and component removal should that become necessary.
Lifting
WARNING
All factory-provided lifting lugs must be used when
lifting the units. Failure to comply with this safety
precaution could result in property damage, serious
injury, or death.
1. Before lifting, be sure that all shipping material has
been removed from unit.
2. To assist in determining rigging requirements,
weights are provided in the Installation, Unit
Dimensions and Weights section of this manual.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach to
unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to lifting
the unit and setting on curb.
11. Do not use fork lifts for handling unit.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®13
Page 16
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
Position the unit roof opening such that the supply
discharge and exhaust inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening.
Do not face the outdoor air intake of the unit into
prevailing wind and keep the intake away from any other
exhaust fans. Likewise, position the exhaust discharge
opening away from outdoor air intakes of any other
equipment.
1. Factory-Supplied Roof Curbs: Roof curbs are
Model GKD, which are shipped in a knockdown kit
(includes duct adapter) and require field assembly
(by others). Assembly instructions are included with
the curb.
2. Install Curb: Locate curb over
roof opening and fasten
in place. Reference
Installation, Curb
Outside Dimensions,
Recommended
Roof Openings
and Weights in this
manual. Check
that the diagonal
dimensions are within
±1/8 inch of each
other and adjust as
necessary. For proper
coil drainage and
unit operation, it is
important that the
installation be level.
Shim as required to
level.
3. Install Ductwork: Installation of all ducts should
be done in accordance with SMACNA and AMCA
guidelines. Duct adapter provided to support ducts
prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above the
curb and duct openings. Guide unit while lowering
to align with duct openings. Roof curbs fit inside the
unit base. Make sure the unit is properly seated on
the curb and is level. Gasketing (by others) needs
to be installed to curb creating a seal between the
ductwork and the base of the unit.
5. Install Vestibule: If unit was ordered with a vestibule
and it has not yet been attached to the unit, caulk
and attach the vestibule at this time.
Optional Piping Vestibule
Insulated enclosure that is mounted externally to the
unit in order to protect the water supply and return
piping. Not available in models with water-source heat
pump or evaporative cooling.
Supply Blower
Access Door
Drain Pan
Connection
Exhaust Blower
Access Door
Outdoor Air
Weatherhood
Cassette/Filter
Access Door
Cooling Coil (with or without heating) or PDX
Exhaust Blower
Access Door
Outdoor Air
Weatherhood
Cassette/Filter
Access Door
Heating Only
Configuration
Unit SizeHeating OnlyCooling Coil
ERCH-20130190
ERCH-45160225
ERCH-55160225
ERCH-90190265
All weights are in pounds.
Piping
Vestibule
Supply Blower
Access Door
Piping
Vestibule
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
14
®
Page 17
R
o
t
a
t
i
o
n
POOR
Rail Mounting / Layout
1. Rails designed to handle the weight of the unit
should be positioned as shown on the diagram (rails
by others).
2. Make sure that rail positioning does not interfere with
the supply air discharge opening or the exhaust air
intake opening on the unit. Avoid area dimensioned
“B” below.
3. Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM) at
minimum airflow and up to 1600 fpm at maximum airflow.
• Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
RITReturn Air Intake TopEDTExhaust Discharge Top
SDESupply Discharge EndEDSExhaust Out Side
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®15
Page 18
Electrical Installation
WARNING
The roof lining contains high voltage wiring. To prevent
electrocution, do not puncture the interior or exterior
panels of the roof.
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
For units with a gas furnace, if you turn off the power
supply, turn off the gas.
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest
edition of the National Electrical Code ANSI/NFPA70
and any local codes that may apply. In Canada, wiring
should be done in accordance with the Canadian
Electrical Code.
IMPORTANT
The equipment must be properly grounded and
bonded. Any wiring running through the unit in the
airstream must be protected by metal conduit, metal
clad cable or raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105°C, except for an
energy cut-off or sensor lead wire which must be rated
to 150°C.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
WARNING
If unit is equipped with a microprocessor, terminals
Y1, Y2 and W1 cannot be wired to a thermostat.
Wiring to these terminals will bypass unit’s internal
safeties.
1. Determine the Size of the Main Power Lines
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.
2. Determine the Size of Electric Heater Wiring
An optional electric heater may require a separate
power supply. The power connection should
be made to the factory-provided electric heater
disconnect and must be compatible with the ratings
on the nameplate, supply power voltage, phase and
amperage. Consult ANSI/NFPA 70 and CSA C22.1
for proper conductor sizing.
3. Provide the Opening(s) for the Electrical
Connections
Electrical openings vary by unit size and arrangement
and are field-supplied.
4. Connect the Power Supplies
Connect the main power lines and electric heater
power lines to the disconnect switches or terminal
blocks and main grounding lug(s). Torque field
connections to manufacturer’s recommendations.
5. Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V
power supply circuit. The circuit must include short
circuit protection which may need to be supplied by
others.
6. Connect Field-Wired Low Voltage Components
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field-wiring, refer to the unitspecific wiring diagram located on the inside of the
control center access door.
If unit is equipped with a microprocessor, terminals Y1,
Y2 and W1 cannot be wired to a thermostat. Wiring to
these terminals will bypass unit’s internal safeties.
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that
field-supplied conduit does not interfere with access
panel operation. All low voltage wiring should be run in
conduit wherever it may be exposed to the weather.
The low voltage control circuit is 24 VAC and control
wiring should not exceed 0.75 ohms. If wire resistance
exceeds 0.75 ohms, an isolation relay should be added
to the unit control center and wired in place of the
remote switch (typically between terminal blocks R
and G on the terminal strip. The relay must be rated
for at least 5 amps and have a 24 VAC coil. Failure to
comply with these guidelines may cause motor starters
to “chatter” or not pull in which can cause contactor
failures and/or motor failures.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
16
®
Page 19
Field-Provided Disconnect
If field-installing an additional disconnect switch, it
is recommended that there is at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
Typical Control Center Components with
Microprocessor Control
8
1
5
Discharge Air Temperature Sensor
Without Indirect Gas Furnace
For units without an indirect gas furnace, the discharge
air temperature sensor is factory-mounted in the blower
discharge section of the unit behind the blower cut off
plate.
WARNING
Discharge air temperature sensor is to be fieldinstalled prior to unit start-up on units with an indirect
gas furnace.
With Indirect Gas Furnace
For units with an indirect gas furnace, the discharge
air temperature sensor is to be
field-installed prior to unit start
up at least three duct diameters
downstream of the heat exchanger
or where good mixed average
temperature occurs in the ductwork.
The discharge air sensor is shipped
loose and can be found in the unit’s
control center. See the unit-specific
wiring diagram for connection locations.
1010
15
1616
17
9
77
2
3
17
11
6
4
14
13
12
Individual components and locations will vary.
1. Main disconnect (non-fusible, lockable)
2. Motor starter - outdoor air fan
3. Motor starter - exhaust air fan
4. Motor contactor - energy wheel
5. 24 VAC control transformer
6. 24 VAC terminal strip
7. Fuses for blower motors
8. Grounding lug
9. Distribution block
10. Compressor fuse blocks
Optional Components
11. Microprocessor controller
12. Dirty filter pressure switches
13. GreenTrol®
14. Frost control pressure switch
15. Energy recovery wheel VFD
16. Compressor contactors
17. Condenser fan contactors
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®17
Page 20
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of different
alarm lights and switches to control the unit. The remote
panel ships loose and requires mounting and wiring in
the field. The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
• Wheel rotation sensor light
Unit Interfacing Terminals
Heating/Cooling Switches and Night Setback Switch/
Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
UNIT ON/OFF
S1
COOL STAGE 1 / ECONOMIZER
S6
COOL STAGE 2
S7
HEAT
S4
C
G
Y1
Y2
W1
6
7
12
7-Day Timer
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
R
BLACKBLUE
RED
(CAPPED)
TIMER
C
G
Y1
Y2
W1
6
7
12
On/Off/Auto Switch & Indictor Light Wiring
TERMINAL BLOCKS IN
UNIT CONTROL CENTER
UNIT ON/OFF
FROST CONTROL
ECONOMIZER
WHEEL ROTATION
ON
OFF
AUTO
* -- BMS, TIMECLOCK,
TSTAT, RTU, ETC.
*
R
C
G
Y1
Y2
W1
6
7
12
UNOCCUPIED RECIRCULATION
S5
Dirty Filter Indicator
(Powered by others)
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
NC
NC
HOTCOMMON
C
C
A
NO
NO
DIRTY FILTER
C
SUPPLY DIRTY
FILTER SWITCH
EXHAUST DIRTY
FILTER SWITCH
ON/OFF/AUTO SWITCH ALLOWS THREE MODES OF OPERATION
"ON" - UNIT IS TURNED ON MANUALLY
"OFF" - UNIT IS TURNED OFF MANUALLY
"AUTO" - UNIT IS CONTROLLED VIA SCHEDULER OF BMS, TIMECLOCK, TSAT, ETC.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
18
NC
NC
NO
C
NO
DIRTY FILTER
®
Page 21
Piping Installation
Optional Gas Piping
Units with indirect gas-fired furnaces require fieldsupplied and installed gas supply piping. The unit gas
connection is
pressure is 14 in. wg.
From Gas Supply
Gas Connections
If this unit is equipped with an indirect gas-fired furnace,
connection to an appropriate gas supply line will be
required. For complete information on installation
procedures for the optional gas furnace, refer the
PVF/PVG Indirect Gas-Fired Heat Module Installation,
Operation, and Maintenance Manual.
Optional Coil Piping
Factory-installed cooling and heating components are
mounted in the coil section of the unit. The coil section
is downstream of the energy wheel on the supply air
side of the unit. Note the coil connection locations on
the picture. Coil connections are located external to the
unit as shown.
Note: DX coil liquid connection is internal to units.
Water Coils
3
⁄4 inch NPT. The maximum allowable gas
Ground
Joint
Gas Cock
Bleeder Valve or
1/8 in Plugged Tap
Typical Gas Supply Piping Connection
Water coil
connections
Union
connection
8 in. Trap
DX coil
liquid
access
door
Gas to
Controls
2. Connect the water supply to the bottom connection
on the air leaving side and the water return to the
top connection on the air entering side. Connecting
the supply and/or return in any other manner will
result in very poor performance. Be sure to replace
factory-installed grommets around coil connections
if removed for piping. Failure to replace grommets
will result in water leakage into the unit and altered
performance.
3. Water coils are not normally recommended for
use with entering air temperatures below 40°F. No
control system can be depended on to be 100% safe
against freeze-up with water coils. Glycol solutions
or brines are the only safe media for operation of
water coils with low entering air conditions. If glycol
or brine solutions are not used, coils must be drained
when freezing conditions are expected. If required,
vent and drain connections must be fieldpiped, external to the unit.
4. Pipe sizes for the system must be selected on
the basis of the head (pressure) available from the
circulation pump. The velocity should not exceed
6 feet per second and the friction loss should be
approximately 3 feet of water column per 100 feet
of pipe.
5. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. Refer to Drain Trap
section.
Direct Expansion (DX) Coils (Split DX)
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should not
be applied at the connection to coil headers.
2. The condensate drain pipe should be sized
adequately to ensure the condensate drains properly.
Refer to Condensate Drain Trap section.
3. When connecting suction and liquid connections
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage. Be
sure to replace factory-installed grommets around
coil connections if removed for piping.
4. Manufacturer does not supply compressor or
condensing units with standard models. For further
instruction on DX coil installation and operation
contact your compressor and/or condenser
manufacturer.
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. When installing couplings,
do not apply undue stress to the connection
extending through the unit. Use a backup pipe
wrench to avoid breaking the weld between coil
connection and header.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®19
Page 22
Condensate Drain Trap
This unit is equipped with a stainless steel condensate
pan with a 1-inch MPT stainless steel drain connection.
It is important that the drain connection be fitted with a
P trap to ensure proper drainage of condensate while
maintaining internal static pressures.
A P trap assembly (kit) is
supplied with each unit and is
to be assembled and installed
as local conditions require and
according to the assembly
instructions provided with the
P trap. If local and area codes
permit, the condensate may
be drained back onto the roof,
but a drip pad should be provided beneath the outlet.
If local and area codes require a permanent drain line,
it should be fabricated and installed in accordance with
Best Practices and all codes.
In some climates, it will be necessary to provide freeze
protection for the P trap and drain line. The P trap
should be kept filled with water or glycol solution at
all times and it should be protected from freezing to
protect the P trap from damage. If severe weather
conditions occur, it may be necessary to fabricate a P
trap and drain line of metal and install a heat tape to
prevent freezing.
Heat Pump Piping Sizes and Connections
Pipe Size
(in. FPT)
1
1.25
1.5
2
ModelTonnage
ERCH-2042
ERCH-4582
ERCH-2052
ERCH-45102
ERCH-2062
ERCH-45
ERCH-55152
ERCH-55
ERCH-90
12.52
152
17.52
202
202
252
302
Number of
Connections
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
20
®
Page 23
Optional Evaporative Cooler
CAUTION
All solenoids valves and traps must be installed below the
roof to protect the supply water line from freezing. If they
cannot be installed below the roof, an alternative method
must be used to protect the lines from freezing.
IMPORTANT
The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.
CAUTION
Provisions must be taken to prevent damage to the
evaporative cooling section during freezing conditions.
The sump, drain lines and supply lines must be drained
prior to freezing conditions or an alternate method must
be used to protect the lines and media.
Recirculating Pump
This option includes a pump that recirculates water over
the evaporative media. The pump is activated by a call
for cooling. A field-adjustable bleed-off valve keeps
mineral concentrations low.
Supply
Line
Supply Line Valve
(Normally Closed)
Drain Line Valve
(Normally Open)
Drain Line
Trap
Recirculating Evaporative Piping
1. Install the Water Supply Line. Supply line opening
requirements vary by unit size and arrangement and
are field-supplied. Connect the water supply line to
the float valve through the supply line opening in
the evaporative cooling unit. Install a manual shutoff
valve in the supply line as shown above.
2. Install the Drain Line. Connect an unobstructed
drain line to the drain and overflow connections
on the evaporative cooler. A manual shut off valve
(by others) is
required for the
evaporative
cooler drain line.
A trap should be
used to prevent
Drain Trap
sewer gas from
being drawn into the unit.
Overflow
6 in. min.
6 in. min.
3. Check/Adjust Water Level. Check the water level in
the sump tank. The water level should be above the
pump intake and below the overflow. Adjust the float
as needed to achieve the proper water level.
Auto Drain and Flush
This option includes a recirculating pump and fieldadjustable timer that will periodically flush the sump to
keep mineral concentrations low.
Sump Overflow
Sump Drain
VALVE C
Sump Drain Solenoid
(Normally Open)
Supply Line Drain Solenoid
VALVE B
(Normally Open)
Auto Drain & Flush Evaporative Piping
Trap
Drain Line
CAUTION
The supply solenoid (Valve A) is NOT the same as the
drain solenoids (Valve B and Valve C). Make sure to
use the proper solenoid for each location. Check your
local code requirements for proper installation of this
type of system.
1. Install the Water Supply Line. Supply line opening
requirements vary by unit size and arrangement and
are field-supplied. Connect the water supply line to
the float valve through the supply line opening in the
evaporative cooling unit. Install the 1/2-inch normally
closed solenoid (Valve A) in the supply line. Install the
1/4-inch normally open solenoid (Valve B) between
the supply line and the drain line.
2. Install the Drain Line. Connect an unobstructed
drain line to the sump drain overflow connection.
Install the 3/4-inch normally open solenoid (ValveC)
between the
sump drain
connection and
the drain line. A
trap should be
used to prevent
Drain Trap
sewer gas from
being drawn into the unit.
3. Check/Adjust Water Level. Check the water level in
the sump tank. The water level should be above the
pump intake and below the overflow. Adjust the float
as needed to achieve the proper water level.
Supply
Line
VALVE A
Supply Solenoid
(Normally Closed)
6 in. min.
6 in. min.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®21
Page 24
Auto Drain & Flush Valves
(when provided by Manufacturer)
Assembly
No.
852178
Mfg
Part No.
ASCO
Part No.
Solenoid
Type
De-Energized
Position
461262 8210G2SupplyClosed
Supply
461263 8262G262
Line
Open
Drain
461264 8210G35
Sump
Drain
Open
Diameter Qty.
1/2-inch
(12.7 mm)
1/4-inch
(6.35 mm)
3/4-inch
(19.05 mm)
1
1
1
Part numbers subject to change.
Water Supply Connection Locations for Evaporative Cooler
Model
Water Supply Connection Locations
ABCD
ERCH-2037.54.54.546
ERCH-4545.254.54.551.5
ERCH-55564.54.557
ERCH-90594.54.568
Dimensions from outside of unit (in inches)
D
C
EXHAUST FILTERS
OUTDOOR AIR
WHEEL CASSETTE
DIRECT
EVAP
INTAKE
Ø0.875 Run 1/4 in. line up through 7/8 in. hole here and
bring around end of sump to supply connection.
1/4 in. water supply connection
ELECTRICAL BOX
INDIRECT
EVAP
RETURN AIR
INTAKE
OUTDOOR AIR FILTERS
1/4 in. water supply connection
Run 1/4 in. line up through 7/8 in. hole here
Ø0.875
and bring around end of sump to supply connection.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
22
B
A
®
Page 25
Unit Overview
Optional Component Overview
Basic Unit
The unit is pre-wired such that when a call for outside
air is made (via field-supplied 24 VAC control signal
wired to unit control center), the supply fan, exhaust fan,
and energy wheel are energized and optional motorized
dampers open.
The unit can be supplied with or without heating and
cooling coils. For units with coils, controls can be
supplied by manufacturer or by the controls contractor.
If supplied by the controls contractor, they would
provide, mount, and wire any temperature controllers
and temperature or relative humidity sensors required
for the unit to discharge air at the desired conditions.
However, temperature, pressure, and current sensors
can be provided by manufacturer for purposes of
monitoring via the BMS.
Summer Operation
Outdoor air is preconditioned (temperature and moisture
levels are decreased) by the transfer of energy from the
cooler, drier exhaust air via the energy recovery wheel.
Units supplied with cooling coils can further cool the
air coming off the wheel and strip out moisture to levels
at or below room design. A heating coil downstream of
the cooling coil can reheat the air to a more comfortable
discharge temperature to the space.
Return Air
75°F
50% RH
Exhaust Air
Supply Air
Outdoor Air
95°F
117 grains/lb.
79°F
75 grains/lb.
Winter Operation
Outdoor air is preconditioned (temperature and moisture
levels are increased) by the transfer of energy from the
warmer, more humid exhaust air via the energy recovery
wheel. Units supplied with heating coils can further heat
the air coming off the wheel to levels at or above room
design.
Economizer
The energy wheel operation can be altered to take
advantage of economizer operation (free cooling).
Two modes are available:
1. Stopping the wheel
2. Modulating the wheel
Stopping the wheel: A field-supplied call for cool (Y1)
is required. De-energizing the wheel is accomplished in
one of three ways:
1. The outdoor air temperature is less than the
outdoor dry bulb set point (DRYBLB SET)
2. The outdoor air temperature is less than the return
air temperature
3. The outdoor air enthalpy is within the preset
enthalpy curve
A low temperature lock out (LOW T LOCK) is also set
to deactivate mechanical cooling when it exceeds
the outdoor air temperature (factory default 32°F).
Effectively, the two sensors create a deadband where
the energy recovery wheel will not operate and free
cooling from outside can be brought into the building
unconditioned.
Modulating the wheel (factory): A variable frequency
drive is fully programmed at the factory. A “call for cool”
must be field-wired to the unit (Terminals provided in
unit. Refer to wiring diagram in unit control center.)
to allow for initiation of economizer mode. The unit
recognizes economizer conditions based one of the
previously mention sensors and set points. The unit will
then modulate the wheel speed to maintain the mixed
air temperature set point (MAT SET).
Modulating the wheel (by others): A variable
frequency drive is fully programmed at the factory.
A field-supplied 0-10 VDC signal will be required for
operation of the energy wheel. The field will be required
to have full control of the energy wheel speed at all
times. If no 0-10 VDC signal is provided, the energy
wheel will run at the factory default of 3 Hz and no
energy transfer will be captured.
Exhaust Air
Outdoor Air
10°F
5 grains/lb.
Return Air
72°F
40% RH
Supply Air
60°F
39 grains/lb.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®23
Page 26
Frost Control
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the energy
recovery wheel. Frost control is an optional feature that
will prevent/control wheel frosting. Three options are
available:
1. Timed exhaust frost control
2. Electric preheat frost control
3. Modulating wheel frost control
All of these options are provided with a thermodisc
mounted in the outdoor air intake compartment and a
pressure sensor to monitor pressure drop across the
energy wheel.
An outdoor air temperature of below 5°F and an
increase in pressure drop would indicate that frost is
occurring. Both the pressure sensor and the outdoor air
thermodisc must trigger in order to initiate frost control.
The two sensors together ensure that frost control is
only initiated during a real frost condition.
Timed exhaust frost control includes a timer in
addition to the thermodisc and wheel pressure sensor.
When timed exhaust frost control is initiated, the timer
will turn the supply blower off. Time exhaust using
default timer setting will shut down the supply fan for
5 minutes every 30 minutes to allow exhaust to defrost
energy wheel. Use the test procedure in the Optional
Start-Up Accessories section for troubleshooting.
Electric preheat frost control includes an electric
heater (at outdoor air intake) in addition to the
thermodisc and pressure sensor on wheel. When
electric preheat frost control is initiated, the electric
preheater will turn on and warm the air entering the
energy wheel to avoid frosting. Use the test procedure
in the Optional Start-Up Accessories section for
troubleshooting.
Modulating wheel frost control includes a variable
frequency drive (VFD) in addition to the thermodisc and
pressure sensor. When modulating wheel frost control
is initiated, the VFD will reduce the speed of the wheel.
Reducing the speed of the energy wheel reduces its
effectiveness, which keeps the exhaust air condition
from reaching saturation, thus, eliminating condensation
and frosting. If the outdoor air temperature is greater
than the frost threshold temperature OR the pressure
differential is less than the set point, the wheel will run
at full speed. If the outdoor air temperature is less than
5°F AND the pressure differential is greater than the
set point, the wheel will run at reduced speed until the
pressure differential falls below the set point. The VFD
will be fully programmed at the factory.
Variable Frequency Drives (VFD)
Variable frequency drives are used to control the speed
of the fan as either multi-speed or modulating control.
Multi-speed VFDs reference a contact which can be
made by a switch or a sensor with a satisfied set point.
Modulating control references a 2-10 VDC signal to the
VFD which will vary the fan speed from a minimum 50%
to full 100% rpm. An optional CO
sensor is available to
2
provide both a set point contact or a modulating 2-10
VDC signal.
CO2 Sensor
This accessory is often used in Demand Control
Ventilation (DCV) applications. The factory-provided
sensors can either be set to reference a set point
for multi-speed operation, or output a 2-10 VDC
signal to modulate the fan speed. These can either
be shipped loose to mount in the ductwork, or can
be factory-mounted in the return air intake. Follow
instructions supplied with sensor for installation and
wiring details.
Phase Monitor
The unit control circuitry includes a phase monitor that
constantly checks for phase reversal or loss of phase.
When a fault is detected, it cuts off the 24 VAC that
goes to the low voltage terminal strip, thereby shutting
down the unit.
Rotation Sensor
The rotation sensor monitors energy wheel rotation. If
the wheel should stop rotating, the sensor will close a
set of contacts in the unit control center. Field-wiring of
a light (or other alarm) between terminals R and 12 in
the unit control center will notify maintenance personnel
when a failure has occurred.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit control
center. Field-wiring of a light (or other alarm) to these
contacts will notify maintenance personnel when
filters need to be replaced. The switch has not been
set at the factory due to external system losses that
will affect the switch. This switch will need minor field
adjustments after the unit has been installed with all
ductwork complete. The dirty filter switch is mounted in
the exhaust inlet compartment next to the unit control
center or in unit control center.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
24
®
Page 27
Microprocessor Control
The microprocessor controller is specifically designed
and programmed to optimize the performance of the
unit with supplemental
heating and cooling. This
option ensures that the
outdoor air is conditioned
to the desired discharge
conditions. The controller and accompanying sensors
are factory-mounted, wired and programmed. Default
settings are pre-programmed, but are easily fieldadjustable.
The microprocessor controller can be interfaced with
a Building Management System through LonWorks®,
BACnet®, or ModBus.
Please refer to the Installation, Operation and
Maintenance manual for detailed information.
Unoccupied Recirculation Damper
The unoccupied recirculation option provides a
recirculation damper from the return air intake to the
supply airstream to reduce heating and cooling loads
when less ventilation is required. During the unoccupied
mode, the exhaust fan will remain off and the supply
air fan will operate with mode of tempering to maintain
unoccupied temperature set point.
Service Outlet
120 VAC GFCI service outlet ships loose for field
installation. Requires separate power source so power
is available when unit main disconnect is turned off for
servicing.
Vapor Tight Lights
Vapor tight lights provide light to each of the
compartments in the energy recovery unit. The lights
are wired to a junction box mounted on the outside of
the unit. The switch to turn the lights on is located in
the unit control center. The switch requires a separate
power source to allow for power to the lights when the
unit main disconnect is off for servicing.
Hot Gas Bypass Valve (standard scroll)
On units equipped with hot gas bypass, hot gas
from the compressor is injected into the liquid line of
the evaporator coil after the thermostatic expansion
valve. This process starts to occur when suction gas
temperatures drop below 28°F, which is 32°-34°F coil
surface temperature. Hot gas helps the evaporator coil
from freezing up and the compressor from cycling. The
valve needs to be adjusted to exact specifications once
unit is installed in the field.
Hot Gas Reheat Valve
Units equipped with a reheat coil
use a three-way valve with actuator
to control the supply air discharge
temperature of the unit during
dehumidification mode. The unit
controller provides a 0-10VDC
signal to control the amount
of reheat to meet the supply
temperature set point.
Digital Scroll Compressor - PDX Only
Refrigeration Modulation
Digital scroll compressors modulate the refrigeration
system, increasing performance. A conventional fixed
scroll compressor runs at full load and then shuts down
when user set points are reached. The digital scroll
compressor modulates its cooling capacity (10-100%)
by means of cycling through rapid load/no-load cycles
without shutting down the compressor motor (digital
control). Because it can operate at less than full load,
evaporator coil temperatures are much more constant
as hysteresis is improved and humidity control is
enhanced.
Electronic Control
The use of a digital
scroll compressor also
requires a controller.
This controller may be
found in the compressor
compartment of the unit.
The controller works
in conjunction with a
microprocessor controller and requires an analog input.
The controller is pre-programmed and wired and does
not require any further servicing by the owner. Detailed
information on the electronic control circuitry will be
found on the unit-specific wiring diagram in the control
center. The controller constantly monitors and controls
the operation of the digital scroll compressor. LED
indicator lights verify the presence of power, operation
of the unloader solenoid and also indicate various alarm
conditions.
Two Compressor Operation Concept
Whenever two compressors are used in a unit, the
digital scroll compressor is part of refrigerant circuit “A”.
A conventional fixed scroll compressor is used for circuit
“B”. The controller requires a 1 VDC signal to verify
control connection at all times. The minimum input
signal that will cause the compressor to run is 1.9 volts
and the maximum is 5 volts (100% cooling). Whenever
there is a call for cooling, circuit A will be activated first.
Circuit A will provide all necessary cooling until the call
for cooling exceeds 50%. When the call for cooling
reaches 50%, the digital scroll will shut down and the
fixed scroll compressor will begin running. Once the
call for cooling exceeds 70%, then the digital scroll will
begin running again, in conjunction with the fixed scroll
compressor.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®25
Page 28
Outdoor Airflow Monitor
A factory-wired, mounted and powered airflow
monitoring system is provided. The airflow control
system offers the following functionality:
• Display of outdoor airflow rate in actual cubic feet
per minute (CFM) or actual liters per second (LPS) on
a 16 character LCD display.
• Two configurable analog outputs for transmitting
outdoor airflow rate, outdoor air temperature, or a
proportional-integral-derivative (PID) control signal
based on an outdoor airflow set point.
• A configurable digital output that operates based on
an airflow set point or range.
Operation
Outdoor airflow monitoring is accomplished using two
thermal dispersion sensors that accurately measure
airflow velocity down to zero feet per minute (fpm). The
airflow controller takes the average measurement for
two sensor configurations, and determines the outdoor
airflow rate based on the effective intake area. Field
calibration of the outdoor airflow monitoring device
determines the effective intake area of the unit.
Refer to GreenTrol® Automation Inc. GF-2200A
technical data sheet for further detail.
Smoke Detector
The Hochiki America DH-98 duct
smoke detector provides early
detection of smoke and products of
combustion present in air moving
through HVAC duct systems. The
DH-98-P is designed to prevent
the recirculation of smoke in areas
by the air handling systems, fans,
and blowers. Complete systems may be shut down
in the event of smoke detection. The Hochiki America
DH-98-P operate on 115 VAC, 24 VAC and 24 VDC.
The DH-98-P is designed and built to meet all local
requirements, as well as the NFPA regulations regarding
duct smoke detectors. Output terminals are provided
for remote accessories such as a horn, strobe, remote
status indicators and reset key switches or push
buttons.
Refer to Hochiki America DH-98-P installation
instructions for further detail.
IMPORTANT
For the outdoor airflow monitoring device to perform
as intended, field calibration is required. Calibration of
the airflow monitoring device requires an independent
measurement of airflow and should be performed
when the system undergoes test and balance.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
26
®
Page 29
Cooling System Overview
Packaged DX Cooling with Digital Scroll Compressor
6
7
8
6
5
Supply
Airflow
10
9
1. Compressor
2. High Limit Pressure Switch
The switch opens when refrigerant pressure
increases above the set point in the liquid line and
it then requires a manual reset.
3. Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a threeway valve with actuator to control the supply
air discharge temperature of the unit during
dehumidification mode. The unit controller provides
a 0-10 VDC signal to control the amount of reheat
to meet the supply temperature set point.
4. Hot Gas Reheat Coil
5. Hot Gas Reheat Check Valve
6. Condenser Fans
7. Condensing Coil
8. Liquid Receiver (optional)
Condenser Airflow
11
9. Sight Glass
10. Liquid Line Filter Drier
11. Thermostatic Expansion Valve (TXV)
12. Evaporative Coil
13. Low Limit Pressure Switch
3
M
2
1
124
13
14
Each unit is equipped with a TXV on each
refrigerant circuit. The valve controls the flow of
liquid refrigerant entering the evaporator coil by
maintaining a constant, factory-set superheat of
10°F. The valve is adjustable and is located on the
side of the evaporator coil and can be accessed
through the inner coil access panel.
The switch is installed in the suction line and
disables the DX system when the suction pressure
drops below the set point. The switch will autoreset when the pressure rises above the auto-reset
set point.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®27
Page 30
Water-Source Heat Pump with Standard Scroll Compressor
Water InWater Out
12
5
10
5
13
M
3
Supply
Airflow
7
8
1. Compressor
2. High Limit Pressure Switch
3. Hot Gas Reheat Valve (optional)
4. Hot Gas Reheat Coil
5. Hot Gas Reheat Check Valve
6. Liquid Receiver (optional)
7. Liquid Line Filter Drier
8. Thermostatic Expansion Valve (TXV)
9. Low Limit Pressure Switch
10. Hot Gas Bypass Valve (optional)
On units equipped with hot gas bypass, hot gas
from the compressor is injected into the refrigerant
line of the evaporator coil after the TXV.
11. Airside Coil
Each unit uses a single refrigerant coil known as
an airside coil. If two compressors are used in the
unit, then the airside coil will be a split configuration
so that each compressor has a dedicated portion
of the airside coil. Depending on whether the
unit is in cooling or heating mode, the airside coil
will function as either a condensing coil or an
evaporator coil.
2
4
11
9
1
6
12. Coaxial Refrigerant-to-Water Heat Exchanger
The unit uses one coaxial heat exchanger per
compressor, essentially a tube inside a tube.
Water flows through the inner copper tube and
compressed refrigerant is forced through the
spaces between the inner and outer tubes.
Depending on whether the unit is functioning in a
cooling or a heating capacity, heat is rejected from
one tube to the other.
13. Reversing Valves
Each compressor is equipped with a reversing
valve to reverse the direction of refrigerant flow.
Changing refrigerant flow allows the unit to operate.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
28
®
Page 31
Start-Up Unit
SPECIAL TOOLS REQUIRED
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
CAUTION
Do not operate without the filters and birdscreen
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans, and
compressors are set-up to run correctly when
supplied power. If any one fan is running backwards
or the compressor is making loud noises,
immediately turn off the power. Switch two leads
on the incoming power to the disconnect. This
will ensure proper operation of the unit. Failure to
comply may damage the compressors and void the
warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
• Do not operate compressor when the outdoor
temperature is below 40°F.
• Do not short-cycle the compressor. Allow 5 minutes
between “on” cycles to prevent compressor
damage.
• Prior to starting up the unit, power must be
energized for 24 hours without a call for cooling to
allow the compressor crankcase heaters time to boil
off any liquid refrigerant present in the compressor.
• DX system is charged with refrigerant. Start-up must
be performed by EPA Certified Technician.
• Voltage Meter (with wire probes)
• Amperage Meter
• Pressure Gauges – (refrigerant)
• Tachometer
• Thermometer
• U-tube manometer or equivalent
Start-Up Procedure
The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running. In order to measure
volts and amps, the control center door needs to be
open and the unit energized.
• Make sure Pre-Start-Up checklist is complete.
• Jumper R to G to enable unit. Jumper R to Y1 and R
to Y2 to enable cooling and R to W1 to enable heat
for units without microprocessor.
• Turn the disconnect on. After 3 minutes,
compressors will come on. Make sure all fans and
compressors are rotating the correct direction.
• Allow the unit to run until the refrigerant system
stabilizes. Approximately 10-15 minutes.
Voltage Imbalance
In a three-phase system, excessive voltage imbalance
between phases will cause motors to overheat and
eventually fail. Maximum allowable imbalance is 2%.
To determine voltage imbalance, use recorded voltage
measurements in this formula.
Key: V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®29
Page 32
Pre Start-Up
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model No. __________________________________
Unit Serial No. ____________________________________
Heat Pump Model No. ____________________________
Energy Wheel Serial Number _______________________
Compressor 1 Model No. _________________________
Compressor 2 Model No. _________________________
Start-Up Date ____________________________________
Start-Up Personnel Name _________________________
Start-Up Company ________________________________
Phone Number ___________________________________
Pre Start-Up Checklist
Disconnect and lock-out all power switches.
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
Check fan rotation.
Start-Up Checklist
Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
Check the fan belt drives for proper alignment and
tension.
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
Verify that non-motorized dampers open and close
properly.
Check the tightness of all electrical wiring
connections.
Verify control wire gauge.
Verify diameter seal settings on the energy recovery
wheel.
Verify proper drain trap installation.
Check condensing fans for any damage or
misalignment. Spin the blades and make sure they
don’t contact any parts and are free-turning without
any resistance.
Look over the piping system. Inspect for oil at all
tubing connections. Oil typically highlights a leak in
the system.
Inspect all coils within the unit. Fins may get
damaged in transit or during construction. Carefully
straighten fins with a fin comb.
If there is an indirect gas-fired furnace in this unit,
refer to the manual provided with this unit for PreStart-Up information.
This unit contains a crankcase heater for each
compressor which needs power supplied to it
24hours prior to start-up. If start-up is scheduled
in 24 hours, unlock the disconnect power and
energize unit.
Line Voltage. Check at unit disconnect.
L1-L2VoltsL2-L3VoltsL1-L3Volts
Motor Amp Draw
Supply Motor AmpsL1AmpsL2AmpsL3Amps
Exhaust Motor AmpsL1AmpsL2AmpsL3Amps
Fan RPM
Supply Fan RPMSupply FanYes / No
Measured AirflowCFM
Exhaust FanRPMExhaust FanYes / No
Measured AirflowCFM
Energy Wheel Motor
L1AmpsL2AmpsL3Amps
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
30
Correct fan rotation direction?
®
Page 33
Heating System / Electric Heat
Pre-HeaterL1-L2VoltsL2-L3VoltsL1-L3Volts
L1AmpsL2AmpsL3Amps
Temp. Rise
Post-HeaterL1-L2VoltsL2-L3VoltsL1-L3Volts
L1AmpsL2AmpsL3Amps
Temp. Rise
Cooling System
Outdoor Air TemperatureDeg FOutdoor Air Relative Humidity% RH
Return Air TemperatureDeg FReturn Air Relative Humidity% RH
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®31
Page 34
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Frost Control Application / Operation Section:SettingFactory Default
YesNoFrost Control set point5°F
Differential2°F
TimerRefer to IOM
YesNoFrost Control ModulatingRefer to IOM
Economizer Application / Operation Section:
YesNoEconomizer (temperature)
Set point65°F
Offset20°F
Differential2°F
YesNoEconomizer (enthalpy)
Set pointB
YesNoEconomizer (modulating)Refer to IOM
Optional Accessories Section:Operational
YesNo Wheel Rotation Sensor
1
(
⁄8 in. from wheel)
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesNo CO2 SensorYes No N/A
YesNo Service OutletYes No N/A
YesNo Vapor Tight LightsYes No N/A
YesNo Remote Control PanelYes No N/A
Yes No N/A
Variable Frequency Drives Section:Operational
YesNo Blower VFDsYes No N/A
YesNo Wheel VFDYes No N/A
Damper Section:Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
YesNo Night Setback DamperYes No N/A
Indirect Gas Furnace:
YesNoRefer to PVF/PVG Installation, Operation and Maintenance for start-up information.
Outdoor Air Monitoring:
YesNoField calibrated.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
32
®
Page 35
Start-Up Components
R
ing
Scr
Scr
ews
ews
Energy Wheel
The energy wheel is installed in the unit’s airstream with
one half of the wheel in the intake airstream and one
half in the return airstream. Air leakage between the two
airstreams has to be kept to a minimum and the wheel
has air seals that must be adjusted for that purpose.
The seals must be adjusted at time of start-up.
Drive Belt
Inspect the drive belt. Make sure the belt rides smoothly
in the pulley and around the outside of the wheel. Note
the directional arrow and data information shown in the
image.
Bearing Support
Push the wheel cassette back into the unit and plug
in the power connector. Turn the main power supply
back on and then observe the operation of the wheel by
opening the wheel access door slightly. Remove filters if
necessary to observe the wheel.
Fans
The unit contains a forward-curved supply fan and a
forward curved exhaust fan. These forward-curved
fans should be checked for free rotation. If any binding
occurs, check for concealed damage and foreign
objects in the fan housing. Be sure to check the
belt drives per the start-up recommendations in the
following section.
Centering of the fan wheel can be accomplished by
loosening the wheel hub set screw and moving the
wheel to the desired position.
Adjustable
Air Seals
Label showing
cassette serial number
and date code
Drive Belt
Drive Pulley
Adjust the Air Seals
The first step in wheel seal adjustment is to make sure
the unit power supply is locked out. Disconnect the
wiring to the wheel module and pull the wheel cassette
out of the cabinet on its tracks. Large cassettes are
not removable. Then slowly
rotate the wheel by hand to
make sure there is no binding
or misalignment. The wheel
should rotate smoothly and
should not bind.
There is a perimeter seal
located around the outside
of the wheel and a diameter
etain
seal across the face of the
wheel on both sides. Check to
make sure that all air seals are
secure and in good condition.
Adjust the air seals by
loosening all the air seal
retaining screws on the
bearing support (see image for
reference). Using a piece of
paper as a feeler gauge, adjust
the seals so they almost touch
Bearing Support Bar
Showing air seal assembly
the face of the wheel while
tugging slightly on the paper. When the wheel is rotated,
there should be a slight tug on the paper. Tighten the
screws, repeat the steps on the other set of seals.
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.), consult
manufacturer to determine if the unit can operate
safely at the new conditions.
Fan Performance Modifications
Due to job specification revisions, it may be necessary
to adjust or change the sheave or pulley to obtain the
desired airflow at the time of installation. The start-up
technician must check blower amperage to ensure that
the amperage listed on the motor nameplate is not
exceeded. Amperage to be tested with access doors
closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by
manufacturer, have been carefully selected for the
unit’s specific operating condition. Utilizing different
components than those supplied could result in unsafe
operating conditions which may cause personal injury or
failure of the following components:
• Fan Shaft • Bearings • Motor
• Fan Wheel • Belt
Tighten all fasteners and set screws securely and realign
drive pulleys after adjustment. Check pulleys and belts
for proper alignment to avoid unnecessary belt wear,
noise, vibration and power loss. Motor and drive shafts
must be parallel and pulleys in line (see diagrams in Belt
Drive Installation section).
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®33
Page 36
Belt Drive Installation
1. Remove the protective coating from the
end of the fan shaft and assure that it is
free of nicks and burrs.
2. Check fan and motor shafts for parallel
and angular alignment.
3. Slide sheaves on shafts. Do not drive
sheaves on as this may result in bearing
damage.
4. Align fan and motor sheaves with a
straightedge to centerline.
5. Place belts over sheaves. Do not pry
or force belts, as this could result in
damage to the cords in the belts.
6. With the fan off, adjust the belt tension
by moving the motor base. (See belt
tensioning procedures in the Routine
Maintenance section of this manual).
When in operation, the tight side of the belts should
be in a straight line from sheave to sheave with a
slight bow on the slack side.
WRONGWRONG
WRONGCORRECT
Proper alignment of motor and drive shaft.
0.25 in.
1.5 in.
centerline
straightedge
2 in.
Pulley
alignment
example
Direction of Fan Wheel Rotation
Blower access is labeled on unit.
Check for proper wheel rotation
by momentarily energizing the
fan. Rotation is determined
by viewing the wheel from the
n
o
i
t
a
t
o
R
Airflow
drive side and should match the
rotation decal affixed to the fan
housing.
a
t
t
o
i
o
R
If the wheel is rotating the wrong
n
way, direction can be reversed
by interchanging any two of the
three electrical leads.
Check
for unusual noise, vibration, or
overheating of bearings. Refer to
the Troubleshooting section of this
manual if a problem develops.
Forward Curved
Fan RPM
Supply fan and exhaust fan will have an adjustable
motor pulley (on 15 HP and below) preset at the factory
to the customer-specified RPM. Fan speed can be
increased or decreased by adjusting the pitch diameter
of the motor pulley. Multi-groove variable pitch pulleys
must be adjusted an equal number of turns open
or closed. Any increase in fan speed represents a
substantial increase in load on the motor. Always check
the motor amperage reading and compare it to the
amperage rating shown on the motor nameplate when
changing fan RPM. All access doors must be installed
except the control center door.
WARNING
Do not operate units with access doors open or
without proper ductwork in place as the fan motors
will overload.
Maximum RPM for
Forward-Curved Blowers
Class I
Max RPM
Class II
Max RPM
Model
ERCH-20
ERCH-45
ERCH-55
ERCH-90
Blower Diameter
x Width
(inches)
10 x 61700--
9 x 917502800
9 x 917502800
12 x 814002000
12 x 1215002000
12 x 1215002000
15 x 1512501725
15 x 1512501725
18 x 1810001450
Vibration
Excessive vibration may be experienced during initial
start-up and can cause a multitude of problems,
including structural and/or component failure.
Many of these conditions can be discovered by careful
observation. Refer to the Troubleshooting section of
Vibration Causes
Off axis or loose components
Drive component unbalance
Poor inlet / outlet conditions
Foundation stiffness
this manual for corrective
actions. If observation
cannot locate the source
of vibration, a qualified
technician using vibration
analysis equipment
should be consulted. If the problem is wheel unbalance,
in-place balancing can be done.
Generally, fan vibration and noise is transmitted to other
parts of the building by the ductwork. To eliminate this
undesirable effect, the use of heavy canvas connectors
is recommended.
Hot Gas Bypass Valve (standard scroll)
To adjust, connect a pressure gauge to the suction line
and block the entering air to the evaporator coil. The
valve should begin to open when the suction pressure
drops to approximately 115 PSIG for R-410A (the valve
will feel warm to the touch). Adjustments are made by
first removing the cap on the bottom of the valve and
then turning the adjusting stem clockwise to increase
the setting pressure (counterclockwise to decrease).
Allow several minutes between adjustments for the
system to stabilize. When adjustment is complete,
replace the cap on the valve.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
34
®
Page 37
Optional Start-Up Components
Dirty Filter Switch
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch.
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (Senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’
of the switch. (Senses pressure at air inlet side of filters)
1. Open the filter compartment and place a sheet of
plastic or cardboard over 50% of the filter media.
2. Replace the filter compartment door.
3. Check to see if there is power at the alert signal
leads (refer to electrical diagram).
4. Whether there is power or not, turn the adjustment
screw on the dirty filter gauge (clockwise if you did
not have power, counterclockwise if you did have
power) until the power comes on or just before the
power goes off.
5. Open the filter compartment and remove the
obstructing material.
6. Replace the door and check to make sure that you
do not have power at the alert signal leads. The unit
is now ready for operation.
Economizer
Relevant Set Points
1. MAT SET The mixed air temperature set point after
the energy wheel. The control will modulate the
energy wheel to maintain temperature as best as it
can (Set point menu, default 53°F)
2. LOW T LOCK The set point for the low temperature
mechanical cooling lockout. (Set point menu, default
32°F)
3. DRYBLB SET The outdoor air set point to call for
economizer. (Set point menu, default 63°F)
4. MIN POS The minimum signal voltage sent to the
energy wheel. This must be set to 2 VDC. (Set point
menu, default 2.8 VDC)
5. AUX1 O The controllers operating sequence
structure. (Set point menu, default ‘None’)
6. ERV OAT SP The set point for low temperature
economizer lockout. This is the low temperature set
point when AUX1 O is set to ERV. (Set point menu,
default 32°F)
7. STG3 DLY Time delay after second cooling stage is
enabled (Advanced setup menu, default 2 hrs.)
Using the Keypad with Settings and Parameters
To use the keypad when working with Set Points,
System and Advanced Settings, Checkout Tests, and
Alarms:
1. Navigate to the desired menu.
2. Press
currently displayed menu.
3. Use the
parameter.
4. Press (enter) to display the value of the currently
displayed item.
5. Press the
displayed parameter value.a
6. Press the
displayed parameter value.
7. Press (enter) to accept the displayed value and
store it in non-volatile RAM.
8. CHANGE STORED displays.
9. Press
parameter.
10. Press
parameter.
a
When values are displayed, pressing and holding the
or button causes the display to automatically
increment.
The table shows which set points are relevant to the
given sequences. Refer to the wiring diagram for the
units’ sequence.
DRYBLB SETXX
MAT SETXXXXXX
LOW T LOCKXXXXXX
ERV OAT SPXXX
MIN POSXXX
AUX1 OUTERVERVERV
STG3 DLYXXXXXX
(enter) to display the first item in the
and buttons to scroll to the desired
button to increase (change) the
button to increase (change) the
a
(enter) to return the current menu
(escape) to return to the current menu
MODULATE WHEELSTOP WHEEL
OA
Temp
OA
Enthalpy
OA/RA
Temp
Differential
OA
Temp
OA
Enthalpy
OA/RA
Temp
Differential
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®35
Page 38
Stop Wheel
1. Navigate to the Checkout menu and press (enter).
2. The energy wheel and cooling should stop.
3. Navigate to Connect ERV and press
(enter) twice
to run the test.
4. Voltage between AUX1-O and C should be 24 VAC.
The energy wheel should activate.
Modulate Wheel
1. Navigate to the Checkout menu and press (Enter).
2. The cooling should turn off and the wheel should be
rotating at full speed.
3. Navigate to Damper Open and press
to run the test.
4. Voltage between terminals ACT 2-10 and ACT COM
should be 10 VDC. This will slow the wheel down to
minimum speed.
5. Press
(escape), navigate to Damper Close and
press (enter) twice to run the test.
6. Voltage between terminal ACT 2-10 and ACT COM
should be 2 VDC. This will speed the wheel up to
maximum speed.
(enter) twice
Frost Control
Timed Exhaust
1. Remove power from unit.
2. Jumper the frost indicating wheel pressure switch in
the unit control center.
3. Jumper the temperature indicating thermodisc in
the unit control center. Thermodisc has a pre-set
temperature of 5°F.
4. Set the frost control timer scale for T1 and T2 to 1m.
Set the timer settings for T1 and T2 to 10.
5. Add power to the unit. Blower should cycle on for
one minute, then turn off for one minute.
6. Remove power from unit and remove jumpers that
were placed. Reset timer settings.
• T1 timer
setting set to
5 and timer
scale set to
10m for 5
minutes of
wheel off time.
• T2 timer
setting set to
5 and timer
scale set to 1h
for 30 minutes
of wheel on
time.
Timer
Scale
Timer
Settings
Timer
Scale
T1
Settings
T2
Settings
Electric Preheat
1. Remove power from unit.
2. Jumper the frost indicating wheel pressure switch in
the preheat control center.
3. Jumper the temperature indicating thermodisc in
the preheat control center. Thermodisc has a pre-set
temperature of 5° F.
4. Apply power to unit. Preheater should turn on.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
36
®
Page 39
Outdoor Airflow Monitor
For additional information on how to navigate through
the airflow controller menus, refer to technical manuals
GF-2200A from GreenTrol® Automation Inc. at www.
greentrol.com.
Field calibration procedure:
1. Turn off power to the unit using the power
disconnect(s).
2. Remove the cover from the GreenTrol airflow
monitoring controller.
3. Install a jumper wire between terminals R and G on
the unit’s terminal board if one isn’t present.
4. When safe, turn the power back on to the unit
using the power disconnect(s).
If no microprocessor controller, skip to step 8. Steps
5-7 are for microprocessor only.
5. Look at the unit’s microprocessor controller screen
and view the status of the unit. If the displayed
status is “System Off” continue with step 6,
otherwise go to step 7.
6. Adjust the unit on/off priorities on the unit’s
microprocessor controller so that the unit will run
for calibration.
a. Push the “Prg” button on the microprocessor
controller.
b. Use the up and down arrows to get to the “On/
Off Unit” menu.
c. Push the enter button to view the current unit
on/off priorities.
d. Push the down arrow to display the Unit ON/
OFF Control screen.
e. Record the settings below so they can be
changed back when calibration is complete.
By digit input: ___________
By BMS: ___________
By Scheduler: ___________
f. Use the enter button to navigate between the
different settings on the page, use the up and
down arrows to change the values so that “By
digit input” is the only setting with “Yes”.
7. Enter the service override menu to control the
damper position.
a. At the Home Screen push the “Prg” button. (If
you’re not at the home screen push the escape
button until you get there).
b. Use the up and down arrows to get to the
“Service” menu, then push the enter button.
c. If you’re asked for a password, enter “1000”
for the password and push enter.
d. Use the up and down arrows to get to the
“Overrides” screen, then push enter.
e. Use the arrow buttons to get the supply
override.
8. Measure the supply airflow rate of the unit using an
approved test and balance method.
9. Without making any changes to the system,
calibrate the airflow monitoring controller so it
reads the airflow measured in step 8 by using the
Field Calibration Wizard.
a. The field calibration lasts for two minutes. Any
significant changes in airflow will affect the
accuracy of the reading.
b. To enter the Field Calibration Wizard, hold the
Down and Enter buttons simultaneously on the
airflow controller, then release the buttons.
c. Push the enter to enter to go Wizard 1
d. Push the enter button twice and change Wiz1
Enable to YES.
e. When asked for the number of calibration
points (Cal Points), set the value to 1.
f. Push the enter button when the display says
“Set Flow 1”.
g. After completing the steps above, set the
FLOW1 value to the airflow measured in
step 8, then push the enter button to begin
calibration.
10. After the calibration is completed, measure the
supply airflow rate again and compare with the
value on the airflow controller’s display
a. If the values are within 5% of each other the
device has been successfully calibrated.
b. If the values are not within 5% of each other
repeat the field calibration process.
11. If you had to change the On/Off priorities on the
microprocessor unit controller, change them back
to the values that were written down in part 6.
12. Turn off power to the unit using the power
disconnect(s) and wait one minute for the variable
frequency drive(s) to lose backup power.
13. Replace the cover to the GreenTrol airflow
monitoring station.
14. If you added a jumper between terminals R and
G in step 3 remove it at this time. If a jumper was
already in place, leave it in place.
15. When safe, turn the power back on to the unit
using the power disconnect(s).
a. Recycling of the power resets the manual
override values that were set during the
calibration.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®37
Page 40
Evaporative Cooler
1. Check the Installation. The media may have been
removed during installation, so its orientation should
be double
checked. The
media should
be installed
with the
steeper flute
Entering Air
angle sloping
down towards
the entering
air side.
Media Orientation
Verify that the stainless steel caps and distribution
headers are in place. The headers should be located
over the media towards the entering air side. The
caps should be placed over the headers.
2. Check the Pump Filter. Check that the pump filter is
around the pump inlet.
3. Fill the Sump and Adjust the Float. Turn on the
water supply and allow the sump tank to fill. Adjust
the float valve to shut-off the water supply when the
sump is filled to within one inch of the bottom of the
overflow.
4. Break-In the Media. Open the bleed-off valve
completely and saturate the media with the blower(s)
off for no less than 20minutes.
5. Check the Flow Rate. The pumps should provide
enough water to saturate the media in 45 to 60
seconds. Consult the factory if adequate flow is not
achieved.
6. Adjust the Water Bleed-Off Rate. The water bleedoff rate is dependent on the water’s mineral content.
The bleed-off should be adjusted based on the
media’s mineral deposits after two weeks of service.
45º
Leaving Air
15º
Set the Timer Scale and Settings dials:
• t timer setting set to 10 and timer scale set to
1d for 1 day of operation
• T2 timer setting set to 10 and the timer scale set
to 10m for 10 minutes of drain time
Timer
Scale
Timer
Settings
Timer
Scale
Auto Drain and Flush Timer
T1
Settings
T2
Settings
8. Put the Unit into Service. Remove the jumper, and
energize the blower(s). Verify proper operation.
IMPORTANT
Check the media for minerals after two weeks of
service and adjust the bleed-off rate accordingly.
Overflow
Bleed-Off
Valve
Pump
Filter
Supply
Connection
Float
Valve
Threaded Float
Adjustment
NOTE
A jumper will need to be installed in the control center
to power the evaporative pumps with the blower(s)
off. Reference the unit’s ladder diagram to determine
proper terminals.
7. Set the Optional Auto Drain and Flush. This
system will automatically drain the sump tank and
fill it with fresh water at the field-adjustable intervals,
typically once every 24 hours. This flushes mineral
build-up and debris from the tank to promote low
maintenance and increase media pad life.
In addition, the system will protect the evaporative
cooler from freezing by draining the sump tank and
supply line when the outside temperatures fall below
the set point of the outside air sensor. This is set
to 45° F and is not adjustable. The auto drain and
fill outdoor air sensor should be installed in an area
that is shaded from direct sunlight so the outside air
sensor probe will detect an accurate air temperature.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
38
Evaporative Cooler Set-Up
®
Page 41
Variable Frequency Drives
Optional factory-installed, wired, and programmed
variable frequency drives (VFDs) may have been
provided for modulating or multi-speed control of the
blowers and energy recovery wheel for economizer and
frost control modes. One VFD, either Yaskawa model
V1000 or J1000, is provided for each blower (supply air
and exhaust) and one Yaskawa model J1000 is provided
for the energy recovery wheel.
Refer to the tables in this section for factory settings
and field wiring requirements. Refer to the unit control
center for unit specific wiring diagram. When making
adjustments outside of the factory set points, refer to
Yaskawa VFD instruction manual, which can be found
online at www.drives.com. For technical support,
contact Yaskawa direct at 1-800-927-5292.
IGS-S+R-R+
MPACAMAC+VA2A1PCP2P1
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
J1000
V1000
A1 AC
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
USER TO PROVIDE CONTACTS AND ISOLATION
AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.
PARAMETER A1-01 CHANGE TO 2
PARAMETER d1-01 FOR NEW 60Hz SETTING
PARAMETER d1-02 FOR NEW 40Hz SETTING
PARAMETER d1-03 FOR NEW 30Hz SETTING
PARAMETER A1-01 CHANGE TO 0
0-10 VDC CONTROL SIGNAL (BY OTHERS)
WIRED TO A1 (+) AND AC (COMMON)
0 VDC=30 Hz
10 VDC=60 Hz
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4SC
NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 40 Hz.
S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.
MA MB MCACAMAC+VA1SCS5S4S3S2S1
Factory Set Points
Variable frequency drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:
• Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30
and 60Hz
• Multi-speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
- Open - Drive runs at 60Hz
- SC to S4 - Drive runs at 40Hz
- SC to S5 - Drive runs at 30Hz
• CO
Sensor:
2
Set Point Control: A carbon dioxide sensor is
provided from the factory for field-mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with two preset speeds of 700
PPM or less CO2 = 50% fan speed and 800 PPM
or greater CO2 = 100% fan speed.
Proportional Control: A carbon dioxide sensor is
provided from the factory for field-mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with default factory settings
of 500 PPM or less CO2 = 50% fan speed and
1000 PPM or greater CO2 = 100% fan speed.
Modulation of VFD occurs proportional to CO
2
between 500 and 1000 PPM.
The terminal locations for Modulating and Multi-speed
are shown on the previous page. Most of the set points
in the VFDs are Yaskawa factory defaults. However, a
few set points are changed at Greenheck and are shown
in the tables. These settings are based on the VFD
mode selected.
Change Set Points
To gain access to change set points on the V1000 and
J1000 drives, parameter A1-01 needs to be set at “2”.
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.
• Drive Operation
- SC to S1 contact for On/Off
- A1 (0-10 VDC) referenced to AC
Can use +15 VDC from +V
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”. Then
go to A1-03 and change it to “1110” and press enter.
The drive is now reset back to the settings programmed
at Greenheck. This option is not available on the J1000.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®39
Page 42
Modulating Control for Fan Speed
(0-10 VDC)
Parameter
Setting
V1000J1000
A1-01Access Level22
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
Motor
FLA
Motor
FLA
H2-01Terminal MA, MC Function55
H3-04Terminal A1 Bias50%50%
L4-01H2-01 Frequency Detection1515
L5-01Auto Restart Attempt55
A1-01Access Level00
CO2 Proportional Control
Parameter
Setting
V1000J1000
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLAFLAFLA
H3-03
H3-04
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
150%150%
25%25%
L2-01Ride Thru Power Loss22
L4-05Frequency Ref Loss0NA
L5-01Auto Restart Attempt55
A1-01Access Level00
CO2 Sensor Control for Fan Speed
(1/2 speed when CO2 drops below 700 PPM)
(Full speed when CO2 rises above 800 PPM)
Multi-Speed Control for Fan Speed
(1/3 or 1/2 speed reduction)
Parameter
Setting
V1000J1000
A1-01Access Level22
B1-01Reference Source (Frequency)00
B1-17VFD Start-Up Setting11
C6-02Carrier Frequency11
D1-01Frequency Reference 160 Hz60 Hz
D1-02Frequency Reference 240 Hz40 Hz
D1-03Frequency Reference 330 Hz30 Hz
D1-04Frequency Reference 460 Hz60 Hz
D2-02Ref Lower Limit50%50%
E2-01Motor Rated FLA
H1-04
H1-05
H1-06
Multi-Function Input Sel 4
(Terminal S4)
Multi-Function Input Sel 5
(Terminal S5)
Multi-Function Input Sel 6
(Terminal S6)
Motor
FLA
33
44
5NA
Motor
FLA
H2-01Terminal MA, MC Function55
H3-10A2 Not UsedFNA
L4-01H2-01 Frequency Detection1515
L5-01Auto Restart Attempt55
A1-01Access Level00
Variable Frequency Drives for
Energy Recovery Wheel
ParameterSetting – J1000
A1-01Access Level2
B1-17VFD Auto Start1
C1-04Decel Time600
*C4-01Torque Gain0.6
C6-02Carrier Frequency2
D2-01Ref Upper Limit40 or 50*
D2-02Ref Lower Limit5%
E2-01Motor Rated FLAMotor FLA
E2-03Motor No-Load Current
H1-02
H2-01
H1-04
Multi-Function Input
(Terminal S2)
Multi-Function Output
(MA, MB, MC)
Multi-Function Input Sel 4
(Terminal S4)
Economizer Signal Source
(0-10 VDC)
H3-03
H3-04
Analog Frequency Reference
(Gain)
Analog Frequency Reference
(Bias)
Must be less
than FLA
6
4
7
Setting
Honeywell
Module
0
40 or
50**
Controller
L1-01Elect Thermal Overload2
L2-01Ride Thru Power Loss2
L4-01Frequency Detection Level15
L5-01Auto Restart Attempt5
A1-01Access Level0
* 208/230 volt only
**36 through 52 inch wheels are 40 (24 Hz)
58 or 74 inch wheel is 50 (30 Hz)
Carel
40 or
50*
0
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
40
®
Page 43
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to the unit to
OFF at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and serious
injury may occur.
This unit requires minimal maintenance to operate
properly. Maintenance requirements for this model
vary for each installation and depend greatly on how
much the system is used and the cleanliness of the air.
Proper maintenance will both increase the life of the
system and maintain its efficiency. Maintenance must
be performed by experienced technicians and in the
case of refrigeration systems, must be done by an EPA
certified technician.
Maintenance frequency is based on a presumed
nominal use of the system. If the system is being
run constantly, the frequency should be adjusted
accordingly. If there is seasonal debris in the air which
can be drawn into the filters and the coils, they should
be checked more frequently. If the system is being
used for only a few hours per day, the frequency may
be reduced. Use the maintenance log at the end of
this manual to record each maintenance session
and observations and then establish a maintenance
schedule that is appropriate for the installation. The
following is provided as a guideline:
Adjust replacement schedule for MERV 13 or
other filters as inspection requires.
Semiannually
1. Check motor and motor bearings
Check for excessive heat, vibration or noise.
Lubricate bearings in accordance with the motor
manufacturer’s recommendations.
2. Condensate Drain (if applicable)
Inspect and clean – refill with water
3. Condenser Coils
Inspect for cleanliness – clean as required
Annually
It is recommended that the annual inspection and
maintenance occur at the start of the cooling season.
After completing the checklist, follow the unit startup checklist provided in the manual to ensure the
refrigeration system operates in the intended matter.
1. Lubrication
Apply lubricant where required
2. Dampers
Check for unobstructed operation
3. Blower Wheel and Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
4. Door Seal
Check if intact and pliable
5. Wiring Connections
Check all connections for tightness
6. Cabinet
Check entire cabinet, inside and out, for dirt
buildup or corrosion. Remove accumulated dirt,
remove any surface corrosion and coat the area
with appropriate finish.
Units with Packaged DX
Semiannually
1. Evaporator Coil Maintenance
Check for cleanliness - clean if required
2. Condenser Coil Maintenance
Check for cleanliness - clean if required
3. Condensate Drain
Inspect and clean - refill with water
4. Condensing Fan Blades and Motors
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion and wear
Units with Heat Pump
An annual inspection of the heat pump system by a
licensed refrigeration mechanic is recommended.
1. Inspect entire heat pump for cleanliness.
2. Record performance data for volts, amps and water
temperature differences (both heating and cooling).
3. Compare annual data to recorded start-up data.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®41
Page 44
Maintenance Procedures
WARNING
REFER TO GENERAL SAFETY INFORMATION
Do not operate this unit without the filters and
birdscreen installed. They prevent the entry of foreign
objects such as leaves, birds, etc.
Do not remove access panels or other unit
components while standing on a ladder or other
unsteady base. Access panels and unit components
are heavy and serious injury may occur.
Lubrication
Check all moving components for proper lubrication.
Apply lubricant where required. Any components
showing excessive wear should be replaced to maintain
the integrity of the unit and ensure proper operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Gas Furnace
Maintain furnace in accordance with instructions in the
Indirect Gas-Fired Heat IOM shipped with this unit.
Fan Belts
Belts must be checked on a regular basis for wear,
tension, alignment, and dirt accumulation. Premature
or frequent belt failures can be caused by improper
belt tension (either too loose or too tight) or misaligned
sheaves. Abnormally high belt tension or drive
misalignment will cause excessive bearing loads and
may result in failure of the fan and/or motor bearings.
Conversely, loose belts will cause squealing on start-up,
excessive belt flutter, slippage, and overheated sheaves.
Both loose and tight belts can cause fan vibration.
When replacing belts on multiple groove drives, all belts
should be changed to provide uniform drive loading. Do
not pry belts on or off the sheave. Loosen belt tension
until belts can be removed by simply lifting the belts off
the sheaves. After replacing belts, insure that slack in
each belt is on the same side of the drive. Belt dressing
should never be used.
Do not install new belts on worn sheaves. If the sheaves
have grooves worn in them, they must be replaced
before new belts are installed.
The proper belt setting is the lowest tension at which
the belts will not slip under peak load operation. For
initial tensioning, set
the belt deflection at
1/64-inch for each inch
of belt span (measured
half-way between sheave
centers). For example, if
the belt span is 64 inches,
Deflection =
Belt Span
Belt Span
64
the belt deflection should be one inch (using moderate
thumb pressure at mid-point of the drive). Check belt
tension two times during the first 24 hours of operation
and periodically thereafter.
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper cooling. Never washdown the motor with high pressure spray. Greasing
of motors is only intended when fittings are provided.
Fan motors typically have two grease fittings. Each
motor manufacturer has different lubrication schedules
for different models. Go to the motor manufacturer’s
website and download their maintenance requirements.
Do not over-lubricate motors or use an incompatible
grease. Many fractional motors are permanently
lubricated for life and require no further lubrication.
Fan Wheel and Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs, the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion, or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20° to 120°F and in a relatively clean
environment. Some bearings are relubricatable and will
need to be regreased depending on fan use. Check your
bearings for grease zerk fittings to find out what type
of bearing you have. If your fan is not being operated
under normal use, bearings should be checked monthly
for lubrication.
Shaft bearings are the most critical moving part of a
fan. Therefore, special attention should be given to
keeping the bearings clean and well lubricated. Proper
lubrication provides for reduction in friction and wear,
transmission and dissipation of heat, extended bearing
life and prevention of rust.
In order for a lubricant to fulfill these tasks, the proper
grease applied at regular intervals is required.
If unusual conditions exist—temperatures below 32°F or
above 200°F, moisture or contaminants—more frequent
lubrication is required.
With the unit running, add grease very slowly with a
manual grease gun until a slight bead of grease forms at
the seal.
Be careful not to unseat the seal by over lubricating
or using excessive pressure. A guide to the amount
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
42
®
Page 45
of grease to be used is to fill 30% to 60% of available
space in the bearing and housing.
A high quality lithium based grease conforming to NLGI
Grade 2 consistency should be used.
Internal Filter
The unit will typically be provided with 2-inch thick
pleated paper filters in the airstream. These filters
should be checked according to a routine maintenance
schedule and replaced as necessary to ensure proper
airflow through the unit. Replacement filters shall be of
same performance and quality as factory-installed filters.
Filters upstream of the coil should be checked regularly.
If the filters are dirty, they should be cleaned or
replaced. It is important the filters stay clean to maintain
desired airflow.
Internal Filter Size and Quantities
Model
ERCH-2020 x 2022
ERCH-4520 x 2533
ERCH-5516 x 2066
ERCH-9020 x 2088
Filter Size
(inches)
Quantity
Supply
Quantity
Exhaust
External Filter
Aluminum mesh, 2-inch thick filters are located in the
supply weatherhood (if the weatherhood
option was purchased). These filters
should be checked and cleaned
on a regular basis for best
efficiency. The frequency of
cleaning depends upon the
cleanliness of the incoming air.
These filters should be cleaned
by rinsing with a mild detergent
in warm water prior to start-up.
External Filter Size and Quantities
Model
ERCH-2016 x 202
ERCH-4516 x 204
ERCH-5516 x 206
ERCH-9016 x 208
Filter Size
(inches)
Quantity
Filter
External Filter
Access
Coils
Coils must be cleaned to maintain maximum
performance. Check coils once per year under normal
operating conditions and if dirty, brush or vacuum clean.
Soiled fins reduce the capacity of the coil, demand
more energy from the fan and create an environment
for odor and bacteria to grow and spread through the
conditioned zone.
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Care must
be taken not to damage the coils, including the fins,
while cleaning. Caution: Fin edges are sharp!
WARNING
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel only.
Drain pans in any air conditioning unit will have some
moisture in them, therefore, algae and other organisms
will grow due to airborne spores and bacteria. Periodic
cleaning is necessary to prevent this buildup from
plugging the drain and causing the drain pan to
overflow. Inspect twice a year to avoid the possibility
of overflow. Also, drain pans should be kept clean to
prevent the spread of disease.
Winterizing Coils
Coil freeze-up can be caused by such things as air
stratification and failure of outdoor air dampers and/
or preheat coils. Routine draining of water cooling coils
for winter shutdown cannot be depended upon as
insurance against freeze-up. Severe coil damage may
result. It is recommended that all coils be drained as
thoroughly as possible and then treated in the following
manner.
WARNING
Carefully read instructions for mixing antifreeze
solution used. Some products will have a higher
freezing point in their natural state than when mixed
with water.
Fill each coil independently with an antifreeze solution
using a small circulating pump and again thoroughly
drain. Check freezing point of antifreeze before
proceeding to next coil. Due to a small amount of water
always remaining in each coil, there will be diluting
effect. The small amount of antifreeze solution remaining
in the coil must always be concentrated enough to
prevent freeze-up.
Door Seals
An EPDM foam rubber bulb seal backed with a high
strength acrylic adhesive is installed on the door frame
of the unit. This creates and air tight seal between the
rubber seal and the door. Inspect at least annually to
ensure that the seal is damage free and still intact.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®43
Page 46
Energy Wheel Maintenance
WARNING
Whenever performing maintenance or inspections,
always disconnect the power source.
Inspection
The wheel should be inspected semiannually
in accordance with the maintenance schedule.
Maintenance of the wheel consists
mainly of inspecting the wheel
for cleanliness and then checking
the drive motor, belt, and pulley
for wear. If the wheel layers
appear dirty, the wheel should be
disassembled and cleaned.
The wheel rotates through the two
airstreams which are moving in
opposite directions, the wheel is
self-cleaning, up to a point. If the
wheel media becomes blocked by
dirt or dust, or if the media collects
Energy Wheel
Cassette
a layer of smoke residue or an oily
film, the energy transfer efficiency drops.
The main factor in the frequency of cleaning is the
cleanliness of the air. If air filters are not changed
frequently, the wheel will collect contaminants and will
then have to be cleaned.
Wheel Disassembly
Wheels are part of a cassette that may be pulled from
the unit for easy access. There may be a small damper
assembly or other component that blocks removal of
the cassette. Before sliding out the cassette or any other
component, disconnect any power supply cord and
secure it so it cannot jam or otherwise get damaged.
Each wheel has removable segments that hold the
coated layers of media and each segment is held in
place with two retaining
clips located on the outer
rim of the wheel. When
removing more than one
segment, remove them in
sequence from opposite
sides of the wheel (180 degrees apart) to reduce the
imbalance. Secure the wheel against rotation. Carefully
release the two retaining clips and swing them fully
open. The segment can now be removed by pushing the
face of the segment close to the outer rim of the wheel.
Wheel segments are built to close tolerances and the
segment may have to be jiggled to remove it. Do not
use a hammer or otherwise force the segment because
these are high value items and are not built to withstand
abuse.
Whenever retaining clips are opened, they should be
closed as soon as possible. If the wheel should rotate
when a clip is open, the clip will jam against the bearing
support bar and could cause damage.
Segment Retaining Clip
Cleaning
Maintenance or cleaning of the wheel segments
should be done with the segments removed from
the wheel cassette to avoid splashing liquids or
cleaning agents inside the cabinet. If the energy wheel
appears excessively dirty, it should be cleaned to
ensure maximum operating efficiency. Only excessive
buildup of foreign materials needs to be removed.
DISCOLORATION AND STAINING OF ENERGY
RECOVERY WHEEL DOES NOT AFFECT ITS
PERFORMANCE.
Thoroughly spray the wheel matrix with a household
cleaner such as Fantastik™ or the equivalent. Gently
rinse with warm water and use a soft brush to remove
any heavy accumulations. A detergent/water solution
can also be used. Avoid aggressive organic solvents,
such as acetone. Wheel segments can be soaked in the
above solution overnight for removal of stubborn dirt or
accumulations.
After cleaning is complete, shake excess water from the
wheel or segments. Dry the wheel or segments before
putting them back into the cassette.
Reassembly
When reinstalling the segments, be sure to install them
with the correct face toward the motor side of the
cassette. Note that one face of each segment is smooth
and the other face has a reinforcing channel or support
cut into the surface.
Wheel Segment
(Pulley Side)
Wheel Segment
(Motor Side)
Wheel Belt
Inspect belts each time filters are replaced. Belts
that look chewed up or are leaving belt dust near the
motor pulley may indicate a problem with the wheel.
Be sure to inspect wheel for smooth and unrestricted
rotation. If a belt requires replacement, contact the
local manufacturer representative. Instructions for
replacement will ship with the new belt.
Wheel Bearing
In the unlikely event that a wheel bearing fails, the
bearing is behind a removable plate on the wheel
support beam (slide cassette halfway out of cabinet to
access). Contact the local manufacturer representative
for detailed instructions on how to replace the bearing.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
44
®
Page 47
Evaporative Cooling Maintenance
Regularly scheduled maintenance is the key to peak
performance, minimized cost, and extended life of the
evaporative cooler. The following is a checklist of items
that need to be looked at on a regular basis.
1. The media should be checked for mineral and
foreign material deposits that have built up. If
these items are left on the media, the life and
performance of the unit will be greatly reduced.
Also, there are risks of water carryover when
this type of condition exists. When signs of
mineral build-up are noticed, you should increase
the bleed off rate. If this does not solve the
problem, chemicals may need to be added to
the water. The evaporative pads tend to be selfcleaning. Depending on water quality and system
maintenance, the useful life of the pads should be 3
to 5 years.
2. The media should be periodically brushed lightly
with a soft bristle brush in an up and down motion
(never brush side-to-side) while flushing with water.
This will also aid in reducing the amount of foreign
material build-up.
3. The water should be shut off and all the lines
drained when the temperature drops below 50°F.
4. When the evaporative cooler is going to be used for
the first time each season, it is recommended that
the media be flushed with clean water for a period
of 2 minutes.
5. At the beginning of each cooling season, the
upright recirculating pump should have the shaft
oiled and spun to eliminate the potential of seizing
and pump burn out.
6. If the cooling media was removed from the unit,
check to make sure that is not installed backwards.
If the media is installed backwards, there will be
large amounts of water carry over downstream of
the evaporative cooler. Continuous operation in this
manner may cause serious damage and void the
warranty.
7. At the end of each cooling season the evaporative
cooler should be thoroughly cleaned. A dispersant
and biocide (consult water treatment consultant
for suitable materials and dosage levels) should be
recirculated for 12 to 24 hours prior to performing
the following steps:
a. Disconnect power to unit.
b. Shut off all water to the unit.
c. Open evaporative cooling section door.
d. Flush distribution headers and media for
20 minutes.
e. Turn off pumps and drain all water distribution
piping, headers, etc.
f. Dry media completely by running blowers.
g. Brush media as described in Step 2 and
repeat steps 7d and 7e.
h. Clean all remaining components (i.e. sump,
pump, etc.) of any mineral deposits or foreign
materials.
i. Replace all worn or non-functioning parts.
j. Reassemble the cooling unit.
k. Close cooling section door.
l. Turn the main disconnect ‘ON’, leaving the
cooling switch in the ‘OFF’ position.
8. If the evaporative cooler will be turned off during
the cooling season for an extended period of time,
it is recommended that the media be dried out.
This can be accomplished by allowing the blowers
to continue to run for one to two hours. Doing so,
will prevent organic build-up on the media and
subsequent odors getting into the space.
9. Media should be permitted to dry once per week
by allowing the blowers to run for one to two hours.
IMPORTANT
Replacement media should be from the same
manufacturer and be the same size as the original
media provided with the unit.
10. A flush cycle should be performed weekly for one
hour with the fans off.
To remove media, disconnect water line to evap header
as shown below. Then slide media section out of unit.
Sump will remain in unit. If media is wet, turn off water
supply, then turn on unit and allow air to flow thru media
for 10 -20 minutes. This will dry the media out and make
it lighter and easier to handle.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®45
Page 48
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.Replace fuse or reset circuit breaker and check amps.
Blower fails to
operate
Motor starters
“chatter” or do
not pull in
Motor over
amps
Defective motor or capacitor.Replace.
Motor overloaded.Reset VFD and check amps.
Electrical.
Control power (24 VAC) wiring run is too
long. (Resistance should not
exceed 0.75 ohms).
Check for On/Off switches. Check for correct supply voltage.
Check Control wiring.
Shorten wiring run to mechanical room or install a relay to turn
unit on/off. Consult factory for relay information. Increase wire
gauge size so that resistance is 0.75 ohms or less.
Incoming supply power is less than
anticipated. Voltage supplied to starter coil
must be within +10% / -15% of nominal
Need to increase supply power or use a special control
transformer which is sized for the actual supply power.
voltage stated on the coil.
Static pressures are higher than design.Check for dirty filters. Improve ductwork.
Motor voltage incorrect.
Motor horsepower too low.
Check motor wiring. Check motor nameplate versus supplied
voltage.
See specifications and catalog for fan curves to determine if
horsepower is sufficient.
Shorted windings in motor.Replace motor.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Improve ductwork to eliminate losses using good duct
practices.
Check maximum motor RPM and compare with catalog data.
Verify that external control wiring is in place if required.
Low airflow
(cfm)
Fan wheels are operating backwards.
Dirty filter.
For 3-phase, see Direction of Fan Wheel Rotation Direction in
Start-Up Components section.
Replace filters or follow cleaning procedures in Routine
Maintenance section of this manual.
Leaks in ductwork.Repair.
High airflow
(cfm)
Excessive
noise or
vibration
Elbows or other obstructions may be
obstructing fan outlet.
Motor base or blower loose.Tighten mounting bolts.
Correct or improve ductwork.
Check for correct maximum fan RPM. Decrease maximum fan
speed if necessary in the VFD.
Induce Ps into system ductwork. Make sure grilles and access
doors are installed. Decrease fan speed if necessary.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing
collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten
collars and fasteners.
Make sure ductwork is supported properly. Make sure ductwork
Noise being transmitted by duct.
metal thickness is sized for proper stiffness. Check duct size at
discharge to ensure that air velocities are not too high.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
46
®
Page 49
Troubleshooting – Refrigeration Circuit
TROUBLESHOOTING NOTE
IMPORTANT
Do not release refrigerant to the atmosphere! If
Before any components are changed on the
refrigeration system, the cause of the failure must be
identified. Further problems will exist unless the true
cause or problem is identified and corrected.
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified EPA Certified Technician.
NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical
supply.
The first step in troubleshooting a refrigeration circuit is to examine the microprocessor and digital scroll compressor
controller (if present) and see if there is a fault code. The next step is to check airflow conditions (e.g. improper
ductwork, atypical wet bulb / dry bulb, etc.). After these steps have been eliminated, proceed with troubleshooting
by following this guide.
SymptomPossible CauseCorrective Action
Open disconnect switch or circuit breaker.Close switch and/or breaker.
Compressor contactor not closing.
Blown fuse or tripped breaker.
Low line voltage.
Check voltage to contactor coil, transformer, slave relay,
system. Replace parts as necessary.
Check for reason and repair. Replace fuse after correcting
problem.
Check line voltage. If more than 10% from compressor marking,
correcting is necessary.
Compressor
will not run or
does not start
Compressor
starts but cuts
out on low
pressure
Low pressure
switch
activates at
50 PSIG
Motor thermal protector automatically resets. Allow time (two
Compressor motor protector open.
Compressor defective.
High pressure switch open
or defective.
Low pressure switch open
or defective.
Open room thermostat or control.
(No cooling required).
Loose wiring.Check all wire terminals and tighten as necessary.
Low or loss of refrigerant charge.Check refrigerant pressures and temperatures (subcooling).
Airflow restricted.
Restriction in refrigerant line.
Defective low pressure switch.Replace.
hours) for compressor to cool down so protector will reset.
Restart and check for reason overheat occurred.
Check motor for open circuit, short circuit, grounded windings,
or burn out. Compressor may be seized; check refrigerant. If
necessary, replace compressor.
If manual reset (high pressure), reset switch. (Switch opens at
600 psi and will not reset above 420 psi for R-410A). Replace if
defective.
Switch will open at 50 psi and auto-close at 90 psi. Replace if
defective.
Check room temperature. If temperature is proper, wait for
thermostat to close.
Check for dirty evaporator coil, dirty filters, dampers closed,
iced evaporator coil, improper belt, check motor amps, check
duct design.
Check refrigerant pressures, look for frosted tubing and
components indicating a restriction. Check pressure drop
across the filter drier.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®47
Page 50
Troubleshooting – Refrigeration Circuit
SymptomPossible CauseCorrective Action
Refrigerant overcharge.Check pressures, charge by subcooling.
Compressor
starts but
cuts out on
high pressure
switch
High pressure
activates at
600 PSIG
Compressor
cuts out
on thermal
overload
Condenser fan motor defective.Check fan motor.
Condenser coil inlet obstructed or dirty.Check coil and clearances. Clean coil if necessary.
Air or non-condensables in system.
Check high side equalized pressures, check thermal expansion
valves.
Defective high pressure switch.Replace.
Restriction in discharge or liquid line.
Check refrigerant line pressures, check thermal expansion
valves, replace any defective component.
Condensing fan relay not pulling in.Replace.
Low voltage.Check voltage.
Sustained high discharge pressure.
High suction and discharge pressures.
Defective compressor overload.
Check running amperage and conditions described under “low
suction pressure” symptoms.
Check thermal expansion valve setting, check for air in system.
Check air conditions and cfm.
If compressor is hot, allow compressor to cool for two hours.
Recheck for open circuit.
Improper refrigerant charge.Check subcooling.
Improperly wired.Review wiring schematics.
Loose wiring.Check all connections.
Defective start relay.Replace relay.
Motor windings damaged.Verify amp draw.
Improperly wired.Review wiring schematics.
Low line voltage.Check voltage.
Compressor
Loose wiring.Check all connections.
hums, but will
not start
Defective start relay.Replace relay.
Motor winding damaged.Verify amp draws. Replace compressor if necessary.
Internal compressor mechanical damage.Replace.
Refrigerant overcharge.Check pressures and subcooling.
Check thermal expansion valve setting. Check for refrigerant
overcharge.
Dampen tubing vibration by taping or clamping. Carefully bend
tubing away from contact where possible.
Compressor
Liquid floodback.
Tubing rattle.
noisy or
vibrating
Scroll compressor rotating in reverse.
(3-phase)
Check high and low side pressures during operation to confirm.
Rewire for opposite rotation.
Damaged compressor.Replace the compressor.
Improper mounting on unit base.
Check that compressor is properly isolated and mounting bolts
are tight.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
48
®
Page 51
Troubleshooting – Refrigeration Circuit
SymptomPossible CauseCorrective Action
High suction
pressure
High discharge
pressure
Excessive load on evaporator coil.
Compressor is unloaded.
(digital scroll)
Expansion valve sensing bulb not secured to
suction line.
Thermostatic expansion valve. Overfeeding.
Room load too large.Reduce the load or add more equipment.
Overcharged.Check pressures and subcooling.
Thermal expansion valve setting.
Air inlet to condenser dirty or obstructed.
Condenser fan motor defective.Check condenser fan motor.
Too much refrigerant.Check subcooling. Remove excess refrigerant.
Non-condensable in system.Remove non-condensable from system.
Check for high entering wet bulb temperature, check for
excessive air flow.
Check digital scroll controller signal and solenoid valve.
Check the thermal expansion valve, ensure bulb is insulated.
Check superheat. If superheat is high, then valve is choking
refrigerant flow.
• Check bulb for contact.
• Adjust valve for superheat ~10°F.
• Replace valve power head or valve.
Check bulb location and clamping. Adjust superheat. Replace
expansion valve power head.
Check thermal expansion setting and calibrate
superheat/subcooling.
Check for proper clearances and possible air recirculating.
Clean coil.
Low suction
pressure
Dirty condenser coil.Clean condenser coil.
Condenser fan not running or running
backwards.
High load conditions.Add more equipment or reduce load.
Refrigerant undercharge/loss of refrigerant
charge.
Blower running backward.
Low entering air temperature.
(Low load conditions).
Refrigerant leak.Check system for leaks. Repair leaks and add refrigerant.
Evaporator dirty or iced-up, or airflow
restricted.
Plugged liquid line filter-drier.Replace filter-drier, check psi across filter.
Improper hot gas bypass setting.Check setting and correct as required.
Expansion valve defective, superheat too
high or valve too small.
Moisture in system, check sight glass.Reclaim refrigerant, check for leaks, recharge.
Insufficient refrigerant charge.
Check electrical circuit and fuse. Check fan cycling controls.
Check pressures and subcooling.
Confirm blower rotation. If reversed, interchange any two wires
from 3-phase disconnect.
Check entering air wet bulb conditions.
Clean the coil. Check fan operation. Check airflow.
Adjust valve for proper superheat or replace the expansion
valve if too small or defective.
Check subcooling, check for leak. Repair leak and add
refrigerant.
Low discharge
pressure
Defective or improperly adjusted expansion
valve.
Low suction pressure.See “low suction pressure”.
Faulty condenser temperature controls.
(Condensing fan cycle switch).
Check superheating and adjust thermal expansion valve.
Check condenser controls and reset to obtain desired
condensing temperature.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®49
Page 52
Troubleshooting – Refrigeration Circuit
SymptomPossible CauseCorrective Action
Thermostat location or controls malfunction.Check thermostat, check heat anticipator setting.
Check equalized high side pressure with equivalent outdoor
temperature.
Check airflow, check filters, check VFD control signal for proper
operation.
Check valve. If defective, replace.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
Troubleshooting - Energy Wheel
SymptomPossible CauseCorrective Action
Air seals are too tight.
Energy wheel
does NOT turn
Energy wheel
runs intermittently
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
50
Broken belt.Replace.
No power to wheel motor.
Wheel motor overloads are tripping due to
rubbing between wheel and air seals.
See Air Seals in the Start-Up Components, Energy Wheel
section.
Make sure wheel drive is plugged in. Verify power is
available.
Recheck air seals, make sure they are not too tight. See
Adjust the Air Seals in the Start-Up Components, Energy
Wheel section.
®
Page 53
Troubleshooting – Evaporative Cooling
SymptomPossible CauseCorrective Action
Insufficient water
volume or recirculation
pump not operating
Irregular water
distribution on cooling
media
Scale and mineral
deposit formation on
face of media
Water level in sump pan too low.
Pump filter clogged.
Pump not getting power.
Check water level in sump pan. Water level should be
maintained at greater than one inch.
Check the pump filter at the inlet. Clean the filter if
clogged or dirty.
If pump is not operating, check wiring for loose
connections and proper voltage.
Remove media from unit
and remove media cover
Clogged header.
to visually inspect header
assembly. Clear holes
with drill if necessary.
Water flow adjustment device improperly set. Check water flow adjustment clamp for proper setting.
Clogged header.
Water distribution header, orifices or media partially
blocked or plugged.
Water flow adjustment device improperly set. Check water flow adjustment clamp for proper setting.
Water mineral concentration too high.Increase bleed rate.
Increase water flow rate. Media is self-cleaning with
flow rate of 1-1/2 to 2 gpm per square foot of media
Water flow rate too low.
top area. Generally this flow rate prevents dissolved
solvents from collecting on the media. To prevent further
trouble, flush and clean the system more frequently.
Header partially clogged.
Check water flow across the face of the media. Irregular
water distribution must be corrected (see above).
C
Water Carryover
Inadequate cooling
Excessive water
discharge into drain
If this condition persists, chemicals may need to be
Poor quality supply water.
added. Water pH should be maintained between
6 and 8.
Header partially clogged.Irregular water distribution on face of media (see above).
Unit moving too much air volume.
Non-uniform airflow across entering media
face.
Average face velocity exceeds 550 fpm. Decrease fan
rpm and airflow.
Localized face velocities exceeding 550 fpm. Air filters
or media face area is partially blocked. Clean or replace
air filters and media.
Sump overflow drain not operating.Check the overflow for blockage.
Header partially clogged.
Unit moving too much air volume.
Poor weather conditions for application.
Water flow rate too low.
Bleeder valve improperly adjusted.
Water level in sump pan too low.
Irregular water distribution over face of media (see
above).
Average face velocity exceeds 550 fpm. Decrease fan
rpm and airflow.
Check outside wet-bulb temperature. High wet-bulb
temperatures can decrease performance.
Check water flow rate over media. Flow rate should be
1-1/2 to 2 gpm per square foot of media top area.
Check the water bleed off rate and make sure that it is
not excessive.
Check water level in sump pan. The level should be at
one inch.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®51
Page 54
Troubleshooting – Evaporative Cooling
Pad installed backwards. To get the performance from
the cooling pads, they must be installed properly. The
pads are manufactured with 15/45 degree flute angles.
The pads must always be installed with the steeper flute
angle sloping down toward the entering air side.
Poor performance
after cooling pad
replacement
Incorrect pad installation.
Entering Air
Leaving Air
°
15
°
45
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
52
®
Page 55
Troubleshooting - Controller Alarms
Troubleshooting - Rotation Sensor
The first step in troubleshooting the unit is to check
the on-board alarm indicators. Several of the electronic
controls in the unit monitor the system for faults and will
go into alarm, shutting down the unit or a single function
within the unit.
Microprocessor Controller
Check the screen on the
microprocessor for an alarm
condition. If it is in alarm condition,
a message will show on the
screen.
The microprocessor controller is located in the main
control center. If it is in alarm condition, the alarm button
will blink red. Press the alarm button to see the specific
condition or to reset the microprocessor. Refer to the
Installation Operations and Maintenance manual for
detailed information on fault codes and see the unitspecific wiring diagram.
Phase Monitor
The phase monitor has two LED
indicator lights, one red and one
green. Green indicates proper
operational status, red indicates the
unit has detected a fault and is in
alarm condition.
Variable Frequency Drive (VFD)
VFDs have a display screen that will
show an alarm condition. If a fault such
as a voltage spike occurs, the VFD will
go into alarm and will not reset until a
hard restart is performed. See the unitspecific manufacturer’s manual supplied
with the unit. VFDs are located in the
main control center.
FX05 Furnace Controller
Present only if an indirect gas-fired furnace option is
present.
The FX05 furnace controller
will display an alarm condition
if present. The controller
will be found in the furnace
control center. See the furnace
Installation, Operation and Maintenance manual and the
controller manufacturer’s unit-specific manual for further
information.
When the unit is first turned on, the LED on the back of
the sensor should turn on and stay on with the wheel
running.
1. When the wheel is spinning, the contact in the
rotation sensor is closed and the small LED light on
the sensor in ON.
2. When the wheel is stopped there is a 10-20 second
delay before the sensor will indicate no rotation.
When the sensor indicates no rotation, it opens the
internal contact and the LED light of OFF.
3. If the LED comes on and then shuts off after
5 seconds or less, the sensor is NOT properly
set. Contact manufacturer for adjustment
procedure.
4. If the LED comes on and then shuts off after 10-20
seconds, the sensor is properly set although it is
either to close to the wheel or not close enough.
It should be 4 mm from the wheel. Verify that the
sensor depth was set using the appropriate gauge.
When the wheel is unplugged and the unit is still
powered on:
1. The LED should stay on for 10-20 seconds and then
turn off.
Troubleshooting - Digital Scroll
Compressor Controller (PDX Only)
The Fault Code chart is printed on the back of the
controller. Note that if the controller generates either a
Code 2 or a Code 4 Lockout, a manual reset must be
performed. Manual Reset is accomplished by shutting
off main power to the unit and then turning it back on.
Digital Compressor Controller Fault Codes
Alert
Code
Code 2*High discharge
Code 3Compressor
Code 4*Locked rotorBlinks 4 timesLockout
Code 5Demand signal
Code 6Discharge
Code 7FutureN/AN/A
Code 8Welded
Code 9Low voltageBlinks 9 timesTrip
* Protective faults that require manual reset
System
Condition
temp trip
protector trip
loss
thermistor fault
contactor
Diagnostic
Alert Light
Blinks 2 timesLockout
Blinks 3 timesLockout
Blinks 5 timesLockout
Blinks 6 timesReduce
Blinks 8 timesUnload
Action
capacity
compressor
compressor
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling®53
Page 56
Troubleshooting - Unit Protection
Module (Heat Pump Only)
Troubleshooting - Economizer
Alarms
Each unit includes one Unit
Protection Module (UPM)
printed circuit board with two
LED indictor lights. The UPM
board will come from the
factory with default settings.
Intelligent Reset
If a fault condition is initiated,
the five minute delay on break
Default Settings
FreezeNO
Temp35°F
Lockout2
ResetT
AlarmCONT
TestNO
Hot/Dry AlarmHOT
time period and the random
start timer is initiated and the unit will restart after
these delays expire. During this period the fault LED
will indicate the cause of the fault. If the fault condition
occurs 2 or 4 times (depending on 2 or 4 setting for
Lockout dip switch) before 60 minutes, the unit will go
into a hard lockout and requires a manual lockout reset.
A single condensate overflow fault will cause the unit
to go into a hard lockout immediately, and will require a
manual lockout reset.
Lockout Reset
A hard lockout can be reset by turning the unit
thermostat off and then back on when the “RESET” dip
switch is set to “Y” or by shutting off unit power at the
circuit breaker when the “RESET” dip switch is set to
“R”.
LED
Color
Green Power LED indicates 18-30 VAC present at the board
Dual or Single
Compressor
Dual
Compressor
Red
Single
Compressor
LED Fault Indication
# of
Status
blinks
High pressure lockout
1
Compressor 1
Low pressure lockout
2
Compressor 1
High pressure lockout
3
Compressor 2
Low pressure lockout
4
Compressor 2
Freeze sensor lockout
5
(optional item)
Condensate overflow in coil
6
drain pan (optional item)
Brownout AC voltage to R
7
and C terminal below 18 VAC
1High pressure lockout
2Low pressure lockout
Freeze sensor lockout
3
(optional item)
Condensate overflow in coil
4
drain pan (optional item)
Brownout AC voltage to R
5
and C terminals below
18 VAC
Addressing Alarms
Alarms will signify a faulty sensor. When this occurs,
verify all connections to the sensor and controller are
secure. Press enter twice to clear the alarm. If the issue
persists, consult the factory.
Clearing Alarms
Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the
(enter).
3. ERASE? displays.
4. Press
(enter).
5. ALARM ERASED displays.
6. Press (escape) to complete the action and return
to the previous menu.
NOTE
If an alarm still exists after you clear it, it redisplays
within 5 seconds.
Reference
Technical Support
For technical support contact the Tempered Air
Products group from Monday - Friday, 8AM-5PM CST
at 1-877-202-6123.
Refer to the following Installation, Operation and
Maintenance Manuals for additional details. All are
available at www.greenheck.com
• DDC Controller for Energy Recovery
• ERCH Curbs
• PVF/PVG Indirect Gas-Fired Heat Modules
General Description - NOT model specificEnergy Recovery Ventilator with Heating and Cooling
54
®
Page 57
Reference - Venting Connection Locations
COMBUSTION AIR INLET
EXHAUST OUTLET
COMBUSTION AIR INLET
EXHAUST OUTLET
B
A
C
Bottom Venting Location
Bottom Venting Location
Housing
Size
ERCH-20
ERCH-45
ERCH-55
ERCH-90
Dimensions are in inches. Dimensions B and D are not needed for standard venting.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck catalog Energy Recovery Ventilator Model ERCH,
provides additional information describing the equipment, fan
performance, available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at: www.amca.org.
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
Model G Direct Drive
Model G is a direct drive downblast centrifugal
exhaust fan. These fans are specifically
designed for roof mounted applications
exhausting relatively clean air. Performance
capabilities range up to 6,300 cfm (10,703
3
m
/hr) and up to 1.75 in. wg (435 Pa) of static
pressure. The maximum continuous operating
temperature is 180°F (82ºC). G models are available
in 20 sizes with nominal wheel diameter ranging from
8 to 22 inches (203 to 558 mm) (060 - 203 unit sizes).
Each fan shall bear a permanently affixed
manufacturer’s engraved metal nameplate containing
the model number and individual serial number. All
fans are UL/cUL Listed Standard 705.
General Safety Information
Only qualified personnel should install this fan.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity is present. If more information is
needed, contact a licensed professional engineer
before moving forward.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC) and the
National Fire Protection Agency (NFPA), where
applicable. Follow the Canadian Electric Code
(CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than max cataloged fan
RPM. Adjustments to fan speed significantly affects
motor load. If the fan RPM is changed, the motor
current should be checked to make sure it is not
exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
Model GB Belt Drive
GB model fans are belt drive downblast
centrifugal exhaust fans. These fans are
specifically designed for roof mounted
applications exhausting relatively clean
air. Performance capabilities range up
to 44,700 cfm (75,950 m
3.25 in. wg (809 Pa) of static pressure.
The maximum continuous operating temperature is
180°F (82ºC). GB models are available in 29 sizes with
nominal wheel diameters ranging from 11 to 54 inches
(279 to 1372 mm) (071-540 unit sizes). Each fan shall
bear a permanently affixed manufacturer’s nameplate
containing the model number and individual serial
number. All fans are UL/cUL Listed Standard 705.
7. Never open access doors to a duct while the fan is
running.
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
CAUTION
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
DANGER
Pour écarter les risques d’incendie, de choc
électrique ou de blessure grave, veiller à toujours
débrancher, verrouiller et étiqueter la source de
courant avant l’installation ou l’entretien.
ATTENTION
Lors de toute intervention sur la soufflante, le moteur
peut être suffisamment chaud pour provoquer une
douleur voire une blessure. Laisser le moteur refroidir
avant toute maintenance.
ATTENTION
Faire preuve de précaution dans les atmosphères
explosives.
3
/hr) and up to
®
Downblast Centrifugal Roof Exhaust1
Page 60
Receiving
Upon receiving the product, check to ensure all
items are accounted for by referencing the delivery
receipt or packing list. Inspect each crate or carton
for shipping damage before accepting delivery. Alert
the carrier of any damage detected. The customer will
make notification of damage (or shortage of items)
on the delivery receipt and all copies of the bill of
lading which is countersigned by the delivering carrier.
If damaged, immediately contact your Greenheck
Representative. Any physical damage to the unit after
acceptance is not the responsibility of Greenheck Fan
Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Figure 2
Figure 3
Screws
Hook With
Safety Latch
(Supplied by others)
(2) Bearing Plate
Lifting Points
(4) Drive Frame
Lifting Points
Screws
Handling
G Direct Drive
Lift unit on to the roof utilizing hooks under the lip
of the shroud. Evenly space the hooks around the
shroud using a minimum of four lifting straps. Use
a spreader bar to ensure the straps do not come in
contact with the unit (see Figure 1).
Figure 1
Spreader Bar
Lifting Strap
Hook
1¾ in.
(44 mm)
Curb Cap
GB Belt Drive
When lifting the unit on to the roof, use either the
four lifting points on the drive frame or the two lifting
points on the bearing plate if present (see Figure
2 for lifting points). Access to the drive frame is
accomplished by removing the screws pointed out in
Figure 3. The cover can then be removed and placed
on a flat surface in an area protected from strong
winds.
When G/GB unit is on the roof, move fan to desired
location using lifting points and fasten securely
through mounting holes in base. Shims may be
necessary depending upon roofing material thickness.
The motor amperage and voltage ratings must be
checked for compatibility to supply voltage prior to
final electrical connection. For G/GB installations, the
electrical supply should be routed through the conduit
chase located between the curb cap and the bottom
of the motor compartment. Wiring must conform to
local and national codes.
Downblast Centrifugal Roof Exhaust2
®
Page 61
Storage
Fans are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the fan and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
Indoor
The ideal environment for the storage of fans and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain or snow. Temperatures should be
evenly maintained between 30° to 110°F (-1° to 43°C)
(wide temperature swings may cause condensation
and “sweating” of metal parts). All accessories must
be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice or snow
and wipe dry before moving to indoor storage. To
avoid “sweating” of metal parts, allow cold parts to
reach room temperature. To dry parts and packages,
use a portable electric heater to get rid of any
moisture buildup. Leave coverings loose to permit air
circulation and to allow for periodic inspection.
The unit should be stored at least 3½ inches (89 mm)
off the floor on wooden blocks covered with moisture
proof paper or polyethylene sheathing. Aisles between
parts and along all walls should be provided to permit
air circulation and space for inspection.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given
to touch-up or repainting. Fans with special coatings
may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lintfree cloths. Polish any remaining rust from surface
with crocus cloth or fine emery paper and oil. Do not
destroy the continuity of the surfaces. Thoroughly
wipe clean with Tectyl
®
506 (Ashland Inc.) or the
equivalent. For hard to reach internal surfaces or for
occasional use, consider using Tectyl
®
511M Rust
Preventive, WD-40® or the equivalent.
Removing From Storage
As fans are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion until the fan equipment
goes into operation.
Table of Contents
Outdoor
Fans designed for outdoor applications may be stored
outdoors, if absolutely necessary. Roads or aisles for
portable cranes and hauling equipment are needed.
The fan should be placed on a level surface to prevent
water from leaking into the fan. The fan should be
elevated on an adequate number of wooden blocks
so that it is above water and snow levels and has
enough blocking to prevent it from settling into soft
ground. Locate parts far enough apart to permit air
circulation, sunlight and space for periodic inspection.
To minimize water accumulation, place all fan parts on
blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Fan wheels should be blocked to prevent spinning
caused by strong winds.
General Safety Information ....................3
Receiving, Unpacking, Handling ................2
Storage ...................................3
Inspection and Maintenance during Storage ......3
Removing from Storage ......................3
Installation
Typical Roof Mounting Installation ............4
Typical Motor Wiring Diagram ...............4
Typical Roof Mounting Installation, Model G ....5
Typical Roof Mounting Installation, Model GB . . .5
Mounting for Severe Duty Installation ............6
Prestarting Checks ........................7-8
Operation ..................................8
Inspection .................................8
Routine Maintenance ........................9
Belt and Bearing Maintenance ...............9
Bearing Lubrication Schedule ..............10
Fan Inlet Connections .......................10
Troubleshooting ............................11
Parts List .................................12
Our Commitment ...........................12
®
Downblast Centrifugal Roof Exhaust3
Page 62
Installation
Typical Roof Mounting Installation
1. On the roof surface, cut an appropriate sized hole
and follow manufacturer’s instructions on curb
installation. Caulk and flash the curb to ensure a
water tight seal.
Roof Curb Installation
10. Check all fasteners for tightness.
11. Mount and wire safety disconnect switch under
motor cover. Wire control switches at ground
level, refer to Figure 4.
12. Replace motor cover.
Typical Wiring Diagram
MOTOR
SUPPLY VOLTAGE
115/208-230/60/1
J-BOX
L1
L2
Figure 4
Vari-Green Wiring
For Vari-Green wiring, refer to the Vari-Green
Motor and Controls Installation, Operation and
Maintenance Manual for complete wiring and
operation instructions.
MOTOR
J-BOX
SUPPLY VOLTAGE
208-230/460/60/3
L1
L2
L3
2. If unit is equipped with a backdraft damper, it
should be installed now.
3. Remove motor cover. Access to the motor
compartment is accomplished by removing the
screws as shown in Figure 3, page 2.
4. On GB Belt Drive fans, use the lifting lugs on the
drive frame or bearing plate to lift and place the
unit on top of roof curb. Refer to Figure 2, page 2.
5. On G Direct Drive fans, lift and place the unit on
top of roof curb using hooks under the lip of the
shroud. Refer to Figure 1, page 2.
6. Secure fan to curb using a minimum of eight lag
screws, metal screws or the suitable fasteners.
Shims may be required depending upon curb
installation and roofing material.
Note: Severe duty applications may require
additional fasteners. See page 6.
7. Verify power line wiring is de-energized before
connecting fan motor to power source.
8. Connect power supply wiring to the motor as
indicated on the motor nameplate or terminal box
cover. Check the power source for compatibility
with the requirements of your equipment.
9. Check fan wheel for free rotation, recenter if
necessary.
* Approximate weight shown in pounds (kilograms) is the largest
cataloged Open Drip Proof motor.
• The roof curb should be 1½ in. (38 mm) less than the curb cap to
allow for roofing and flashing.
®
Downblast Centrifugal Roof Exhaust5
Page 64
Mounting for Severe Duty Installations
Fan to Curb Mounting
5/16-inch self-drilling fasteners are to be installed on
each side of fan with one fastener 4 inches from each
edge and one fastener in the center. Fasteners are to
be equally spaced.
Curb to Deck Mounting
Fasteners need to be located on all four sides of the curb.
Roof Curb Roof Curb
3/8 in. (10 mm) S.S. Hilti Kwik Bolt
Three Expansion Anchors
Min. 2-1/2 in. (64 mm) Engagement
1/4 in. - 14 Self-Drilling Screw
Min. 1/2 in. (13 mm) of Threads Through
Roof Curb
Fan Size
Fasteners
Per Side
≤ 1633
180 to 2405
≥ 2609
1¼ in.
(32 mm)
1¼ in.
(32 mm)
Curb Corner
Anchor Detail
Roof Curb
Model GPF, GPFHL,
GPFHD or Equivalent
18 ga. min.
High wind ratings – 42 in. Tall Max
Seismic ratings – 24 in. Tall Max
Steel Welded Construction
3/8 in. (10 mm) Lag Bolt (Zinc Plated)
Min. 3 in. (76 mm) Thread Engagement
2500 Min. PSI
Concrete
Concrete
Deck Anchoring
High Wind Ratings
Fan
Size
≤ 141
Concrete
> 141
≤ 141
Steel
> 141
≤ 141
Timber
> 141
All dimensions are in inches (millimeters).
Curb Cap Size
17x17 to 22x22
(432x432 to 559x559 mm)
26x26 to 40x40
(660x660 to 1016x1016 mm)
17x17 to 22x22
(432x432 to 559x559 mm)
26x26 to 40x40
(660x660 to 1016x1016 mm)
17x17 to 22x22
(432x432 to 559x559 mm)
26x26 to 40x40
(660x660 to 1016x1016 mm)
Steel
Deck Anchoring
Self-Drilling
Screw Size
3/8”
1/4” - 14
3/8”
Roof Truss
1/8 in. (3 mm) Thick
or 12 ga. Min.
Fasteners
Per Side
Total
Fasteners
312
312
312
416
312
416
Wood Timber
Min. 4 in. (102 mm)
Nominal Thickness
Min. G = 0.42
G: Specific Gravity
of Lumber
Timber Anchoring
Seismic Ratings
Fan Size
060-30028
330-540312
060-30028
330-540312
060-30028
330-540312
NOTE: Installation instructions for seismic ratings are only
recommendations.
Final design must be determined by Structural Engineer
of Record (SEOR) including requirements for curb
construction, mounting of unit to curb and mounting of
curb to structure.
Fasteners
Per Side
Total
Downblast Centrifugal Roof Exhaust6
®
Page 65
Pre-Starting Checks
1. Check all fasteners and setscrews for tightness.
The wheel should rotate freely and be aligned as
shown in Figure 7.
Overlap
Figure 7
ModelSize
G060-095–3/32 (2)
G097-1631/4 (6)–
GB071-1611/4 (6)–
G183-2433/8 (10)–
GB180-2403/8 (10)–
GB260-5401/2
Overlap
in. (mm)
(13)–
2. Wheel position is preset and the unit is test run at
the factory. Movement may occur during shipment
and realignment may be necessary.
3. Only G model - Centering height alignment can
be accomplished by loosening the set screws in
the wheel and moving the wheel to the desired
position.
4. Only GB model - Centering can be accomplished
by loosening the bolts holding the drive frame
to the shock mounts and repositioning the drive
frame.
Wheel and inlet cone overlap can be adjusted by
loosening the set screws in the wheel and moving
the wheel to the desired position.
Fan RPM should be checked and verified with a
tachometer.
5. Check wheel rotation (viewing from the shaft side)
by momentarily energizing
the unit. Rotation should be
clockwise as shown in Figure
8 and correspond to rotation
decal on the unit.
If wheel rotation is incorrect,
reverse two of the wiring leads
or check motor wiring for
single phase.
Figure 8
Gap
Gap
in. (mm)
Clockwise Rotation
WARNING
Correct direction of wheel rotation is critical.
Reversed rotation will result in poor air performance,
motor overloading and possible motor burnout.
AVERTISSEMENT
La turbine doit impérativement tourner dans le bon
sens. Une rotation en sens inverse entraînerait
de mauvaises performances de soufflage, une
surcharge du moteur voire un grillage du moteur.
IMPORTANT
The fan has been checked for mechanical noises at
the factory prior to shipment. If mechanical noise
should develop, suggested corrective actions are
offered in the Troubleshooting section.
IMPORTANT
Over tightening will cause excessive bearing wear
and noise. Too little tension will cause slippage at
startup and uneven wear.
Model GB Pre-Starting Belt Tension Checks
6. Always loosen tension enough to install belts
without stretching, see Figure 9.
Do not force belt(s). Forcing the belts will break the
cords and cause belt failure.
Figure 9
7. For units with two groove pulleys, adjust so the
tension is equal in both belts.
8. If adjustments are made, it is very important to
check the pulleys for proper alignment. Misaligned
pulleys lead to excessive belt wear vibration, noise
and power loss, see Figure 10.
CORRECTWRONGWRONGWRONG
Figure 10
9. For GB units: Belt tension can be adjusted by
loosening four fasteners on the drive frame, see
Figure 11. The motor plate slides on the slotted
adjusting arms and
drive frame angles in
the same manner.
Four (4) fasteners in
total.
Identical fasteners on
opposing side must
also be loosened.
Figure 11
®
Downblast Centrifugal Roof Exhaust7
Page 66
10. Belt tension can be adjusted by loosening four
fasteners on the drive frame, see Figure 11. The
motor plate slides on the slotted adjusting arms
and drive frame angles in the same manner.
11. Sizes 071-161: Belts should be tensioned just
enough to prevent slippage at full load.
Note: Belts should have a slight bow on the slack
side while running at full load, see Figure 12a.
Deflection =
Slack
Side
Figure 12aFigure 12b
Belt Span
64
Belt
Span
Sizes 180-540: Belt tension should be adjusted
to allow 1/64 in. (0.397 mm) of deflection per inch
of belt span. For example, a 15 in. (381 mm) belt
span should have 15/64 in. (0.234 mm) (or about
1/4 in. (6 mm)) of deflection with moderate thumb
pressure at mid-point between pulleys, see
Figure 12b.
12. The adjustable motor pulley is factory set for
the RPM specified. Speed can be increased by
closing or decreased by opening the adjustable
motor pulley.
13. Any increase in speed represents a substantial
increase in the horsepower required by the unit.
14. Motor amperage should always be checked to
avoid serious damage to the motor when speed
is varied.
Operation
1. Before starting up or operating fan, check all
fasteners for tightness. In particular, check the
setscrews in wheel hub.
2. While in the OFF position or before connecting the
fan to power, turn the fan wheel by hand to be sure
it is not striking the venturi or any obstacle.
3. Start the fan and shut it off immediately to check
rotation of the wheel with directional arrow in the
motor compartment.
4. When the fan is started, observe the operation and
check for any unusual noises.
5. With the system in full operation and all ductwork
attached, measure current input to the motor and
compare with the nameplate rating to determine if
the motor is operating under safe load conditions.
6. Keep inlets and approaches to fan clean and free
from obstruction.
IMPORTANT
Adjust (tighten) belt tension after the first
24-48 hours of operation.
Inspection
Inspection of the fan should be conducted at the
first 30 minute and 24 hour intervals of satisfactory
operation.
30 Minute Interval
Inspect bolts, setscrews and motor mounting bolts.
Adjust and tighten as necessary.
24 Hour Interval
Check all internal components. On GB unit only,
inspect belt alignment and tension. Adjust and tighten
as necessary.
Downblast Centrifugal Roof Exhaust8
®
Page 67
Routine Maintenance
DANGER
Disconnect and secure to the “off” position all
electrical power to the fan prior to inspection
or servicing. Failure to comply with this safety
precaution could result in serious injury or death.
DANGER
Pour écarter les risques de blessure grave ou
de mort, débrancher et verrouiller l’alimentation
électrique en position « Arrêt » avant tout contrôle
ou entretien.
IMPORTANT
Uneven cleaning of the wheel will produce an out of
balance condition that will cause vibration in the fan.
WARNING
This unit should be made non-functional when
cleaning the wheel or housing (fuses removed,
disconnect locked off).
AVERTISSEMENT
L’appareil doit être rendu non opérationnel lors
du nettoyage de la turbine ou du caisson (fusibles
retirés, sectionneur verrouillé).
Greasing of motors is only intended when fittings are
provided. Many fractional horsepower motors are
permanently lubricated and should not be lubricated
after installation. Motors supplied with grease fittings
should be greased in accordance with manufacturers’
recommendations. Where motor temperatures do not
exceed 104ºF (40ºC), the grease should be replaced
after 2,000 hours of running time as a general rule.
Wheels require very little attention when moving
clean air. Occasionally, oil and dust may accumulate
causing imbalance. When this occurs, the wheel and
housing should be cleaned to ensure smooth and safe
operation.
All fasteners should be checked for tightness each
time maintenance checks are performed prior to
restarting unit.
A proper maintenance program will help these units
deliver years of dependable service.
Belt and Bearing Maintenance for GB
Model
1. Belts tend to stretch after a period of time. They
should be checked periodically for wear and
tightness. When replacing belts, use the same
type as supplied with the unit.
2. Matched belts should always be used on units
with multi-groove pulleys.
3. For belt replacement, loosen the tensioning device
enough to allow removal of the belt by hand.
4. Once installed, adjust belts as shown in
“Pre-Starting Checks.”
5. To ensure tightness, check pulley setscrews.
Proper keys must be in keyways.
6. Fan RPM should not be readjusted. Only use
pulleys of identical size and type when replacing
pulleys.
7. Shaft bearings can be classified in two
groups: relubricating and non-relubricating. All
non-relubricating bearings on model GB fans
are factory lubricated and require no further
lubrication under normal use (between -20º
to 180ºF (-29º to 82ºC) in a relatively clean
environment).
8. On GB belt driven fans, the standard cast pillow
block bearings are factory lubricated and are
provided with external grease fittings. Annual
lubrication is recommended, or more frequently
if needed (See Table 2). Do not over-grease. Use
only one or two shots of lubricant with a hand
gun. Maximum hand gun rating is 40 psi. Rotate
bearings during lubrication where good safety
practice permits. Caution should be employed to
prevent over packing or contamination.
9. Grease fittings should be wiped clean. The unit
should be in operation while lubricating. Extreme
care should be used around moving parts.
10. Grease should be pumped in very slowly until a
slight bead forms around the seal. A high grade
lithium base grease should be used. (See Table 3)
11. During the first few months of operation,
check bearing setscrews periodically to ensure
tightness.
12. If unit is to be left idle for an extended period,
remove belts and store in a cool, dry place to
avoid premature belt failure.
®
Downblast Centrifugal Roof Exhaust9
Page 68
Recommended Bearings Lubrication
Frequency in Months
NOTE: If unusual environment conditions exist
(extreme temperature, moisture or contaminants)
more frequent lubrication is required.
A good quality lithium base grease, conforming to
NLGI Grade 2 consistency, such as those listed in
Table 3 may be used.
Table 2: Suggested Fan Bearing Lubrication Intervals
Interval
(months)
1 to 3
3 to 6
6 to 12
12 to 18 Infrequent operation or light duty in clean atmosphere
Heavy duty in dirty, dusty locations; high ambient
temperatures; moisture laden atmosphere; vibration.
12 to 24 hours per day, heavy duty, or if moisture is
present
8 to 16 hours per day in clean, relatively dry
atmosphere
Table 3: Grease Manufacturers
Manufacturer Grease (NLGI #2)
U.S. Electric MotorsGrease No. 83343
Chevron U.S.A. IncChevron SRI Grease #2
Mobil Oil Corporation
Texaco, Inc.
Amoco Oil Co.Rykon Premium #2
ExxonUnirex N2
ShellB Shell Alvania #2
Type of Service
Mobilith
Mobil 532
Premium BRB #2
Texaco Multifak #2
Fan Inlet Connections
In order to assure proper fan performance, caution
must be exercised in fan placement and connection
to the ventilation system. Obstructions, transitions,
poorly designed elbows, improperly selected
dampers, etc., can cause reduced performance,
excessive noise and increased mechanical stress.
For performance to be as published, the system must
provide uniform and stable airflow into the fan.
Poor
Dampers must open fully.
Use motorized dampers in
low airflow applications to
reduce losses.
Good
Avoid sharp turns or
entrance conditions which
cause uneven flow. Use
turning vanes in elbows to
reduce adverse effects.
Poor
Good
Provide uniform airflow at
fan inlet and through the
damper to assure optimum
performance. The curb
cap should be three wheel
diameters from the radius.
Use turning vanes in duct
when possible.
Provide uniform airflow at
fan inlet to assure optimum
performance.
Downblast Centrifugal Roof Exhaust10
®
Page 69
Troubleshooting
WARNING
Before taking any corrective action, make certain
unit is not capable of operation during repairs.
PROBLEMCAUSECORRECTIVE ACTION
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars
on shaft.
Tighten pulleys on motor/fan shaft. Adjust belt tension. Align pulleys
properly, see page 7, Figure 9-10. Replace worn belts or pulleys.
Replace defective bearing(s). Lubricate bearings. Tighten collars
and fasteners.
Clean all dirt off wheel. Check wheel balance, rebalance in place if
necessary.
Center wheel on inlet, see page 7, Figure 7.
Excessive
noise
or vibration
Wheel rubbing inlet
V-belt drive
Bearings
Wheel unbalance
Belts too tight or too looseAdjust tension, see page 8, Figure 12a-b.
Wheel improperly aligned and
rubbing
Loose drive or motor pulleysAlign and tighten. See “Pre-Starting Checks”, see page 7.
Foreign objects in wheel or
housing
Remove objects, check for damage or unbalance.
Fan base not securely anchoredSecure properly.
Motor hood loose and rattlingTighten screws securing motor hood.
High
horsepower
Fan does
not operate
Defective or loose motor
bearings
FanCheck rotation of wheel, see page 7, Figure 8. Reduce fan speed.
Duct system
Electrical supply
DriveCheck for broken belts. Tighten loose pulleys.
Motor
Replace motor with same frame size, RPM-HP.
Resize ductwork. Check proper operation of face and bypass
dampers. Check filters and access doors.
Check fuses/circuit breakers. Check for switches off. Check for
correct supply voltage.
Assure motor is correct horsepower and not tripping overload
protector.
LubricationCheck for excessive or insufficient grease in the bearing.
Mechanical
Replace damaged bearing. Relieve excessive belt tension. Align
bearings. Check for bent shaft.
Belt slippageAdjust tension or replace bad belts, see page 7-8.
Motor
overloads
or overheats
Over/Under line voltageContact power company.
Incorrect wheel rotation
Wheel RPM too high
Check motor wiring (page 4) verify motor is wired for correct
rotation.
Check drives or slow down fan by opening variable pitch pulley on
motor shaft.
Undersized motorCheck motor ratings with catalog speed and air capacity chart.
Motor wired incorrectlyCheck motor wiring to wiring diagram located on fan motor.
System resistance too high
Check system: Proper operation of backdraft or control dampers,
obstruction in ductwork, clean dirty filters.
Unit running backwardsCorrect as shown on page 7, Figure 8.
Excessive dirt buildup on wheels Clean wheel.
Reduced
airflow
Improper wheel alignmentCenter wheel on inlets, see Pre-Starting checks on page 7, Figure 7.
Dampers closedInspect and repair.
Blocked duct/clogged filterClean or replace.
Belt slippage Replace and adjust tension.
Speed too slowCheck for correct drives.
Avant d’entreprendre toute action corrective,
s’assurer que l’appareil ne pourra pas fonctionner
durant les réparations.
AVERTISSEMENT
®
Downblast Centrifugal Roof Exhaust11
Page 70
Parts List
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts. Before
taking any corrective action, make certain unit is not capable of operation during repairs.
CAUTION
A fan manufactured with an explosion resistant
motor does not certify the entire unit to be explosion
proof. Refer to ULListing Mark for the fans
approved usage.
La présence d’un moteur antidéflagrant sur un
ventilateur ne garantit pas que tout l’appareil est
antidéflagrant. Pour connaître les emplois autorisés
de l’appareil, voir son marquage de conformité UL.
G Direct DriveGB Belt Drive
Motor Cover
Shaft Pulley
Bearings
Drive Frame
Assembly
Shock Mounts
Shroud
Wheel
Conduit
Chase
Vertical
Support
Shock
Mounts
Shroud
Birdguard
Wheel
Curb Cap/
Venturi
Motor
Hood Clip
Shroud Brace
Vertical
Support
Lower
Windband
CAUTION
Motor Cover
Belt
Motor Pulley
Motor
Fan Shaft
Birdguard
Shroud Brace
Windband
Curb Cap/
Venturi
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Centrifugal Upblast and Sidewall Exhaust
catalog provides additional information describing the
equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.
Page 71
Document 474680
Model SP
®
Model CSP
Ceiling Exhaust and Inline Fans
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
Model SP
Model SP is a direct drive ceiling
exhaust fan designed for clean
air applications where low sound
levels are required. Many options
and accessories are available such
as lights, motion detectors, ceiling radiation dampers
and speed controls. Capacities range from 25 to 1,600
cfm (42 to 2,718 m
Licensed for Sound and Air Performance.
ENERGY STAR® Certified models include:
SP-A, 50, 70, 90, 200, 250, 290 and 410;
SP-B, 50, 70, 80 and 90.
To reduce the risk of fire, electric shock, or injury to persons,
observe the following:
• Suitable for use with solid state speed controls.
• Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
• Before servicing or cleaning unit, switch power off at service panel
and lock service disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
• Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) and the local code authorities.
• When cutting or drilling into wall or ceiling, do not damage
electrical wiring or other hidden utilities.
• Acceptable for use over a bathtub or shower when installed
in a GFCI protected branch circuit. (Up through size SP-A390)
• Never place a switch where it can be reached from a tub or
shower.
• Ducted fans must always be vented to the outdoors.
• These fans are not recommended for cooking exhaust
applications. They are designed primarily for low temperature,
clean air applications only. The diagram shows the minimum
distance these fans should be placed in relation to cooking
equipment.
• Fan/Light
insulated to a value greater than R40.
• For general ventilating use only. Do not use to exhaust hazardous
or explosive materials and vapors.
combination not to be installed in a
3
/hr) and 1 in. wg (248 Pa). AMCA
WARNING!
ceiling thermally
CAUTION!
Model CSP
Model CSP is a direct drive inline
exhaust fan designed for clean
air applications where low sound
levels are required. Capacities
range from 70 to 3,800 cfm (119 to
6,456 m
AMCA Licensed for Air Performance.
Pour réduire le risque d’incendie, de choc électrique ou de
blessure corporelle, respecter cd qui suit:
• Appareil pouvant être utilisé avec un régulateur de vitesse à semi-
• Utiliser cet appareil exclusivement comme prévu par le fabricant. En
• Avant tout entretien ou nettoyage de l’appareil, couper l’alimentation
• La pose et le câblage électrique doivent être effectués par des
• Une quantité d’air suffisante est nécessaire pour la bonne combustion
• Lors de la découpe ou du perçage de murs ou plafonds, ne pas
• Pose admissible au-dessus d’une baignoire ou d’une douche sous
• Ne jamais placer d’interrupteur à un emplacement à portée d’une
• Les caissons d’extraction à gaine doivent toujours être évacués vers
• Ces caissons ne sont pas conseillés pour les applications
• Le combiné ventilateur/luminaire ne devra pas être installé dans un
• À utiliser pour la ventilation générale uniquement. Ne pas utiliser
3
/hr) and 1 in. wg (248 Pa).
AVERTISSEMENT!
conducteurs.
cas de questions, communiquer avec le fabricant à l’adresse ou au
numéro de téléphone figurant dans la garantie.
sur le tableau électrique et verrouiller le dispositif de sectionnement
pour empêcher toute mise sous tension accidentelle. Si le dispositif
de sectionnement ne peut pas être verrouillé, attacher un moyen
de mise en garde bien visible, tel qu’un panonceau, au tableau
électrique.
personnes qualifiées en conformité avec les codes et normes en
vigueur, y compris pour la résistance au feu du bâtiment.
et l’extraction des gaz brûlés par le conduit d’évacuation (cheminée)
d’appareils à combustible afin d’éviter le refoulement. Veiller à suivre
les indications du fabricant du matériel de chauffe, les normes de
sécurité telles que celles publiées par la National Fire Protection
Association (NFPA) et l’American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE) et la réglementation en
vigueur.
endommager les câbles électriques et autres conduites masquées.
réserve de raccordement à un circuit de dérivation à protection GFCI
(disjoncteur différentiel). (Jusqu’à la taille SP-A390 incluse)
baignoire ou d’une douche.
l’extérieur.
d’aspiration de vapeurs de cuisson. Ils sont conçus essentiellement
pour l’aspiration d’air propre à basse température. Le schéma
indique la distance minimale de placement de ces caissons par
rapport à l’équipement de cuisson.
plafond ayant une isolation thermique d’une valeur supérieure à R40.
ATTENTION!
pour l’aspiration de matières et vapeurs dangereuses ou explosives.
®
Ceiling Exhaust and Inline Fans1
Page 72
Prepare the fan
Power Assembly
If power assembly (motor, wheel, and scroll) is not
installed in housing, insert the electrical plug into fan
socket, then slide scroll end of power assembly into
fan housing. Attach by using two sheet metal screws
provided.
B Model
A Model
Fan Rotation
To rotate from horizontal to vertical discharge
A-Models Only
Remove Wiring Knockout
Remove either top or side wiring knockout,
depending on wiring
direction, by
bending it back
E
lectrical
A
cce
P
ane
ss
l
and forth to
break tabs.
K
nockout
s
Ductwork
Check ductwork to see if the fan’s discharge requires
rotation from horizontal to vertical discharge.
Airflow
Airflow
A-50-500, 710, 780 Models
Remove the two screws holding the power assembly
in and pull power assembly out. Rotate power
assembly 180 degrees and put back into fan. Use
the same screws to reattach power assembly to fan
housing. Flip fan over and remove the four screws
holding the discharge duct and damper assembly.
Exchange the assembly with plate mounted on top of
fan, as shown in these illustrations.
A-700, 900-1500 Models
Remove the eight screws
holding the access panel or
collar as shown in picture.
Rotate the fan housing so
the discharge is facing up.
Replace access panel or
collar and screws.
Access
Panel
Access
Panel
Ceiling Exhaust and Inline Fans2
®
Page 73
Ceiling Radiation Damper (CRD)
A
A
If fan is to be used in a fire resistive membrane
ceiling, a ceiling radiation damper must be used.
If the ceiling radiation damper is already mounted to
the fan from the factory, proceed to Install the Fan.
To mount the ceiling radiation damper to fan, make sure
grille attachment tabs are facing down. Then place the inlet
part of the fan into the ceiling radiation damper collar, and
use self-tapping sheet metal screws (by others) to screw
through the damper collar and into the fan housing. If the
fan/light combination is being used, make sure ceiling
radiation damper has
an electrical plug in it.
The electrical plug must
be inserted into the fan.
Make sure the electrical
wire will not interfere with
damper operation as
shown in figure below.
Wires to ceiling fan
Attachment Tabs
A-50-510, 710, 780 Models
B-Models
Discharge Installation SP-A 50-90 Models
12
Insert plastic duct tab into SP-A box slots.
SP-A Box
SP-A Box Slot
Plastic SPDuct Adapter Tabs
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Plastic SPDuct Adapter (PN
3
Install screws provided to secure discharge.
473388
A-700, 900-1550 Models
Rotate plastic SP-A duct adapter (PN 473388)
until the screw tabs meets SP-A box.
)
SP-A Box
Plastic SP-A
Duct Adapter (PN 473388)
Wires from lighted grille
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Screw Tabs
Do not allow
interference
in this area
®
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Screw holes
Ceiling Exhaust and Inline Fans3
Page 74
Discharge Installation SP/CSP-B 50-200 Models
12
Insert SP-B box scroll tab into SP-B box
scroll slots.
SP-B
Box Scroll Tabs
SP-B
Box Scroll Slots
Rotate plastic SP-B duct adapter (PN 474433)
until the two SP-B mounting tabs fully engage
into the two SP-B box mounting slots.
SP-B
Box Mounting Slots
SP-B
Box Mounting Tabs
TR 6x4 Pin
3
TR 6x4
(PN 473324)
OPTIONAL
Align the pins on the TR 6x4 adaptor to the
duct pin hole on the SP-B 6-inch duct. Push
until the adaptor snaps into place.
SP-B
Plastic Duct Pin Hole
SP-B
6-inch
Plastic Duct
(PN 474433)
Ceiling Exhaust and Inline Fans4
®
Page 75
Install the Fan
1. For best
performance,
choose a location
with the shortest
possible duct run
and minimum
number of elbows.
Do not mount near
cooking equipment, as
shown in Fig. 1.
2. Attach adjustable
mounting brackets
to fan, but leave the
screws loose until
proper height is
determined, shown
in Fig. 2. Cut hole to
dimensions shown
in table below:
45°45°
Bottom Mount
Bottom Mount
Top Mount
Do not install
fan in this area
Brackets can be
used in either
position to adapt to
most mounting
situations
Fig. 1
Fig. 2
For Frame Construction:
Position unit between
joists. Position brackets
such that bottom
edge of housing will
be flush with finished
ceiling, and tighten the
adjustable mounting
brackets, shown in
Fig. 3.
For Hanging
Installations:
Use Greenheck’s
optional vibration
isolator kit Part Number
VI Kit. Using the fan’s
standard adjustable
mounting brackets and
10 by 32 threaded rod
(by others), hang unit as
shown in Fig. 4.
Fig. 4
Slots in the
brackets
allow fine
adjustment
for flush
fit with
wall/ceiling
opening
Model SP-A 50-90 are standard with a round duct.
Should Model SP-A 110-190 require a round duct,
Model RDC (Round Duct Connector) may be ordered
from Greenheck for field installation.
Wire the Fan
1. If installed, remove
wiring cover. If fan/light
combination is being
used, make sure the
fan plug is connected
to the fan receptacle
and the light plug is
connected to the light
receptacle, shown in
Fig. 6
Fig. 6. Using proper
wire connectors, wire the fan as shown in Fig. 7a.
For wiring of light proceed to Fig. 7b.
2. Push all wiring into the unit’s cover and replace
wiring cover.
Fan
Light
Light Outlet (bottom)
Fan Outlet (top)
3. Installation of ductwork
is critical to the performance
of the fan, shown in Fig. 5.
Straight ductwork (1) or
ductwork that turns in
the same direction as the
Fig. 5
2
(GOOD)
1
(GOOD)
AIRFLOW
3
(POOR)
wheel (2) is recommended.
Ductwork turning opposite
the wheel direction (3) will
cause turbulence and back
pressure resulting in poor
performance.
4. Slide ductwork over the fan’s discharge collar and
securely attach it with sheet metal screws.
Make sure the screws do not interfere with damper
operation. Check damper to make sure it opens freely.
Fig. 7aFig. 7b
115 & 277 Volt
Black wire is “Hot”
White wire is “Neutral”
Green wire is “Ground”
220 - 240 Volt
Black wire is “Hot”
White wire is “Hot”
Green wire is “Neutral/Ground”
®
Ceiling Exhaust and Inline Fans5
Page 76
Attach the Grille
1. If lighted grille is being used, plug wire into fan
socket.
If lighted grille and ceiling radiation damper are
being used, plug wire from lighted grille into ceiling
radiation damper socket. Do not plug wire directly
into the fan socket. Make sure the wire does not
interfere with the ceiling radiation damper operation.
2. Attach grille with two screws provided. Make sure
not to over tighten; over tightening will damage
grille.
3. Slide attachment screw covers over the attachment
screws, shown in Figure 8 and 9.
4. If lighted grille is being used, install light bulb(s) into
light socket(s). For incandescent lights, use maximum
100 watt bulb (by others). For fluorescent lights, use
27W GU24 bulbs. Greenheck has replacement 27W
GU24 bulbs call 1-800-355-5354 to order.
5. If lighted grille is being used, snap lens into place, by
pushing on the outside edges of lens, shown in Fig.9.
To remove lens, use small screw driver and pry on
one side of lens.
6. Turn on power and check fan and light operation.
Fig. 8
Fig. 9
Squeeze
tabs to
insert/remove lens
Converting from ceiling to cabinet design for Model SP fans
All SP convertible sizes will be shipped with grille and duct collar cover.
Conversion Kit Parts List
• Qty. of 1 Blower Box Cover
Tools Required
• Phillips Head Screwdriver
Step 1: Remove grille (A) by removing the two
grille screws (B).
Step 2: Remove duct collar cover (C) by
removing the four duct collar screws (D).
Step 3: Discard grille (A), two grille screws (B),
and duct collar cover (C).
Step 4: Remove the six (6) tinnerman clips (E)
by twisting them to one side and pulling
straight out. Discard two of the six
tinnerman clips.
Step 5: Insert the remaining four tinnerman clips
(E) on grille opening side.
Step 6: Place blower box cover (F) over
tinnerman clips (E), which were inserted
in step 5.
Step 7: Screw the blower box cover (F) into place
with four blower box cover screws (D).
C
D
B
A
E
D
F
Ceiling Exhaust and Inline Fans6
SP/CSP models shown are
UL and cUL listed E 33599
E
®
Page 77
Other Installation Considerations
Flex Duct
Connections
Ductwork and Noise
Fiberglass ductboard is a better choice than metal
ductwork for reducing fan noise and is highly
recommended for low sound applications. Where metal
duct is used, sound transmission can be reduced with
flexible duct connections between the fan and the duct.
Sound and Location
The location of these fans must be taken into
consideration before installation. In critical sound
installations, insulated ductwork, flexible duct
connections or placing the fan in a remote section of
ductwork are solutions to meeting the required fan sound
levels.
Filters
The addition of an intake filter is highly recommended
for these fans, even in clean air environments excess
dirt can accumulate on wheels and motors causing
reduced performance and imbalance.
Filters, once installed, should be checked and cleaned
periodically to maintain performance.
Greenheck offers washable aluminum mesh filters
specifically designed for these fans. Please consult our
SP/CSP catalog for more information.
CSP and SP-C
Converted
to Inline
Fiberglass
Ductboard
Correct Low
Sound Installation
Remote
Mounted
SP and SP-C
Mounted Directly
Overhead
Incorrect
SP/CSP models shown are
UL and cUL listed E 33599
General Maintenance Suggestions
Model SP/CSP ceiling exhaust fans require very little maintenance. But since small problems over time left
unchecked could lead to loss of performance or early motor failure, we do recommend that the unit be inspected
periodically (once or twice a year).
The fan motor and wheel should be checked for dust and dirt accumulations. Dirt buildup can lead to loss of
performance and motor overheating. Cleaning can be accomplished by brushing off any dust that may have
accumulated. Even filtered units can accumulate build-up and should be checked when cleaning filters.
The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole
provided. A few drops of all purpose oil (SAE 20) will be sufficient.
®
Ceiling Exhaust and Inline Fans7
Page 78
Typical Installation
INSULATION*
(Place around and over Fan Housing.)
FAN HOUSING
POWER CABLE*
Seal gaps around
Housing.
ROUND
DUCT*
Seal duct joints
with tape.
*Purchase separately.
OR
ROUND
ELBOWS*
ROOF CAP*
(with built-in damper)
Keep duct runs short.
WALL CAP*
(with built-in damper)
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Centrifugal Ceiling and Cabinet Exhaust Fans
catalog provides additional information describing the
equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.