Greenheck ERCH-45H User Manual

Energy Recovery with Cooling & Heating
Model ERCH
• Commercial • Institutional
• 10,000 cfm
• 1.5 in. wg external static pressure
February
2005
Product Features
Model ERCH
Energy Recovery Ventilator With Cooling & Heating
The model ERCH combines the benefits of the total energy wheel with supplemental heating and cooling. The result is a product that is specifically designed to process 100% outdoor air to desired supply conditions. Four housing sizes provide air flow capacities from 1,000 cfm to 10,000 cfm with external static pressures up to 1.5 in. wg (for requirements above this performance, refer to Model ERT or APEX).
Product operation is simple:
Fresh outdoor air is pre-conditioned by the total enthalpy wheel, recovering a majority of the energy from the exhaust air.
The coil section further conditions the outdoor air to desired conditions (typically near room conditions).
Standard Construction
Single Point Wiring is standard.
A disconnect switch and low voltage terminal strip are provided.
Hinged Access Doors provide
easy access to blowers, energy wheel, filters, and coil section for inspection and routine service.
Forward Curved Blowers are
mounted on neoprene vibration isolators.
Double Wall Housing is
constructed of heavy gauge steel with 1-inch insulation. The supply and exhaust side are internally lined with galvanized steel.
A Control Box is furnished
with motor starters for the supply blower, exhaust blower and wheel motors. Also included is a 24 volt control circuit.
Model ERCH shown with optional chilled water coil and indirect gas heater.
The Coil Section
provides supplemental cooling or heating of the outdoor air after pre-conditioning by the energy wheel. Tempering options include chilled water, direct expansion, hot water, electric heat, and indirect gas.
Greenheck Fan Corporation certifies that the ERCH models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings Program.
Energy recovery wheels certified by the ARI Air­to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with ARI Standard 1060. Actual performance in packaged equipment may vary. Certified Ratings are available in the Certified Product Directory at http://www.airdirectory.org/ari/erv.php
Benefits
Healthy Buildings: Ventilate buildings adequately
without losing control of indoor humidity levels. The ERCH is capable of conditioning summer air to room design conditions. Also, it helps prevent overly dry winter air that can contribute to respiratory irritation.
System Design Simplicity: The ERCH is designed
specifically to provide outdoor air to the space at desired conditions. This effectively de-couples the outdoor air load from the building load, enabling the traditional VAV system to perform as it was intended in response to building loads.
2
Load Reduction: The energy wheel saves 3 to 4 tons
of cooling AND 50-60 MBH of heating for every 1,000 cfm of outdoor air for many climates.
Low Maintenance:
Servicing is minimal. All components have a well established history of reliable operation.
ASHRAE 62 Compliance: By assuring that minimum
outdoor air volumes are delivered to the room spaces, compliance with the ASHRAE 62 Standard is clearly demonstrated.
50
60
70
80
180
160
140
120
100
80
60
40
20
90%
70%
50%
30%
10%
Reheat
Room Air
Outdoor Air
Wheel
Cooling
Coil
Supply Air
W
e
t
B
u
l
b
T
e
m
p
.
Dry Bulb Te mp.
Specific Humidity
30
40
50
60
70
80
180
160
140
120
100
80
60
40
20
90%
70%
50%
30%
10%
Supply Air
Room Air
Outdoor Air
Wheel
Heating
Coil
10
W
e
t
B
u
l
b
T
e
m
p
.
Dry Bulb Te mp.
Specific Humidity
20 30 40 50 60 70 80 90 100 110
Cooling and Heating Capabilities
To expand the cooling and heating capabilities of the energy recovery wheel, a variety of tempering options are available. The coil section of the ERCH accommodates a cooling coil, a heating coil, or both.
A description of the cooling and heating processes along with a psychrometric illustration is shown below. Cooling and heating coil options are also listed.
Consult your Greenheck representative for coil selections or for tempering options not listed.
COOLING
Supplemental cooling is recommended when the air conditions leaving the energy recovery wheel have not been cooled or dehumidified to the desired leaving conditions.
Cooling Options
• ChilledWater
• DirectExpansion
Re-heat Options
• Electric
• HotWater
• IndirectGas
1. Outdoor air enters ERCH unit.
2. The energy recovery wheel cools and dehumidifies outdoor air using energy from the exhaust airstream. Load is reduced by 3 to 4 tons per 1,000 cfm for many climates.
3. The cooling coil provides supplemental cooling to further treat the outdoor air to desired supply conditions.
4. Optional reheat available to provide space neutral air.
1
2
3
4
1
2
3
4
HEATING
Supplemental heating is recommended when the air conditions leaving the energy recovery wheel have not been heated to the desired leaving conditions.
Heating Options
• Electric
• HotWater
• IndirectGas
1. Outdoor air enters ERCH unit.
2. The energy recovery wheel heats and humidifies
winter outdoor air using energy from the exhaust airstream. Heating bills are significantly reduced and overly dry indoor conditions are eliminated.
3. The heating coil or furnace
1
provides supplemental heating to further treat the outdoor air to desired supply conditions.
2
3
3
Air Performance
ERCH-20M
CFM OV
1000 1142
1300 1485
1600 1828
ERCH-20H
CFM OV
1600 1828
1900 2171
2200 2514
ERCH-45L
CFM OV
2200 2109
2700 2588
3200 3068
ERCH-45H
CFM OV
3200 2184
3800 2593
4400 3003
ERCH-55H
CFM OV
4200 1989
5100 2415
6000 2842
ERCH-90H
CFM OV
6000 2066
8000 2755
10000 3444
Gross supply air performance ratings (airflow, pressure, and power) are at port 2 with port 1, port 3 and port 4 at
0.0 in. wg. Gross exhaust air performance ratings (airflow, pressure, and power) are to port 3 with port 1, port 2 and port 4 at 0.0 in. wg. Power rating (bhp) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
4
RPM 1141 1344 1498
BHP 0.36 0.51 0.53
RPM 1265 1426 1578 1857
BHP 0.55 0.72 0.90 1.05
RPM 1418 1553 1684 1934 2189
BHP 0.87 1.03 1.21 1.67 2.17
RPM 1308 1446 1575 1816
BHP 0.74 0.89 1.04 1.37
RPM 1453 1574 1691 1907 2108 2306
BHP 1.10 1.27 1.45 1.80 2.19 2.65
RPM 1608 1717 1820 2020 2205 2375
BHP 1.57 1.77 1.96 2.39 2.79 3.20
RPM 797 892 986 1166 1329
BHP 0.68 0.81 0.96 1.29 1.65
RPM 900 977 1053 1209 1359 1494 1628
BHP 1.10 1.25 1.40 1.77 2.18 2.58 3.03
RPM 1010 1079 1143 1274 1406 1533 1655 1768
BHP 1.67 1.87 2.04 2.41 2.86 3.33 3.82 4.29
RPM 900 989 1071 1220 1360 1495
BHP 1.17 1.34 1.53 1.92 2.35 2.83
RPM 1004 1083 1157 1297 1422 1542 1654 1769
BHP 1.79 1.99 2.20 2.64 3.11 3.61 4.12 4.70
RPM 1114 1185 1252 1380 1499 1609 1713 1815
BHP 2.60 2.85 3.08 3.57 4.09 4.64 5.18 5.78
RPM 749 832 906 1038 1155
BHP 1.54 1.82 2.10 2.65 3.21
RPM 839 913 982 1107 1216 1318 1412 1520
BHP 2.43 2.77 3.11 3.80 4.45 5.15 5.81 6.73
RPM 940 1003 1065 1181 1287 1382 1472 1558
BHP 3.67 4.05 4.45 5.26 6.06 6.84 7.64 8.44
RPM 612 682 746 862 962 1058
BHP 1.99 2.37 2.75 3.52 4.33 5.21
RPM 723 783 841 941 1036 1122 1202 1275
BHP 3.91 4.41 495 5.94 6.97 7.98 9.08 10.14
RPM 845 897 946 1040 1124 1201 1277 1348
BHP 7.00 7.56 8.18 9.50 10.78 12.00 13.29 14.52
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
External Static Pressure in inches of wg.
0.50 0.75 1.00 1.50 2.00 2.50 3.00 3.50
Greenheck Fan Corporation certifies that the ERCH models shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings Program.
Air Performance
The air performance data on page 4 accounts for the pressure drop across the energy recovery wheel and the internal housing losses, but does not include pressure drop for filters or tempering options. Add filter and/or tempering option pressure drop (from tables below) to external static pressure to determine correct rpm and horsepower.
Filter Pressure Drop (30% eff.)
Model CFM
ERCH-20
ERCH-45
ERCH-55
ERCH-90
1000 0.04
2200 0.22
2200 0.06
4400 0.24
4200 0.09
6000 0.18
6000 0.10
10000 0.27
Pressure Drop
(in. wg)
Intake & Discharge Options
WiththeERCH,youhavemanyairintake
and discharge options available to simplify duct layout for rooftop and equipment room installations. Refer to the table below for the intake and discharge locations available for outdoor air (OA) and exhaust air (EA).
Tempering Options Pressure Drop
Model CFM
ERCH-20
ERCH-45
ERCH-55
ERCH-90
NOTE: Coil data assumes 6 row cooling coils and 1 row heating coils.
1000 0.17 0.02 0.03
2200 0.62 0.08 0.13
2200 0.31 0.04 0.09
4400 0.66 0.08 0.34
4200 0.38 0.04 0.10
6000 0.64 0.08 0.26
6000 0.28 0.03 0.24
10000 0.66 0.08 0.55
Outdoor Air
Intake
End
Cooling Coil
(in. wg)
Top
Heating Coil
(in. wg)
Top
Bottom
Indirect Gas
(in. wg)
Outdoor Air
Discharge
End
Side
Bottom Top Side End
OA Intake X X
OK Discharge X X X
EA Intake X X X
EA Discharge X X X
1
Side OA Discharge is ONLY available with
1
the Indirect Gas (IG) heater.
2
End OA Discharge is NOT available with the Indirect Gas (IG) heater.
2
X
Top
Exhaust
Discharge
Side
Top
Exhaust
Intake
End
End
Bottom
5
Accessories
Weather Hoods
A louvered intake hood with 2-inch aluminum mesh filters, and an exhaust hood with an integral backdraft damper are available.
Dampers — Internally Mounted
A variety of motorized control dampers are available. Intake and exhaust dampers are internally mounted at the outdoor and exhaust air inlets. Dampers are factory wired to a single point power disconnect.
Filters
Standard size 2-inch, MERV 8, pleated, medium efficiency filters and filter racks are available for outdoor air and/or exhaust air streams.
Frost Control
In cold climates, the recovery wheel may develop frost, which will decrease airflow. Three factory mounted options are available to address frosting:
Timed Exhaust Frost Control
The timed exhaust frost control turns the supply
blower off and on intermittently. Control is triggered by an outdoor air temperature set point in conjunction with an increased pressure drop across the energy wheel.
Modulating Wheel Frost Control
The modulating wheel frost control enables
continuous unit operation. A variable frequency drive (VFD) reduces wheel speed when the outdoor air temperature falls below the frost threshold set point and upon an increase in the differential pressure across the energy wheel. The temperature and pressure differential set points are set at the factory, but are field-adjustable. The VFD will be fully programmed and wired at the factory.
Preheat Frost Control
The preheat frost control enables continuous unit
operation. An electric heater warms the outdoor air above the frost threshold before it enters the energy recovery wheel. Control is triggered by the outdoor air temperature set point in conjunction with increased pressure drop across the energy wheel.
Rotation Sensor
Senses when a wheel rotation failure occurs and sends a signal to an indicator light. The light is available on a remote control panel from the factory.
Microprocessor Discharge Temperature Control
The microprocessor controller is specifically designed and programmed to optimize the performance of an ERCH unit with supplemental heating and cooling. This option ensures that the outdoor air is conditioned to the desired discharge conditions. The controller and accompanying sensors are factory mounted, wired and programmed. Default settings are pre­programmed, but are easily field adjustable. The microprocessor controller can be interfaced with a Building Management System (BMS) through
LonWorks,BACNET,orModBus.
Economizer Control (Free Cooling)
Whencooloutdoorairisavailable,theenergywheel
may be controlled to provide free cooling. Economizer operation can be initiated by the unit sensors alone or in conjunction with a call for cooling (field wired). Two factory installed options are available.
Wheel Off: De-energizes the wheel when the
outdoor temperature is below the field adjustable set point (enthalpy sensor also available). An automatic economizer override is included to engage the wheel for winter heating operation.
Wheel Modulation: Modulates the energy recovery
wheel to maintain a 55°F discharge temperature during economizer operation.
Note: Control centers in Greenheck energy recovery ventilators enable the control of the energy wheel and fans via 24-volt control signals (by others). Controls by others may be preferred when air handling units are equipped with an economizer section.
Variable Air Volume
Model ERCH utilizes variable frequency drives (VFD’s) for multi-speed or modulating blower control to vary airflows. This includes a separate VFD for each blower.
Additional Accessories:
Remote Panels
GFCI Service Outlet (control power by others)
Service Lights (control power by others)
 SpareWheelSegments
Roof Curbs
Painted Exteriors
Factory Mounted Sensors
6
Typical Specifications
General: Energy Recovery Ventilator shall be as manufactured
by Greenheck or approved equal provided all specifications are met. Greenheck Model ERCH is used as the basis of design. Units shall be listed per ANSI/UL 1995, Heating and Cooling Equipment. Energy transfer ratings of the energy recovery wheel shall be ARI Certified. Ventilators shall bear the AMCA Certified Rating seal for Air Performance. Performance shall be as scheduled on plans. Exhaust discharge and outside air intake shall not be located on the same side on roof top units.
Unit Casing and Frames: Unit shall be of internal frame
type construction of galvanized steel. Frame and panels shall be G90 galvanized steel. All panels exposed to the weather shall be a minimum of 18 gauge galvanized steel. Unit shall be internally lined with galvanized sheet metal creating a
double wall. Where top panels are joined there shall be
an overlapping, standing seam to insure positive weather protection. All metal-to-metal seams shall be factory sealed, requiring no caulking at job site. Permatector™ exterior finish is available for outdoor units. Unit base to be designed for curb mounting. Unit base shall overhang the curb for a positive seal against water run-off.
Weatherhoods: Weatherhoods shall be the same finish
as the unit. Outdoor air weatherhood shall incorporate a
louvered design and moisture eliminator. Weatherhoods
shall be tested in accordance with AMCA Standard 500-L to prevent water penetration up to 3 in/hr at 29 mph.
Insulation: Unit casing to be insulated with 1-inch fiberglass.
Insulation shall meet requirements of NFPA 90A and tested to meet UL 181 erosion requirements. Insulation to be enclosed in double wall construction.
Energy Recovery Wheel: Wheelshallbeoftheenthalpytype
for both sensible and latent energy recovery and be designed to insure laminar flow. Energy transfer ratings must be ARI Certified to Standard 1060 and bear the ARI Certification symbol for ARI Air-to-Air Energy Recovery Ventilation Equipment Certification Program based on ARI 1060. Ratings “in accordance with 1060” without certification are not acceptable. Desiccant shall be silica gel for maximum latent
energy transfer. Wheel shall be constructed of lightweight
polymer media to minimize shaft and bearing loads. Polymer media shall be mounted in a stainless steel rotor for corrosion resistance.
Wheeldesignshall consist of removable segments for ease
of service and/or cleaning. Silica gel desiccant shall be permanently bonded to wheel media to retain latent heat
capabilityaftercleaning.Wheelswithsprayedondesiccant coatingsare not acceptable.Wheelswithdesiccantapplied
after wheel formation are not acceptable. Energy recovery device shall transfer moisture entirely in the vapor phase.
Energy recovery drive belt material shall be high strength urethane and shall be factory installed in a pre-stretched state, eliminating the need for field belt tension adjustment. Link style belts are not acceptable.
Hinged Access Doors: All components shall be easily
accessible through hinged access doors for exhaust, supply, filter, and damper compartments. Energy recovery wheels (smaller than 58 inches) shall be mounted in a slide-out track for ease of inspection, removal, and cleaning.
Roof Curbs: Roof curb to be supplied by unit manufacturer
for field assembly. Curb shall consist of die formed galvanized steel sections. Curb shall be full perimeter type with gasketing provided for field installation between curb and unit base.
Fan Sections: Centrifugal fans to be double width, double
inlet, forward curved type. All blower wheels shall be statically and dynamically balanced. Ground and polished steel fan shafts shall be mounted in permanently lubricated, sealed ball bearing pillow blocks. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speeds. Separate motors for exhaust and supply blowers shall be provided. Adjustable sheaves on belt-driven fans with motors less than 10 hp shall allow independent balancing of exhaust and supply airflow. Fan and motor assemblies are mounted to unit base with neoprene isolators as standard. Fans shall be located in draw-through position in reference to the energy recovery wheel.
Motors and Drives: Motors shall be energy efficient,
complying with EPACT standards, for single speed ODP and TE enclosures. Motors shall be permanently lubricated, heavy-duty type, matched to the fan load and furnished at the specified voltage, phase, and enclosure. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast type, keyed and securely attached to the fan wheel and motor shafts; 10 hp and less shall be supplied with an adjustable drive pulley. Energy wheel motors shall have integral overload protection.
Filters: Supply and exhaust air filters shall be 2-inch thick
pleated fiberglass, 30% efficient and tested to meet UL Class 2. Filter racks shall be die-formed galvanized steel.
Electrical: All internal electrical components shall be factory
wired for single point power connection. Units with electric reheat will be wired with independent power supply. All electrical components shall be UL Listed, Approved, or Classified where applicable and wired in compliance with the National Electrical Code.
Weatherproof, integral doorinterlocking disconnect switch,
motor starters, control circuit fusing, control transformer for 24 VAC circuit, and terminal strip shall be supplied as standard components in the control center. Motor starters consist of a contactor and Class 20 electronic adjustable overload protection and shall be provided for all fan motors.
Cooling Coil: Direct expansion (DX) and chilled water coils
shall be factory tested and rated in accordance with ARI 410. Coils shall have copper tubes with permanently expanded aluminum fins, 12 fpi or less. DX coils shall be equipped with distributors to receive expansion valves at the liquid connections. DX coils shall include stainless steel drain pan.
Indirect Gas: Indirect fired gas furnace shall be 80%
efficient, UL Certified and Listed per ANSI Z83.8 - 2002, C.G.A. approved per 2.6 - 2002 and have a blow through fan design. Furnace shall be capable of operation with natural or LP gas and have a power venting system. The burner and heat exchanger shall be constructed of aluminized steel. Standard furnace features shall include main gas pressure regulator, main gas valve, electronic staged or electronic modulating controls, direct spark ignition system, high limit and a 24 volt control transformer.
Hot Water Coil: Hot water coil shall be factory tested and rated
in accordance with ARI 410. Coils shall have copper tubes with permanently expanded aluminum fins, 12 fpi or less.
Electric Heat: Electric heat shall be UL listed and circuit
fused per NEC over 48 amps. Heater shall be multi-step control, factory wired and installed. Control will be 24 volt with class 2 transformer. Standard air flow switch to shut down heater if air ceases to flow across heater.
7
Dimensional Data
Outdoor Air
Hood
Outdoor Air
Hood
Exhaust
Hood
2 in. filters
2 in. filters
2 in. filters
Wheel Cassette
Wheel Cassette
Coil
Section
Coil
Section
Optional
IG Heater
Optional
IG Heater
Electrical Box
DA
B
C
E
F
Model A B C D E F
ERCH-20 98 50 56 18 18 9
ERCH-45 106 69 66 16 20 11
ERCH-55 118 70 76 16 25 11
ERCH-90 131 85 96 16 27 11
All dimensions shown are in inches.
Model Approximate Weight (lbs)
ERCH-20 1500
ERCH-45 2300
ERCH-55 3000
ERCH-90 5000
Actual weight is dependent upon unit configuration.
Side View
Top
View
OurWarranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the purchase date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
GreenheckP.O.Box410•Schofield,WI54476-0410•Phone(715)359-6171•greenheck.com
Copyright©2005GreenheckFanCorp.•CatalogERCHSNRev.4February 2005
Prepared to Support
Green Building Efforts
Loading...