Greenheck EMV-11 User Manual

Pressure (in. w.g.)
483624120
8
6
4
2
0
4.0 in. w.g.
6.0 in. w.g.
Damper Width (in.)
10
8.0 in. w.g.
10.0 in. w.g.
012243648
0
60
74
3000 fpm
2500 fpm
Damper Height (in.)
Damper Width (in.)
3500 fpm
36
Extruded
W* H*
3 18 in.
Airflow
1 12 in.
3 in.
5 in.
11
1
8
in.
/
BACKDRAFT DAMPER
ADJUSTABLE COUNTERBALANCE
EMV-11
Horizontal Mount Vertical Airflow Up
Application and Design
The EMV-11 is a horizontally mounted backdraft damper that is designed to allow vertical airflow up and prevent reverse airflow. The damper is opened by air pressure differential and closed by gravity. Standard models include adjustable counterbalance to assist opening.
Ratings (See page 2 for specific limitations) Pressure: 4.0 - 10.0 in. wg (996 Pa - 2491 Pa)
differential pressure
Velocity: 2500 to 3500 fpm (13 m/s - 18 m/s)
Standard Construction
Frame: Heavy gauge 6063T5 extruded aluminum
(0.125 in. thickness [3.2mm])
Blades: Heavy gauge 6063T5 extruded aluminum (0.070 in. thickness [1.8mm])
Axles:
Bearings: Oil impregnated stainless steel sleeve type
Linkage:
Blade Seals: Vinyl. Paint Finish: Hi Pro Poyester Counterbalance weight material: Stainless steel
1
/2 in. (13mm) dia. stainless steel
1
/8 in. (3mm) stainless steel
*W & H dimensions furnished approximately 1/4 in.(6mm) under size.
EMV-11
Size Limitations
Minimum Size: 8 in. W x 11 in. H
Flange On Discharge
(203mm x 279mm)
Maximum Panel Size: 48 in. W x 74 in. H (1219mm x 1880mm)
Sizes larger than maximum shown will be supplied as two or more equal size smaller dampers required to make up the size specified. These larger multiple damper assemblies require field assembly and may require additional reinforcement (not supplied by Greenheck) to support the assembly.
Pressure LimitationsVelocity Limitations
Counterbalance weights may require field adjustment. Instructions are available at www. greenheck.com.
Velocity (fpm)
1
x 10
Pressure Loss ( In. w.g.)
10
9 8 7 6
5
4
3
2
2 3 4 5 6 7 8 9 10
1.0 .9 .8 .7
.6
.5
.4
.3
.2
.10 .09 .08 .07
.06
.05
.04
.03
.02
x 100
2 3 4 5 6 7 8 9 10
x 1000
2 3 4 5 6 7 8 9 10
1.0
.9
.8
.7
.6
.5
.4
.3
.2
6
5
4
3
2
Static Pressure Difference
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
Static Pressure Difference
1.0
.9 .8 .7
.6
.5
.4
.3
.2
10
9 8 7
6
5
4
3
2
Air Leakage in CFM/Sq. Ft.
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 150
EM-10
Air Leakage in CFM/Sq. Ft.
1 2 3 4 5 6 7 8 9 10
20 30 40 50 60 70 80 90 100 150
1.0 .9 .8
.7
.6
.5
.4
.3
.2
8.5
8 7
6
5
4
3
2
Static Pressure Difference
130
With Seal
s
Without Seal
s
Performance Data EMV-11
Performance data results from testing a 36 in. x 36 in. (914mm x 914mm) damper in accordance with AMCA Standard 500-D using Figure 5.7B (unducted). All data has been corrected to represent standard air at 0.075 lb/ft3 (1.201 kg/m3).
ÆP in. wg Velocity
Standard Bearings Blades Fully Open 0.06 (15) 680 (3.5)
Leakage testing was conducted in accordance with AMCA Standard 500-D and is expressed as CFM per sq. ft. of damper face area. All data has been corrected to represent standard air at 0.075 lb/ft3 (1.201 kg/m3).
Operational Data
Damper with
Blades Start to Open 0.05 (12) 55 (.28)
(Pa) fpm (m/s)
Leakage
36 in. x 36 in. Damper
Pressure Drop
Specifications
Backdraft dampers meeting the following specifications shall be furnished and installed where shown on plans and/or as described in schedules.
Dampers shall consist of: heavy gauge 6063T5 extruded aluminum channel frame (0.125 in. [3.2mm] thick) with 31/8 in. (79mm) depth; blades from 0.070 in. (1.8mm) 6063T5 extruded aluminum; 1/2 in. (13mm) dia. stainless steel axles turning in oil impregnated stainless steel sleeve type bearings; damper shall be equipped with extruded vinyl blade seals; and internal 1/8 in. (3mm) stainless steel
blade-to-blade linkage with counterbalance weights. Damper manufacturer’s printed application and performance data including pressure, velocity and temperature limitations shall be submitted for approval showing damper suitable for pressures to 10 in. wg (2491 Pa), velocities to 3500 fpm (18 m/s) and temperatures to 180°F (82ºC). Testing and ratings to be in accordance with AMCA Standard 500-D.
Basis of design is Greenheck model EMV-11.
Copyright © 2009 Greenheck Fan Corporation