Application and Design
EHM-601 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates drain gutters in the head member and horizontal blades to channel water to the jambs where water is further channeled through vertical downspouts and out at the sloped sill. The EHM­601 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
6 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Dual drainable design, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 37º and 45º angles on approximately 6 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Extended sill . . . Formed aluminum
Minimum Size . . 12 in. W x 16 in. H
Maximum Single Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
EHM-601
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Filter rack
• Flanged frame (on head and jambs only)
• Security bars
• Welded construction
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
l/m2oz/ft2
Hidden Mullion Louver Dual Drainable Blade
Free Area Chart (Sq. ft.)
Louver Height Inches
12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
16 0.30 0.50 0.70 0.90 1.09 1.29 1.49 1.63 1.83 2.03 2.23 2.42 2.62 2.82 3.01 3.16 3.36 3.56 3.75
18 0.30 0.50 0.70 0.90 1.09 1.29 1.49 1.63 1.83 2.03 2.23 2.42 2.62 2.82 3.01 3.16 3.36 3.56 3.75
24 0.57 0.93 1.30 1.67 2.04 2.40 2.77 3.05 3.41 3.78 4.15 4.52 4.88 5.25 5.62 5.89 6.26 6.63 7.00
30 0.83 1.37 1.90 2.44 2.98 3.52 4.06 4.46 5.00 5.53 6.07 6.61 7.15 7.69 8.22 8.63 9.16 9.70 10.24
36 1.09 1.80 2.51 3.22 3.92 4.63 5.34 5.87 6.58 7.28 8.00 8.70 9.41 10.12 10.83 11.36 12.07 12.77 13.48
42 1.35 2.23 3.11 3.99 4.87 5.75 6.62 7.28 8.16 9.04 9.92 10.80 11.67 12.55 13.43 14.09 14.97 15.85 16.72
48 1.62 2.67 3.71 4.76 5.81 6.86 7.91 8.70 9.74 10.79 11.84 12.86 13.94 14.99 16.04 16.82 17.87 18.92 19.97
54 1.86 3.07 4.28 5.49 6.70 7.91 9.11 10.02 11.23 12.44 13.65 14.85 16.06 17.27 18.48 19.39 20.59 21.80 23.01
60 2.09 3.45 4.81 6.17 7.53 8.88 10.24 11.26 12.62 13.98 15.33 16.69 18.05 19.41 20.77 21.78 23.14 24.50 25.86
66 2.32 3.83 5.34 6.85 8.35 9.86 11.37 12.50 14.01 15.51 17.02 18.53 20.04 21.54 23.05 24.18 25.69 27.20 28.70
72 2.40 3.96 5.52 7.08 8.64 10.20 11.76 12.93 14.49 16.05 17.61 19.17 20.73 22.29 23.85 25.02 26.58 28.14 29.70
78 2.67 4.40 6.13 7.86 9.59 11.32 13.05 14.34 16.07 17.80 19.53 21.26 22.99 24.82 26.45 27.75 29.48 31.21 32.94
84 2.93 4.83 6.73 8.63 10.53 12.43 14.33 15.76 17.66 19.56 21.46 2..36 25.26 27.16 29.06 30.48 32.38 34.28 36.18
90 3.19 5.26 7.33 9.40 11.47 13.54 15.61 17.17 19.24 21.31 23.38 25.45 27.52 29.59 31.66 33.21 35.28 37.35 39.42
96 3.45 5.69 7.94 10.18 12.42 14.66 16.90 18.58 20.82 23.06 25.30 27.54 29.78 32.02 34.26 35.94 38.18 40.43 42.67
102 3.72 6.13 8.54 10.95 13.36 15.77 18.18 19.99 22.40 24.81 27.22 29.63 32.05 34.46 36.87 38.68 41.09 43.50 45.91
108 3.98 6.56 9.14 11.72 14.30 16.89 19.47 21.40 23.98 26.57 29.15 31.73 34.31 36.89 39.47 41.41 43.99 46.57 49.15
114 4.24 6.99 9.74 12.50 15.25 18.00 20.75 22.82 25.57 28.32 31.07 33.82 36.57 39.32 42.08 44.14 46.89 49.64 52.39
120 4.50 7.43 10.35 13.27 16.19 19.11 22.04 24.23 27.15 30.07 32.99 35.91 38.84 41.76 44.68 46.87 49.79 52.71 55.64.
Louver Width in Inches
EHM-601PERFORMANCE DATA
Extruded Aluminum
Greenheck Fan Corporation certifies that
WATER
AIR
®
the EHM­601 louvers shown herein are licensed to bear the
PENETRATION
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION
AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Model EHM-601 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
3
) Water Penetration (Standard Air - .075 lb/ft3)
Test size 48 in. x 48 in. Test duration of 15 min.
m
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
ft/min:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
1000 1050 1100 1150 1200 1250 1300
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.5 6.6
m/s:
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model EHM-601 is 1065 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.