Part #474641
Installation Instructions
EHH-601D
Flange/Sleeve Installation
Florida Product Approval No: FL10088
Miami-Dade NOA No.: 12-0830.08
Maximum Wind-load: 150 PSF
Installation, Operation, and Maintenance Instructions
This manual is the property of the owner, and is required for future maintenance.
Please leave it with the owner when the job is complete.
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury
or death. Read the installation, operating, and maintenance instructions thoroughly before installing or
servicing this equipment.
1
Installation Instructions
Flange/Sleeve Installation
Florida Product Approval No: FL10088
Miami-Dade NOA No.: 12-0830.08
Maximum Wind-load: 150 PSF
EHH-601D
Maximum Size and Installation Information
Model EHH-601D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the
installation instructions shown herein. Model EHH-601D is qualified for installation within concrete/masonry, steel stud, structural
steel or wood framed building conditions. Model EHH-601D is structurally calculated to withstand positive and negative wind-loads
up to 150 PSF. The maximum single section rough opening width is 72.50 in. The maximum single section rough opening height
is 144.50 in. While the maximum rough opening height is limited to 144.50 in., the rough opening width is limited to 1,000 in. as
multiple sections may be installed side by side in accordance with installation instructions.
Minimum Rough
Opening Size
12 in. W x 7 in. H
Building Condition/Substrate Limitations
• All wood substrate shall be G= 0.55 density or better
• All metal stud substrate should be min. 16 Ga. FY= 50 KSI
• All structural steel substrate shall be min. 0.25 in. thick FY= 36 KSI
• All concrete substrate shall be min. 3000 PSI
• Concrete masonry shall be ASTM C90, Type II, 2000 PSI, grout-filled
2
Maximum Single Section
Rough Opening Size
72.50 in. W x 144.50 in. H
Installation Instructions
Flange/Sleeve Installation
Single Section
EHH-601D
Florida Product Approval No: FL10088
Miami-Dade NOA No.: 12-0830.08
Maximum Wind-load: 150 PSF
3