Wind-Driven Rain Louver
Horizontal Blade
Application and Design
EHH-501 is a Wind-Driven Rain louver designed to protect
air intake and exhaust openings in building exterior walls that
are sensitive to direct water penetration. Design incorporates
a drainable head member and horizontal rain resistant blades
to provide maximum resistance to wind driven rain in even the
most extreme weather conditions. The EHH-501 is an AMCA
CERTIFIED LOUVER enabling designers to select and apply
with confidence.
Standard Construction
Frame � � � � � � � � �Heavy gauge extruded 6063-T5 aluminum,
5 in. x 0.081 in. nominal wall thickness
Blades � � � � � � � � �Horizontal rain resistant style, heavy gauge
extruded 6063-T5 aluminum, 0.081 in.
nominal wall thickness, positioned on
approximately 2 in. blade spacing
Construction . . . .Mechanically fastened
Birdscreen � � � � � �3/4 in. x 0.051 in. flattened expanded
aluminum in removable frame, inside
mount (rear)
Finish � � � � � � � � � �Mill
Sil Pan � � � � � � � � �0.063 formed aluminum
Minimum Size � � �12 in. W x 7 in. H
Maximum Single
Section Size � � � �120 in. W or 120 in. H (limited to 70 ft. sq.)
EHH-501
WATER
PENETRATION
AIR
PERFORMANCE
WIND
DRIVEN RAIN
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panel
• Clip angles
• Filter rack
• Flanged frame (head and jamb only)
• Security bars
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel
Kynar
*Width and height dimensions furnished
approximately ¼ inch under size.
Wind-Driven Rain Performance
75 mm/h (3 in./hr) Rainfall &
13 m/s (29 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
Water
Penetration
(fpm) (m/s) (fpm) (m/s) Class Effective (fpm) (m/s) (fpm) (m/s) Class Effective
0 0 0 0 0 0 0 0 B 98.5
198 1.0 98 0.5 278 1.4 138 0.7 B 98.1
397 2.0 197 1.0 419 2.1 208 1.1 B 97.8
595 3.0 295 1.5 587 3.0 291 1.5 B 97.4
794 4.0 394 2.0 837 4.3 415 2.1 B 97.8
992 5.0 492 2.5 978 5.0 485 2.5 B 98.2
1192 6.1 591 3.0 1185 6.0 588 3.0 B 98.4
1355 6.9 672 3.4 A 99.9 1343 6.8 666 3.4 B 98.0
1585 8.1 786 4.0 A 99.5 1569 8.0 778 4.0 B 97.5
1766 9.0 876 4.5 A 99.3 1766 9.0 876 4.5 B 96.4
2016 10.2 1000 5.1 B 98.7 1986 10.1 985 5.0 C 93.8
Discharge Loss Coefficient Class (Intake) = 2
Weather louvers shall be classified by their ability to reject simulated rain. The
table shows different classifications based on the maximum simulated rain
penetration per square meter (square feet) of louver. Water penetration rating
at a given louver face velocity is determined by the water penetration while the
louver is subjected to a selected simulated rainfall rate and wind velocity.
Airflow Resistance (Standard Air - �075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
0.09
20
0.08
0.07
0.06
0.05
10
0.04
9
8
0.03
7
6
5
0.02
ft/min:
m/s:
Model EHH-501 resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
202 mm/h (8 in./hr) Rainfall &
22 m/s (50 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
3
)
Water
Penetration
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min�
0.30
80
0.25
0.20
60
0.15
40
0.10
20
0.05
Water Penetration per Unit Free Area
0.00
0
1100 1150 1200 1250 1300
ft/min:
m/s:
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
the penetration of rainfall under specific laboratory test conditions.
The beginning point of water penetration is defined as that velocity
where the water penetration curve projects through 0.01 oz. of water
(penetration) per sq. ft. of louver free area. *The beginning point of
water penetration for Model EHH-501 is above 1250 fpm free area
velocity. These performance ratings do not guarantee a louver to be
weather-proof or stormproof and should be used in combination with other
factors including good engineering judgement in selecting louvers.
Discharge Loss Coefcient Classications
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
Greenheck Fan Corporation
certifies that the EHH-501
louvers shown herein are licensed
WATER
to bear the AMCA Seal. The
AIR
PERF
ratings shown are based on
WIND
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
tests and procedures performed
in accordance with AMCA
Publication 511 and comply with
®
the requirements of the AMCA
Certified Ratings Program. The AMCA Certified
Ratings Seal applies to air performance, water
penetration, and wind-driven rain ratings.
Test Size 48 in. x 48 in.
Test Period 15 minutes
Standard Air - .075 lb/ft
6.5 7.0 7.5
3
Free Area Velocity
EHH-501PERFORMANCE DATA
Wind-Driven Rain Louver
Extruded Aluminum
Wind-driven Rain
Penetration ClassesClass Discharge Loss Coefcient
D Below 0.80