Greenheck EHH-201 Installation Manual

Wind-Driven Rain Louver
Horizontal Blade
Application and Design
EHH-201 is a Wind-Driven Rain louver designed to protect air intake and exhaust openings in building exterior walls that are sensitive to direct water penetration. Design incorporates a drainable head member and horizontal rain resistant blades to provide maximum resistance to wind driven rain in even the most extreme weather conditions. The EHH-201 is an AMCA CERTIFIED LOUVER enabling designers to select and apply with confidence.
Standard Construction
Frame � � � � � � � � �Heavy gauge extruded 6063-T5 aluminum,
2 in. x 0.063 in. nominal wall thickness
Blades � � � � � � � � �Horizontal rain resistant style, heavy gauge
extruded 6063-T5 aluminum, 0.063 in. nominal wall thickness, positioned on approximately 1 in. blade spacing
Construction . . . .Mechanically fastened
Birdscreen � � � � � �3/4 in. x 0.051 in. flattened expanded
aluminum in removable frame, inside mount (rear)
Finish � � � � � � � � � �Mill
Sill Pan � � � � � � � �0.063 formed aluminum
Minimum Size � � �6 in. W x 6 in. H
Maximum Single Section Size � � � �96 in. W x 84 in. H
EHH-201
WATER
PENETRATION
AIR
PERFORMANCE
WIND
DRIVEN RAIN
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panel
• Clip angles
• Filter rack
• Flanged frame (head and jamb only)
• Security bars
• A variety of architectural finishes including: Clear anodize
Integral color anodize Baked enamel Kynar
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Air Velocity
ml/m2
oz/ft2
Wind-Driven Rain Performance
75 mm/h (3 in./hr) Rainfall &
13 m/s (29 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
Water
Penetration
(fpm) (m/s) (fpm) (m/s) Class Effective (fpm) (m/s) (fpm) (m/s) Class Effective
0 0 0 0 A 99.9 0 0 0 0 A 99.7
306 1.6 131 0.7 A 99.8 250 1.3 107 0.5 B 98.5
442 2.2 189 1.0 A 99.5 512 2.6 219 1.1 B 96.5
702 3.6 300 1.5 B 98.5 697 3.5 298 1.5 C 94.5
908 4.6 388 2.0 B 96.3 901 4.6 385 2.0 C 91.6
1088 5.5 465 2.4 C 92.5 1123 5.7 480 2.4 C 88.5
1361 6.9 582 3.0 C 82.1 1357 6.9 580 2.9 C 86.1
1586 8.1 678 3.4 D 73.8 1598 8.1 683 3.5 C 80.5
Discharge Loss Coefficient Class (Intake) = 3
Weather louvers shall be classified by their ability to reject simulated rain. The table shows different classifications based on the maximum simulated rain penetration per square meter (square feet) of louver. Water penetration rating at a given louver face velocity is determined by the water penetration while the louver is subjected to a selected simulated rainfall rate and wind velocity.
202 mm/h (8 in./hr) Rainfall &
22 m/s (50 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
Water
Penetration
EHH-201PERFORMANCE DATA
Wind-Driven Rain Louver
Extruded Aluminum
Discharge Loss Coefcient Classications
Class Discharge Loss Coefcient
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
Greenheck Fan Corporation certifies
that the EHH-201 louvers shown herein are licensed to bear the
AMCA Seal. The ratings shown are
PENETRATION
PERFORMANCE
DRIVEN RAIN
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
performed in accordance with
AIR
AMCA Publication 511 and comply
WIND
with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air
®
performance, water penetration, and
based on tests and procedures
WATER
wind-driven rain ratings.
Wind-driven Rain
Penetration Classes
D Below 0.80
Airflow Resistance (Standard Air - �075 lb/ft
Pa
in. wg
1
0.9
200
0.8
0.7
0.6
0.5
100
0.4
90 80
0.3
70
60
50
0.2
40
30
0.1
0.09
20
0.08
0.07
Static Pressure Drop
0.06
0.05
10
0.04
9 8
0.03
7
6
5
0.02
ft/min:
m/s:
Model EHH-201 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection
information.
Test Size 48 in. x 48 in.
St andard Ai r - .075 lb/ft
200 300 400 500 600 700800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
)
Water Penetration
Test size 48 in� x 48 in� Test Duration of 15 min�
0.30
Test Size 48 in. x 48 in.
80
0.25
0.20
60
0.15
40
0.10
20
0.05
Water Penetration per Unit Free Area
0
0.00
ft/min:
m/s:
Test Period 15 minutes
Standard Air - .075 lb/ft
850 900 950 1000 1050 1100
4.0 5.0
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of water
penetration for Model EHH-201 is 914 fpm free area velocity
These perfor mance ratings do not guarantee a louver to be weather­proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Loading...