Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
Energy Recovery & Make-Up Air Technical Support
Call 1-800-240-0870, press 1 for Service
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
The unit is prewired such that when a call for outside air
is made (via field-supplied 24 VAC control signal wired
to unit control center), the supply and exhaust fans are
energized and optional motorized dampers open. The
unit is normally interlocked (24 volt) to the rooftop air
handler. When the rooftop air handler starts, the auxiliary
contactor in the air handler closes to start the unit.
Summer Operation
Outdoor air is preconditioned (temperature and moisture
levels are decreased) by the transfer of energy from the
cooler, drier return air through the energy recovery core.
The preconditioned air is typically mixed with return air
going back to the air handler for final conditioning.
Winter Operation
Outdoor air is preconditioned (temperature and moisture
levels are increased) by the transfer of energy from
the warmer, more humid return air through the energy
recovery core. The preconditioned air is typically mixed
with return air going back to the air handler for final
conditioning.
Exhaust Air
Summer
Operation
Supply Air
82° F
88 grains/lb.
Outdoor Air
95° F
125 grains/lb.
Return Air
75° F
50% RH
Energy Core Ventilator2
®
Page 3
Receiving
This product may have been subject to road salt
during transit. If so, immediately wash off all visible
white reside from all exterior surfaces. Upon receiving
the product, check to ensure all items are accounted
for by referencing the delivery receipt or packing list.
Inspect each crate or carton for shipping damage before
accepting delivery. Alert the carrier if any damage is
detected, do not refuse shipment. The customer shall
make notation of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading should
be countersigned by the delivering carrier. If damaged,
immediately contact your manufacturer’s representative.
Any physical damage to the unit after acceptance is not
the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Unpacking
Verify that all required parts and the correct quantity of
each item have been received. Inspect interior of unit
cabinet for any shipped loose items. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
The ideal environment for the storage of units and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain, or snow. Units designed for outdoor
applications may be stored outdoors. All accessories
must be stored indoors in a clean, dry atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To
avoid condensation, allow cold parts to reach room
temperature. Leave coverings loose to permit air
circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off
the floor. Clearance should be provided to permit air
circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated so that it is above water and snow levels.
Ensure sufficient support to prevent unit from settling
into soft ground. Locate parts far enough apart to
permit air circulation, sunlight, and space for periodic
inspection. To minimize water accumulation, place all
unit parts on blocking supports so that rain water will
run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Units with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl
hard to reach internal surfaces or for occasional use,
consider using Tectyl
or the equivalent.
®
506 (Ashland Inc.) or the equivalent. For
®
511M Rust Preventive, WD-40®
Removing from Storage
As units are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion until the equipment goes
into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
®
Energy Core Ventilator3
Page 4
Installation
Outdoor Mounting Options
EXHAUST AIR
DISCHARGE
SUPPLY AIR
DISCHARGE
F
(NON ELECTRICAL SIDE)
A
Outdoor Air Discharge Bottom
Indoor Mounting Options
EXHAUST AIR
DISCHARGE
E
E
SUPPLY AIR
DISCHARGE
(NON ELECTRICAL SIDE)
A
EXHAUST AIR
DISCHARGE
C
SUPPLY AIR
DISCHARGE
G
B
RETURN AIR INTAKE
OUTDOOR
AIR INTAKE
E
(NON ELECTRICAL SIDE)
A
C
G
B
OUTDOOR
AIR INTAKE
RETURN AIR INTAKE
Outdoor Air Discharge End
EXHAUST AIR
DISCHARGE
D
D
B
OUTDOOR AIR INLET
C
RETURN AIR INLET
SUPPLY AIR
DISCHARGE
E
F
(NON ELECTRICAL SIDE)
A
G
D
OUTDOOR AIR INTAKE
C
B
RETURN AIR INTAKE
Top and Bottom ConnectionsTop and End Connections
EXHAUST AIR
DISCHARGE
SUPPLY AIR
DISCHARGE
E
E
(NON ELECTRICAL SIDE)
A
D
D
B
OUTDOOR AIR INTAKE
C
RETURN AIR INTAKE
Intake and Discharge Options
BottomTopSideEnd
OA IntakeXX
SA DischargeXX
RA IntakeXX
EA DischargeXX
End Connections
Dimensional Data and Weights
Unit
Size
ECV-1054.828.943.918.4 x 15.913.6 x 13.68.5 x 11.610.25 x 15.25485
ECV-206543.956.931.2 x 19.213.6 x 13.68.6 x 11.815.8 x 27.8816
ECV-306961.460.743.2 x 18.220 x 2016 x 13.840.9 x 15.91286
All dimensions are in inches. *Weight assumes outdoor unit with filters, weatherhoods, outdoor air intake damper, controls
and internal double-wall sheet metal.
Exterior DimensionsUnit Connection Dimensions
AB CDEFG
Approx. Weight*
(lbs.)
Energy Core Ventilator4
®
Page 5
Service Clearances
The ECV unit requires minimum clearances to perform routine maintenance, such as filter replacement and energy
core inspection. Blower and motor assemblies, energy recovery core and filter sections are always provided with a
service door or panel for proper component access. Clearances for component removal may be greater than the
service clearances, refer to drawing below for these dimensions.
*NO END CLEARANCE ON UNITS WITHOUT WEATHER HOODS.
ModelA (in.)
ECV-1042
ECV-2042
ECV-3030
CLEARANCE
WITH
BOLTED DOOR
ACCESS
24"
ACCESS DOOR
CORE REMOVAL
ACCESS DOOR
36"
HINGED ACCESS
CLEARANCE
WITH
*A
OUTDOOR
AIR HOOD
CLEARANCE
WITH
BOLTED DOOR
ACCESS
24"
CORE
ELECTRICAL
CORE REMOVAL
ACCESS DOOR
EXHAUST
AIR HOOD
*24"
ACCESS DOOR
36"
HINGED ACCESS
CLEARANCE
WITH
Access Panel Locations
The ECV is provided with access panels on both sides of the unit. The non electrical side can be placed against
a wall. Clearance to the electrical side is essential to provide access to the control center and component
maintenance.
1 Control Center
Core, filters, inlet
2
dampers, bypass
dampers, blowers
3 Blowers
2
®
1
2
3
Electrical SideNon Electrical Side
Energy Core Ventilator5
Page 6
Handling
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation.
The system design and installation should follow
accepted industry practice, such as described in the
ASHRAE Handbook. Adequate space should be left
around the unit for filter replacement and maintenance.
Sufficient space should be provided on the side of the
unit for routine service and component removal should
that become necessary.
Lifting
WARNING
All factory provided lifting lugs must be used when
lifting the unit. Failure to comply with this safety
precaution could result in property damage, serious
injury or death.
1. Before lifting, be sure that all shipping material has
been removed from unit.
2. To assist in determining rigging requirements,
weights are shown under the Dimensional Data
and Weights section.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach to
unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
6. Always test-lift the unit to check for proper balance
and rigging before hoisting to desired location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to lifting
the unit and setting on curb.
11. Do not use fork lifts for handling unit.
Energy Core Ventilator6
®
Page 7
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be clear
of structural members of the building.
1. Factory Supplied Roof Curbs: Roof curbs are
Model GKD. The GKD ships in a knockdown kit
(includes duct adapter) and requires field assembly
(by others). Assembly instructions are included.
2. Install Curb: Locate curb over roof opening and
fasten in place. (Refer to Recommended Roof
Openings). Check that the diagonal dimensions
are within ±1/8 inch of each other and adjust as
necessary. For proper unit operation, it is important
that the installation be level. Shim as required to
level.
3. Install Ductwork: Installation of all ducts should
be done in accordance with SMACNA and AMCA
guidelines. Duct adapter provided to support ducts
prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above the
curb and duct openings. Guide unit while lowering
to align with duct openings. Roof curbs fit inside
the unit base. Make sure the unit is properly seated
on the curb and is level.
5. Fasten the Unit: Fasten the unit to the curb/
equipment support(s) using appropriate methods.
The installer is responsible for determining
appropriate support and fastening methods to
ensure compliance with all applicable codes.
Curb Outside Dimensions and Weights
D
C
AA
B
Unit
Size
ECV-10 52.3 26.4 16.5 x 11.5 8.5 x 11.660
ECV-20 62.5 41.3 30.5 x 17.211 x 1480
ECV-306557.441 x 15.716 x 13.9106
All dimensions are in inches. Weight is for 14-inch high
model GKD curbs.
ABCD
Curb Weight
(lbs.)
Side of Unit
A
B
C
D
E
Roof Curb
Curb Cap Details for Factory-Supplied Roof Curbs
Unit SizeABCDE
ECV-101.95.34.30.80.4
ECV-201.95.34.30.80.4
ECV-301.95.34.30.80.4
All dimensions are in inches.
Base
1-inch Insulation
®
Energy Core Ventilator7
Page 8
Ductwork Connections
R
o
t
a
t
i
o
n
POOR
Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.
n
o
i
t
a
t
o
R
Recommended Discharge Duct Size and Length
Unit
Size
Blower Size
(dia.-width)
ECV-1010-614 x 1435
ECV-2010-614 x 1435
ECV-30 12-8 12-1220 x 2050
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM)
at minimum airflow and up to 1600 fpm at maximum airflow.
Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication 201.
Calculated values have been rounded up to nearest foot.
Length of Straight Duct
GOOD
Duct Size
(in.)
Straight Duct Length
(ft.)
Rail Mounting / Layout
• Rails designed to handle the weight of the unit
should be positioned as shown on the diagram
(rails by others).
• Make sure that rail positioning does not interfere
with the supply air discharge opening or the
exhaust air intake opening on the unit. Avoid area
dimensioned “B” below.
• Rails should extend beyond the unit a minimum of
12 inches on each side.
A
B
Unit SizeAB
ECV-104.211.5
ECV-20515
ECV-302.913.8
All dimensions are in inches.
Energy Core Ventilator8
®
Page 9
Electrical Information
The unit must be electrically grounded in accordance
with the current National Electrical Code,
ANSI/NFPA 70. In Canada, use current CSA Standard
C22.1, Canadian Electrical Code, Part 1. In addition,
the installer should be aware of any local ordinances
or electrical company requirements that might apply.
System power wiring must be properly fused and
conform to the local and national electrical codes.
System power wiring is to the unit main disconnect
(door interlocking disconnect switch standard on most
units) or distribution block and must be compatible with
the ratings on the nameplate: supply power voltage,
phase, and amperage (Minimum Circuit Amps - MCA,
Maximum Overcurrent Protection - MOP). All wiring
beyond this point has been done by the manufacturer
and cannot be modified without affecting the unit’s
agency / safety certification.
If field installing an additional disconnect switch, it
is recommended that there be at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and size
according to the rating plate.
If power supply is desired through bottom of unit, run
the wiring through the curb, cut a hole in the cabinet
bottom, and wire to the disconnect switch. Seal
penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent
requirements for the system to operate properly. Voltage
supply and voltage imbalance between phases should
be within the following tolerances. If the power is not
within these voltage tolerances, contact the power
company prior to operating the system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at all
line disconnect switches. Readings must fall within the
allowable range on the rating plate.
Key:V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
Most factory-supplied electrical components are
prewired. To determine what electrical accessories
require additional field wiring, refer to the unit specific
wiring diagram located on the inside of the unit control
center access door. The low voltage control circuit
is 24 VAC and control wiring should not exceed
0.75ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge
Field Control Wiring Length/Gauge
Total Wire
Length
125 ft.18
200 ft.16
300 ft.14
450 ft.12
Control wires should not be run inside the same conduit
as that carrying the supply power. Make sure that fieldsupplied conduit does not interfere with access panel
operation.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit control
center and wired in place of the remote switch (typically
between terminal blocks R and G on the terminal strip
(located on the 24 VAC terminal strip under the Typical
Control Center Components). The relay must be rated
for at least 5 amps and have a 24 VAC coil. Failure to
comply with these guidelines may cause motor starters
to “chatter” or not pull in which can cause contactor
failures and/or motor failures.
Minimum
Wire Gauge
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced with
wiring material having a temperature rating of at least
105ºC.
®
Energy Core Ventilator9
Page 10
Typical Control Center Components
1. Main Disconnect (nonfusible, lockable)
2. Motor Starter – Exhaust Air Fan
3. Motor Starter – Outdoor Air Fan
4. Speed Controllers/VFDs (Supply & Exhaust)
5. 24 VAC Control Transformer
6. 24 VAC Terminal Strip
Optional Control Center Components
7. Economizer Controller
8. Dirty Filter Pressure Switches
9. BMS Controller
10. Frost Control Timer
11. Thermostat
1
2
3
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of different
alarm lights and switches to control the unit. The remote
panel ships loose and requires mounting and wiring in
the field. The remote panel is available with the following
options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
7-Day Timer
5
11
10
8
4
9
BLACK
TIMER
RED
(CAPPED)
BLUE
CC
RRRG4
C
7
Y1
6
6
7
On/Off/Auto Switch & Indictor Light Wiring
Energy Core Ventilator10
CONTROL
CENTER
DOOR
®
Page 11
Dirty Filter Indicator
(powered by others)
Motor Potentiometer/0-10 VDC Fan Motor Control
Model ECV-10-VG (reference unit wiring diagram)
CLOSED 115-120V
OPEN 208-230/277V
T1
RED
BLACK
ST1
WHITE
T3
SUPPLY FAN
CLOSED 115-120V
OPEN 208-230/277V
T1
RED
BLACK
ST2
WHITE
T3
EXHAUST FAN
RED
M1
MOTOR
RED
M2
MOTOR
BLACK
2CBL-M1
BLACK
2CBL-M2
RED
2CBL-M1
RED
2CBL-M2
POT
BLACK
ORANGE
POT
BLACK
ORANGE
15
16
17
18
BLACK
(-)
0-10VDC
(+)
BLACK
(-)
0-10VDC
(+)
®
Energy Core Ventilator11
Page 12
Optional Component Overview
Economizer
The energy core operation can be altered to take
advantage of economizer operation (free cooling). Two
control options are available:
1. Bypass damper
2. Exhaust only operation
Bypass damper: An integral bypass damper will cycle
into a bypass condition allowing cool air to flow past the
energy recovery core rather than flow through it. When
outdoor air conditions are not suitable for economizer
operation, the damper will remain closed. Economizer
mode is initiated by temperature or enthalpy and
dependent on the sensor. To eliminate unnecessary
control sequences and the concern of overloading fans.
Energizing the bypass damper is accomplished one of
two ways:
1. The outdoor air temperature is <40ºF or >65ºF.
2. The outdoor air temperature is <40ºF or >65ºF DB
or >55˚F dew point.
Exhaust only operation: This option allows for the
exhaust fan to run continuously while the supply fan is
off.
Frost Control
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the energy
recovery core. Timed exhaust and a electric preheater
are optional frost control features that will prevent/
control core frosting.
Timed exhaust frost control includes a timer as well as
an adjustable thermostat (preset at 35°F) that is factory
installed in the exhaust airstream. When timed exhaust
frost control is initiated, the timer will turn the supply
blower off. Timed exhaust uses a default timer setting
that will shut down the supply fan for 5 minutes every
30minutes to allow for the exhaust air to defrost the
energy core.
Electric preheat comes standard as single-stage
on/off control. Preheaters are single point wired at
the factory. An adjustable thermostat (preset at 35°F)
is mounted in the exhaust airstream to monitor the
discharge air temperature and enable the preheater if
required. If the temperature falls below the set point,
the electric preheater will turn on. Access to the electric
preheat is through the outdoor air filter access door.
Reference Optional Start Up Components, Frost Control Test Procedure for troubleshooting.
Variable Frequency Drives (VFD)
VFDs are used to control the speed of the fan as either
multi-speed or modulating control. Multi-speed VFDs
reference a contact which can be made by a switch or
a sensor with a satisfied set point. Modulating control
references a 2-10 VDC signal to the VFD which will vary
the fan speed from a minimum 50% to full 100% rpm.
An optional CO
sensor is available to provide both a
2
set point contact or a modulating 2-10 VDC signal.
CO2 Sensor
The factory-provided sensors can be set to reference a
set point for on/off operation.
On model ECV, this accessory is often used in Demand
Control Ventilation (DCV) applications. The factory
provided sensor can be set to reference a set point for
multi-speed operation on the ECV-20 and ECV-30. The
CO
sensor can also be used to output a 2-10 VDC
2
signal to modulate the fan speed on the ECV-10-VG,
ECV-20 and ECV-30.
The CO
sensor is either shipped loose to mount in
2
the room space, ductwork, or is factory-mounted in
the return air intake. Follow instructions supplied with
sensor for installation and wiring details.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit control
center. Field-wiring of a light (or other alarm) to these
contacts will notify maintenance personnel when filters
need to be replaced. The switch has not been set at the
factory due to external system losses that will affect the
switch. This switch will need minor field adjustments
after the unit has been installed with all ductwork
complete. The dirty filter switch is mounted in the unit
control center.
Energy Core Ventilator12
®
Page 13
Start-Up
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
WARNING
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Do not operate energy core ventilator without the
filters and birdscreens installed. They prevent the
entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Thermometer
• Tachometer
• Incline Manometer or Equivalent
General Start-Up Information
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model Number _______________________________
Unit Serial Number _______________________________
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
(e.g. 04C99999 or 10111000)
(e.g. ECV-10)
Pre Start-Up Checklist – check as items are
completed.
Disconnect and lock-out all power switches
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
Rotate the fan wheels by hand to ensure no parts are
rubbing. If rubbing occurs, refer to Start-Up section
for more information.
Confirm the EC motor voltage is correct. Reference
unit wiring diagram.
Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more
information).
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood
(refer to Routine Maintenance section).
Verify that non-motorized dampers open and close
properly.
Check the tightness of all factory wiring connections.
Verify control wire gauge (refer to the Electrical
Connections section).
Start-Up Checklist
The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running. In order to measure
volts & amps, the control center door must be open,
and the unit energized using a crescent wrench to turn
the disconnect handle.
Check line voltage at unit disconnect
_______ L1-L2 volts
_______ L2-L3 volts
_______ L1-L3 volts
Motor Amp Draw
• Supply Fan • Exhaust Fan
_______ L1 amps ______ L1 amps
_______ L2 amps ______ L2 amps
_______ L3 amps ______ L3 amps
Fan RPM
_______ Supply Fan ______ Exhaust Fan
Correct fan rotation direction
Supply Fan Yes / No
Exhaust Fan Yes / No
®
Energy Core Ventilator13
Page 14
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit?
Frost Control Application / Operation section:SettingFactory Default
YesNoFrost Control set point32ºF
Differential2ºF
TimerRefer to page 17
Economizer Application / Operation section:
YesNoEconomizer (temperature)
Set point65ºF
Offset20ºF
Differential2ºF
YesNoEconomizer (enthalpy)
Set pointD
Optional Accessories section: Operational
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesN o CO
YesNo Remote Control PanelYes No N/A
SensorYes No N/A
2
Variable Frequency Drives section: Operational
YesNo Blower VFDsYes No N/A
Damper section: Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
Energy Core Ventilator14
®
Page 15
Start-Up Components
Fans
The unit contains two forward
curved (supply and exhaust)
fans. These forward curved
fans should be checked for free
rotation. If any binding occurs,
check for concealed damage and
foreign objects in the fan housing.
Be sure to check the belt drives
per the start-up recommendations
in the following section. (Not
applicable to ECV-10. The ECV-10 has direct drive fans).
Forward Curved
Exhaust Fan
5. Place belts over sheaves. Do not pry or force belts,
as this could result in damage to the cords in the
belts.
6. With the fan off, adjust the belt tension by moving
the motor base. (See belt tensioning procedures in
the Routine Maintenance section of this manual).
When in operation, the tight side of the belts should
be in a straight line from sheave to sheave with a
slight bow on the slack side.
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.), consult
Greenheck to determine if the unit can operate safely
at the new conditions.
Fan Performance Modifications
Due to job specification revisions, it may be necessary
to adjust or change the sheave or pulley to obtain
the desired airflow at the time of installation. Start-up
technician must check blower amperage to ensure that
the amperage listed on the motor nameplate is not
exceeded. Amperage to be tested with access doors
closed and ductwork installed.
Fan Belt Drives
The fan belt drive components, when supplied by
Greenheck, have been carefully selected for the
unit’s specific operating condition. Utilizing different
components than those supplied could result in unsafe
operating conditions which may cause personal injury or
failure of the following components:
• Fan Shaft • Bearings • Motor
• Fan Wheel • Belt
Tighten all fasteners and set screws securely and realign
drive pulleys after adjustment. Check pulleys and belts
for proper alignment to avoid unnecessary belt wear,
noise, vibration and power loss. Motor and drive shafts
must be parallel and pulleys in line (see diagrams in this
section).
Belt Drive Installation
1. Remove the protective coating from the end of the
fan shaft and assure that it is free of nicks and burrs.
2. Check fan and motor shafts for parallel
and angular alignment.
3. Slide sheaves on shafts. Do not
drive sheaves on as this may
result in bearing damage.
4. Align fan and motor sheaves
with a straight-edge or string
and tighten.
WRONGWRONG
WRONGCORRECT
Direction of Fan Wheel Rotation
Blower access is labeled on unit. Check for proper
wheel rotation by momentarily energizing the fan.
Rotation is determined by viewing the wheel from the
drive side and should match the rotation decal affixed
to the fan housing (see Rotation Direction figures). If
the wheel is rotating the wrong way, direction can be
reversed by interchanging any two of the three electrical
leads.
Check for unusual noise, vibration, or overheating
of bearings. Refer to the Troubleshooting section of this
manual if a problem develops.
t
t
a
i
o
o
n
R
n
o
i
t
a
t
o
R
Airflow
Forward Curved
Fan RPM
Supply fan and exhaust fan will have an adjustable
motor pulley (on 15 HP and below) preset at the factory
to the customer specified RPM. Fan speed can be
increased or decreased by adjusting the pitch diameter
of the motor pulley. Multi-groove variable pitch pulleys
must be adjusted an equal number of turns open
or closed. Any increase in fan speed represents a
substantial increase in load on the motor. Always check
the motor amperage reading and compare it to the
amperage rating shown on the motor nameplate when
changing fan RPM. All access doors must be installed
except the control center door. Do not operate units
with access doors open or without proper ductwork in
place as the fan motors will overload.
®
Energy Core Ventilator15
Page 16
Optional Start-Up Components
Economizer
Dirty Filter Switch
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (Senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’
of the switch. (Senses pressure at air inlet side of filters)
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch.
1. Open the filter compartment and place a sheet of
plastic or cardboard over 50% of the filter media.
2. Replace the filter compartment door.
3. Check to see if there is power at the alert signal
leads (refer to electrical diagram).
4. Whether there is power or not, turn the adjustment
screw on the dirty filter gauge (clockwise if you did
not have power, counterclockwise if you did have
power) until the power comes on or just before the
power goes off.
5. Open the filter compartment and remove the
obstructing material.
6. Replace the door and check to make sure that you
do not have power at the alert signal leads.
The unit is now ready for operation.
Relevant Set Points
1. MAT SET The outdoor air temperature set point
after the energy core. The control will open/close
the bypass damper to maintain temperature as
best as it can. (Set point menu, default 53°F )
2. LOW T LOCK The set point for the low
temperature mechanical cooling lockout.
(Set point menu, default 32°F)
3. DRYBLB SET The outdoor air set point to call for
economizer. (Set point menu, default 63°F)
4. AUX1 O The controllers operating sequence
structure. (Set point menu, default ‘None’)
5. ERV OAT SP The set point for low temperature
economizer lockout. This is the low temperature
set point when AUX1 O is set to ERV. (Set point
menu, default 40°F)
Using the Keypad with Settings and Parameters
To use the keypad when working with set points, system
and advanced settings, checkout tests, and alarms:
1. Navigate to the desired menu.
2. Press
currently displayed menu.
3. Use the and buttons to scroll to the desired
parameter.
4. Press
displayed item.
5. Press the button to increase (change) the
displayed parameter value.*
6. Press the
displayed parameter value.
7. Press (enter) to accept the displayed value and
store it in non-volatile RAM.
8. CHANGE STORED displays.
9. Press
parameter.
10. Press
parameter.
*
When values are displayed, pressing and holding
the or button causes the display to
automatically increment.
(enter) to display the first item in the
(enter) to display the value of the currently
button to increase (change) the
*
(enter) to return the current menu
(escape) to return to the current menu
Energy Core Ventilator16
®
Page 17
Frost Control Test Procedure
Timed Exhaust
1. Remove power from unit.
2. Jumper the temperature indicating sensor in the unit
control center. Thermostat controller has a pre-set
temperature of 35ºF.
3. Set the frost control timer scale for T1 and T2 to 5m.
Set the timer settings for T1 and T2 to 30.
4. Add power to the unit. Blower should cycle on for 30
minutes, then turn off for 5 minutes.
5. Remove power from unit and remove jumpers that
were placed. Reset timer settings.
• T1 timer setting set to 5 and timer scale set to
10m for 5 minutes of blower off time.
• T2 timer setting set to 5 and
timer scale set to 1h for 30
minutes of blower on time.
Electric Preheat
1. Remove power from unit.
2. Place wire jumper between
terminal R and G.
3. Turn dial on the thermostat TS1
Timer
Scale
Timer
Settings
Timer
Scale
T1
T2
to highest temperature setting.
4. Apply power to unit. Preheater
should turn on.
5. Remove power from unit, if
applicable remove wire jumper placed between R
and terminal G, and turn dial on thermostat TS1 to
factory setting (35ºF).
CO2 Proportional Control
Speed Controller
A carbon dioxide sensor is provided from the factory for
field mounting OR unit mounting in the space(s) being
served by the energy recovery unit.
The ECV-10-VG carbon dioxide sensor is wired to
the speed controller with default factory settings for
proportional control of 500 PPM or less CO
speed and 1500 PPM or greater CO
= 100% fan speed.
2
= 50% fan
2
The blower’s speed proportionally modulates between
500 and 1500 PPM CO
.
2
Variable Frequency Drive
The ECV-20 and ECV-30 are wired to the Variable
Frequency Drive (VFD). Refer to the Variable Frequency
Drive section for control sequence and programming.
Vari-Green® Electronically
Commutated (EC) Motor
Features
Soft Start – All motors
feature soft-start technology
which eliminates inrush
current at start-up. The
motors will reliably start at
any speed setting.
Overload Protection – If the motor becomes
overloaded, it will automatically reduce its speed until it
is no longer overloaded. This means that the motor will
never operate in the “service factor” which is possible
with many AC motors.
Locked Rotor Protection – If the motor ever
encounters a locked-rotor scenario, the motor will
automatically shut itself down. It will try to restart up to
3 times and if after the 3rd time the motor will still not
rotate, the motor will not attempt to start again until
power is cycled.
Thermal Protection – The motors will have an internal
thermal protection which electronically regulates the
RPM limit until an acceptable temperature is met.
Operation and Wiring
These motors have the ability to accept a plug in
potentiometer for speed adjustment AND the ability to
accept a 0-10V signal for remote control.
Motor Potentiometer - Turn the dial with your fingers to
adjust. To increase the speed, rotate the dial clockwise.
To decrease the speed, rotate the dial counterclockwise.
Turning the dial full counterclockwise will turn the motor
off.
0-10 VDC Signal - From 0-1.9V, the motor will be off
and will operate within the 2-10V range. This motor
does not require 24V power for operation.
®
Energy Core Ventilator17
Page 18
Variable Frequency Drives
Optional factory installed, wired, and programmed
variable frequency drives (VFDs) may have been
provided for modulating or multi-speed control of the
blowers. One VFD, either Yaskawa model V1000 or
J1000, is provided for each blower (supply air and
exhaust).
Refer to the tables in this section for factory settings
and field wiring requirements. Refer to the unit control
center for unit specific wiring diagram. When making
adjustments outside of the factory set points, refer to
Yaskawa VFD instruction manual, which can be found
online at www.drives.com. For technical support,
contact Yaskawa direct at 1-800-927-5292.
IGS-S+R-R+
MPACAMAC+VA2A1PCP2P1
MA MB MCRPH1SCHCS7S6S5S4S3S2S1
J1000
V1000
OPTION 1 - 0-10 VDC CONTROL
USER TO PROVIDE ISOLATION AS REQUIRED
A1 AC
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.
USER TO PROVIDE CONTACTS AND ISOLATION AS REQUIRED
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL
0-10 VDC CONTROL SIGNAL (BY OTHERS)
WIRED TO A1 (+) AND AC (COMMON)
0 VDC = 30 Hz
10 VDC = 60 Hz
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL
OPTION 2 - MULTI SPEED CONTROL
S5S4SC
NEITHER S4 OR S5 CONTACT CLOSED
DRIVE SPEED = 60 Hz.
S4 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 40 Hz.
S5 TO SC CONTACT CLOSED (BY OTHERS)
DRIVE SPEED = 30 Hz.
MA MB MCACAMAC+VA1SCS5S4S3S2S1
Factory Set Points
Variable frequency drives (VFDs) for the blowers are
factory setup to operate in one of the three following
modes:
• Modulating: 0-10 VDC signal wired in the field by
others varies the speed of the blower between 30
and 60 Hz
• Multi-speed: Digital contact closures by others
command the VFD to run at multiple speed settings:
ż Open - Drive runs at 60 Hz
ż SC to S4 - Drive runs at 40 Hz
ż SC to S5 - Drive runs at 30 Hz
• CO
Sensor:
2
żSet Point Control: A carbon dioxide sensor is
provided from the factory for field mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with two preset speeds of 700
PPM or less CO2 = 50% fan speed and 800 PPM
or greater CO
= 100% fan speed.
2
ż Proportional Control: A carbon dioxide sensor
is provided from the factory for field mounting OR
unit mounting in the space(s) being served by the
energy recovery unit. The CO
sensors are wired
2
to the unit VFD’s with default factory settings
of 500 PPM or less CO2 = 50% fan speed and
1000 PPM or greater CO2 = 100% fan speed.
Modulation of VFD occurs proportional to CO
2
between 500 and 1000PPM.
The terminal locations for modulating and multi-speed
are shown on the previous page. Most of the set points
in the VFDs are Yaskawa factory defaults. However,
a few set points are changed at Greenheck and are
shown in the tables. These settings are based on the
VFD mode selected.
Change Set Points
To gain access to change set points on the V1000 and
J1000 drives, parameter A1-01 needs to be set at “2”.
To prevent access or tampering with drive settings on
either drive, change parameter A1-01 to “0”.
• Drive Operation
żSC to S1 contact for On/Off
ż A1 (0-10 VDC) referenced to AC.
Can use +15 VDC from +V.
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults, go to parameter A1-01 and set it to “2”. Then
go to A1-03 and change it to “1110” and press enter.
The drive is now reset to the settings programmed at
Greenheck. This option is not available on the J1000.
L2-01Ride Thru Power Loss22
L4-05Frequency Ref Loss0NA
L5-01Auto Restart Attempt55
A1-01Access Level00
®
Energy Core Ventilator19
Page 20
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Once the unit has been put into operation, a routine
maintenance program should be set up to preserve
reliability and performance. Items to be included in this
program are:
Lubrication
Apply lubrication where required
Dampers
Check for unobstructed operation
Fan Belts
Check for wear, tension, alignment
Motors
Check for cleanliness
Blower Wheel & Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
Bearings
Check for cleanliness
Check set screws for tightness
Lubricate as required
External Filter
Check for cleanliness - clean if required
Internal Filter
Check for cleanliness - replace if required
Door Seal
Check if intact and pliable
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication.
Apply lubrication where required. Any components
showing excessive wear should be replaced to maintain
the integrity of the unit and ensure proper operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Fan Belts
Belts must be checked on a regular basis for wear,
tension, alignment, and dirt accumulation. Premature
or frequent belt failures can be caused by improper
belt tension (either too loose or too tight) or misaligned
sheaves. Abnormally high belt tension or drive
misalignment will cause excessive bearing loads and
may result in failure of the fan and/or motor bearings.
Conversely, loose belts will cause squealing on start-up,
excessive belt flutter, slippage, and overheated sheaves.
Both loose and tight belts can cause fan vibration.
When replacing belts on multiple groove drives, all belts
should be changed to provide uniform drive loading. Do
not pry belts on or off the sheave. Loosen belt tension
until belts can be removed by simply lifting the belts off
the sheaves. After replacing belts, insure that slack in
each belt is on the same side of the drive. Belt dressing
should never be used.
Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.
The proper belt setting is the lowest tension at which
the belts will not slip under peak load operation. For
initial tensioning, set the belt deflection at 1/64-inch
for each inch of belt span (measured half-way between
sheave centers). For example, if the belt span is
64inches, the belt deflection should be oneinch
(using moderate thumb
pressure at mid-point
Deflection =
Belt Span
64
of the drive). Check
belt tension two times
during the first 24hours
of operation and
periodically thereafter.
Belt Span
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup on
the motor housing assists proper motor cooling. Never
wash-down motor with high pressure spray. Greasing
of motors is only intended when fittings are provided.
Many fractional motors are permanently lubricated for
life and require no further lubrication.
Energy Core Ventilator20
®
Page 21
Fan Wheel & Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively clean
environment. Some bearings are relubricatable and will
need to be regreased depending on fan use. Check your
bearings for grease zerk fittings to find out what type
of bearing you have. If your fan is not being operated
under normal use, bearings should be checked monthly
for lubrication.
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
ordered). Filters should be checked and cleaned on
a regular basis for best efficiency. The frequency of
cleaning depends upon the cleanliness of the incoming
air. These filters should be cleaned prior to start-up.
Clean filters by rinsing with a mild detergent in warm
water.
Internal Filter Maintenance
The units will typically be provided with 2-inch, pleated
filters in the outdoor air and exhaust airstreams. These
filters should be checked per a routine maintenance
schedule and replaced as necessary to ensure proper
airflow through the unit. See table for pleated filter size
and quantity for each unit. Replacement filters shall be
of same performance and quality as factory installed
filters. Filter type must be pleated design with integral
metal grid. Two acceptable filter replacements are
Aerostar Series 400 or Farr 30/30
Outdoor Air Filters: Access to the outdoor air filters is
through the door labeled as “Filter Access” on the sides
of the unit.
®
.
Exhaust Air Filters: Access to the exhaust air filters is
through the door labeled as “Filter Access” on the sides
of the unit.
Refer to Access Panel Location section for additional
information on filter locations.
Door Seal Maintenance
A bulb seal is installed on the perimeter of the door
frame. Inspect at least annually to ensure that the seal is
still intact.
Energy Recovery Core
Annual inspection of the energy recovery core is
recommended. Units ventilating smoking lounges and
other nonclean air spaces should have energy recovery
core inspections more often based upon needs.
Accessing the energy recovery core - Disconnect
the power to the ECV. Remove access panel.
Removing the energy recovery core - Once the
energy core access doors are removed, the core can be
pulled from the housing. To replace the core, reverse the
procedure.
Recommended cleaning procedure - First, remove
the energy recovery core by following the instructions
on this page.
Once the core is removed, gently vacuum the surfaces
of the core to remove the dirt and debris that has
accumulated.
Frequency of cleaning - A regular cleaning cycle must
be established for the energy recovery core in order to
maintain optimum sensible and latent energy transfer. In
reasonably clean environments such as schools, offices
or retail stores, the energy recovery core should be
inspected annually and cleaned as needed.
Failure to follow a regular cleaning cycle for the energy
recovery core can result in significant energy transfer
performance losses.
WARNING
Do not wash, soak in water or use detergents and
cleaners on the core. This will result in a damaged
core.
Pleated Filter Size and Quantities
Unit Size
ECV-1016 x 20220 x 202
ECV-2016 x 20220 x 202
ECV-3020 x 20320 x 203
All dimensions in inches.
®
SupplyExhaust
SizeQtySizeQty
Energy Core Ventilator21
Page 22
Troubleshooting - Economizer
Alarms
Addressing Alarms
Alarms will signify a faulty sensor. When this occurs,
verify all connections to the sensor and controller are
secure. Press enter twice to clear the alarm. If the issue
persists, consult the factory.
Clearing Alarms
Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the
3. ERASE? displays.
4. Press (enter).
5. ALARM ERASED displays.
6. Press
to the previous menu.
If an alarm still exists after you clear it, it redisplays
within 5 seconds.
(enter).
(escape) to complete the action and return
NOTE
Energy Core Ventilator22
®
Page 23
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air and
exhaust air is being supplied and removed from a building, respectively. There are no set rules on what information
must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low, prior to
contacting the factory, please determine the following information:
Unit #1Unit #2Unit #3Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in accordance
with SMACNA and AMCA guidelines.
®
Energy Core Ventilator23
Page 24
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Replace fuse or reset circuit breaker and check
amps.
Check for On/Off switches. Check for correct
supply voltage.
Check for broken or loose belts. Tighten loose
pulleys.
Shorten wiring run to mechanical room or install a
relay which will turn unit on/off. Consult factory for
relay information.
Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.
If higher, ductwork should be improved.
If lower, fan rpm should be lower.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Improve ductwork to eliminate losses using good
duct practices.
For 3-phase, see Direction of Fan Wheel Rotation
under Unit Start-Up section.
Follow cleaning procedures in Routine Maintenance
section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed if
necessary.
Induce Ps into system ductwork. Make sure grilles
and access doors are installed. Decrease fan speed
if necessary.
Adjust frost temperature sensor set point as
needed.
Blower fails
to operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Low airflow (cfm)
High airflow (cfm)
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Blown fuse or open circuit breaker.
Defective motor or capacitor.Replace.
Motor starter overloaded.Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the coil.
CFM too high.Check cfm and adjust drives if needed.
Static pressures are higher or lower than design.
Blower rotation is incorrect.Check rotation and reverse if necessary.
Motor voltage incorrect.Check motor nameplate versus supplied voltage.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.Check for correct drives and rpm with catalog data.
Fan wheels are operating backwards.
Dirty filter or energy core.
Leaks in ductwork.Repair.
Elbows or other obstructions may be obstructing
fan outlet.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to
requesting parts or service information.
Energy Core Ventilator24
®
Page 25
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Adjust wheel and/or inlet cone. Tighten wheel hub
or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.
Excessive noise
Fan wheel rubbing on inlet.
Bearings.
Motor base or blower loose.Tighten mounting bolts.
or vibration
Bearing and drive misaligned.Realign.
Make sure ductwork is supported properly. Make
Noise being transmitted by duct.
sure ductwork metal thickness is sized for proper
stiffness. Check duct size at discharge to ensure
that air velocities are not too high.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to
requesting parts or service information.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.
Greenheck catalog, Energy Core Ventilators, Model MiniCore
and ECV, provides additional information describing the
equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.