Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Model:
ECV-10
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch
or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components
may be hot enough to cause pain or injury. Allow
time for cooling before servicing.
CAUTION
Precaution should be taken in explosive
atmospheres.
1. Follow all local electrical and safety codes, as well
as the National Electrical Code (NEC), the National
Fire Protection Agency (NFPA), where applicable.
Follow the Canadian Electrical Code (CEC) in
Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
®
Energy Core Ventilator
1
Page 2
Receiving
Upon receiving the product, check to ensure all
items are accounted for by referencing the delivery
receipt or packing list. Inspect each crate or carton
for shipping damage before accepting delivery. Alert
the carrier of any damage detected. The customer will
make a notion of damage (or shortage of items) on
the delivery receipt and all copies of the bill of lading
which is countersigned by the delivering carrier.
If damaged, immediately contact your Greenheck
Representative. Any physical damage to the unit after
acceptance is not the responsibility of Greenheck Fan
Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle each piece in such a manner as to keep from
scratching or chipping the coating. Damaged finish
may reduce ability of the unit to resist corrosion.
Machined parts coated with rust preventive should
be restored to good condition promptly if signs of
rust occur. Immediately remove the original rust
preventive coating with petroleum solvent and clean
with lint-free cloths. Polish any remaining rust from
surface with crocus cloth or fine emery paper and oil.
Do not destroy the continuity of the surfaces. Wipe
clean thoroughly with Tectyl
the equivalent. For hard to reach internal surfaces or
for occasional use, consider using Tectyl® 511M Rust
Preventive or WD-40® or the equivalent.
®
506 (Ashland Inc.) or
Storage
Units are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the unit and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.
Inspection and Maintenance during
Storage
While in storage, inspect units once per month. Keep
a record of inspection and maintenance performed
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate all moving components by hand
ten to fifteen revolutions to distribute lubricant on
motor and bearings. If paint deterioration begins,
consideration should be given to touch-up or
repainting. Units with special coatings may require
special techniques for touch-up or repair.
Energy Core Ventilator
2
Page 3
Table of Contents
Product Overview
Product Overview . . . . . . . . . . . . . 3
Standard Components . . . . . . . . . . . 3
Installation
Dimensional Data . . . . . . . . . . . . . 4
Indoor Mounting Options . . . . . . . . . . 4
Outdoor Mounting Options . . . . . . . . . 4
Recommended Roof Openings & Weights . . . 5
Service Clearances . . . . . . . . . . . . 5
Access Panel Locations . . . . . . . . . . 6
Handling . . . . . . . . . . . . . . . . . 6
Lifting . . . . . . . . . . . . . . . . . . 6
Roof Curb Mounting . . . . . . . . . . . . 7
Curb Outside Dimensions and Weights . . . . 7
Ductwork Connections . . . . . . . . . . . 8
Rail Mounting / Layout . . . . . . . . . . . 8
Electrical Information
General Electrical Information . . . . . . . . 9
Control Center Components . . . . . . . . . 10
Optional Accessory Wiring Schematics . . . . 10
Unit Overview
Basic Unit . . . . . . . . . . . . . . . . 11
Optional Component Overview
Economizer . . . . . . . . . . . . . . . 12
Frost Control . . . . . . . . . . . . . . . 12
CO
Sensor . . . . . . . . . . . . . . . 12
2
Dirty Filter Switch . . . . . . . . . . . . . 12
Start-Up
General . . . . . . . . . . . . . . . . . 13
Pre Start-Up Checklist . . . . . . . . . . . 13
Special Tools Required . . . . . . . . . . . 13
Start-Up Checklist . . . . . . . . . . . . . 13
Optional Accessories Checklist . . . . . . . 14
Start-Up Components
Fans . . . . . . . . . . . . . . . . . . 15
EC Motors . . . . . . . . . . . . . . . . 15
Optional Start-Up Components
Dirty Filter Switch . . . . . . . . . . . . . 15
Economizer . . . . . . . . . . . . . . . 16
Frost Control . . . . . . . . . . . . . . . 16
Routine Maintenance . . . . . . . . . . 17-18
Troubleshooting
Economizer Alarms . . . . . . . . . . . . 19
Airflow. . . . . . . . . . . . . . . . . . 20
Unit . . . . . . . . . . . . . . . . . .21-22
Maintenance Log . . . . . . . . . . . . . 23
Our Commitment . . . . . . . . . Backcover
The ECV brings in fresh, outdoor air and removes
stale, exhaust air. Prior to discharging the exhaust
air, the energy recovery core transfers energy from
the exhaust air to the outdoor air at an efficiency
of 50-60%. Simply put, this unit preconditions the
outdoor air to save money on heating and cooling
costs.
Standard Components
Outdoor Air Weatherhood
Outdoor air weatherhood will be factory-mounted.
Exhaust Weatherhood
The exhaust weatherhood is shipped separately as a
kit with its own instructions.
Dampers
Backdraft dampers are always included as an integral
part of the exhaust hood assemblies. Motorized
outdoor air and exhaust air dampers are optional and
are factory-mounted and wired at the intake.
Energy Core Ventilator
3
Page 4
Installation
Dimensional Data
Unit Size
Exterior DimensionsUnit Opening Dimensions
ABCDEFG
ECV-1054.828.943.918.4 x 15.913.6 x 13.68.2 x 11.316.5 x 11.5
All dimensions are in inches.
Unit Size
Intake and Discharge Options
BottomTopSideEnd
OA IntakeXX
SA DischargeXX
RA IntakeXX
EA DischargeXX
Indoor Mounting Options
E
EXHAUST AIR
DISCHARGE
SUPPLY AIR
DISCHARGE
E
OUTDOOR AIR INTAKE
D
C
SUPPLY AIR
DISCHARGE
EXHAUST AIR
DISCHARGE
E
F
OUTDOOR AIR INTAKE
D
C
(NON ELECTRICAL SIDE)
A
End ConnectionsTop and Bottom Connections
Outdoor Mounting Options
EXHAUST AIR
DISCHARGE
SUPPLY AIR
DISCHARGE
F
(NON ELECTRICAL SIDE)
A
G
D
RETURN AIR INTAKE
B
EXHAUST AIR
DISCHARGE
C
OUTDOOR AIR
INTAKE
B
RETURN AIR INTAKE
SUPPLY AIR
DISCHARGE
(NON ELECTRICAL SIDE)
A
E
(NON ELECTRICAL SIDE)
A
G
RETURN AIR INTAKE
B
C
G
B
RETURN AIR INTAKE
OUTDOOR AIR
INTAKE
Outdoor Air Discharge BottomOutdoor Air Discharge End
Energy Core Ventilator
4
Page 5
Recommended Roof Openings & Weights
Position the unit roof opening such that the supply
discharge and return inlet of the unit will line up with
the corresponding ductwork. Be sure to allow for the
recommended service clearances when positioning
opening (see Service Clearances). Do not face the
outdoor air intake of the unit into prevailing wind
and keep the intake away from any other exhaust
fans. Likewise, position the exhaust discharge
opening away from outdoor air intakes of any other
equipment.
When cutting only duct openings, cut opening 1-inch
(25 mm) larger than duct size to allow clearance for
installation. Area enclosed by roof curb must comply
with clearance to combustible materials. If the roof is
constructed of combustible materials, area within the
roof curb must be ventilated, left open, or covered
with non-combustible material which has an “R”
value of at least 5. If area within curb is open, higher
radiated sound levels may result.
Where the supply or warm air duct passes thru a
combustible roof, a clearance of 1-inch must be
maintained between the outside edges of the duct
and combustible material in accordance with NFPA
Standard 90A.
Service Clearances
The ECV-10 unit requires minimum clearances
to perform routine maintenance, such as filter
replacement and energy core inspection. Blower and
motor assemblies, energy recovery core and filter
sections are always provided with a service door
or panel for proper component access. Clearances
for component removal may be greater than the
service clearances, refer to drawing below for these
dimensions.
C
E
A
D
E
C
CORE
CORE
CONTROL
PANEL
4.4
5.2
18.5
13.5
RETURN
AIR INTAKE
13.33.4
SUPPLY AIR
DISCHARGE
CONTROL PANEL
7.0
10.2
Unit SizeApprox. Weight (lbs.)
ECV-10485
All dimensions are in inches. *Weight assumes outdoor
unit with filters, weatherhoods, outdoor air intake damper,
controls and internal double-wall sheet metal.
FH
G
B
Recommended Service Clearances
Unit SizeABCDEFGH
ECV-10102.9 120.8 35.5 28.9223654.830
All dimensions are in inches.
Energy Core Ventilator
5
Page 6
Access Panel Locations
The ECV is provided with access panels on both
sides of the unit. The nonelectrical side can be placed
against a wall. Clearance to the electrical side is
essential to provide access to the control center and
component maintenance.
1
2
Electrical Side
2
3
Handling
While this unit was constructed with quality and
dependability in mind, damage still may occur during
handling of the unit for installation.
The system design and installation should follow
accepted industry practice, such as described in
the ASHRAE Handbook. Adequate space should
be left around the unit for filter replacement and
maintenance. Sufficient space should be provided on
the side of the unit for routine service and component
removal should that become necessary.
Lifting
WARNING
All factory provided lifting lugs must be used when
lifting the unit. Failure to comply with this safety
precaution could result in property damage, serious
injury or death.
1. Before lifting, be sure that all shipping material
has been removed from unit.
2. To assist in determining rigging requirements,
weights are shown under the Recommended
Roof Openings & Weights section.
3. Unit must be lifted by all lifting lugs provided on
base structure.
4. Rigger to use suitable mating hardware to attach
to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent
damage to the cabinet by the lift cables.
1
2
3
6
Control Center
Core
Filters
Inlet Dampers
Bypass Damper
Blowers
Blowers
Energy Core Ventilator
Nonelectrical Side
6. Always test-lift the unit to check for proper
balance and rigging before hoisting to desired
location.
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be
completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by
others) has been applied to the curb prior to
lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
Page 7
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The
duct connections must be located so they will be
clear of structural members of the building.
1. Factory Supplied Roof Curbs: Roof curbs are
Model GKD. The GKD ships in a knockdown
kit (includes duct adapter) and requires field
assembly (by others). Assembly instructions are
included.
2. Install Curb: Locate curb over roof opening and
fasten in place. (Refer to Recommended Roof
Openings). Check that the diagonal dimensions
are within ±1/8 inch of each other and adjust
as necessary. For proper unit operation, it is
important that the installation be level. Shim as
required to level.
3. Install Ductwork: Installation of all ducts should
be done in accordance with SMACNA and AMCA
guidelines. Duct adapter provided to support
ducts prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above
the curb and duct openings. Guide unit while
lowering to align with duct openings. Roof curbs
fit inside the unit base. Make sure the unit is
properly seated on the curb and is level.
Curb Outside Dimensions and Weights
AA
B
Unit SizeABCurb Weight (lbs.)
ECV-1052.226.360
All dimensions are in inches. Weight is for 14-inch high
model GKD curbs.
Side of Unit
A
B
C
D
E
Roof Curb
Curb Cap Details for Factory Supplied Roof Curbs
Unit SizeA
ECV-101.95.34.34.30.8
All dimensions are in inches.
BCDE
Base
1-inch Insulation
Energy Core Ventilator
7
Page 8
Ductwork Connections
R
o
t
a
t
i
o
n
POOR
Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will
result in low airflow and
other system effects.
n
o
i
t
a
t
o
R
Recommended Discharge Duct Size and Length
ModelBlower Size Duct Size Straight Duct Length
ECV-1010-614 x 1436 ft.
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project.
Refer to plans for appropriate job specific duct size and/or
velocity limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
Length of Straight Duct
GOOD
Rail Mounting / Layout
• Rails designed to handle the weight of the unit
should be positioned as shown on the diagram
(rails by others).
• Make sure that rail positioning does not interfere
with the supply air discharge opening or the
exhaust air intake opening on the unit. Avoid area
dimensioned “B” below.
• Rails should extend beyond the unit a minimum of
12 inches on each side.
• Set unit on rails.
A
B
Unit SizeA
ECV-104.211.5
All dimensions are in inches.
B
Energy Core Ventilator
8
Page 9
Electrical Information
The unit must be electrically grounded in accordance
with the current National Electrical Code,
ANSI/NFPA 70. In Canada, use current CSA Standard
C22.1, Canadian Electrical Code, Part 1. In addition,
the installer should be aware of any local ordinances
or electrical company requirements that might apply.
System power wiring must be properly fused and
conform to the local and national electrical codes.
System power wiring is to the unit main disconnect
(door interlocking disconnect switch standard
on most units) or distribution block and must be
compatible with the ratings on the nameplate: supply
power voltage, phase, and amperage (Minimum
Circuit Amps - MCA, Maximum Overcurrent Protection
- MOP). All wiring beyond this point has been done
by the manufacturer and cannot be modified without
affecting the unit’s agency / safety certification.
If field installing an additional disconnect switch, it
is recommended that there be at least four feet of
service room between the switch and system access
panels. When providing or replacing fuses in a fusible
disconnect, use dual element time delay fuses and
size according to the rating plate.
If power supply is desired through bottom of unit, run
the wiring through the curb, cut a hole in the cabinet
bottom, and wire to the disconnect switch. Seal
penetration in cabinet bottom to prevent leakage.
The electric supply to the unit must meet stringent
requirements for the system to operate properly.
Voltage supply and voltage imbalance between
phases should be within the following tolerances.
If the power is not within these voltage tolerances,
contact the power company prior to operating the
system.
Voltage Supply: See voltage use range on the rating
plate. Measure and record each supply leg voltage at
all line disconnect switches. Readings must fall within
the allowable range on the rating plate.
Key:V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA
WARNING
To prevent injury or death due to electrocution or
contact with moving parts, lock disconnect switch
open.
Most-factory supplied electrical components are
prewired. To determine what electrical accessories
require additional field wiring, refer to the unit specific
wiring diagram located on the inside of the unit
control center access door. The low voltage control
circuit is 24 VAC and control wiring should not exceed
0.75ohms.
Refer to Field Control Wiring Length/Gauge table for
wire length maximums for a given wire gauge.
Field Control Wiring Length/Gauge
Total
Wire Length
125 ft.18
200 ft.16
300 ft.14
450 ft.12
Minimum
Wire Gauge
Control wires should not be run inside the same
conduit as that carrying the supply power. Make sure
that field-supplied conduit does not interfere with
access panel operation.
If wire resistance exceeds 0.75 ohms, an industrialstyle, plug-in relay should be added to the unit
control center and wired in place of the remote switch
(typically between terminal blocks R and G on the
terminal strip (located on the 24 VAC terminal strip
under the Typical Control Center Components). The
relay must be rated for at least 5 amps and have a 24
VAC coil. Failure to comply with these guidelines may
cause motor starters to “chatter” or not pull in which
can cause contactor failures and/or motor failures.
CAUTION
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced
with wiring material having a temperature rating of
at least 105ºC.
Energy Core Ventilator
9
Page 10
Typical Control Center Components
1. Main Disconnect (nonfusible, lockable)
2. Motor Starter – Exhaust Air Fan
3. Motor Starter – Outdoor Air Fan
4. Speed Controllers (Supply & Exhaust)
5. 24 VAC Control Transformer
6. 24 VAC Terminal Strip
Optional Control Center Components
7. Economizer Controller
8. Dirty Filter Pressure Switches
9. BMS Controller
10. Frost Control Timer
11. Thermostat
1
2
3
Optional Accessory Wiring Schematics
Remote Panel
The remote panel is available with a number of
different alarm lights and switches to control the unit.
The remote panel ships loose and requires mounting
and wiring in the field. The remote panel is available
with the following options:
• Unit on/off switch
• Unit on/off light
• 7-day time clock
• Hand/off/auto switch
• Dirty filter light
• Economizer light
• Frost control light
7-Day Timer
5
11
10
8
4
9
6
7
On/Off/Auto Switch & Indictor Light Wiring
Energy Core Ventilator
10
CONTROL
CENTER
DOOR
Page 11
Dirty Filter Indicator
(powered by others)
Unit Overview
Basic Unit
The unit is prewired such that when a call for outside
air is made (via field-supplied 24 VAC control signal
wired to unit control center), the supply and exhaust
fans are energized and optional motorized dampers
open. The unit is normally interlocked (24 volt) to
the rooftop air handler. When the rooftop air handler
starts, the auxiliary contactor in the air handler closes
to start the unit.
Summer Operation
Outdoor air is preconditioned (temperature and
moisture levels are decreased) by the transfer of
energy from the cooler, drier exhaust air through
the energy recovery core. The preconditioned air is
typically mixed with return air going back to the air
handler for final conditioning.
Winter Operation
Outdoor air is preconditioned (temperature and
moisture levels are increased) by the transfer of
energy from the warmer, more humid exhaust air
through the energy recovery core. The preconditioned
air is typically mixed with return air going back to the
air handler for final conditioning.
Exhaust Air
Supply Air
82° F
88 grains/lb.
Outdoor Air
95° F
125 grains/lb.
Summer
Operation
Return Air
75° F
50% RH
Energy Core Ventilator
11
Page 12
Optional Component Overview
Economizer
The energy core operation can be altered to take
advantage of economizer operation (free cooling).
Two modes are available:
1. Bypass damper
2. Independent blower control
Bypass damper: An integral bypass damper will
cycle into a bypass condition allowing cool air to
flow past the energy recovery core rather than
flow through it. When outdoor air conditions are
not suitable for economizer operation, the damper
will remain closed. Economizer mode is initiated
by temperature or enthalpy and dependent on the
sensor. To eliminate unnecessary control sequences
and the concern of overloading fans. Energizing the
bypass damper is accomplished one of two ways:
1. The outdoor air temperature is <40ºF or >65ºF.
2. The outdoor air temperature is <40ºF or >65ºF
DB or >55˚F dew point.
Independent blower control: The unit will have the
capability to receive an external signal to power off
the supply fan.
Dirty Filter Sensor
Dirty filter sensors monitor pressure drop across the
outdoor air filters, exhaust air filters, or both. If the
pressure drop across the filters exceeds the set point,
the sensor will close a set of contacts in the unit
control center. Field-wiring of a light (or other alarm)
to these contacts will notify maintenance personnel
when filters need to be replaced. The switch has not
been set at the factory due to external system losses
that will affect the switch. This switch will need minor
field adjustments after the unit has been installed
with all ductwork complete. The dirty filter switch is
mounted in the unit control center.
Frost Control
Extremely cold outdoor air temperatures in
combination with higher indoor humidity levels, can
cause moisture condensation and frosting on the
energy recovery core. Timed exhaust frost control is
an optional feature available to prevent and/or control
core frosting.
This option is provided with a temperature sensor
installed in the exhaust airstream to measure the
temperature of the air leaving the core. When the
exhaust air temperature drops below 32ºF, frost
control is initiated.
Timed exhaust includes a timer in addition to the
temperature sensor. If the exhaust air temperature is
below 32ºF, the supply blower is cycled approximately
30 minutes on and 5 minutes off to allow the warm
exhaust air to heat the core. Once the exhaust air
temperature rises above 32ºF, the supply blower is no
longer cycled.
CO2 Sensor
The factory-provided sensors can be set to reference
a set point for on/off operation.
Energy Core Ventilator
12
Page 13
Start-Up
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit
to OFF at disconnect switch(es). Unit may have
multiple power supplies.
WARNING
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Do not operate energy core ventilator without the
filters and birdscreens installed. They prevent the
entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage
to internal components may result and void
warranty.
General Start-Up Information
Every installation requires a comprehensive startup to ensure proper operation of the unit. As part
of that process, the following checklist must be
completed and information recorded. Starting up
the unit in accordance with this checklist will not
only ensure proper operation, but will also provide
valuable information to personnel performing future
maintenance. Should an issue arise which requires
factory assistance, this completed document
will allow unit experts to provide quicker resolve.
Qualified personnel should perform start-up to ensure
safe and proper practices are followed.
Unit Model Number _______________________________
Unit Serial Number _______________________________
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check as items are
completed.
Disconnect and lock-out all power switches
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
(e.g. ECV-10)
(e.g. 04C99999 or 10111000)
Rotate the fan wheels by hand to ensure no parts
are rubbing. If rubbing occurs, refer to Start-Up
section for more information.
Check the fan belt drives for proper alignment
and tension (refer to Start-Up section for more
information).
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood
(refer to Routine Maintenance section).
Verify that non-motorized dampers open and close
properly.
Check the tightness of all factory wiring
connections.
Verify control wire gauge (refer to the Electrical
Connections section).
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Thermometer
• Tachometer
• Incline Manometer or Equivalent
Start-Up Checklist
The unit will be in operational mode during start-up.
Use necessary precautions to avoid injury. All data
must be collected while the unit is running. In order to
measure volts & amps, the control center door must
be open, and the unit energized using a crescent
wrench to turn the disconnect handle.
Check line voltage at unit disconnect
_______ L1-L2 volts
Correct fan rotation direction
Supply Fan Yes / No
Exhaust Fan Yes / No
Energy Core Ventilator
13
Page 14
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit?
Frost Control Application / Operation section:SettingFactory Default
YesNoFrost Control Set Point32ºF
Differential2ºF
TimerRefer to page 16
Economizer Application / Operation section:
YesNoEconomizer (temperature)
Set Point65ºF
Offset25ºF
Differential2ºF
YesNoEconomizer (enthalpy)
Set PointD
Optional Accessories section: Operational
YesNo OA Dirty Filter SensorYes No N/A
YesNo EA Dirty Filter SensorYes No N/A
YesN o C O
YesNo Remote Control PanelYes No N/A
SensorYes No N/A
2
Damper section: Operational
YesNo Outdoor Air DamperYes No N/A
YesNo Exhaust Air DamperYes No N/A
Energy Core Ventilator
14
Page 15
Start-Up Components
Airflow
Optional Start-Up Components
Fans
The unit contains two forwardcurved (supply and exhaust)
fans. These forward-curved
fans should be checked for
free rotation. If any binding
occurs, check for concealed
damage and foreign objects in
the fan housing.
Forward-Curved Fan
Check Blower Wheel Rotation
First, hand rotate the blower to ensure that the wheel is
not rubbing against the scroll. If the blower is rotating in
the wrong direction, the
unit will move some air
but not perform properly.
To check the rotation,
open the blower access
n
o
i
t
a
t
o
R
panel, and run the
blower momentarily to
determine the rotation.
Forward Curved
CAUTION
When operating conditions of the fan are to be
changed (speed, pressure, temperature, etc.),
consult Greenheck to determine if the unit can
operate safely at the new conditions.
Optional EC Motor
Features
Soft start – All motors
feature soft start
technology which
eliminates inrush
current at start-up. The
motors will reliably start
at any speed setting.
Overload protection – If the motor becomes
overloaded, it will automatically reduce its speed until it
is no longer overloaded. This means that the motor will
never operate in the “service factor” which is possible
with many AC motors. The motor and control are
electrically protected with lightning surge protection.
Optional Dirty Filter Switch
Setscrew (on front of switch) must
be manually adjusted after the
system is in operation.
Negative pressure connection
is toward the ‘front or top’ of
the switch. (Senses pressure on
the blower side of filters)
Positive pressure connection is toward the ‘back or bottom’
of the switch. (Senses pressure at air inlet side of filters)
To adjust the switch, the unit must be running with
all of the access doors in place, except for the
compartment where the switch is located (exhaust
intake compartment). The adjusting screw is located on
the top of the switch.
1. Open the filter compartment and place a sheet of
plastic or cardboard over 50% of the filter media.
2. Replace the filter compartment door.
3. Check to see if there is power at the alert signal
leads (refer to electrical diagram).
4. Whether there is power or not, turn the adjustment
screw on the dirty filter gauge (clockwise if you did
not have power, counter-clockwise if you did have
power) until the power comes on or just before the
power goes off.
5. Open the filter compartment and remove the
obstructing material.
6. Replace the door and check to make sure that you
do not have power at the alert signal leads.
The unit is now ready for operation.
Energy Core Ventilator
15
Page 16
Optional Economizer
Relevant Set Points
1. MAT SET The outdoor air temperature set point
after the energy core. The control will open/close
the bypass damper to maintain temperature as
best as it can. (Set point menu, default 53°F )
2. LOW T LOCK The set point for the low
temperature mechanical cooling lockout. (Set
point menu, default 32°F)
3. DRYBLB SET The outdoor air set point to call for
economizer. (Set point menu, default 63°F)
4. AUX1 O The controllers operating sequence
structure. (Set point menu, default ‘None’)
5. ERV OAT SP The set point for low temperature
economizer lockout. This is the low temperature
set point when AUX1 O is set to ERV. (Set point
menu, default 40°F)
Using the Keypad with Settings and Parameters
To use the keypad when working with Set points,
System and Advanced Settings, Checkout tests, and
Alarms:
1. Navigate to the desired menu.
2. Press
currently displayed menu.
3. Use the and buttons to scroll to the desired
parameter.
4. Press
currently displayed item.
5. Press the button to increase (change) the
displayed parameter value.*
6. Press the
displayed parameter value.
7. Press (enter) to accept the displayed value and
store it in non-volatile RAM.
8. CHANGE STORED displays.
9. Press
parameter.
10. Press
parameter.
*
When values are displayed, pressing and holding
the
automatically increment.
(enter) to display the first item in the
(enter) to display the value of the
button to increase (change) the
*
(enter) to return the current menu
(escape) to return to the current menu
or button causes the display to
Optional Frost Control
Timed Exhaust
1. Remove power from unit.
2. Jumper the temperature indicating sensor in the
unit control center. Thermostat controller has a
pre-set temperature of 32ºF.
3. Set the frost control timer scale for T1 and T2 to
5m. Set the timer settings for T1 and T2 to 30.
4. Add power to the unit. Blower should cycle on for
30 minutes, then turn off for 5 minutes.
5. Remove power from unit and
remove jumpers that were
placed. Re-set timer settings.
• T1 timer setting set to 5 and
timer scale set to 10m for 5
minutes of blower off time.
• T2 timer setting set to 5 and
timer scale set to 1h for 30
minutes of blower on time.
Timer
Scale
Timer
Settings
Timer
Scale
T1
T2
Energy Core Ventilator
16
Page 17
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit
to OFF at disconnect switch(es). Unit may have
multiple power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Once the unit has been put into operation, a routine
maintenance program should be set up to preserve
reliability and performance. Items to be included in
this program are:
Lubrication
Apply lubrication where required
Dampers
Check for unobstructed operation
Fan Belts
Check for wear, tension, alignment
Motors
Check for cleanliness
Blower Wheel & Fasteners
Check for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion, wear
Bearings
Check for cleanliness
Check set screws for tightness
Lubricate as required
External Filter
Check for cleanliness - clean if required
Internal Filter
Check for cleanliness - replace if required
Door Seal
Check if intact and pliable
Maintenance Procedures:
Lubrication
Check all moving components for proper lubrication.
Apply lubrication where required. Any components
showing excessive wear should be replaced to
maintain the integrity of the unit and ensure proper
operation.
Dampers
Check all dampers to ensure they open and close
properly and without binding. Backdraft dampers can
be checked by hand to determine if blades open and
close freely. Apply power to motorized dampers to
ensure the actuator opens and closes the damper as
designed.
Fan Motors
Motor maintenance is generally limited to cleaning
and lubrication. Cleaning should be limited to exterior
surfaces only. Removing dust and grease buildup
on the motor housing assists proper motor cooling.
Never wash-down motor with high pressure spray.
Greasing of motors is only intended when fittings are
provided. Many fractional motors are permanently
lubricated for life and require no further lubrication.
Fan Wheel & Fasteners
Wheels require very little attention when moving clean
air. Occasionally oil and dust may accumulate on the
wheel causing imbalance. When this occurs the wheel
and housing should be cleaned to assure smooth and
safe operation. Inspect fan impeller and housing for
fatigue, corrosion or wear.
Routinely check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness. A proper maintenance
program will help preserve the performance and
reliability designed into the fan.
Bearings
Most bearings are permanently lubricated and require
no further lubrication under normal use. Normal use
being considered -20ºF to 120ºF and in a relatively
clean environment. Some bearings are relubricatable
and will need to be regreased depending on fan use.
Check your bearings for grease zerk fittings to find
out what type of bearing you have. If your fan is not
being operated under normal use, bearings should be
checked monthly for lubrication.
Energy Core Ventilator
17
Page 18
External Filter Maintenance
Aluminum mesh, 2-inch deep filters are located in the
supply weatherhood (if the weatherhood option was
purchased). Filters should be checked and cleaned
on a regular basis for best efficiency. The frequency
of cleaning depends upon the cleanliness of the
incoming air. These filters should be cleaned prior to
start-up.
Clean filters by rinsing with a mild detergent in warm
water.
Internal Filter Maintenance
The units will typically be provided with 2-inch,
pleated filters in the outdoor air and exhaust
airstreams. These filters should be checked per
a routine maintenance schedule and replaced as
necessary to ensure proper airflow through the
unit. See table for pleated filter size and quantity
for each unit. Replacement filters shall be of same
performance and quality as factory installed filters.
Filter type must be pleated design with integral metal
grid. Two acceptable filter replacements are Aerostar
Series 400 or Farr 30/30
Pleated Filter Size and Quantities
Unit SizeSize
ECV-1020 x 2511
All dimensions in inches.
Outdoor Air Filters: Access to the outdoor air filters
is through the door labeled as “Filter Access” on the
sides of the unit.
Exhaust Air Filters: Access to the exhaust air filters
is through the door labeled as “Filter Access” on the
sides of the unit.
Refer to Access Panel Location section for additional
information on filter locations.
®
.
Supply
Qty.
Exhaust
Qty.
Energy Recovery Core
Annual inspection of the energy recovery core is
recommended. Units ventilating smoking lounges and
other nonclean air spaces should have energy recovery
core inspections more often based upon needs.
Accessing the energy recovery core - Disconnect
the power to the ECV. Remove access panel.
Removing the energy recovery core - Once the
energy core access doors are removed, the core can be
pulled from the housing. To replace the core, reverse the
procedure.
Recommended cleaning procedure - First, remove
the energy recovery core by following the instructions
on this page.
Once the core is removed, gently vacuum the surfaces
of the core to remove the dirt and debris that has
accumulated.
Frequency of cleaning - A regular cleaning cycle
must be established for the energy recovery core in
order to maintain optimum sensible and latent energy
transfer. In reasonably clean environments such as
schools, offices or retail stores, the energy recovery
core should be inspected annually and cleaned as
needed.
WARNING
Do not wash, soak in water or use detergents and
cleaners on the core. This will result in a damaged
core.
Failure to follow a regular cleaning cycle for the energy
recovery core can result in significant energy transfer
performance losses.
Door Seal Maintenance
A bulb seal is installed on the perimeter of the door
frame. Inspect at least annually to ensure that the seal
is still intact.
Energy Core Ventilator
18
Page 19
Troubleshooting - Economizer
Alarms
Addressing Alarms
Alarms will signify a faulty sensor. When this occurs,
verify all connections to the sensor and controller are
secure. Press enter twice to clear the alarm. If the
issue persists, consult the factory.
Clearing Alarms
Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the
3. ERASE? displays.
4. Press (enter).
5. ALARM ERASED displays.
6. Press
return to the previous menu.
If an alarm still exists after you clear it, it redisplays
within 5 seconds.
(enter).
(escape) to complete the action and
NOTE
Energy Core Ventilator
19
Page 20
Troubleshooting – Airflow
Test and Balance Report
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,
prior to contacting the factory, please determine the following information:
Unit #1Unit #2Unit #3Unit #4
Model Number
Serial Number
Nameplate Information
Voltage
Hertz
Phase
Outdoor Air Fan Amps
Exhaust Fan Amps
Outdoor Air Fan Horsepower
Exhaust Fan Horsepower
Design Airflow
Outdoor Air
Exhaust
Measured Airflow
Outdoor Air
Exhaust
Measured Data
Blower Rotation
Outdoor Air Fan RPM
Exhaust Fan RPM
Outdoor Air Fan Amp Draw
Exhaust Fan Amp Draw
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in
accordance with SMACNA and AMCA guidelines.
Energy Core Ventilator
20
Page 21
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
Blown fuse or open circuit breaker.
Defective motor or capacitor.Replace.
Replace fuse or reset circuit breaker and check
amps.
Blower fails to
operate
Motor starters
“chatter” or
do not pull in
Motor over amps
Motor starter overloaded.Reset starter and check amps.
Electrical.
Drive.
Control power (24 VAC) wiring run is too long
(resistance should not exceed 0.75 ohms).
Incoming supply power is less than anticipated.
Voltage supplied to starter coil must be within
+10% / -15% of nominal voltage stated on the coil.
CFM too high.Check cfm and adjust drives if needed.
Static pressures are higher or lower than
design.
Blower rotation is incorrect.Check rotation and reverse if necessary.
Motor voltage incorrect.
Motor horsepower too low.
Shorted windings in motor.Replace motor.
Check for On/Off switches. Check for correct
supply voltage.
Check for broken or loose belts. Tighten loose
pulleys.
Shorten wiring run to mechanical room or
install a relay which will turn unit on/off. Consult
factory for relay information.
Need to increase supply power or use a special
control transformer which is sized for the actual
supply power.
If higher, ductwork should be improved.
If lower, fan rpm should be lower.
Check motor nameplate versus supplied
voltage.
See specifications and catalog for fan curves to
determine if horsepower is sufficient.
Low airflow (cfm)
High airflow (cfm)
Unit damper not fully open.Adjust damper linkage or replace damper motor.
System static pressure too high.
Blower speed too low.
Fan wheels are operating backwards.
Dirty filter or energy core.
Leaks in ductwork.Repair.
Elbows or other obstructions may be
obstructing fan outlet.
Improve ductwork to eliminate losses using
good duct practices.
Check for correct drives and rpm with catalog
data.
For 3-phase, see Direction of Fan Wheel
Rotation under Unit Start-Up section.
Follow cleaning procedures in Routine
Maintenance section.
Correct or improve ductwork.
Check for correct fan rpm. Decrease fan speed
if necessary.
Induce Ps into system ductwork. Make sure
grilles and access doors are installed. Decrease
fan speed if necessary.
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Energy Core Ventilator
21
Page 22
Troubleshooting – Unit
SymptomPossible CauseCorrective Action
One or both
blowers turn off
intermittently and
back on after
about 2 minutes
Frost control sensors are tripping.
Adjust frost temperature sensor set point as
needed.
Fan wheel rubbing on inlet.
Bearings.
Excessive noise
or vibration
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or
service information.
Motor base or blower loose.Tighten mounting bolts.
Bearing and drive misaligned.Realign.
Noise being transmitted by duct.
Adjust wheel and/or inlet cone. Tighten wheel
hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate
bearings. Tighten collars and fasteners.
Make sure ductwork is supported properly.
Make sure ductwork metal thickness is sized for
proper stiffness. Check duct size at discharge to
ensure that air velocities are not too high.
Energy Core Ventilator
22
Page 23
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Energy Core Ventilator
23
Page 24
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck catalog, Energy Core Ventilators, Model MiniCore
and ECV, provides additional information describing the
equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.