Greenheck ECV Maintenance Manual

Document 480955
Model ECV
®
Energy Core Ventilator
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Energy Recovery Technical Support
Call 1-800-240-0870
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before movingforward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplateamps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with theequipment.
7. Never open access doors to the unit while it isrunning.
®
Energy Core Ventilator 1
®
Table of Contents
Unit Overview
Unit Overview . . . . . . . . . . . . . . . . . . . . . 2
Receiving, Handling and Storage . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Information. . . . . . . . . . . . . . . . . . 9
Optional Component Overview . . . . . . . . . . . .12
Start-Up . . . . . . . . . . . . . . . . . . . . . . . .13
Start-Up Components . . . . . . . . . . . . . . . . .15
Optional Start-Up Components . . . . . . . . . . . .16
Routine Maintenance . . . . . . . . . . . . . . . . .20
Troubleshooting . . . . . . . . . . . . . . . . . . . .21
Our Commitment. . . . . . . . . . . . . . . Backcover
Basic Unit
The unit is prewired such that when a call for outside air is made (via field-supplied 24 VAC control signal wired to unit control center), the supply and exhaust fans are energized and optional motorized dampers open. The unit is normally interlocked (24 volt) to the rooftop air handler. When the rooftop air handler starts, the auxiliary contactor in the air handler closes to start the unit.
Summer Operation
Outdoor air is preconditioned (temperature and moisture levels are decreased) by the transfer of energy from the cooler, drier return air through the energy recovery core. The preconditioned air is typically mixed with return air going back to the air handler for final conditioning.
Outdoor Air
95°F
Exhaust Air
125 grains/lb.
Return Air
75°F
50% RH
Supply Air
82°F
99 grains/lb.
Summer Operation
Winter Operation
Outdoor air is preconditioned (temperature and moisture levels are increased) by the transfer of energy from the warmer, more humid return air through the energy recovery core. The preconditioned air is typically mixed with return air going back to the air handler for final conditioning.
Outdoor Air
-13°F
Exhaust Air
1 grains/lb.
Return Air
72 °F
Supply Air
40°F
20 grains/lb.
Winter Operation
Energy Core Ventilator2
50% RH
Receiving
This product may have been subject to road salt during transit. If so, immediately wash off all visible white reside from all exterior surfaces. Upon receiving the product, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier if any damage is detected, do not refuse shipment. The customer shall make notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading should be countersigned by the delivering carrier. If damaged, immediately contact your manufacturer’s representative. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. Inspect interior of unit cabinet for any shipped loose items. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Units designed for outdoor applications may be stored outdoors. All accessories must be stored indoors in a clean, dry atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation. Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid condensation, allow cold parts to reach room temperature. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor. Clearance should be provided to permit air circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated so that it is above water and snow levels. Ensure sufficient support to prevent unit from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive, WD-40® or the equivalent.
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the equipment goes into operation.
Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.
®
Energy Core Ventilator 3
®
Installation
RETURN AIR INTAKE
AIR INTAKE
RETURN AIR INTAKE
Outdoor Mounting Options
EXHAUST AIR DISCHARGE
SUPPLY AIR DISCHARGE
F
(NON ELECTRICAL SIDE)
A
Outdoor Air Discharge Bottom
Indoor Mounting Options
EXHAUST AIR DISCHARGE
E
E
SUPPLY AIR DISCHARGE
(NON ELECTRICAL SIDE)
A
EXHAUST AIR DISCHARGE
C
SUPPLY AIR DISCHARGE
G
B
RETURN AIR INTAKE
OUTDOOR
E
(NON ELECTRICAL SIDE)
A
C
G
B
OUTDOOR AIR INTAKE
RETURN AIR INTAKE
Outdoor Air Discharge End
EXHAUST AIR DISCHARGE
D
D
B
OUTDOOR AIR INLET
C
RETURN AIR INLET
SUPPLY AIR DISCHARGE
E
F
(NON ELECTRICAL SIDE)
A
G
OUTDOOR AIR INTAKE
D
C
B
Top and Bottom ConnectionsTop and End Connections
EXHAUST AIR DISCHARGE
SUPPLY AIR DISCHARGE
E
E
(NON ELECTRICAL SIDE)
A
D
D
B
OUTDOOR AIR INTAKE
C
Intake and Discharge Options
Bottom Top Side End
OA Intake X X
SA Discharge X X
RA Intake X X
EA Discharge X X
End Connections
Dimensional Data and Weights
Unit Size
ECV-10 54.8 28.9 43.9 18.4 x 15.9 13.6 x 13.6 8.5 x 11.6 10.3 x 15.2 485
ECV-20 60 43.8 44.9 30.5 x 16 24.5 x 16 23.4 x 14 28 x 13.5 813
ECV-30 60 61.3 44.9 50 x 16 44 x 16 38.1 x 14.5 47.5 x 13.5 1075
ECV-40 60 81 44.9 69.3 x 16 52 x 16 52 x 14.5 66.7 x 13.5 1279
All dimensions are in inches. *Weight assumes outdoor unit with filters, weatherhoods, outdoor air intake damper, controls and internal double-wall sheet metal.
Energy Core Ventilator4
Exterior Dimensions Unit Connection Dimensions
A B C D E F G
Approx. Weight*
(lbs.)
Installation
Service Clearances
The ECV unit requires minimum clearances to perform routine maintenance, such as filter replacement and energy core inspection. Blower and motor assemblies, energy recovery core and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the
service clearances, refer to drawing below for these dimensions.
NON ELECTRICAL SIDE
BLOWER CABINET
CORE(S)
Electrical Side Non-Electrical Side Intake End Discharge End
Unit Size
Recommended Minimum Recommended Minimum
ECV-10 ECV-20 ECV-30
36 26 36
ECV-40
All dimensions are in inches.
INTAKE
END
BYPASS DAMPER
(OPTIONAL)
CONTROL
PANEL
ELECTRICAL SIDE
ECV Service Clearance Requirements
Weatherhood
Yes
No Access
Required
33
DISCHARGE
END
Weatherhood NoWeatherhood
Yes
No Access
Required
24
Weatherhood
No
No Access
Required
Electrical Side Non-Electrical Side Intake End Discharge End
Unit Size
Recommended Minimum Recommended Minimum
ECV-10
ECV-20
ECV-30
30
ECV-40
All dimensions are in inches.
®
20
20
(25 with
bypass
damper)
ECV Service Clearance Requirements
Weatherhood
30
No Access
Required
Yes
33
Weatherhood NoWeatherhood
Yes
No Access
Required
24
Energy Core Ventilator 5
Weatherhood
No
No Access
Required
®
2
1
Installation
Access Panel Locations
The ECV is provided with access panels on both sides of the unit. The non electrical side can be placed against a wall. Clearance to the electrical side is essential to provide access to the control center and component maintenance.
1 Control Center
Core, filters, inlet
2
dampers, bypass dampers, blowers
3 Blowers
1
2
Electrical Side Non Electrical Side
Handling
While this unit was constructed with quality and dependability in mind, damage still may occur during handling of the unit for installation.
The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook. Adequate space should be left around the unit for filter replacement and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.
Lifting
WARNING
All factory provided lifting lugs must be used when lifting the unit. Failure to comply with this safety precaution could result in property damage, serious injury or death.
1. Before lifting, be sure that all shipping material has been removed from unit.
2. To assist in determining rigging requirements, weights are shown under the Dimensional Data and Weights section.
3. Unit must be lifted by all lifting lugs provided on base structure.
4. Rigger to use suitable mating hardware to attach to unit lifting lugs.
5. Spreader bar(s) must span the unit to prevent damage to the cabinet by the lift cables.
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
2
3
7. Never lift units by weatherhoods.
8. Never lift units in windy conditions.
9. Preparation of curb and roof openings should be completed prior to lifting unit to the roof.
10. Check to be sure that gasketing (supplied by others) has been applied to the curb prior to lifting the unit and setting on curb.
11. Do not use fork lifts for handling unit.
Energy Core Ventilator6
Installation
Roof Curb Mounting
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
1. Factory Supplied Roof Curbs: Roof curbs are Model GKD. The GKD ships in a knockdown kit (includes duct adapter) and requires field assembly (by others). Assembly instructions are included.
2. Install Curb: Locate curb over roof opening and fasten in place. (Refer to Recommended Roof Openings). Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper unit operation, it is important that the installation be level. Shim as required to level.
3. Install Ductwork: Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
4. Set the Unit: Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.
5. Fasten the Unit: Fasten the unit to the curb/ equipment support(s) using appropriate methods. The installer is responsible for determining appropriate support and fastening methods to ensure compliance with all applicable codes.
Curb Outside Dimensions and Weights
D
C
A
B
Unit Size
ECV-10 52.3 26.4 16.5 x 11.5 8.5 x 11.6 60
ECV-20 55.8 39.8 28 x 13.5 25.2 x 15.6 79
ECV-30 55.8 57.7 47.5 x 13.5 42.7 x 15.6 95
ECV-40 55.8 76.8 66.7 x 13.5 54 x 15.6 110
All dimensions are in inches. Weight is for 14-inch high model GKD curbs.
A B C D
Curb
Weight
(lbs.)
Side of Unit
A
B
C
D
E
Roof Curb
Curb Cap Details for Factory-Supplied Roof Curbs
Unit Size A B C D E
ECV-10 1.9 5.3 4.3 0.8 0.4
ECV-20 1.9 6.8 5.8 1.6 0.4
ECV-30 1.9 6.8 5.8 1.6 0.4
ECV-40 1.9 6.8 5.8 1.6 0.4
All dimensions are in inches.
Base
1-inch Insulation
®
Energy Core Ventilator 7
®
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Tu rning
Vanes
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
GOODPOOR
Tu rning
Vanes
Installation
Ductwork Connections
Examples of poor and good fan-to-duct connections are shown. Airflow out of the fan should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result in low airflow and other system effects.
n
o
i
t
a
t
o
R
Recommended Discharge Duct Size and Length
Unit
Size
ECV-10 14 x 14 4
ECV-20 24.5 x 16 6
ECV-30 44 x 16 6
ECV-40 52 x 16 6
• Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.
• Straight duct lengths were calculated based on 100% effective duct length requirements as prescribed in AMCA Publication 201. Calculated values have been rounded up to nearest foot.
Length of Straight Duct
GOOD
Duct Size
(in.)
Straight Duct
Length
(ft.)
Rail Mounting / Layout
• Rails designed to handle the weight of the unit should be positioned as shown on the diagram (rails by others).
• Make sure that rail positioning does not interfere with the supply air discharge opening or the exhaust air intake opening on the unit. Avoid area dimensioned “B” below.
• Rails should extend beyond the unit a minimum of 12 inches on each side.
A
B
Unit Size A B
ECV-10 4.2 11.5
ECV-20 3.1 18.5
ECV-30 3.1 18.5
ECV-40 3.1 18.5
All dimensions are in inches.
Energy Core Ventilator8
Loading...
+ 16 hidden pages