Greenheck EAD-401 Installation Manual

Adjustable Louver
Drainable Blade
Application and Design
EAD-401 is an adjustable louver designed to protect air intake and exhaust openings in building exterior walls that require tight air shut off. Design incorporates a drainable head member and adjustable drainable blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The EAD-401 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.125 in. nominal wall thickness
Blades . . . . . . . .Drainable design, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 45º angles on approximately 4 in. centers
Seals . . . . . . . . .Dual-durometer extruded vinyl blade seals
Compressible stainless steel jamb seals
Temperature
Restrictions . . . .(-20º F) - (+180ºF)
Linkage . . . . . . .Side linkage, out of airstream (concealed in frame)
Bearings . . . . . .Synthetic sleeve type
Axles . . . . . . . . .½ in. dia. zinc plated steel
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . .Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single Section Size . . . 60 in. W x 96 in. H
Options (at additional cost)
• A variety of bird and insect screens
• A variety of electric, pneumatic or manual actuators
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
EAD-401
*Width and height dimensions furnished
approximately ¼ inch under size.
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
400
Free Area Chart (Sq. ft.)
Louver Height Inches
12 15 18 21 24 27 30 33 36 39 42 48 54 60
12 0.19 0.26 0.32 0.38 0.44 0.50 0.56 0.62 0.68 0.75 0.81 0.93 1.05 1.17
15 0.34 0.45 0.56 0.66 0.77 0.88 0.99 1.09 1.20 1.31 1.42 1.63 1.85 2.06
21 0.49 0.64 0.79 0.95 1.10 1.26 1.41 1.56 1.72 1.87 2.02 2.33 2.64 2.95
24 0.63 0.83 1.03 1.23 1.43 1.63 1.83 2.03 2.23 2.43 2.63 3.03 3.43 3.83
30 0.78 1.03 1.27 1.52 1.76 2.01 2.26 2.50 2.75 3.00 3.24 3.74 4.23 4.72
33 0.93 1.22 1.51 1.80 2.10 2.39 2.68 2.97 3.27 3.56 3.85 4.44 5.02 5.61
39 1.07 1.41 1.75 2.09 2.43 2.77 3.11 3.44 3.78 4.12 4.46 5.14 5.82 6.49
42 1.22 1.60 1.99 2.37 2.76 3.14 3.53 3.91 4.30 4.68 5.07 5.84 6.61 7.38
48 1.37 1.80 2.23 2.66 3.09 3.52 3.95 4.38 4.82 5.25 5.68 6.54 7.40 8.27
51 1.51 1.99 2.47 2.94 3.42 3.90 4.38 4.85 5.33 5.81 6.29 7.24 8.20 9.15
60 1.81 2.38 2.95 3.52 4.09 4.66 5.23 5.80 6.37 6.94 7.51 8.65 9.79 10.93
66 1.95 2.57 3.18 3.80 4.42 5.03 5.65 6.27 6.88 7.50 8.11 9.35 10.58 11.81
78 2.39 3.15 3.90 4.66 5.41 6.17 6.92 7.68 8.43 9.19 9.94 11.45 14.47 14.47
84 2.54 3.34 4.14 4.94 5.74 6.54 7.34 8.15 8.95 9.75 10.55 12.15 15.36 15.36
96 2.98 3.92 4.86 5.80 6.74 7.68 8.62 9.56 10.50 11.44 12.38 14.26 18.02 18.02
Greenheck Fan Corporation certifies that the EAD­401 louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies
®
to air performance and water penetration ratings.
Louver Width in Inches
Water Penetration (Standard Air - .075 lb/ft
Test size 48 in. x 48 in. Test duration of 15 min.
Adjustable Louver Drainable Blade
Extruded Aluminum
Air Leakage
(with damper section closed)
Test size 48 in. x 48 in.
kPa
in. wg
2
0.475
0.45
0.425 1
0.9
0.4
0.8
0.7
0.375
0.6
0.35
0.5
0.4
0.325
Pressure
0.3
0.3
0.2
0.275
0.25
0.1
0.225
0.09
2
112345678910
cfm/ft
2
cmh/m
20 30 40 50 60 70 80 90 100 200
Leakage
EAD-401PERFORMANCE DATA
3
)
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
Test Size 48 in. x 48 in.
Standard Air - .075 lb/ft
200 300
3
Intake
Exhaust
400 500 600 700 800 900 1000 2000 3000
2345678910
200
100
90 80
70
60
50
40
30
20
Static Pressure Drop
10
9 8
7
6
5
ft/min:
m/s:
3
)
Free Air Velocity
Model EAD-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
800 850 900 950 1000 1050 1100
4.0
3
5.0
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model EAD-401 is 920 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.