Greenheck EACN-601 Installation Manual

Combination Louver/Damper
Non-Drainable Blade
Application and Design
EACN-601 is a combination louver/damper designed to protect air intake and exhaust openings in building exterior walls that, at times, require tight air shut off. Design incorporates a drainable head member, J style stationary blades and operable blades. When the operable blades are open, airflow is permitted through the louver, when the blades are closed, a tight seal is created to prevent the passage of air. The EACN-601 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
6 in. x 0.125 in. nominal wall thickness
Blades . . . . . . . .Stationary blade: J style design, heavy gauge
extruded 6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 45º angles on approximately 6 in. centers Operable blade: heavy gauge extruded 6063-T5 aluminum, 0.081 nominal wall thickness
Seals . . . . . . . . .Dual-durometer extruded vinyl blade seals
Compressible stainless steel jamb seals
Temperature
Restrictions . . . .(-20º F) - (+180ºF)
Linkage . . . . . . .Side linkage out of airstream (concealed in frame)
Bearings . . . . . .Synthetic sleeve type
Axles . . . . . . . . .½ in. dia. zinc plated steel
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . .Mill
Minimum Size . . 12 in. W x 16 in. H
Maximum Single Section Size . . . 60 in. W x 96 in. H
EACN-601
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• A variety of electric, pneumatic or manual actuators
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Hinged frame
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height Inches
12 15 18 21 24 27 30 33 36 39 42 48 54 60
16 0.24 0.32 0.40 0.48 0.56 0.64 0.72 0.80 0.88 0.96 1.04 1.20 1.36 1.52
21 0.49 0.64 0.80 0.96 1.12 1.28 1.44 1.60 1.76 1.92 2.08 2.40 2.72 3.04
24 0.49 0.64 0.80 0.96 1.12 1.28 1.44 1.60 1.76 1.92 2.08 2.40 2.72 3.04
30 0.73 0.97 1.20 1.44 1.68 1.92 2.16 2.40 2.64 2.88 3.12 3.59 4.07 4.55
33 0.93 1.23 1.54 1.84 2.15 2.45 2.76 3.06 3.37 3.67 3.98 4.59 5.20 5.81
39 0.97 1.29 1.61 1.92 2.24 2.56 2.88 3.20 3.52 3.83 4.15 4.79 5.43 6.06
42 1.21 1.61 2.01 2.40 2.80 3.20 3.60 3.99 4.39 4.79 5.19 5.98 6.78 7.57
48 1.45 1.93 2.41 2.88 3.36 3.84 4.31 4.79 5.27 5.75 6.22 7.18 8.13 9.09
51 1.45 1.93 2.41 2.88 3.36 3.84 4.31 4.79 5.27 5.75 6.22 7.18 8.13 9.09
60 1.93 2.57 3.21 3.84 4.48 5.12 5.75 6.39 7.02 7.66 8.30 9.57 10.84 12.11
66 2.17 2.88 3.59 4.31 5.02 5.73 6.44 7.16 7.87 8.58 9.29 10.72 12.15 13.57
78 2.42 3.21 4.01 4.80 5.60 6.39 7.19 7.98 8.78 9.57 10.37 11.96 13.55 15.14
84 2.66 3.53 4.41 5.28 6.16 7.03 7.91 8.78 9.65 10.53 11.40 13.15 14.90 16.65
96 3.14 4.18 5.21 6.24 7.28 8.31 9.34 10.38 11.41 12.44 13.47 15.54 17.61 19.67
Louver Width in Inches
Combination Louver/Damper
Air Leakage
(with damper section closed)
Test size 48 in. x 48 in.
kPa
in. wg
2
0.475
0.45
0.425
0.375
0.325
Pressure
0.275
1
0.9
0.4
0.8
0.7
0.6
0.35
0.5
0.4
0.3
0.3
0.2
EACN-601PERFORMANCE DATA
Extruded Aluminum
Greenheck Fan Corporation certifies that the EACN-601 louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are
WATER
PENETRATION
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
based on tests and procedures performed in
AIR
accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified
®
Ratings Seal applies to air performance and water penetration ratings.
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90 80
70
60
50
40
30
20
Static Pressure Drop
10
9 8
7
6
5
ft/min:
m/s:
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
3
)
Model EACN-601 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
0.25
0.1
0.225
0.09
2
112345678910
cfm/ft
2
cmh/m
20 30 40 50 60 70 80 90 100 200
Water Penetration (Standard Air - .075 lb/ft
Leakage
3
)
Test size 48 in. x 48 in. Test duration of 15 min.
0.30
Test Size 48 in. x 48 in.
0.25
Test Period 15 minutes
Standard Air - .075 lb/ft
3
0.20
0.15
0.10
0.05
Water Penetration per Unit Free Area
0.00
1100 1150 1200 1250 1300
ft/min:
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
water penetration for Model EACN-601 is 1193 fpm free area
The beginning point of
*
velocity. These perfor mance ratings do not guarantee a louver to be
weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.