Greenheck EACC-401 User Manual

Combination Louver/Damper
Concealed Actuator
Application and Design
EACC-401 is a combination louver/damper designed to protect air intake and exhaust openings in building exterior walls that, at times, require tight air shut off. Design incorporates a drainable head member, drainable stationary blades, operable blades and a concealed actuator within the louver sill. When the operable blades are open, airflow is permitted through the louver, when the blades are closed, a tight seal is created to prevent the passage of air.
Frame � � � � � � � �Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.125 in. nominal wall thickness
Blades � � � � � � � �Stationary blade: drainable design, heavy gauge
extruded 6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 45º angles on approximately 4 in. centers Operable blade: heavy gauge extruded 6063-T5 aluminum, 0.081 nominal wall thickness
Seals . . . . . . . . .Dual-durometer extruded vinyl blade seals
Compressible stainless steel jamb seals
Temperature
Restrictions . . . .(-20º F) - (+180ºF)
Linkage . . . . . . .Side linkage, out of airstream (concealed in frame)
Bearings . . . . . .Synthetic sleeve type
Axles . . . . . . . . .½ in. dia. zinc plated steel
Actuator . . . . . .Invensys MA series, 2 position spring return
Construction . . .Mechanically fastened
Birdscreen � � � � �3/4 in. x 0.051 in. flattened expanded aluminum in
removable frame, inside mount (rear)
Finish � � � � � � � � �Mill
Minimum Size � �18 in. W x 20 in. H
Maximum Single Section Size � � � 60 in. W or 96 in. H
EACC-401
Options (at additional cost)
• A variety of bird and insect screens
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including:
Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
1100 1150 1200 1250 1300
0.00
0.05
0.10
0.15
0.20
0.25
0.30
Test Size 48 in. x 48 in.
Test Period 15 minutes
Standard Air - .075 lb/ft
3
ml/m2
m/s:
ft/min:
oz/ft2
5.5 6.0 6.5
0
20
40
60
80
Water Penetration per Unit Free Area
Free Area Velocity
Free Area Chart (Sq. ft.)
Louver Height Inches
18 21 23 26 29 32 35 38 41 44 48 51 54 57 60
20 0.21 0.25 0.28 0.32 0.36 0.40 0.45 0.49 0.53 0.57 0.63 0.67 0.71 0.75 0.79
24 0.45 0.54 0.60 0.69 0.77 0.86 0.95 1.04 1.13 1.22 1.33 1.42 1.51 1.60 1.69
28 0.69 0.82 0.91 1.05 1.19 1.32 1.46 1.59 1.73 1.86 2.04 2.18 2.31 2.45 2.59
32 0.93 1.11 1.23 1.41 1.60 1.78 1.96 2.14 2.33 2.51 2.75 2.94 3.12 3.30 3.48
36 1.17 1.40 1.55 1.78 2.01 2.24 2.47 2.70 2.93 3.16 3.46 3.69 3.92 4.15 4.38
40 1.41 1.68 1.87 2.14 2.42 2.70 2.97 3.25 3.53 3.80 4.17 4.45 4.72 5.00 5.28
44 1.64 1.96 2.17 2.50 2.82 3.14 3.46 3.78 4.11 4.43 4.86 5.18 5.50 5.82 6.14
48 1.82 2.18 2.42 2.78 3.14 3.50 3.86 4.21 4.57 4.93 5.41 5.77 6.13 6.49 6.84
52 1.88 2.25 2.50 2.87 3.24 3.61 3.98 4.35 4.73 5.10 5.59 5.96 6.33 6.70 7.07
56 2.12 2.54 2.82 3.24 3.65 4.07 4.49 4.91 5.32 5.74 6.30 6.72 7.13 7.55 7.97
60 2.36 2.83 3.14 3.60 4.07 4.53 4.99 5.46 5.92 6.39 7.01 7.47 7.94 8.40 8.87
64 2.60 3.11 3.45 3.97 4.48 4.99 5.50 6.01 6.52 7.04 7.72 8.23 8.74 9.25 9.76
68 2.84 3.40 3.77 4.33 4.89 5.45 6.01 6.56 7.12 7.68 8.43 8.99 9.54 10.10 10.66
72 3.08 3.68 4.09 4.69 5.30 5.91 6.51 7.12 7.72 8.33 9.14 9.74 10.35 10.95 11.56
76 3.32 3.97 4.41 5.06 5.71 6.36 7.02 7.67 8.32 8.97 9.84 10.50 11.15 11.80 12.46
80 3.55 4.25 4.71 5.41 6.11 6.81 7.50 8.20 8.90 9.60 10.53 11.23 11.93 12.62 13.32
84 3.74 4.47 4.96 5.69 6.43 7.16 7.90 8.63 9.37 10.10 11.08 11.82 12.55 13.29 14.02
88 3.80 4.54 5.04 5.79 6.53 7.28 8.03 8.77 9.52 10.27 11.26 12.01 12.76 13.50 14.25
92 4.03 4.83 5.36 6.15 6.95 7.74 8.53 9.33 10.12 10.91 11.97 12.77 13.56 14.35 15.15
96 4.27 5.11 5.68 6.52 7.36 8.20 9.04 9.88 10.72 11.56 12.68 13.52 14.36 15.20 16.04
Airflow Resistance (Standard Air - �075 lb/ft
Pa
in. wg
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
200 300
Test Size 48 in. x 48 in.
Standard Air - .075 lb/ft
3
Exhaust
400
500 600 700800 900 1000 2000 3000
2345678910
Free Air Velocity
200
100
90 80
70
60
50
40
30
0.09
20
0.08
0.07
Static Pressure Drop
Model EACC-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air
0.06
0.05
10
0.04
9 8
0.03
7
6
5
0.02
ft/min:
m/s:
exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Louver Width Inches
Intake
3
) Water Penetration (Standard Air - �075 lb/ft3)
Test size 48 in. x 48 in. Test duration of 15 min.
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of
water penetration for Model EACC-401 is 1192 fpm free area velocityThese perfor mance ratings do not guarantee a louver to be
weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
EACC-401PERFORMANCE DATA
Combination Louver/Damper
Extruded Aluminum
Air Leakage (with damper section closed)
Test size 48 in. x 48 in.
kPa
in. wg
2
0.475
0.45
0.425
0.375
0.325
Pressure
0.275
0.225
1
0.9
0.4
0.8
0.7
0.6
0.35
0.5
0.4
0.3
0.3
0.2
0.25
0.1
0.09
2
112345678910
cfm/ft
2
cmh/m
20 30 40 50 60 70 80 90100 200
Leakage
Loading...
+ 3 hidden pages