Greenheck Duct Smoke Detector none User Manual

Gasket 1 Req’ d
J-Box Cover 1 Req’ d
#10 1/2 in. Te k Scr ew 2 Req’ d
J-Box 1 Req’ d
3
2
4
6
Part Number 459840
Installation Instruction
for RRL (resettable/reusable link) on
FSD, SSFSD, SEFSD, IMO series
Combination Fire Smoke Dampers
Steps to install an RRL in a Fire Smoke Damper:
1) Drill/Saw a 3 5/8 in. (92mm) diameter hole in sleeve (Detail
2).
2) Insert OCI unit through hole in sleeve (round end inside).
3) Place 4 x 4 in. J-Box over the flange of the OCI unit and align holes.
4) Mount control box to sleeve/sideplate with #10-16 x 3/4 in. (19mm) TEK screw (or equivelant) (Detail 1).
5) Complete wiring and install J-Box cover.
Detail 1
D
Ø3.625
>11" NOM HEIGHT
< 11" NOM HEIGHT
8.375
3.563
SURF ACE
INSIDE
Resettable Reusable Link
Electrical Capacity = 10 AMP (max)
Orange
NC
Black
Black White
Optional Momentary Contact Test Switch
P= Primary temperature sensor
Electric Damper Actuator or Pneu. Solenoid Valve
NOM. STEEL 3V SEC. AIRFOIL
STYLE HEIGHT STYLE
6 2.625 2.625
7 2.625 2.625 8 3.125 3.125 9 3.625 3.625 10 2.625 3.625 11 2.625 3.625 12 2.625 4.125 13 2.625 4.125 14 3.125 4.625 15 3.125 4.625 16 3.625 5.125 17 4.125 5.625 18 13.125 13.125 19 14.125 14.125 20 14.625 14.625 21 15.625 15.625 22 16.625 16.625 23 17.125 17.125 24 18.125 18.125 25 19.625 19.625 26 20.625 20.625 27 21.625 21.625 28 22.125 22.125 29 23.125 23.125 30 24.125 24.125 31 25.125 25.125 32 26.625 26.625 33 27.625 27.625 34 28.625 28.625 35 29.125 29.125 36 30.625 30.625 37 31.125 31.125 38 32.125 32.125 39 21.625 21.625 40 21.625 21.625 41 21.625 21.625 42 22.125 22.125 43 23.125 23.125 44 24.125 24.125 45 25.125 25.125 46 28.625 28.625 47 27.625 27.625 48 30.625 30.625 49 29.125 29.125 50 32.125 32.125 51 31.125 31.125 52 32.125 32.125 53 23.625 23.625 54 24.625 24.625 55 25.125 25.125 56 25.125 25.125 57 23.125 23.125 58 24.125 24.125 59 25.125 25.125 60 4.125 4.125
Note: Operator Mounted Upside-Down On Steel Airfoil
Wiring Diagram
Units From 10 in. to 17 in. (254mm to 432mm) High
Detail 2
All dimensions shown in inches.
Copyright © 2008 Greenheck Fan Corporation
459840 RRL IOM Rev. 4 July 2008
Loading...