Greenheck CRD Series Installation Manual

Page 1
Document #481550
Field Instructions for Installing a Volume
®
Controller on CRD Series Dampers
Installation Manual
These instructions apply to the field installation of Volume Controller on CRD series dampers.
Tools Required:
Electric or battery operated drill
Locking C-clamp or spring clamp
3
32 dia. drill bit
#2 Phillips screwdriver
Wire cutter
Instructions
2. Insert the drill guide (Figure 1) between the spring and the damper center bar. Using the notches at the center of the drill guide, align the center of the drill guide with the spring. Open the damper blades to allow the drill guide to settle onto the damper center bar.
Secure the blades in the open position. The blades
can be held open using a clamp or by reinstalling the fusible link. (Figure 2) (Note; If the drill guide does not fit over the damper center bar, the tabs on the guide can be bent outward, equally on both sides, until it fits over the center bar.)
3. Using the two small holes in the drill guide, drill two
3
32 diameter holes through the damper center bar. (Figure 3) Release the damper blades and remove the drill guide.
4. Using a wire cutter, cut off the fusible link wires near the rivet head. They are no longer needed. (Figure 4)
5. Install the volume controller onto the damper center bar using the (2) #10 screws provided. Tighten the screws but be careful not to strip out the screw holes. (Figure 5 & 6)
Note: Do not use longer screws since longer screws will
interfere with the operation of the blades.
Figure 1: Drill Guide Figure 2: Clamping the
blade open
Figure 3: Drilling the holes
using the drill guide
Figure 4: Removing the
fusible link wire
Volume Controller for CRD Series
1
Page 2
6. Manually operate the blades to check for binding or interference.
7. Check that the volume controller lift wires do not interfere with the frame of the damper.
8. Adjust the volume controller to the desired open position.
Figure 5: Volume controller
Figure 6: Volume controller top view
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
481550 Volume Controller for CRD Series IOM Rev. 1 April 2016 Copyright 2016 © Greenheck Fan Corporation