Do you want to start and
stop your fans via a prewired
control package?
No
Field wired or optional
factory mounted switches.
Yes
Do you want the system
to vary the exhaust and
supply rates based on the
cooking load?
No
Do you ONLY require a
temperature interlock
to comply with IMC
507.2.1.1?
No
Do you require factory
prewired options such
as exhaust on in fire,
temperature interlock (IMC
507.2.1.1), etc?
No
Yes
Yes
Yes
Greenheck Vari-Flow System
or Melink Intelli-Hood
System
(Both systems comply with *IMC 507.2.1.1)
Temperature Interlock
Kitchen Fan Control Center
(KFCC)
IMC International Mechanical Code
Do you have:
• More than two fans?
• 3-phase motors?
• The need for thermal
overloads?
No
Relay Box
Yes
Kitchen Fan Control Center
(KFCC)
All Greenheck controls are UL Listed to
Standard 891 or 710 as it applies.
2
3
Greenheck’s relay box is compact, prewired and offers a low-cost method of starting one or several single-
phase fan motors. The relay box can be used in place of larger, more expensive starters.
All
Greenheck Controls
When switches are moved to the on position, lights turn
Relay Box
Standard Construction Features
Requirements:
Limitations:
Temperature Interlock
Standard Construction Features
Volt or 120Volt.
Greenheck Controls
When switches are moved to the on position, motor
Kitchen Fan Control Center (KFCC)
Standard Construction Features
Kitchen Fan Control Center Options
Exhaust on in Fire Mode —
Trim Ring —
Removal of Starter When Supplied in Unit —
Up To 2 Status Lights —
Up To 2 Extra Fire Relays —
Lights Out in Fire —
Supply Fan Failure Indicator Light —
Exhaust Fan Failure Indicator Light —
Single Light/Fan Switch —
Power For Shunt Trip —
Automatic Damper Switch —
Temperature Interlock —
Greenheck Controls
Variable Volume
Greenheck offers variable volume ventilation systems that track the cooking load and vary the exhaust
and supply ventilation based on demand. Since the cooking load varies throughout the day, your exhaust
system doesn’t need to run at the maximum exhaust air volume all day. Greenheck understands that by
varying the speed of the fans based on the cooking load, you will save money by reducing power and
heating and cooling costs. See figures 1 and 2 below.
Standard Construction Features
• The system monitors the cooking operation and adjusts the exhaust and supply unit fans so that when the
cooking load is reduced, the fans operate at a reduced level providing energy savings
• Satisfies International Mechanical Code 507.2.1.1 requirement to start fans when cooking
operationsoccur
• System is prewired, UL Listed and includes wiring diagrams
Payback:
• Typical payback of 1 to 3 years
• Improved efficiency by reducing fan speed
Additional Benefits:
• Ventilation equipment life is extended by soft-starting starting fans, therefore reducing stress on belts
and bearings
• Reduced sound levels to improve customer and employee comfort
The charts below are an example of how the cooking load in a typical restaurant varies
throughout the day and how the variable volume system can generate money savings.
Variable Volume Matches Airflow to Cooking Load
100%
100%
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $$ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
80%
80%
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $
$
$ $ $ $ $
60%
60%
$ $ $ $ $
CFM
40%
40%
20%
20%
0%
0%
Breakfast
Lunch
Dinner
11109876543211211109876
11109876543211211109876
Operating Hours
= Variable Volume
100%
80%
60%
CFM
40%
20%
0%
Constant Volume Design Airflow
Breakfast
Lunch
Dinner
Operating Hours
= Constant Volume
11109876543211211109876
Figure 1 — The cooking load throughout the day varies
significantly. However, the kitchen only requires maximum
ventilation for a small percentage of the day. The shaded
area represents the savings potential for a variable volume
system. The dashed red line is showing fan operation at
100% regardless of cooking load.
Figure 2 — A variable volume system will track the
cooking load (dashed red line) and vary the exhaust
and supply ventilation. The area above the red line
represents energy savings.
5
Greenheck Controls
When as little as seven percent of the optics infrared beam is blocked the exhaust
Greenheck Vari-Flow Air Management System
Standard Construction Features
• ExceptionalValue—
• SpacePressureControl—
• 5TimesQuickerResponse—
• FullyModulatingTurndownupto50%—
Melink Intelli-hood System
Standard Construction Features
HOOD
LIGHTS
FAN
ON/OFF
FAN
100%
SYSTEM
FAULT
472621
• SecondaryOpticSensors—
• ProfessionalStart-upintheField—
• Easily Accommodates Larger Systems —
• FullyModulatingTurndownupto50%—
Greenheck Controls
Which Variable Volume System is best for your application?
Greenheck
System Decision Matrix
Factory Installed System
IMC 507.2.1.1 Compliant
Full Fan Speed Override
Supply Controlled by Space Static Pressure
Supply Controlled ProportionallyOptional
Professional Start-up by Factory Representative
Lower Cost
Secondary Optic Sensors for
smoke and steam
Small to Medium Size Applications
Large or Steam Intensive Applications
Vari-Flow
System
nn
nn
nn
n
n
n
Looking to Decrease the Payback Period?
Melink
Intelli-hood
System
n
n
n
n
Fully
Modulating
Turndown up
to 50%
Many state and local governments offer rebate and credit programs that the Vari-Flow Air Management
System and Melink Intelli-hood system may qualify for. Rebates can decrease the upfront cost of
thesystems.
Going for LEED™ Certification?
The Vari-Flow Air Management System and the Melink Intelli-hood system align with the following
LEEDcredits and may contribute toward earning up to two LEED credits.