Greenheck BIDW, IP, AFDW, LSF Installation, Operation And Maintenance Manual

Page 1
Document 463687
Centrifugal (BIDW, AFDW)
®
Industrial Process (IP)
Filtered Supply (LSF)
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
General Safety Information
Only qualified personnel should install this fan. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving
BIDW, AFDW
IP
forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electric Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free to rotate without striking or rubbing any stationary objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than max cataloged fan rpm. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to a duct while the fan is running.
LSF
DANGER
Always disconnect power before working on or near a fan. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
Centrifugal, Industrial and Filtered Supply 1
Page 2
Receiving
Upon receiving the product check to make sure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The customer will make a notation of damage (or shortage of items) on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your local representative. Any physical damage to the unit after acceptance is not the responsibility of manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Fans are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce the ability of the fan to resist corrosion. Fans should never be lifted by the shaft, fan housing, motor, belt guard or accessories.
Storage
• Rotate fan wheel monthly and purge bearings once every three months.
• Energize fan motor once every three months.
• Store belts flat to keep them from warping and stretching.
• Store unit in location which does not have vibration.
• After storage period, purge grease before putting fan into service.
If storage of fan is in a humid, dusty or corrosive atmosphere, rotate the fan and purge the bearings once a month. Improper storage which results in damage to the fan will void the warranty.
Fans are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the fan and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR - The ideal environment for the storage of
fans and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F to 110°F (-1°C to 43°C). Wide temperature swings may cause condensation and “sweating” of metal parts. All accessories must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
OUTDOOR - Fans designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The fan should be placed on a level surface to prevent water from leaking into the fan. The fan should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all fan parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Fan wheels should be blocked to prevent spinning caused by strong winds.
Inspection & Maintenance during Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
®
506 (Ashland Inc.) or the equivalent.
Centrifugal, Industrial and Filtered Supply2
Page 3
Removing from Storage
As fans are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the fan equipment goes into operation.
Prior to assembly and installation of the unit and system components, inspect the fan assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base and accessories for tightness.
2. Rotate the fan wheel by hand and assure no parts are rubbing. Access to the wheel is obtained through a bolted panel located on the side of the fan housing.
3. Ensure proper wheel settings for radial gap and alignment. Refer to Radial Gap, Overlap and Wheel Alignment section on page 8.
Table of Contents
General Information
To ensure a successful installation, the instructions in this manual should be read and adhered to. Failure to comply with proper installation procedures may void the warranty.
Unit and System Identification Tags
Each fan has a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number.
The tag shown is an example of an identification nameplate on the fan. The information provides general details about the fan, as well as contains specific information unique to the unit. When contacting your local manufacturer’s representative with future needs or questions, have the information on this label available. Tags are mounted in an area which is clearly visible, usually on the side of the fan cabinet.
General Safety Information .................... 1
Receiving / Unpacking / Handling / Storage ...... 2
Inspection and Maintenance during Storage ..... 2
Removing from Storage ..................... 3
General Information .......................... 3
Unit and System Identification Tags ........... 3
Pre-Installation Information .................. 3
Electrical Disconnects ...................... 3
Moving Parts ............................. 3
Guards / Access Doors ...................... 4
Air Pressure and Suction .................... 4
Fans - Rigging and Lifting ..................... 4
Installation ................................. 5
Ducted Inlet Installations .................... 5
Ducted Outlet Installations ................... 5
Non-Ducted Installations .................... 5
Fan Drainage Piping and Trap Detail ........... 6
Bases ................................... 6
Belt Guards .............................. 7
Electrical Connections ....................... 7
Radial Gap, Overlap and Wheel Alignment ....... 8
Unit Start-Up ............................... 9
Visual Inspection of Equipment ............... 9
Additional Steps for Initial Start-Up ............ 9
Vibration .................................. 9
Routine Maintenance ....................... 10
Motors ................................. 10
Shaft Bearings ........................... 10
Belt Drive Maintenance .................... 11
Belt Adjustment .......................... 11
Variable Frequency Drive Operation ............ 12
Field Coating Touch-Up Procedure ............. 12
Parts List ...............................13-14
Troubleshooting ............................ 15
Maintenance Log .....................Backcover
Our Commitment .....................Backcover
Pre-Installation Information
Before installation, it is important to be certain the mounting surface will bear the operating weight of the unit. For proper unit operation, it is also important that it be operated in a completely level position.
For further details on safety practices involving industrial and commercial fans, please refer to AMCA Publication410.
Electrical Disconnects
All fan motors should have disconnects located in close visual proximity to turn off electrical service. Service disconnects shall be locked-out when maintenance is being performed.
Moving Parts
All moving parts must have guards to protect personnel. Refer to local codes for requirements as to the number, type and design. Fully secure fan wheel before performing any maintenance. The fan wheel may start “free wheeling” even if all electrical power has been disconnected. Before the initial start-up or any restart, check the following items to make sure that they are installed and secure.
• Do not spin fan wheel faster than the maximum cataloged fan RPM.
• Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
Centrifugal, Industrial and Filtered Supply 3
Page 4
Guards – Motor Cover, Weatherhood, Shaft, Belt, Inlet or Outlet Guard
Do not operate fans without proper protective devices in place. Failure to do so may result in serious bodily injury and property damage. Check local codes to ensure compliance for all protective devices.
Access Doors
Before opening access doors, ensure the fan wheel has stopped moving and that the wheel has been secured from being able to rotate. Do not operate fan without access door in its fully closed position.
Air Pressure and Suction
In addition to the usual hazards associated with rotating machinery, fans also create a dangerous suction at the inlet. Special caution needs to be used when moving around a fan, whether it is in operation or not. Before start-up, make sure the inlet area is clear of personnel and loose objects.
Typical Arrangement 10 without Isolation Base
Fans - Rigging and Lifting
IMPORTANT
Fans should never be lifted by the shaft, motor, motor cover or accessories.
1. Before lifting, be sure that all shipping materials have been removed from the unit.
2. Use standard lifting and rigging practices.
3. ALL lifting brackets on each unit must be utilized at the same time.
4. Fan to be kept level during lifting and installation.
5. Spreader bars must span the unit to prevent damage to the unit by the lifting cables.
6. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
7. Never lift unit in windy conditions.
8. Preparation of roof opening should be completed prior to lifting unit to the roof.
Fans are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of fan to resist corrosion.
See coating repair section of this manual for details regarding touch-up of damaged surfaces.
Typical Arrangement 4 Without Isolation Base
Typical with Isolation Base
If the fan assembly has an isolation base, lift the entire assembly by the four corner holes located in each corner of the base. This is the case for both the standard base or base with height savings bracket.
IMPORTANT
Spreader bars are recommended to prevent damage to the unit. Failure to use spreader bars may result in damage which becomes the installer’s responsibility.
Centrifugal, Industrial and Filtered Supply4
Isolation Base Isolation Base with
Height Savings Bracket
Page 5
R
o
t
a
t
i
o
n
R
o
t
a
t
i
o
n
POOR
Length of Straight Duct
GOOD
Installation
Move the fan to the desired location. Check and tighten fasteners throughout the unit and then fasten securely through mounting holes provided in the base angles. The unit must be set level (shimming may be necessary). Flexible duct connections and vibration isolators should be used where noise is a factor.
The motor voltage and ampere rating must be checked for compatibility with the electrical supply prior to final electrical connection. Supply wiring to the fan must be properly fused, and conform to local and national electrical codes.
Installations with inlet or discharge configurations that deviate from this standard may result in reduced fan performance. Restricted or unstable flow at the fan inlet can cause pre-rotation of incoming air or uneven loading of the fan wheel yielding large system losses and increased sound levels. Free discharge or turbulent flow in the discharge ductwork will also result in system effect losses. Refer to the following diagrams for the most efficient installation conditions.
Ducted Inlet Installations
Inlet Duct Turns - Installation of a duct turn or elbow
too close to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel. To achieve full fan performance, there should be at least three fan wheel diameters between the turn or elbow and the fan inlet.
Ducted Outlet Installations
Discharge Duct Turns - Duct turns located near the
fan discharge should always be in the direction of the fan rotation.
Fan performance is reduced when duct turns are made immediately off the fan discharge. To achieve cataloged fan performance there should be at least three equivalent duct diameters of straight ductwork between the fan discharge and any duct turns.
Non-Ducted Installations
Inlet Clearance - Installation of a fan with an open
inlet too close to a wall or bulkhead will cause reduced fan performance. It is desirable to have one fan wheel diameter between parallel fan units and a minimum of three-fourths of a wheel diameter between the fan inlet and the wall.
POOR
Three fan wheel diameters
Turning
Vanes
GOOD
Inlet Spin - Inlet spin is a frequent cause of reduced fan performance. The change in fan performance is a function of the intensity of spin and not easily defined. The best solution is proper duct design and airflow patterns. Turning vanes reduce the effects of inlet spin.
R
o
Turning
t
a
Vanes
t
i
o
n
POOR GOOD
3/4 to
one fan
wheel
diameter
3/4 to one
fan
wheel
diameter
Single Fan Installation
One fan
diameter
Parallel Fan Installation
3/4 to one
fan
wheel
diameter
3/4 to
one fan
wheel
diameter
Free Discharge - Free or abrupt discharge into a plenum results in a reduction in fan performance. The effect of discharge static regain is not realized.
R
o
t
a
t
i
o
n
Centrifugal, Industrial and Filtered Supply 5
Page 6
Fan Drainage Piping and Trap Detail (by others)
Fans may have been supplied with an optional drain. Drains are located at the underside of the scroll housing. The drain may need to be connected to a drainage system to ensure proper disposal of any water or condensate that may occur.
Drain connections with and without a plug are
1inch (25.4 mm)
Installed piping to have a downward angle to allow
for drainage.
Fill traps to recommended level before start-up.
Note: A conservative method of trap design is to set
N = total static pressure.
Positive Pressure Trap
Connect this end to fan drain.
N
H/2 H/2
H
FAN ONFAN OFF
N = Negative fan pressure (inches W.C.) H = N - 0.5 inches minimum
Check local codes for proper disposal of drain water which has been in contact with the exhaust air.
Fans used for grease exhaust need to be equipped with a separate grease collector.
Drain Options
IP
AFDW / BIDW
LSF
None
Without plug
None
With plug
None
1.25 inch minimum
Bases (Foundation and Isolation)
Critical to every fan installation is a strong, level foundation. A reinforced poured concrete pad with a structural steel base or inertia base provides an excellent foundation. Structural bases must be sturdy enough, with welded construction, to prevent flexing and vibration.
To eliminate vibration and noise from being transferred to the building, vibration isolators should be used. The fan is mounted directly on the isolation base and must be supported for the entire length of the fan base angle (Refer to the Centrifugal Fan Isolation Base Assembly Instructions if the base was supplied by manufacturer). Isolators are installed between the isolation base and the foundation.
After the fan, isolation base, and isolators are installed, the entire assembly must be leveled. Position the level on the isolation base, not the fan shaft, for proper leveling. Additionally, the motor and fan shafts must be level and parallel relative to each other for proper alignment.
When installing a fan, ensure the proper protective devices are used to protect personnel from moving parts and other hazards. A complete line of protective accessories are available from the manufacturer including: inlet guards, outlet guards, belt guards, shaft guards, protective cages and electrical disconnects.
Electrical Disconnects
All fan motors should have disconnects located in close visual proximity to turn off electrical service. Service disconnects shall be locked out when maintenance is being performed.
Moving Parts
All moving parts must have guards to protect personnel. Refer to local codes for requirements as to the number, type and design. Fully secure fan wheel before performing any maintenance. The fan wheel may start “free wheeling” even if all electrical power has been disconnected. Before the initial start-up or any restart, check the guards (belt, shaft, inlet and outlet) and check the access doors to ensure that they are installed and secure.
Typical Fan on Isolation Base
CAUTION
Centrifugal, Industrial and Filtered Supply6
Page 7
Belt Guards
X/Y
Fan
Z
W
Motor position and fan rotation are determined from drive side
Greenheck offers various types of customized belt guards dependent upon fan model, arrangement and motor position. Motor position is determined from the drive side.
The various types of belt guards are shown in illustrations. If the guard is not purchased from Greenheck, they must be supplied by the installer or owner.
If the belt guard is not factory mounted or was not supplied by manufacturer, then it must be field mounted. Brackets and mounting hardware are the responsibility of the installer. The figures below illustrate suggested attachment points for belt guard mounting bracket locations. These locations vary with motor mounting position, arrangement, and fan type. The bearing supports and fan structure are used in most instances and when the motor is not mounted to the fan itself, a bracket should also be located near it. This information is intended only as a guide and actual field conditions may dictate another mounting location for the guard brackets. Refer to local codes for securing guarding.
Typical Belt Guard
Industrial Process – Arr. 1 & 9
Motor Position: W/Z
Arrangement - 1, 3
Motor Position: L/R
Arrangement 9
Suggested Belt Guard Attachment Points
(shaded gray)
Motor Position: X/Y
Arrangement - 1, 3
Electrical Connections
Before electrical connections are made, the supply voltage, phase and ampere capacity must be checked for compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to local and national electrical codes. If the unit is supplied with a safety disconnect switch, ensure proper wiring to the fan motor. Be sure the disconnect is switched to the “OFF” position before connecting supply wires. If no disconnect is supplied, ensure the supply wire is not live before connection. Supply wires are then connected to the optional safety disconnect switch (if supplied) or motor.
AFDW, BIDW - Arr. 3
Centrifugal, Industrial and Filtered Supply 7
Page 8
Radial Gap, Overlap and Wheel Alignment
Efficient fan performance can be maintained by having the correct radial gap, overlap and wheel alignment. These items should be checked after the fan has been in operation for 24 hours and before start-up after the unit has been serviced. Radial gap and overlap information applies to models: BIDW, AFDW, LSF and IP with air handling wheel.
IP (Air Handling)
Unit Size
5 3.67 7 5.36
9 6.88 11 8.38 13 9.92 15 11.39 17 12.95 19 14.48 21 15.95 23 17.50 26 20.00 29 22.31 33 25.75 37 28.82 41 31.38
Inlet Cone to Backplate
A Dimension
± Tolerance (in.)
±
1/8 93
±
1/8 136
±
1/8 175
±
1/4 213
±
1/4 252
±
3/8 289
±
3/8 329
±
3/8 368
±
3/8 405
±
1/2 445
±
1/2 508
±
1/2 567
±
1/2 654
±
1/2 732
±
1/2 797
Dimension
± Tolerance (mm)
±
3
±
3
±
3
±
6
±
6
±
10
±
10
±
10
±
10
±
13
±
13
±
13
±
13
±
13
±
13
BIDW, AFDW, LSF
Unit Size
± Tolerance (in.)
12 4.00
13 4.44
15 5.00 16 5.44 18 6.38 20 7.00 22 7.81 24 8.63 27 9.44 30 10.56 33 11.44 36 12.75 40 14.19 44 15.56 49 17.13 54 18.81 60 20.94 66 22.88 73 25.50
Inlet Cone to Backplate
Dimension
±
1/8 102
±
1/8 113
±
1/8 127
±
1/8 138
±
1/8 162
±
3/16 178
±
3/16 198
±
1/4 219
±
1/4 240
±
3/8 268
±
3/8 291
±
3/8 324
±
3/8 360
±
3/8 395
±
1/2 435
±
1/2 478
±
1/2 532
±
1/2 581
±
1/2 648
Dimension
± Tolerance (mm)
±
3
±
3
±
3
±
3
±
3
±
5
±
5
±
6
±
6
±
10
±
10
±
10
±
10
±
10
±
13
±
13
±
13
±
13
±
13
Radial Gap is adjusted by loosening the inlet cone bolts and centering the cone on the wheel. If additional adjustment is required to maintain a constant radial gap, loosening the bearing bolts and centering the wheel is acceptable as a secondary option.
Overlap or offset, is adjusted by loosening the wheel hub from the shaft and moving the wheel to the desired position along the shaft.
The transition between the inlet cone and wheel should be as shown; there is a smooth feel to the profile when moving from one component to the other. Overlap on double width fans is set by having equal spacing on each side of the wheel.
Correct wheel alignment for an industrial process fan (open radial or backplated/wool wheel) is achieved by centering the wheel in the housing.
Clockwise Rotation
Centrifugal
Backward Inclined
Always viewed from the drive side.
Centrifugal
Airfoil
Overlap
Wheel
Inlet
Cone
A
Radial
Gap
IP (Air Handling)
Overlap Overlap
Radial
Gap
BIDW, AFDW, LSF
Equal Spacing
Housing
Wheel
Wheel Alignment
IP (Open Radial or Backplated)
Industrial Process
Radial Blade
Centrifugal, Industrial and Filtered Supply8
Page 9
Unit Start-Up
Visual Inspection of Equipment
The equipment type and arrangement should be verified as ordered at once when it arrives at the job site. When a discrepancy is found, the local sales representative must be notified immediately so that corrective action may be investigated, also verify electrical conformance to specifications. Unauthorized alterations and unauthorized back charges will not be recognized by the manufacturer.
After the unit has been assembled, installed and all utilities have been hooked up, the unit is now ready for operation.
WARNING
Disconnect and secure to the “Off” position all electrical power to the fan prior to inspection or servicing. Failure to comply with this safety precaution could result in serious injury or death.
Before starting the unit, check the following:
1. Disconnect and lock-out all power switches to fan. See warning below.
2. Check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness.
3. Rotate the fan wheel manually to be sure that it is free to operate. Remove any dirt or debris that may have accumulated during installation.
4. Check for bearing alignment and lubrication.
5. Check for coupling alignment (Arr. 8 only).
6. Check the V-belt drive for proper alignment and tension.
7. Check all guarding (if supplied) to ensure that it is securely attached and not interfering with rotating parts.
8. Check operation of variable inlet vanes or discharge dampers (if supplied) for freedom of movement.
9. Check all electrical connections for proper attachment.
10. Check housing and ductwork, if accessible, for obstructions and foreign material that may damage the fan wheel.
Additional Steps for Initial Start-Up
1. Check for proper wheel rotation by momentarily
energizing the fan. Rotation is always determined by viewing the wheel from the drive side and should correspond to the rotation decal affixed to the unit.
One of the most frequently encountered problems
with centrifugal fans is motors which are wired to run in the wrong direction. This is especially true with 3-phase installations where the motor will run in either direction, depending on how it has been wired. To reverse rotation of a 3-phase motor, interchange any two of the three electrical leads. Single phase
motors can be reversed by changing internal
connections as described on the motor label or wiring diagram.
2. If the fan has inlet vanes, they should be partially closed to reduce power requirements. This is especially important if the fan is designed for a high temperature application and is being started at room temperature.
3. Fans with multi-speed motors should be checked on low speed during initial start-up.
4. Check for unusual noise, vibration or overheating of bearings. Refer to the “Troubleshooting” section of this manual if a problem develops.
5. Grease may be forced out of the bearing seals during initial start-up. This is a normal self-purging feature of this type of bearing.
Vibration
Excessive vibration is the most frequent problem experienced during initial start-up. Left unchecked,
excessive
Common Sources of Vibration
1. Wheel unbalance
2. Drive pulley misalignment
3. Incorrect belt tension
4. Bearing / coupling misalignment
5. Mechanical looseness
6. Faulty belts
7. Drive component unbalance
8. Poor inlet / outlet conditions
9. Foundation stiffness
by careful observation. Refer to the troubleshooting section of this manual for corrective actions. If observation cannot locate the source of vibration, a qualified technician using vibration analysis equipment should be consulted. If the problem is wheel unbalance, in-place balancing can be done providing there is access to the fan wheel. Any correction weights added to the wheel should be welded to either the wheel back (single-plane balance) or to the wheel back and wheel cone (two-plane balance).
Greenheck performs a vibration test on all centrifugal fans before shipping. Three vibration readings are taken on each bearing in the horizontal, vertical, and axial directions. The allowable maximum vibration for belt drive units is 0.15 in/sec. peak velocity filter-in for rigid mount and 0.20 in/sec. peak velocity filter-in for flexible mount at the fan RPM per AMCA Standard 204. These vibration signatures are a permanent record of how the fan left the factory and are available upon request.
Generally, fan vibration and noise is transmitted to other parts of the building by the ductwork. To eliminate this undesirable effect, the use of heavy canvas connectors is recommended. If fireproof material is required, Flexweave™1000 - Type FN-30 can be used.
vibration can cause a multitude of problems, including structural and/ or component failure.
Many of these conditions can be discovered
Centrifugal, Industrial and Filtered Supply 9
Page 10
Routine Maintenance
WARNING
Before taking any corrective action, make certain unit is not capable of operation during repairs.
Once the unit has been put into operation, a routine maintenance schedule should be set up to accomplish the following:
1. Lubrication of bearings and motor (see below).
2. Wheel, housing, bolts and set screws on the entire fan should be checked for tightness.
3. Any dirt accumulation on the wheel or in the housing should be removed to prevent unbalance and possible damage.
4. Isolation bases should be checked for freedom of movement and the bolts for tightness. Springs should be checked for breaks and fatigue. Rubber isolators should be checked for deterioration.
5. Inspect fan impeller and housing looking for fatigue, corrosion or wear.
When performing any service to the fan, disconnect the electrical supply and secure fan impeller.
Motors
Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only. Removing dust and grease build up on the motor housing assists proper motor cooling. Never wash-down motor with high pressure spray.
Greasing of motors is only intended when fittings are provided. Many fractional motors are permanently lubricated for life and require no further lubrication. Motors supplied with grease fittings should be greased in accordance with the manufacturer’s recommendations.
CAUTION
When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult Greenheck to determine if the unit can operate safely at the new conditions.
Shaft Bearings
The bearings for Greenheck fans are carefully selected to match the maximum load and operating conditions of the specific class, arrangement, and fan size. The instructions provided in this manual and those provided by the bearing manufacturer will minimize any bearing problems. Bearings are the most critical moving part of the fan, therefore special care is required when mounting them on the unit and maintaining them.
Refer to the following chart and the manufacturers instructions for grease types and intervals for various operating conditions. Never mix greases made with different bases. This will cause a breakdown of the grease and possible failure of the bearing.
Recommended Bearing Lubrication Schedule
Relubrication Schedule in Months*
Fan
RPM
To 250 12 12 12 12 12 12 10 8
500121211108754
750129876432
1000 12 7654321
1250 12 6 5 4 3 2 1 .5
1500 12 54321.75
2000 12 3321.5.25
2500 12 2 2 1 .5 .25
3000 12 2 1 .5 .25
3500 12 1 .5 .25
4000 12 .5 .25
5000 12 .25
Number
of shots**
* Lubrication interval is based on 12 hour day operation and
maximum 160˚F housing temperature. For 24 hour per day operation, the interval should be cut in half.
** Lubricant should be added with the shaft rotating and
until clean grease is seen purging from the bearing. The lubrication interval may be modified based on the condition of the purged grease. If bearing is not visible to observe purged grease, lubricate with number of shots indicated for bore size.
• For conditions including high temperatures, moisture, dirt or excessive vibration, consult the factory for a specific lubrication interval for your application.
• Lubricant should be a high quality lithium complex grease conforming to NLGI Grade 2. Factory recommends Mobilux EP-2 or synthetic Mobilith SHC100.
• The use of synthetic lubricants will increase lubrication intervals by approximately three times.
• Storage periods of three months or longer require monthly rotation of the shaft and purging grease prior to storage and start-up.
1
2 - 111⁄8 -
11⁄2
4 8 8 10 16 25 41 57
Bearing Bore (inches)
15⁄8 -
115⁄16 -
17⁄8
23⁄16
27⁄16
- 3
33⁄16 -
31⁄2
315⁄16 -
41⁄2
415⁄16 -
51⁄2
Centrifugal, Industrial and Filtered Supply10
Page 11
Belt Drive Maintenance
V-belt drives must be checked on a regular basis for wear, tension, alignment and dirt accumulation. Premature or frequent belt failures can be caused by improper belt tension, (either too loose or too tight) or misaligned sheaves. Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result in failure of the fan and/or motor bearings. Conversely, loose belts will cause squealing on start-up, excessive belt flutter, slippage, and overheated sheaves. Either excessively loose or tight belts may cause fan vibration.
When replacing V-belts on multiple groove drives all belts should be changed to provide uniform drive loading. Use a set of matched belts whenever possible. Do not pry belts on or off the sheave. Loosen belt tension until belts can be removed by simply lifting the belts off the sheaves.
Deflection =
After replacing belts, insure that slack in each belt is on the same side of the drive. Belt dressing
Belt Span
should never be used.
Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced before new belts are installed.
The proper tension for operating a V-belt drive is the lowest tension at which the belts will not slip at peak load conditions. For more information about measuring belt tension, refer to Greenheck’s Product Application Guide, FA/127-11, Measuring Belt Tension, found online at greenheck.com in the Resources section.
Check belt tension before start up and after the first 24 hours of operation. The belt tension should also be checked periodically thereafter.
Belt Span
64
Belt Adjustment
Belts on model IP are adjusted from the exterior of the fan. Covers should be opened or removed so the belt(s) can be inspected and checked for proper tension.
L-Adjustment
Bolts
Plate Bolts
The tension of the belt(s) are adjusted by raising and lowering the motor plate. There are bolts on each side of the fan that must be used in order to adjust the belt(s). Each side has two plate bolts and two L-adjustment bolts.
1. Loosen, but DO NOT remove the two plate bolts on each side of the motor plate.
2. Loosen, then adjust the L-bolts to raise or lower the motor in order to tighten or loosen the belt(s) as needed. The nuts on the L-adjustment bolts should be adjusted evenly so the motor plate is raised or lowered as level as possible.
3. Tighten all the L-adjustment bolts and the plate bolts to lock motor in place after proper tension is reached.
NOTE
Loosen the plate bolts as minimal as possible to allow the plate to move, but so the plate has minimal movement when bolts are re-tightened.
WARNING
Improper sheave
alignment
WARNING
Do not overtighten belts. Excessive belt tension can lead to premature belt and/or bearing failure.
Be sure to raise or lower the motor plate as even as possible for proper belt engagement and to avoid jamming the plate.
Proper sheave
alignment
Centrifugal, Industrial and Filtered Supply 11
Page 12
Variable Frequency Drive Operation
WARNING
For operation with a Variable Frequency Drive (VFD), always check motor amps when adjusting the operating frequency. Motor may be sized for the original selected operating speed under 60 Hz. Bypassing the VFD or increasing the speed from this original selection, even if less than 60 Hz, may cause motor overload or failure. Consult factory with fan serial number before increasing the upper limiting frequency. Always check the fan rpm when adjusting the operating frequency. Do not exceed maximum class fan rpm of the wheel as stated on the unit identification nameplate.
It is the responsibility of the installing body to perform coast-down tests and identify any resonant frequencies after the equipment is fully installed. These resonant frequencies are to be removed from the operating range of the fan by using the “skip frequency” function in the VFD programming. Failure to remove resonant frequencies from the operating range will decrease the operating life of the fan and void the warranty.
Field Coating Touch-Up Procedure for Scratched Areas
Standard coating and color is RAL7023 Concrete Grey. The procedure outlines the correct method for repairing minor scratches in the coating.
TOUCH-UP PAINT REPAIR KIT CONTENTS
• One pint of Kem Kromik® primer
- including a technical data sheet
• One pint of industrial enamel
- including a technical data sheet
• Four disposable foam brushes
• One sheet sandpaper
• Repair procedure details
1. Scuff affected area to be repaired using medium sandpaper (provided) or medium Scotch Brite™ pad. Feather the edges.
2. Clean affected area to be touched up using an alkaline based cleaner and rinse.
3. Apply Kem Kromik (provided). Follow technical data sheet instructions.
4. Allow primer to dry a minimum of 2-1/2 hours before top coating.
5. Apply topcoat with industrial enamel using 1 inch foam brush (provided). Follow technical data sheets instructions. Allow painted units to air-dry and cure before putting into service. See Technical Data sheets (included with kit) for detailed drying and cure schedules at different temperatures.
®
primer using 1 inch foam brush
NOTE
While the manufacturer provides heavy-duty, quality products for marine environments, routine paint touch-ups may be required in coastal regions where salt or marine air could damage the coating. The severe environment will accelerate the damage from any scratches or chips and it is recommended that those be repaired immediately.
To order additional coating repair kits please reference part number HAZ2597 PNT FIELD REPAIR KIT, RAL7023 CONCRETE GREY. Please contact factory with your fan’s serial number for colors other than our standard.
Centrifugal, Industrial and Filtered Supply12
Page 13
Parts List
B
Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information will assist the local manufacturer’s representative and the factory in providing service and replacement parts. Before taking any corrective action, make certain unit is not capable of operation during repairs.
CAUTION
A fan manufactured with an explosion resistant motor does not certify the entire unit to be explosion proof. Refer to UL Listing Mark for the fans approved usage.
Centrifugal • Double-Width
Backward Inclined Wheel
Bearing
Shaft
Motor
Belt Guard
Isolation Base
Vibration Isolators (4)
LSF
Filters
Filter
Channels
Shaft
Bearings
Vibration
Isolation Base
Motor
Motor Slide
Base
Drives/Sheaves
Centrifugal, Industrial and Filtered Supply 13
Page 14
Volume Control Damper
Outlet Companion Flange
Industrial Process
Outlet Flange
Inlet Flange
Inlet Companion Flange
Heat Slinger
Shaft
Bearings
Belts
Motor Drives / Sheaves
Weatherhood Arrangement 10 only
Centrifugal, Industrial and Filtered Supply14
Page 15
Troubleshooting
WARNING
Before taking any corrective action, make certain unit is not capable of operation during repairs.
Problem Cause Corrective Action
Wheel rubbing (inlet)
V-belt drive
Excessive Noise
Bearings
Wheel unbalance
Low CFM
High CFM
Static Pressure Wrong
High Horsepower
Fan Doesn’t Operate
Overheated Shaft Bearing
Excessive Vibration
*Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor and result in motor failure. Do not exceed the maximum cataloged RPM of the fan.
NOTE: Always provide the unit model and serial numbers when requesting parts or service information.
Fan Check wheel for correct rotation. Increase fan speed.*
Duct system See page 3.
Fan Decrease fan speed.
Duct system Resize ductwork. Access door, filters, grilles not installed.
Duct system has more or less restriction than anticipated
Dirty filters
• Model LSF
Fan Check rotation of wheel. Reduce fan speed.
Duct system
Electrical supply
Drive Check for broken belts. Tighten loose pulleys.
Motor
Lubrication Check for excessive or insufficient grease in the bearings.
Mechanical
Belts
System unbalance
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Tighten Sheaves on motor/fan shaft. Adjust belt tension. Align sheaves properly (see V-Belt Drives section). Replace worn belts or sheaves.
Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Clean all dirt off wheel. Check wheel balance, rebalance in place if necessary.
Change obstructions in system. Use correction factor to adjust for temperature/altitude. Resize ductwork. Clean filters/coils. Change fan speed.*
Filters need to be cleaned or replaced. To remove the existing filters, open the top hood panel(s). The filters can now be removed by lifting them vertically and out of their racking. Be sure to carefully note the quantity and size of the filters being removed as some LSF units utilize multiple filters sizes. After the filters have been cleaned, or new filters are ready to be installed, place the filters back into the racks in the reverse order of which they were removed. When all filters are in place, close and secure the top roof panels.
Resize ductwork. Check proper operation of face and bypass dampers. Check filters and access doors.
Check fuses/circuit breakers. Check for switches turned off or disconnected. Check for correct supply voltage.
Assure motor is correct horsepower and not tripping overload protector.
Replace damaged bearing. Relieve excessive belt tension. Align bearings. Check for bent shaft.
Adjust tightness of belts. Replacement belts should be a matched set.
Check alignment of shaft, motor and pulleys. Adjustable pitch pulleys with motors over 15 hp are especially prone to unbalance. Check wheel balance, rebalance if necessary.
Centrifugal, Industrial and Filtered Supply 15
Page 16
Maintenance Log
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Date ___________________Time _____________ AM/PM Notes: ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.
Greenheck’s Centrifugal Fans and Industrial Process Fans catalogs provides additional information describing the equipment, fan performance, available accessories, and specification data.
®
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
463687 • Centrifugal, Industrial and Filtered Supply, Rev. 10, April 2019 Copyright 2019 © Greenheck Fan Corporation16