Greenheck AX 113-533 User Manual

Greenheck Product Category
High Performance Axial Fans
Models
Descriptor or Bullets
Performance Supplement
July
Month
2004
YEAR
High Performance Axial Fans
Page Header
Performance information is for the model AX standard configuration. Optional configurations include; upblast design with butterfly dampers and curb cap, detachable air straightening vane section, and shortened case. These options can effect performance. For estimated pressure drops on these accessories, consult your local Greenheck representative.
AX Short CasingAX Vane SectionAX Upblast
Greenheck certifies that the Model AX fan shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings Program.
Hubs and Blades
The AX blade shape and hub are designed to move high volumes of air with less power to save on long-term energy costs. The choice of five different hub diameters, along with variations in blade quantities, ensures that the most economical air performance can be achieved. In addition, during the design process, close attention was paid to the “hub to tip” ratios. This is a comparison of the hub diameter to the “tip to tip” dimension of the blades. Different choices of hub to tip ratios further optimize fan performance and provide a cost effective solution by not over sizing a hub to produce required volumes and pressures. The hubs are constructed from cast aluminum and use a taper lock bushing to secure the hub to the motor shaft.
Available Hub Sizes (mm) / Number of Blades
160 190 275 400 533
Size
(4 or 6 ) (4 or 6) (6 or 9) (6 or 9) (8 or 12)
31 X
36 X
41 X X
47 X X
54 X X X
63 X X X
72 X X
80 X X X
90 X X
103 X X
113 X X X
123 X X
140 X X
160 X X
2
AX 31-160 4 Blades
Air density = 1.2 kg/m
3
Air density = 0.075 lbs/ft
3
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Total
Pressure
Performance shown is for installation type B; free inlet, ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: free inlet, ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
Pitch Angle º
rpm 5 10 15 20 25 30 35
3500 (Bhp/kW)
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
1770 (Bhp/kW)
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
2900 (kW)
0.08 0.13 0.18 0.24 0.30 0.37 0.45
1450 (kW)
0.01 0.02 0.02 0.03 0.04 0.05 0.06
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +20 +8.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
ft/min = cfm / 0.82
m/s = m³/s / 0.08
Tip Speed
ft/min = rpm X 3.20
m/s = rpm X 0.98
68
68
68
67
67
67
66
65
69
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 31-160 4 Blades
Performance Manual Guide
Page Header
How to use this performance manual
The performance pages contains information in metric and english units. These are color coded with motor power frequency and motor speed for easy and quick reference in finding air performance, power requirements, and sound information. See back cover for selection example.
Model size and hub
1
diameter
Total Pressure Axis
2
in Pascals (Pa) and Inches Water Gauge (in. wg)
Static Pressure
3
- Lines of constant static pressure
Color coded power
4
frequency and motor speed (rpm)/poles
Volume - Axis
5
displays two different units of measure for each power frequency and motor speed.
Blade pitch -
6
Shown in 5 degree increments, integral pitches are available between the displayed limits.
Sound power (LwA)
7
- Color coded sound power level levels are displayed as a percentage of peak power; 100%, 50% and 0%. Use corrections in the sound power table to find corresponding LwA and dBA levels for a specific power frequency and motor speed.
2
4
9
1
11
7
8
6
10
3
5
Total Efficiency curves - Curves show total efficiency levels at different performance points. Those curves
8
do not reflect static efficiency levels.
9
Peak Absorbed Power table - Table displays the maximum power required by pitch angle and motor rpm. Values provided are in brake horse power and kilowatts.
Outlet Velocity and Tip Speed formulas - For deriving outlet velocity, use either cfm or m³/s in the
11
appropriate Outlet Velocity equation. Tip speed equation is only dependent on motor rpm.
Sound Power and Sound Pressure table - Table displays the corrections required by motor rpm.
10
3
AX 31-160 4 Blades
Page Header
Total
Pressure
68
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 0.82
m/s = m³/s / 0.08
ft/min = rpm X 3.20
m/s = rpm X 0.98
65
67
67
66
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
³
68
68
67
69
³
Volume
Sound Power A-Weighted [LwA]
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Pitch Angle º
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only.
Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
0.19/0.14 0.30/0.22 0.43/0.32 0.56/0.42 0.71/0.53 0.88/0.66 1.07/0.80
0.03/0.02 0.04/0.03 0.06/0.04 0.07/0.05 0.09/0.07 0.11/0.09 0.14/0.10
0.08 0.13 0.18 0.24 0.30 0.37 0.45
0.01 0.02 0.02 0.03 0.04 0.05 0.06
4
4
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +20 +8.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
AX 31-160 6 Blades
Page Header
Total
Pressure
Impeller Diameter = 12.25 inches (311 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 0.82
m/s = m³/s / 0.08
ft/min = rpm X 3.20
m/s = rpm X 0.98
69
70
71
66
68
68
67
70
69
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.38/0.28 0.43/0.32 0.56/0.42 0.73/0.54 0.93/0.69 1.16/0.87 1.41/1.06
0.05/0.04 0.06/0.04 0.07/0.05 0.09/0.07 0.12/0.09 0.15/0.11 0.18/0.11
0.16 0.18 0.24 0.31 0.39 0.49 0.60
0.02 0.02 0.03 0.04 0.05 0.06 0.08
5
5
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +20 +8.5 1770 - -11.5 2900 +14 +2.5 1450 -5 -16.5
AX 36-160 4 Blades
Page Header
Total
Pressure
73
Impeller Diameter = 14.25 inches (362 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.11
m/s = m³/s / 0.10
ft/min = rpm X 3.73
m/s = rpm X 1.14
71
69
72
70
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
³
73
73
71
73
³
Volume
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Pitch Angle º
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
0.42/0.31 0.61/0.46 0.87/0.65 1.18/0.88 1.52/1.13 1.89/1.41 2.31/1.72
0.05/0.04 0.08/0.06 0.11/0.08 0.15/0.11 0.20/0.15 0.24/0.18 0.30/0.22
0.18 0.26 0.37 0.50 0.64 0.80 0.98
0.02 0.03 0.05 0.06 0.08 0.10 0.12
6
6
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +19 +7.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
Page Header
AX 36-160 6 Blades
Total
Pressure
AX 41-160 6 Blades
Impeller Diameter = 14.25 inches (362 mm)
Outlet Velocity
Tip Speed
70
ft/min = cfm / 1.11
m/s = m³/s / 0.10
ft/min = rpm X 3.73
m/s = rpm X 1.14
72
73
73
71
74
74
73
75
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.72/0.54 0.94/0.70 1.25/0.93 1.64/1.22 2.07/1.55 2.54/1.89 3.00/2.24
0.09/0.07 0.12/0.09 0.16/0.12 0.21/0.16 0.27/0.20 0.33/0.24 0.39/0.29
0.31 0.40 0.53 0.70 0.88 1.08 1.27
0.04 0.05 0.07 0.09 0.11 0.13 0.16
7
7
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +19 +7.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
AX 41-160 4 Blades
Page Header
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.44
m/s = m³/s / 0.13
ft/min = rpm X 4.25
m/s = rpm X 1.30
77
72
75
76
74
77
76
75
76
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.78/0.58 1.21/0.90 1.76/1.31 2.36/1.76 3.02/2.25 3.73/2.78 4.52/3.37
0.10/0.08 0.16/0.12 0.23/0.17 0.31/0.23 0.39/0.29 0.48/0.36 0.58/0.44
0.33 0.51 0.74 1.00 1.28 1.58 1.92
0.04 0.06 0.09 0.13 0.16 0.20 0.24
8
8
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +18 +6.5 1770 - -11.5 2900 +12 +0.5 1450 -6 -17.5
AX 41-160 6 Blades
Page Header
Total
Pressure
77
77
AX 41-160 6 Blades
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
Tip Speed
76
73
75
ft/min = cfm / 1.44
m/s = m³/s / 0.13
ft/min = rpm X 4.25
m/s = rpm X 1.30
77
78
77
78
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
1.11/0.82 1.76/1.32 2.44/1.82 3.15/2.35 3.90/2.91 4.76/3.55 5.76/4.30
0.14/0.11 0.23/0.17 0.32/0.24 0.41/0.30 0.51/0.38 0.62/0.46 0.75/0.56
0.47 0.75 1.04 1.34 1.66 2.02 2.44
0.06 0.09 0.13 0.17 0.21 0.25 0.31
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +16 +4.5 1770 - -11.5 2900 +12 +0.5 1450 -7 -18.5
9
9
AX 41-190 4 Blades
Page Header
Total
Pressure
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.44
m/s = m³/s / 0.13
ft/min = rpm X 4.25
m/s = rpm X 1.30
77
77
73
76
77
74
78
75
78
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.80/0.60 1.24/0.92 1.79/1.34 2.43/1.81 3.11/2.32 3.81/2.84 4.55/3.40
0.10/0.08 0.16/0.12 0.23/0.17 0.31/0.23 0.40/0.30 0.49/0.37 0.59/0.44
0.34 0.52 0.76 1.03 1.32 1.62 1.93
0.04 0.07 0.10 0.13 0.16 0.20 0.24
10
10
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +19 +7.5 1770 - -11.5 2900 +13 +1.5 1450 -6 -17.5
AX 41-190 6 Blades
Page Header
Total
Pressure
74
AX 41-190 6 Blades
Impeller Diameter = 16.25 inches (413 mm)
Outlet Velocity
Tip Speed
72
ft/min = cfm / 1.44
m/s = m³/s / 0.13
ft/min = rpm X 4.25
m/s = rpm X 1.30
76
78
74
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
³
76
79
76
78
³
Volume
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Pitch Angle º
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
1.09/0.81 1.59/1.18 2.23/1.67 3.00/2.24 3.84/2.87 4.71/3.51 5.58/4.16
0.14/0.11 0.21/0.15 0.29/0.22 0.39/0.29 0.50/0.37 0.61/0.45 0.72/0.54
0.46 0.67 0.95 1.27 1.63 2.00 2.37
0.06 0.08 0.12 0.16 0.20 0.25 0.30
11
11
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +18 +6.5 1770 - -11.5 2900 +13 +1.5 1450 -6 -17.5
AX 47-160 4 Blades
Page Header
Total
Pressure
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.84
m/s = m³/s / 0.17
ft/min = rpm X 4.81
m/s = rpm X 1.47
69
65
69
71
69
70
66
68
69
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 1770 (Bhp/kW) 1170 (Bhp/kW) 1450 (kW) 950 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.17/0.12 0.26/0.20 0.37/0.28 0.49/0.36 0.62/0.47 0.79/0.59 1.01/0.75
0.05/0.04 0.08/0.06 0.11/0.08 0.14/0.11 0.18/0.13 0.23/0.17 0.29/0.22
0.07 0.11 0.15 0.20 0.26 0.33 0.41
0.02 0.03 0.04 0.06 0.07 0.09 0.12
12
12
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 1770 +11 -0.5 1170 - -11.5 1450 +6 -5.5
950 -6 -17.5
AX 47-160 6 Blades
Page Header
Total
Pressure
70
70
AX 47-160 6 Blades
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
Tip Speed
66
68
ft/min = cfm / 1.84
m/s = m³/s / 0.17
ft/min = rpm X 4.81
m/s = rpm X 1.47
70
71
72
70
71
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 1770 (Bhp/kW) 1170 (Bhp/kW) 1450 (kW) 950 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.21/0.16 0.37/0.27 0.51/0.38 0.65/0.49 0.82/0.61 1.03/0.77 1.31/0.98
0.06/0.05 0.11/0.08 0.15/0.11 0.19/0.14 0.24/0.18 0.30/0.22 0.38/0.28
0.09 0.15 0.21 0.27 0.34 0.42 0.54
0.02 0.04 0.06 0.08 0.09 0.12 0.15
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 1770 +9 -2.5 1170 - -11.5 1450 +5 -6.5
950 -6 -17.5
13
13
AX 47-190 4 Blades
Page Header
Total
Pressure
80
80
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.84
m/s = m³/s / 0.17
ft/min = rpm X 4.81
m/s = rpm X 1.47
80
76
81
77
79
82
81
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
1.57/1.17 2.32/1.73 3.26/2.43 4.36/3.25 5.61/4.19 7.01/5.23 8.54/6.37
0.20/0.15 0.30/0.22 0.42/0.31 0.56/0.42 0.73/0.54 0.91/0.68 1.10/0.82
0.67 0.98 1.38 1.85 2.38 2.97 3.62
0.08 0.12 0.17 0.23 0.30 0.37 0.45
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +19 +7.5 1770 - -11.5 2900 +13 +1.5 1450 -7 -18.5
14
14
AX 47-190 6 Blades
Page Header
Total
Pressure
AX 47-190 6 Blades
Impeller Diameter = 18.38 inches (467 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 1.84
m/s = m³/s / 0.17
ft/min = rpm X 4.81
m/s = rpm X 1.47
80
77
79
82
75
81
77
83
80
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
2.04/1.52 2.94/2.19 4.11/3.06 5.48/4.09 7.04/5.25 8.71/6.49 10.4/7.78
0.26/0.20 0.38/0.28 0.53/0.40 0.71/0.53 0.91/0.68 1.13/0.84 1.35/1.01
0.87 1.25 1.74 2.33 2.99 369 4.43
0.11 0.16 0.22 0.29 0.37 0.46 0.55
15
15
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +19 +7.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
AX 54-160 4 Blades
Page Header
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 2.49
m/s = m³/s / 0.23
ft/min = rpm X 5.60
m/s = rpm X 1.71
74
76
74
69
73
74
75
70
72
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 1770 (Bhp/kW) 1170 (Bhp/kW) 1450 (kW) 950 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.29/0.22 0.48/0.36 0.69/0.52 0.93/0.69 1.20/0.90 1.52/1.13 1.92/1.43
0.08/0.06 0.14/0.10 0.20/0.15 0.27/0.20 0.35/0.26 0.44/0.33 0.55/0.41
0.12 0.20 0.28 0.38 0.49 0.62 0.79
0.03 0.06 0.08 0.11 0.14 0.18 0.22
16
16
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 1770 +12 +0.5 1170 - -11.5 1450 +6 -5.5
950 -5 -16.5
AX 54-160 6 Blades
Page Header
Total
Pressure
AX 54-160 6 Blades
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 2.49
m/s = m³/s / 0.23
ft/min = rpm X 5.60
m/s = rpm X 1.71
75
75
75
76
70
72
76
77
74
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
0.40/0.30 0.64/0.48 0.93/0.69 1.25/0.94 1.62/1.21 2.04/1.52 2.52/1.88
0.11/0.09 0.19/0.14 0.27/0.20 0.36/0.27 0.47/0.35 0.59/0.44 0.73/0.54
0.16 0.26 0.38 0.51 0.67 0.84 1.03
0.05 0.07 0.11 0.14 0.19 0.24 0.29
17
17
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +12 +0.5 1770 - -11.5 2900 +7 -4.5 1450 -6 -17.5
AX 54-190 4 Blades
Page Header
Total
Pressure
85
84
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 2.49
m/s = m³/s / 0.23
ft/min = rpm X 5.60
m/s = rpm X 1.71
85
80
86
82
83
87
84
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
2.57/1.91 4.08/3.05 6.01/4.48 8.23/6.14 10.7/7.99 13.5/10.1 16.5/12.3
0.33/0.25 0.53/0.39 0.78/0.58 1.06/0.79 1.39/1.03 1.74/1.30 2.14/1.59
1.09 1.73 2.55 3.49 4.55 5.72 7.01
0.14 0.22 0.32 0.44 0.57 0.72 0.88
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +18 +6.5 1770 - -11.5 2900 +13 +1.5 1450 -6 -17.5
18
18
AX 54-190 6 Blades
Page Header
Total
Pressure
82
AX 54-190 6 Blades
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
Tip Speed
80
ft/min = cfm / 2.49
m/s = m³/s / 0.23
ft/min = rpm X 5.60
m/s = rpm X 1.71
85
86
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
³
82
88
84
84
86
³
Volume
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Pitch Angle º
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
3.38/2.52 5.66/4.22 8.03/5.99 10.6/7.93 13.6/10.1 17.0/12.7 21.1/15.7
0.44/0.33 0.73/0.55 1.04/0.78 1.37/1.03 1.75/1.31 2.20/1.64 2.73/2.03
1.43 2.40 3.41 4.51 5.75 7.20 8.94
0.18 0.30 0.43 0.56 0.72 0.90 1.12
19
19
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +18 +6.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5
AX 54-275 6 Blades
Page Header
Total
Pressure
Impeller Diameter = 21.38 inches (543 mm)
Outlet Velocity
Tip Speed
ft/min = cfm / 2.49
m/s = m³/s / 0.23
ft/min = rpm X 5.60
m/s = rpm X 1.71
85
81
88
86
82
88
88
85
88
Air density = 1.2 kg/m Air density = 0.075 lbs/ft
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
rpm 5 10 15 20 25 30 35 3500 (Bhp/kW) 1770 (Bhp/kW) 2900 (kW) 1450 (kW)
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings Seal applies to air performance ratings only. Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and 0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
³
³
Pitch Angle º
3.02/2.26 5.30/3.96 7.73/5.77 10.4/7.75 13.4/10.0 16.9/12.6 21.0/15.7
0.39/0.29 0.69/0.51 1.00/0.75 1.34/1.00 1.74/1.29 2.19/1.63 2.72/2.03
1.28 2.25 3.28 4.41 5.69 7.18 8.92
0.16 0.28 0.41 0.55 0.71 0.90 1.12
20
20
Volume
Sound Power A-Weighted [LwA] Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA 3500 +18 +6.5 1770 - -11.5 2900 +13 +1.5 1450 -5 -16.5