The R7824C Rectification Flame Amplifier is a solid state
plug-in amplifier that responds to a rectified signal from a
C7024E,F Self-Check Ultraviolet Flame Detector to indicate
the presence of flame when used with an RM7824 Relay
Module.
PRODUCT DATA
FEATURES
• Flame failure response time of 0.8 or 1 second; or 2.0 or
3.0 seconds, depending on the amplifier and relay
module selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed
circuit board edge connector keyed for proper
orientation.
• Flame signal test jacks measure amplifier flame signal
voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading rang e.
• Color coded label identifies flame detection type:
• R7847B, R7848B, R7849B Dynamic Ampli-Check®
circuitry tests all flame amplifier components 12 times
per minute. The 7800 SERIES Relay Module locks out on
safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification
Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier
and R7886A Dynamic Self-Check Ultraviolet Amplifier
test the detectors and all electronic components in the
flame detection system 12 times per minute. The 7800
SERIES Relay Module locks out on safety shutdown
with flame detection system failure.
NOTE: R7824C, Series 2 or greater, and R7847C,
Series 4 or greater, pulse shutter when signal of
1.5 Vac is sensed.
The R7847A,B Rectification Flame Amplifiers are solid state
plug-in amplifiers that respond to a rectified signal from a
rectification type flame detector to indicate the presence of
flame when used with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a
solid state plug-in amplifier that responds to a rectified signal
from a C7012E,F Self-Check Ultraviolet Flame Detector to
indicate the presence of flame when used with 7800 SERIES
Relay Modules. This is not European Community (CE)
approved for EC7810, EC7820, EC/RM7830 or EC/RM7850
Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plugin amplifiers that respond to an infrared signal from a C7015
Infrared Flame Detector to indicate the presence of flame
when used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state
plug-in amplifiers that respond to an ultraviolet signal from a
C7027, C7035 or C7044 Ultraviolet Flame Detector to
indicate the presence of flame when used with 7800 SERIES
Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid
state plug-in amplifier that responds to an ultraviolet signal
from a C7061 Self-Check Ultraviolet Flame Detector to
indicate the presence of flame when used with 7800 SERIES
Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a
solid state plug-in amplifier that responds to a pulsed direct
current signal from a C7076A,C Ultraviolet Flame Detector
with adjustable sensitivity to indicate the presence of flame
when used with 7800 SERIES Relay Modules.
NO T E : EN298 Approved: When these amplifiers are used
with an EC7810, EC7820, EC/RM7830, or
EC/RM7850 Relay Module.
Flame Signal (V olts dc):
Minimum Acceptable: 1.25 Vdc.
Flame Signal Voltage Range (displayed on K e yboard Display
Module or measured with a 1M ohm/volt meter plugged into
amplifier test jacks): 0.0 to 5.0 Vdc.
Accessories:
Flame Simulators:
Rectification: 123514A.
Ultraviolet: 203659.
Flame Detectors (ordered separately): select from Tab le 2.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1.Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.Home and Building Control Customer Logistics
Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—62
R7824, R7847, R7849, R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
Table 2. Flame Detection Systems.
Plug-in Flame Signal AmplifiersApplicable Flame Detectors
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner
operation and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter.
Applies to R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector
wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use
C7012E,F Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame
Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously
for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or
at 4.5 seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
a
FuelTypeModels
3Gas, oil,
coal
2/3Gas, oil,
coal
2/3 Gas, oil,
coal
2/3Gas, oil,
coal
coal
coal
coal
2/3Gas, oil,
coal
Ultraviolet
C7024E,F
(Purple
Peeper®)
C7004, C7007,
Flame Rod
Holders
j
C7011 Complete
Assemblies: C7008,
C7009, Q179
C7003, C7010,
Photocell
Ultraviolet
C7013, C7014
C7012A,C.
(Purple
Peeper®)
C7004, C7007,
Flame Rod
Holders
b
C7011 Complete
Assemblies: C7008,
C7009, Q179
C7003, C7010,
Photocell
Ultraviolet
C7013, C7014
C7012A,C
(Purple
Peeper®)
Ultraviolet
C7012E,F
(Purple
Peeper®)
Infrared (Lead
C7015
Sulfide)
Infrared (Lead
C7015
Sulfide)
C7027, C7035,
(Minipeeper)
C7044
C7027, C7035,
(Minipeeper)
C7044
UltravioletC7061
Ultraviolet
C7076
(Adjustable
Sensitivity)
d
d
g
g
65-0109—63