Greenheck Amplifier User Manual

R7824, R7847, R7848, R7849,
R7861, R7886 Amplifiers for
7800 SERIES Relay Modules
APPLICATION
The R7824C Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7024E,F Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with an RM7824 Relay Module.
PRODUCT DATA
FEATURES
• Flame failure response time of 0.8 or 1 second; or 2.0 or
3.0 seconds, depending on the amplifier and relay module selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed circuit board edge connector keyed for proper orientation.
• Flame signal test jacks measure amplifier flame signal voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading rang e.
• Color coded label identifies flame detection type:
Green—rectification. Red—infrared. Purple—ultraviolet. Blue—pulsed rectification.
• R7847B, R7848B, R7849B Dynamic Ampli-Check® circuitry tests all flame amplifier components 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier and R7886A Dynamic Self-Check Ultraviolet Amplifier test the detectors and all electronic components in the flame detection system 12 times per minute. The 7800 SERIES Relay Module locks out on safety shutdown with flame detection system failure.
NOTE: R7824C, Series 2 or greater, and R7847C,
Series 4 or greater, pulse shutter when signal of
1.5 Vac is sensed.
The R7847A,B Rectification Flame Amplifiers are solid state plug-in amplifiers that respond to a rectified signal from a rectification type flame detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a solid state plug-in amplifier that responds to a rectified signal from a C7012E,F Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules. This is not European Community (CE) approved for EC7810, EC7820, EC/RM7830 or EC/RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plug­in amplifiers that respond to an infrared signal from a C7015 Infrared Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state plug-in amplifiers that respond to an ultraviolet signal from a C7027, C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid state plug-in amplifier that responds to an ultraviolet signal from a C7061 Self-Check Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a solid state plug-in amplifier that responds to a pulsed direct current signal from a C7076A,C Ultraviolet Flame Detector with adjustable sensitivity to indicate the presence of flame when used with 7800 SERIES Relay Modules.
Contents
Application............................................................................. 1
Features ................................................................................ 1
Specifications ........................................................................ 2
Ordering Information ............................................................. 2
Installation ............................................................................. 4
Checkout ............................................................................... 6
65-0109-6
R7824, R7847, R7849, R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
SPECIFICA TIONS
Models:
Flame Detection Systems (see Table 2):
Rectification:
R7824C for use with C7024E,F Solid State Ultra violet
Detectors.
R7847A for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors .
R7847B for use with flame rods, rectifying photocells or
C7012A,C Solid State Ultraviolet Detectors .
R7847C for use with C7012E,F Solid State
Ultraviolet Detectors.
Infrared:
R7848A for use with C7015 Infrared (lead sulfide) Detector . R7848B for use with C7015 Infrared (lead sulfide) Detector .
Ultraviolet:
R7849A for use with C7027/C7035/C7044 Minipeeper
Ultraviolet Detectors.
R7849B for use with C7027/C7035/C7044 Minipeeper
Ultraviolet Detectors. R7861A for use with C7061A Ultraviolet Detector . R7886A for use with C7076A,D Ultraviolet Detectors with
adjustable sensitivity .
Flame Failure Response Time :
See T able 1.
Table 1. Relay Module Flame Failure Response Time (FFRT).
Flame Failure Response
Time (FFRT)
Relay Module
EC7810, EC7820,
EC/RM7830, EC/RM7850
RM/EC7823, RM/EC7885, RM/EC7890, RM/EC7895,
RM7896, RM7888, RM7838,
RM7800, RM7840
RM7824 N/A 3.0
0.8 or 1.0 seconds
1.0 2.0
0.8 3.0
2.0 or 3.0 seconds
Envir onmental Ratings:
Ambient T emper ature:
Operating: -40 °F to 140°F (-40°C to 60°C).
Storage: -40°F to 150°F (-40°C to 65°C). Humidity: Oper ating 85% rh continuous, noncondensing. Vibration: Contin uous 0.5G environment.
Dimensions:
See Fig. 1.
S
3-9/16 (91)
–+
FLAME AMPLIFIER
3
(76)
3/8 (9)
7/8 (23)
M11460
Fig. 1. Flame amplifier dimensions in in. (mm).
Weight:
2.5 oz (71g), unpacked.
Approvals:
Underwriters Laboratories Inc. Listed: File no. MP268, Guide no.
MCCZZ: R7847A, R7847B , R7847C , R7861A, R7886A,
R7848A, R7848B, R7849A, R7849B. Underwriters Laboratories Inc. Component Recognized: File no.
MP268, Guide no. MCCZZ: R7824C. Canadian Standards Association Certified: LR95329-3. Factory Mutual Approv ed: Report J.I.1V9A0.AF. Industrial Risk Insurers: Acceptable .
NO T E : EN298 Approved: When these amplifiers are used
with an EC7810, EC7820, EC/RM7830, or EC/RM7850 Relay Module.
Flame Signal (V olts dc):
Minimum Acceptable: 1.25 Vdc. Flame Signal Voltage Range (displayed on K e yboard Display
Module or measured with a 1M ohm/volt meter plugged into amplifier test jacks): 0.0 to 5.0 Vdc.
Accessories:
Flame Simulators:
Rectification: 123514A.
Ultraviolet: 203659. Flame Detectors (ordered separately): select from Tab le 2.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0109—6 2
R7824, R7847, R7849, R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
Table 2. Flame Detection Systems.
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Flame Failure
Type Color Self-Checking Model
Rectification Green Dymanic Self-
R7824C
b,c, i
Time (sec)
Check
Response
No
No
No
Dynamic
R7847A
R7847A
R7847A
R7847B
h
h
h
e,h
0.8/1 or 2/3 Gas Rectifying
0.8/1 or 2/3 Oil Rectifying
0.8/1 or 2/3 Gas Rectifying
Ampli-Check®
Dynamic
R7847B
e,h
0.8/1 or 2/3 Oil Rectifying
Ampli-Check® Dynamic
R7847B
e,h
Ampli-Check®
Dynamic
R7847C
c,f, i
Self-Check
Infrared Red No R7848A 2/3 Gas, oil,
Dynamic
R7848B
e
3 sec Gas, oil,
Ampli-Check®
Ultraviolet Purple No R7849A 0.8/1 or2/3 Gas, oil Ultraviolet
Dynamic
R7849B
d
0.8/1 or 2/3 Gas, oil Ultraviolet
Ampli-Check® Dynamic
R7861A
c,f
0.8/1 or 2/3 Gas, oil,
Self-Check
,f
Blue Dynamic
R7886A
c
Self-Check
a
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES Relay Module.
b
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.
c
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down burner if detection system fails.
d
Use only Honeywell part no. 38316 Photocell.
e
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.
f
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies to R7847C series 3 or greater; R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.
g
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use C7012E,F Flame Detector with R7847C Amplifier, C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detection system for appliances with burners that remain on continuously for twenty-four hours or longer.
h
R7847A,B Amplifiers with 0.8/1 second FFRT should not be used with C7012A,C Solid State Ultraviolet Detectors.
i
R7824C Series 2 and greater and R7847C Series 4 and greater check flame detector system when flame reaches 1.5 Vdc or at 4.5 seconds, whichever occurs first.
j
Order flame rod separately; see flame detector Instructions for holder.
a
Fuel Type Models
3 Gas, oil,
coal
2/3 Gas, oil,
coal
2/3 Gas, oil,
coal
2/3 Gas, oil,
coal
coal
coal
coal
2/3 Gas, oil,
coal
Ultraviolet
C7024E,F (Purple Peeper®)
C7004, C7007, Flame Rod Holders
j
C7011 Complete
Assemblies: C7008,
C7009, Q179
C7003, C7010, Photocell
Ultraviolet
C7013, C7014
C7012A,C. (Purple Peeper®)
C7004, C7007, Flame Rod Holders
b
C7011 Complete
Assemblies: C7008,
C7009, Q179
C7003, C7010, Photocell
Ultraviolet
C7013, C7014
C7012A,C (Purple Peeper®)
Ultraviolet
C7012E,F (Purple Peeper®)
Infrared (Lead
C7015 Sulfide)
Infrared (Lead
C7015 Sulfide)
C7027, C7035, (Minipeeper)
C7044
C7027, C7035, (Minipeeper)
C7044 Ultraviolet C7061
Ultraviolet
C7076 (Adjustable Sensitivity)
d
d
g
g
65-0109—63