Installation, Operation, and Maintenance Instructions
This manual is the property of the owner, and is required for future maintenance. Please leave it with the
owner when the job is complete.
Safety Warning:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing
this equipment.
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all
necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts
of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of 100°F (37ºC).
Due to continuing research, Greenheck reserves the right to change specifications without notice.
Pre-Installation Guidelines
The basic intent of a proper installation is to secure
the AMD-xx-TD series damper into the opening
in such a manner as to prevent distortion and
disruption of damper operation. The following items
will aid in completing the damper installation in a
timely and effective manner.
1. Check your schedule for proper damper locations
within the building. Visually inspect the damper
for damage.
2. When you lift or handle the damper use the sleeve
or frame. Do not lift damper using blades, linkage,
actuators, probes, or jackshafting. When you
handle multiple section assemblies, use sufficient
support to evenly lift at each section mullion (see
drawing). Do not drag, step on, apply excessive
bending, twisting, or racking.
3. Do not install screws in damper frame that will
interfere with unexposed blade linkage and prevent
damper blades from opening and/or closing.
Pre-Installation Guidelines cont...
4. Damper must be installed into duct or opening
square and free of twist or other misalignment.
Spreader Bar
Attachments
Multi section dampers
Damper must not be squeezed or stretched into
duct or opening. Out of square, racked, twisted
or misaligned installations can cause excessive
leakage and/or torque requirements to exceed
damper/actuator design.
5. Damper, actuator, and transmitter must be kept
clean, dry and protected from dirt, dust and other
foreign materials prior to and after installation.
Examples of such foreign materials include but
are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
6. Damper should be sufficiently covered as to
prevent overspray if wall texturing or spray
painting will be performed within 5 feet (1.5m)
of the damper. Excessive dirt or foreign material
deposits on the damper can cause excessive
leakage and/or torque requirements and
inaccurate airflow measurement to exceed
damper/actuator design.
7. ACCESS: Suitable access (actuators maintenance,
etc.) must be provided for damper inspection
and servicing. Where it is not possible to achieve
sufficient size access, it will be necessary to
install a removable section of duct.
Installation- Failure to follow instructions will void all warranties
1. Ensure the AMD-xx-TD series damper is
mounted with measurement probes upstream
of the damper.
2. Your duct opening or opening square should
measure 1/4 inch (6mm) larger than damper
dimension and should be straight and level.
3. Use shims between damper frame and
duct opening or opening space to prevent
distortion of frame by fasteners holding it
in place. Brace at every horizontal mullion
and vertically brace at every 8 feet (2.4m) of
damper width for strength. Dampers in high
velocity (2000 fpm [610m per second]) may
require more bracing.
Note: Greenheck dampers are specifically
designed and engineered for structural
integrity based on model and conditions.
Attachment, framing, mating flanges,
and anchoring of damper assemblies
into openings, ductwork, or walls is the
responsibility of the installer. Design
calculations for these retaining and
supporting members should be determined
by field engineers for that particular
installation.
4. Individual damper sections, as well as
entire multiple section assemblies must be
completely square and free from racking,
twisting, or bending. Measure diagonally from
upper corners to opposite lower corners of
each section.
5. Damper blades, axles, and linkage must
operate without binding. Before system
operation, you can cycle dampers after
2
A
C
E
installation to assure proper operation. On
multiple section assemblies all sections
should open and close simultaneously.
6. AMD-xx-TD series more than one section
high will be shipped separately in individual
sleeves. Using the provided RJ-45 cable
connect the bottom probe on the top section
to the top probe on the bottom section. The
bottom section has the transmitter mounted
to it.
B
Do not twist
D
AF = BE
AB = CD
F
or bow. Mount
damper plumb
in the opening.
Electrical Guidelines
Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable codes, ordinances and regulations.
SAFETY CAUTION !
Verify power requirements before wiring
actuator. Greenheck is not responsible for
any damage to, or failure of the unit caused
by incorrect field wiring.
Connect electrical connection to terminal strip as shown in drawings on pages 4 and 5.
Electrical input may be needed for
this equipment. This work should be
performed by a qualified electrician.
SAFETY DANGER !
Setup and Operation for AMD-xx-TD Series Damper
All AMD-xx-TD’s are supplied with a Vari-Green®
airflow rate transmitter that is factory wired to one or
more Vari-Green airflow measurement probe(s). The
transmitter has been configured at the factory with
customer supplied parameters. For normal applications
the transmitter’s configuration should not need to be
modified in the field. However, if field configuration is
necessary please reference the Vari-Green transmitter
Installation, Operation, and Maintenance Manual
available at www.greenheck.com.
Once electrical power is applied, the transmitter
will go through a standard start-up sequence
during which it will identify and enable each airflow
sensor. This will take approximately 30 seconds.
Once the start-up sequence has been completed
the transmitter's display will show the measured
volumetric airflow rate, velocity, and ambient air
temperature (see below). Under normal operation a
dot in the upper right corner of the display will blink
rapidly (4 times per second).
You can order AMD-xx-TD’s with or without a factory supplied controller. When a factory supplied controller
is ordered, the controller can be configured for either analog operation or operation via a BACnet MS/TP
connection. Setup and operation for these different options are described on the following pages.
3
AMD-xx-TD Series Dampers without a Factory Supplied Controller
Units ordered without a factory supplied controller
are supplied with a standard modulating actuator.
The Vari-Green transmitter and actuator are wired to
a factory supplied terminal block. Figure 1 shows the
field wiring side of the terminal block.
The 0-10 VDC analog output at terminals 3 and
4 comes from the Vari-Green transmitter and is
proportional to the velocity going through the
AMD-xx-TD. A 10 VDC signal represents the
maximum velocity that was selected at the time the
unit was ordered. The selected maximum velocity
and the area of the AMD-xx-TD are listed on a label
adjacent to the terminal block. An example of how
you can determine the velocity and/or cfm going
through the unit is shown below.
Figure 1
Example 1: Determine the CFM from a 24 in.
x 24 in. AMD-xx-TD (area of 4 ft2) with a selected
maximum velocity of 2,000 fpm and a voltage reading
across terminals 3 and 4 of 3.5 VDC.
AMD-xx-TD’s Ordered with a Factory Supplied Controller
When you order a factory supplied controller, it comes with a Greenheck exclusive VAFB24-BAC-GTD actuator
which has the controller integrated inside of it. The actuator/controller is configured by the factory at the time
the unit is ordered for either analog or BACnet operation. This selection is made by setting the Setpoint Source
datapoint to Local AI or BACnet. A complete list of the all the BACnet datapoints is listed in Table 1 (page 7).
AMD-xx-TD Series Dampers with an Analog Factory Supplied Controller
Figure 2 shows field wiring for an AMD-xx-TD ordered with a factory supplied controller configured for analog
operation.
Factory Installed
Terminal Block
1
~
24VAC
Figure 2
S
45
Flow
23
0-10 VDC Output
Proportional to
S
0-10VDC
Input
Setpoint
7
6
AMD-XX-TD w/Analog
Factory Supplied
Controller
8
9
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.