Greenheck AMD Installation Manual

Page 1
®
Vari-Green Constant Volume Controller
for AMS & AMD Damper Series
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
These instructions apply to Greenheck’s Vari-Green Constant Volume damper controller. The controller accepts an analog output from a factory supplied pressure transducer on a Greenheck AMS airflow measuring station or AMD airflow measuring damper to calculate the realtime volumetric airflow rate (cfm) going through the unit. Using PID logic the controller then controls the damper’s actuator to achieve a target cfm setpoint. The cfm setpoint can be established either remotely via an analog input to the controller or locally using touch sensitive buttons on the cover of the controller.
Table of Contents
General Operation of the Controller .............2
• Setting the Flow Setpoint ...................... 2
• Airflow Output Signal ............................. 2
Document number 479830
Varigreen Damper
Controller
Controller Display and Interface Buttons ...2-3
Controller Configuration ............................3-6
• Factory Configuration .........................3-4
• Field Configuration ..............................4-6
• Manual Control ......................................6
• Factory Defaults ....................................6
Diagnostic LED ............................................. 7
Wiring of Controller ...................................7-8
Receiving
Upon receiving the control, check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make notification of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Greenheck Representative. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts.
Storage
Controls are protected against damage during shipment. If the control cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the control during storage. The user assumes responsibility of the control and any accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
Indoor
The ideal environment for the storage of controls is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain or snow. Temperatures should be evenly maintained between 30° to 110°F (-1° to 43°C). Wide temperature swings may cause condensation and “sweating” of metal parts. All accessories must be stored indoors in a clean, dry atmosphere.
Removing from Storage
As controls are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the control goes into operation.
1
Page 2
General Operation of the Controller
The Vari-Green Constant Volume Controller has two operating modes. The controller is factory set to its Flow Control Mode. In Flow Control Mode the controller will modulate the position of the damper to achieve a target airflow setpoint. The controller can also be put into Position Control Mode. In Position Control Mode the controller treats the setpoint as a target damper blade position.
In addition to the two operating modes the controller has a parameter called Setpoint Location that can be configured to either Remote or Local. The controller ships from the factory with the Setpoint Location set to Remote. In Remote mode the controller uses a voltage sent to one of its analog inputs to establish the setpoint (see the Setting the Flow Setpoint section below). When the Setpoint Location is in Local mode the interface on the front cover of the controller is used to establish the setpoint and the voltage sent to the analog input is ignored.
See the Field Configuration section of this document to learn how to change the Control Mode and Setpoint Location. The following section assumes that the controller is in the factory default Flow Control and Remote Setpoint Location modes.
Setting the Flow Setpoint
The controller accepts an analog input (configurable for either 0-10 or 2-10 VDC) that is proportional to a target volumetric airflow rate (cfm). The voltage corresponding to the setpoint can be determined using the following formulas:
0 - 10 VDC setpoint
C = Q /(V
2 - 10 VDC setpoint
C = Q /(V
Formula 1
Where:
C = Flow Setpoint (VDC)
Q = Desired Airflow (cfm)
V
= Maximum Velocity as specified at the time the unit
max
was ordered (fpm)
A = Face Area of the Damper (ft2)
max
* A) * 8 + 2
max
* A) * 10
Airflow Output Signal
The controller outputs an analog signal (configurable for either 0-10 or 2-10 VDC) that is proportional to the real-time airflow rate (cfm) going through the AMD/AMS. The cfm corresponding to the voltage output can be determined using the following formulas:
0 - 10 VDC setpoint
Q = (C * V
max
* A) /10
2 - 10 VDC setpoint
Q = ((C - 2) * V
max
* A) /8
Formula 2
Where:
C = Voltage Output Signal (VDC)
Q = Real-time Airflow (cfm)
V max = Maximum Velocity as specified at the time the unit
was ordered (fpm)
A = Face Area of the Damper (ft2)
Controller Display and Interface Buttons
There are four touch sensitive buttons on the controller’s cover that are used to interface with the controller: Back, Enter, Up and Down (see Figure 2).
Figure 1 - Label affixed to AMS/AMD that lists the V
Example: The BMS desires 2,000 cfm through a 24 in. x 24 in. AMD-42 that was ordered with a maximum velocity of 1,000 fpm. Find the voltage setpoint that corresponds to 2,000 cfm:
C = 2,000 / (1,000 * 4) * 10 = 5 VDC (0-10 VDC)
C = 2,000 / (1,000 * 4) * 8 +2 = 6 VDC (2-10 VDC)
2
and damper area.
max
DisplayBack Button
Up Arrow
Figure 2 - Outside of the controller's cover
Down Arrow Enter Button
Page 3
Controller Display and Interface Buttons cont...
The controller also has a two line backlit LCD display. By using the up and down arrows the display can be toggled through three sets of data:
XXXXX CFM Setpt XXXXX CFM
Top Screen: Real-Time CFM and CFM Setpoint
Middle Screen: Real-Time Velocity (fpm) and Velocity Setpoint
XXXX FPM Setpt XXXX FPM
Bottom Screen: Real-Time Differential Pressure Measurement and Actuator Position
X.XX in WC Act XX.X% Open
Figure 3 - Run Mode display screens
Controller Configuration
The Vari-Green Constant Volume Controller is shipped in “Run Mode”. When calculating the airflow rate going through the AMS/AMD and to control the damper (on AMD models) the controller should be left in run mode. In most cases the controller should not need to be taken out of run mode. However, a variety of parameters can be adjusted in the field as needed by opening the controller’s cover and moving the toggle switch into the PROG position (see Figure 2).
When in program mode the display can be toggled through a “Top Level Menu” by using the up and down arrows on the controller’s cover (see Figure 4). The desired menu item can be accessed by pressing the “Enter” button.
Factory Config Enter to Select
Field Config Enter to Select
Manual Control Enter to Select
Factory Defaults Enter to Select
Figure 4 - Top level menu in Program Mode.
Factory Configuration
The controller comes from the factory configured with the physical parameters of the AMD/AMS it was ordered with. These parameters include:
Flow Measurement Device – should always be left as
“Diff Pressure”
The unit’s K & M Values – damper specific constants
used to calculate airflow. These values are set at the factory and can also be found on the label affixed to the AMD/AMS (see Figure 1)
Maximum Pressure – this parameter represents
the top-end of the AMD/AMS pressure transducer range. The selectable values are: 0.25” wc, 0.5” wc,
1.0” wc, 2.0” wc, 2.5” wc, 3.0” wc, and 5.0” wc. The maximum pressure is also a configurable value on the pressure transducer (see the transducer instructions). The top-end of the controller’s pressure range and the transducer’s pressure range must match for the controller to operate properly. They are set at the factory to the same values.
Damper Area - the face area of the AMD/AMS (ft2)
Maximum Velocity – this parameter represents the velocity corresponding to a 10 VDC remote setpoint. This parameter is set by the factory to the value selected at the time the unit was ordered. The selectable values are: 500 fpm, 1000 fpm, 1500 fpm, 2000 fpm, 2500 fpm, 3000 fpm, 3500 fpm and 4000 fpm. To achieve optimal accuracy the lowest value that meets the application should be selected. Changing the maximum velocity value will affect the flow setpoint and flow output calculations. See formulas 1 and 2 on page 2.
Minimum Velocity – this is the minimum velocity the unit is designed to accurately measure airflow and control the damper at. To avoid “hunting” the controller will treat setpoints below the minimum velocity as a setpoint of zero. The controller is set to a value of 300 fpm at the factory.
While the parameters in the factory configuration menu don’t normally require adjustment, they can be changed by putting the controller into Program Mode (see above) and then pressing enter on the “Factory Config” option in the top level menu. The factory configuration menu structure, see Figure 5, can be navigated by using the up and down arrows on the controller’s cover. When the parameter you wish to adjust is shown in the display press the "Enter" button to enter the edit mode. The parameter can then be adjusted by using the up and down arrows (parameter will blink on display when in edit mode). Once the desired value is selected press "Enter" again to leave edit mode. Once all of the parameters have been adjusted press the "Back" button on the controller to return to the top level menu or return the slider switch inside the controller to run mode.
3
Page 4
Return
Flow Measure Dev Thermal Disp
Flow Measure Dev Diff Pressure
AMD “K” Value 2000
AMD “M” Value
0.5
Maximum Pressure
1.00 in WC
Damper Area
4.00 ft^2
Maximum Velocity 2,000 FPM
Minimum Velocity 300 FPM
Figure 5 - Factory Configuration Menu Structure
Field Configuration
The controller comes from the factory with the parameters in the field configuration menu (see Figure 6) set to the most commonly used values. The field configuration menu can be accessed from the top level menu (see Figure 4).These parameters include:
Units of Measure – the controller comes with imperial units selected. The controller can be configured to display in metric units.
Actuator Setpoint – this parameter sets the type of analog output signal the controller will use to control the damper’s actuator. The default selection is 2-10 VDC, but the controller can be configured to send a 0-10 VDC signal to the actuator.
Velocity Output – this parameter sets the type of analog signal the controller uses to output the airflow rate. The default selection is 0-10 VDC, but the controller can be configured to output a 2-10 VDC signal.
Control Mode – this parameter determines how the controller treats the setpoint. The default selection is Flow Control mode. In Flow Control mode the controller treats the setpoint as the desired airflow (cfm). See the section on Setting the Flow Setpoint. The controller can also be put into Position Control mode. In this mode the controller treats the setpoint as the desired position of the actuator.
Setpoint Location – this parameter determines where the controller gets its setpoint from. The default setpoint location is Remote. In Remote setpoint location mode the controller uses the signal from its analog input as the target setpoint. See the section on Setting the Flow Setpoint. The controller can also be put into Local setpoint location mode. In Local setpoint location mode the controller will ask for a Flow or Damper Position setpoint (depending on the selected control mode) to be entered using the up
and down arrows on the controller’s cover when in the Field Configuration Menu (see the Field Configuration menu structure). When the controller’s toggle switch is moved back into run mode it will control the damper to the entered setpoint instead of the value sent to the analog input. Local setpoint mode should be used when the desired flow or position setpoint is constant.
Setpoint Input - this parameter sets the type of analog signal that will be sent to the controller as the remote setpoint. The default selection is 0-10 VDC, but the controller can be configured to accept a 2-10 VDC signal.
Field Correction – this parameter can be used to adjust the airflow calculation of the controller. The default value is 1.0. Changing this value will adjust the calculated flow proportionally. For example, setting the Field Correction factor to 0.95 will reduce the calculated flow values by 5%. Setting it to 1.05 will increase the calculated flow by 5%.
Air Density Correction – this parameter adjusts the airflow calculation to account for changes in the dry bulb temperature of the air being measured and/or the elevation above sea level of the jobsite. The default value is 1.00, which corresponds to an air temperature of 70° F and an elevation of 0 ft. Table 1 shows the Air Density Correction as a function of air temperature and elevation
Response Time – this parameter determines how the controller responds to changes in the setpoint or system conditions. The controller has three available response times. It comes from the factory set to the fastest response time. If, because of system conditions, the controller is “hunting” without settling on a point one of the slower response times should be selected. The Medium response time should be tried first. If the controller is still not settling on a point the Slow setting should be used.
4
Page 5
Field Configuration cont....
Control Deadband – this parameter determines the range of acceptable values around the setpoint that the controller will attempt to achieve. The factory default Control Deadband is 25 fpm. As an example, with a 25 fpm deadband and a setpoint of 1,000 fpm the controller will adjust the damper’s position until the real-time velocity is between 975 fpm and 1,025 fpm (note that fpm can be converted to cfm by multiplying by the AMD/AMS area). Larger deadbands will make it easier for the controller to reach an acceptable point, but may result in the realtime flow being further from the setpoint.
Override Out – the controller has a voltage free non- grounded contact that can be used to override the normal operation of the controller. When the contact is
Units of Measure Imperial
Actuator Setpnt 0 to 10 VDC
open the controller functions normally. However, if the contact is closed the controller will drive the actuator to an override position. The override position is set to 100% open from the factory, but may be adjusted to any position between 0 and 100%.
Sensor Filter – this parameter establishes the amount of averaging the controller performs on the pressure reading before it updates the airflow calculation. The factory default setting is 3 seconds. The value should not be adjusted below 3 seconds and should only be increased above 3 seconds if turbulence such as wind gusts result in sporadic airflow measurement readings. If the sensor filter is increased above 3 seconds one of the slower response time settings will likely need to be used to avoid the actuator hunting for the setpoint.
Units of Measure Metric
Actuator Setpnt 2 to 10 VDC
Setpoint Input 0 to 10 VDC
Setpoint Location: Remote
Setpoint Input 2 to 10 VDC
Response Time Fast
Velocity Output 0 to 10 VDC
Control Mode Flow
Setpoint Location: Local
Flow Setpoint XXXX CFM
Field Correction
1.00
Air Density Corr
1.00
Response Time Medium
Control Deadband 20 FPM
Velocity Output 2 to 10 VDC
Control Mode Position
Setpoint Location: Local
Damp Pos Setpnt XX%
Response Time Slow
Setpoint Input 0 to 10 VDC
Setpoint Location: Remote
Setpoint Input 2 to 10 VDC
Override Out % 100%
Sensor Filter 0 Seconds
Return
Figure 6- Field Configuration Menu Structure
5
Page 6
Duct Air
Temp
°F
(Deg. C)
-40 (-40) 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.9 0.92 0.93 0.95 0.97 0.99
-20 (-29) 0.83 0.85 0.86 0.88 0.89 0.91 0.93 0.94 0.96 0.98 0.99 1.02 1.04 0 (-18) 0.87 0.88 0.9 0.92 0.93 0.95 0.97 0.99 1 1.02 1.04 1.06 1.08
20 (-7) 0.91 0.92 0.94 0.96 0.97 0.99 1.01 1.03 1.05 1.07 1.08 1.11 1.13 40 (4) 0.94 0.96 0.98 1 1.01 1.03 1.05 1.07 1.09 1.11 1.13 1.16 1.18 70 (21) 1 1.02 1.04 1.06 1.08 1.1 1.12 1.14 1.16 1.18 1.2 1.22 1.25
80 (27) 1.02 1.04 1.06 1.08 1.1 1.12 1.14 1.16 1.18 1.2 1.22 1.25 1.27 100 (38) 1.06 1.08 1.1 1.12 1.14 1.16 1.18 1.2 1.22 1.25 1.27 1.29 1.32 120 (49) 1.09 1.11 1.13 1.16 1.18 1.2 1.22 1.24 1.27 1.29 1.31 1.34 1.37 140 (60) 1.13 1.15 1.17 1.2 1.22 1.24 1.26 1.29 1.31 1.34 1.36 1.39 1.41 160 (71) 1.17 1.19 1.21 1.24 1.26 1.28 1.31 1.33 1.35 1.38 1.4 1.43 1.46 180 (82) 1.21 1.23 1.25 1.28 1.3 1.32 1.35 1.37 1.4 1.42 1.45 1.48 1.51 200 (93) 1.25 1.27 1.29 1.32 1.34 1.36 1.39 1.42 1.44 1.47 1.49 1.53 1.55
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
(0) (152.4) (304.8) (457.2) (609.6) (762) (914.4) (1066.8) (1219.2) (1371.6) (1524) (1676.4) (1828.8)
Air Density Correction Factors
Elevation Dimensions in feet and (meters)
Table 1 - Air Density Correction Factor
Manual Control
Manual Control mode allows the user to directly change the percent the damper is open by using the up and down arrows on the controller’s cover. This can be done by entering the top level menu, scrolling down to Manual Control, and pressing "Enter". You can leave Manual Control mode at any time by pressing the "Back" button or by putting the slider switch inside the controller back into the run position.
Factory Defaults
For trouble shooting purposes, it may be desirable to reset the controller’s parameters back to the factory defaults. This can be done by entering the top level menu, scrolling down to “Factory Defaults” and pressing enter. You will see an option to “Resort Factory Defaults”. Select Yes and then select Yes again when asked “Are You Sure?”. Once this is done you will need to go through each parameter in both the factory and field configuration menus and select the appropriate value.
6
Page 7
Diagnostic LED
Wiring the Controller
The controller has a multicolor LED that is used to distinguish between operating modes and to indicate trouble conditions.
Solid Green – Flow Control with Remote Setpoint (Control Mode = Flow; Setpoint Source = Remote; Request Velocity >= Minimum Velocity)
Blinking Green – Flow Control with Local Setpoint (Control Mode = Flow; Setpoint Source = Local; Request Velocity >= Minimum Velocity)
Solid Blue – Position Control with Remote Setpoint (Control Mode = Position Setpoint Source = Remote; Request Velocity >= Minimum Velocity)
Blinking Blue – Position Control with Local Setpoint (Control Mode = Position Setpoint Source = Local; Request Velocity >= Minimum Velocity)
Solid Purple – Parameter Editing or Manual Mode
Solid Pink – Override activated
Blinking Yellow – Low Velocity Setpoint. The LED will blink yellow when the requested velocity is greater than 20 fpm, but less than the minimum velocity parameter. This indicates that the user is sending a velocity request, but that it is under the defined minimum velocity.
Blinking Red – No Velocity Setpoint. When in Remote Setpoint Source mode regardless of the control mode, if the velocity request is less than 20 fpm the LED should blink red.
The basic wiring of the controller is shown below in Figure
7. The controller’s three terminal blocks can be accessed by opening the cover of the enclosure.
Powering the Controller
The controller is powered by applying electrical power to the “Power In” terminal block. The controller can run off of 24 VAC +/- 20% 50/60 Hz or 24 VDC +/- 10%
Connecting the Pressure Transducer
The second terminal block is labeled “Remote Sensor” and is used to connect to the pressure transducer. The three terminals from the Remote Sensor block connect directly to the pressure transducer as shown in Figure 6. The controller supplies the transducer with its power and reads the pressure signal.
Connecting the Damper Actuator
The actuator can be powered either by the same power supply as the controller, as shown in Figure 7, or by running a separate power supply to terminals 4 and 5 of the factory supplied terminal block on the AMD/AMS. In addition, the “Control Out” from the controller (terminal 7) must be run to terminal 6 on the damper’s terminal block.
Connecting the Flow (or position) Set­point Signal
Connect the 0-10 VDC or 2-10 VDC flow (or position) setpoint to the controller terminals 1 and 3. The controller’s terminal 1, labeled Remote Setpoint, is the positive terminal and the controller’s terminal 3 is the common terminal.
Connecting to the Flow Output Signal
Connecting to controller terminals 6 and 3 allows the user to read the 0-10 VDC or 2-10 VDC flow output that is proportional to the cfm measured by the AMD/AMS. To convert the voltage signal to cfm see the section above on Airflow Output Signal.
Override Mode
The functionality of the override feature is described above in the Field Configuration section of this document. The override feature can be activated by closing the contacts of an external relay across terminals 2 and 3 (or by simply putting a jumper wire across them).
7
Page 8
Vari-Green Constant Volume Controller Wiring Diagram
Remote Transducer Wiring Connector
Control Wiring Connector
PROG/RUN Switch
Power Wiring Connector
All wiring above terminal block done at factory when the actuator is externally mounted. When the actuator is internally mounted the actuator must be wired to the terminal block in the field.
Figure 7 - Basic Wiring of Vari-Green Constant Pressure Controller
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warrantees can be located on greenheck.com within the product area tabs and listed in the Library under Warrantees.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
479830 • BAPI Controller for AMD & AMS, Rev. 1, April 2015 Copyright 2015 © Greenheck Fan Corporation
Loading...