Greenheck ABD Series Installation, Operation And Maintenance Manual

Page 1
®
Document 483591
ABD Series
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
These instructions apply to the automatic balancing damper, including dampers with a transition and a grille mount box. The ABD is a reversible product and can be used for exhaust or supply applications.
NOTE: The ABD is air flow dependent and the direction of airflow through the product is critical for proper operation.
See complete marking on product.
UL 2043 Classification R39668
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Table of Contents
General Installation ............................................ 2
Round Duct/Opening Installation ...................... 2
Square Duct/Box Transition Installation ........... 3
Grille Mount Box Installation ............................. 3
Operation - CFM Set-Point Adjustment ............ 4
Maintenance ..................................................... 4
Safety Warning
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when the job is complete.
Automatic Balancing Dampers 1
Page 2
General Installation
®
Greenheck’s ABD dampers can be installed anywhere a constant volume of air is required. Assure that the airflow direction is properly aligned for your application (see Figure 1).
The ABD is designed for installation without the need for any screws or fasteners. The adjustment of the cfm set-point is accomplished by positioning the set-point indicator to the notch corresponding to the desired cfm (see Figure 2). The damper must be mounted such that the set-point ridges are located on the bottom of the damper (see Figure 3).
Airflow
Figure 1
Figure 3
Figure 2
Round Duct/Opening Installation
The damper can be pressed into a round duct without the need for fasteners. The provided perimeter gasket provides a press fit grip to hold the valve in place without the need for additional fasteners or adhesives.
Remove the adapter plate from the end of the ABD and slide the damper into either spiral duct or round duct (see Figure 4), or any rigid round opening, such as the neck of a diffuser.
Note: The perimeter gasket material can be removed from one end and moved to the opposite end if needed for installation.
Figure 4
Automatic Balancing Dampers2
Spiral Duct or Round Collar
(by others)
Page 3
Square Duct/Box Transition Installation
®
Installation into square duct requires a square to round transition. Greenheck model ABD-T is supplied with a factory square to round transition. The size of the transition can be specified at the time it is ordered. (see Figure 5).
The square to round transition can be inserted into a square duct or plenum box (see Figure 6). Sheet metal screws can then be used to secure the ABD-T into place.
Note: If the valve is installed in a continuous duct run, an access panel or door should be provided for periodic cleaning, inspection, or adjustment.
4 in. model with 6 in. x 6 in.
transition shown
Figure 6Figure 5
Grille Mount Box Installation
Greenheck model ABD-GM is designed for applications where round duct terminates at a square grille. The ABD-GM is supplied with a factory installed grille mounting box (see Figure 7). The grille can also be factory supplied. Factory supplied grilles are shipped loose. Screws can be used to secure the grille mount box into place.
Figure 7
Automatic Balancing Dampers 3
Page 4
Operation - CFM Set-Point Adjustments
The design of the Greenheck ABD allows for easy field adjustment to over 20 cfm set-points.The set-point range for the 4 and 5 inch damper is 25 to 125 cfm. For the 6 inch damper, the range is 55 to 250 cfm.
Adjusting the damper to the target cfm set-points can be done without tools. Simply slide the set-point indicator on the face of the damper to the desired point.
The damper should only be adjusted by means of the adjustment arm. Do not operate the damper via the blade. Adjusting or operating the damper by the blade can change the tension of the stainless steel spring and could change the operating range of the damper.
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, wash with water. No solvents should be used in cleaning, as they could damage the valve or gasket. In addition, ABD dampers incorporate Steri-BalanceTM into all plastic components. Steri-Balance inhibits antimicrobial growth.
TM
is a non-caustic material that
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.
®