Greenheck 452413 User Manual

Document 452413
Kitchen Hoods
®
Type I and Type II
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
Type IIType I
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near a fan. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) and ULC-S650 in Canada.
2. The rotation of the fan wheel is critical. It must be free to rotate without striking or rubbing any stationary objects.
3. Fan motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan rpm. Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to a duct while the fan is running.
®
Kitchen Hoods • Type I and Type II
1
Receiving
Upon receiving the product, check to make sure all items are accounted for by referencing the packing list and ensuring all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and filed with the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading. Filters are shipped on a separate skid in their original packaging. Do not remove factory packaging or install filters until just prior to commissioning. Remove all other shipping/packing materials including fan tie down straps.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR - The ideal environment for the storage of
units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C). Wide temperature swings may cause condensation and “sweating” of metal parts. All accessories must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts, allow cold parts to reach room temperature. To dry parts and packages, use a
portable electric heater to get rid of any moisture buildup. Leave coverings loose to permit air circulation and to allow for periodic inspection.
OUTDOOR - Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The unit should be placed on a level surface to prevent water from leaking into it. The unit should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance during Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. Every three months, the fan motor should be energized. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint­free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
• Check all fasteners, set screws on the fan, wheel,
• Rotate the fan wheel(s), where applicable, by hand
® or the equivalent.
bearings, drive, motor base, and accessories for tightness.
and assure no parts are rubbing.
Kitchen Hoods • Type I and Type II
2
®
Table of Contents
Receiving, Unpacking, Handling and Storage . . . . .2
Inspection and Maintenance during Storage . . . . . .2
Removing from Storage . . . . . . . . . . . . . . . . .2
Hood Weight . . . . . . . . . . . . . . . . . . . . . . .3
Installation
Wall or Single Island Style Hoods . . . . . . . . . . . .4
Hood Installation Overview . . . . . . . . . . . . . . .4
Hanging the Hood . . . . . . . . . . . . . . . . . . . .4
Filler Panel Installation . . . . . . . . . . . . . . . . . .5
Installing Back Supply Plenum . . . . . . . . . . . . .5
Installing the Supply Duct Collar . . . . . . . . . . .5
Hanging the Back Supply Plenum. . . . . . . . . . .5
Hood Hanging Height . . . . . . . . . . . . . . . . . .5
Double Island Style Hoods . . . . . . . . . . . . . . . .6
Installing U-Channel Strips . . . . . . . . . . . . . . .6
Continuous Capture Plenum Hoods. . . . . . . . . . .6
Electrical Connections . . . . . . . . . . . . . . . . . .6
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . .6
Installing External Supply Plenums . . . . . . . . . . .7
Supply Plenum Clip . . . . . . . . . . . . . . . . . . .7
Uni-strut . . . . . . . . . . . . . . . . . . . . . . . . .7
Hanger Brackets and Threaded Rod . . . . . . . . . .7
Installing the Supply Duct Collar to the Plenum . . . .7
External Supply Plenum
Weights and Dimensions . . . . . . . . . . . . . . . .8
Clearance Reduction Methods . . . . . . . . . . . . .8
Installing Enclosure Panels . . . . . . . . . . . . . . .9
Installing End Skirts . . . . . . . . . . . . . . . . . . .9
Installing Backsplash Panels. . . . . . . . . . . . . . 10
Installing Duct Collars
Exhaust Duct Collars . . . . . . . . . . . . . . . . . 11
Supply Duct Collars . . . . . . . . . . . . . . . . . . 11
Exhaust Air Balancing Baffles . . . . . . . . . . . 11-12
Balancing the Kitchen Exhaust System . . . . . . . . 12
Testing Hood Air Volume - Procedures
with Baffle Filters (GH Series) . . . . . . . . . . . 12-15
with High Velocity Cartridge Filters (GK Series). . 16-17
with High Efficiency Filters (GX Series) . . . . . . 18-20
Wiring
Fire Suppression Wiring Diagrams. . . . . . . . . 21-22
Overall Wiring Plan View . . . . . . . . . . . . . . . . 23
Wiring for Hood Switch Panels . . . . . . . . . . . . 24
Circuit Diagrams . . . . . . . . . . . . . . . . . . . . 25
Maintenance . . . . . . . . . . . . . . . . . . . . . . 26
Hood Baffle and Air Diffusers . . . . . . . . . . . . . 26
Grease Grabber™ Filters . . . . . . . . . . . . . 26-27
Filter Cleaning and Maintenance . . . . . . . . . . 27
Filter Washing Frequency Guide . . . . . . . . . . 28
Troubleshooting. . . . . . . . . . . . . . . . . . . 29-30
Replacement Parts . . . . . . . . . . . . . . . . . . . 31
Maintenance Log . . . . . . . . . . . . . . . . . . . . 32
Our Commitment . . . . . . . . . . . . . . . . . . . . 32
Hood Depth (Multiply by Length) for Hood Weight*
Hood Model
GH, GK, GXEW
GH, GX, GXDW
GH, GK, GXFW
GH, GK, GXCW
GH, GK, GXSW
GGEW
GGDW
GGFW
GGCW
GGSW
GH, GK, GXEV
GH, GK, GXFV
GH, GK, GXCV
GH, GK, GXSV
GO/GD1
GD2
GD3
2 ft
.6096 m
20 lbs/ft
29.76 kg/m
2.5 ft
.762 m
24 lbs/ft
35.72 kg/m
3 ft
.914 m
30 lbs/ft
44.64 kg/m
36 lbs/ft
53.57 kg/m
39 lbs/ft
58.04 kg/m
45 lbs/ft
66.97 kg/m
28 lbs/ft
41.67 kg/m
43 lbs/ft
63.99 kg/m
58 lbs/ft
86.31 kg/m
3.5 ft
1.067 m
32 lbs/ft
47.62 kg/m
38 lbs/ft
56.55 kg/m
40 lbs/ft
59.53 kg/m
48 lbs/ft
71.43 kg/m
44 lbs/ft
65.48 kg/m
41 lbs/ft
61.01 kg/m
47 lbs/ft
69.94 kg/m
49 lbs/ft
72.92 kg/m
57 lbs/ft
84.83 kg/m
53 lbs/ft
78.87 kg/m
32 lbs/ft
47.62 kg/m
48 lbs/ft
71.43 kg/m
64 lbs/ft
95.24 kg/m
4 ft
1.219 m
35 lbs/ft
52.09 kg/m
41 lbs/ft
61.01 kg/m
44 lbs/ft
65.48 kg/m
51 lbs/ft
75.90 kg/m
48 lbs/ft
71.43 kg/m
44 lbs/ft
65.48 kg/m
50 lbs/ft
74.41 kg/m
53 lbs/ft
78.87 kg/m
60 lb/ft
89.29 kg/m
57 lbs/ft
84.83 kg/m
52 lbs/ft
77.38 kg/m
61 lbs/ft
90.78 kg/m
36 lbs/ft
53.57 kg/m
53 lbs/ft
78.87 kg/m
70 lbs/ft
104.17 kg/m
4.5 ft
1.372 m
38 lbs/ft
56.55 kg/m
44 lbs/ft
65.48 kg/m
48 lbs/ft
71.43 kg/m
54 lbs/ft
80.36 kg/m
52 lbs/ft
77.38 kg/m
47 lbs/ft
69.94 kg/m
53 lbs/ft
78.87 kg/m
57 lbs/ft
84.83 kg/m
63 lbs/ft
93.75 kg/m
61 lbs/ft
90.78 kg/m
54 lbs/ft
80.36 kg/m
66 lbs/ft
98.22 kg/m
66 lbs/ft
98.22 kg/m
40 lbs/ft
59.52 kg/m
58 lbs/ft
86.31 kg/m
76 lbs/ft
113.10 kg/m
5 ft
1.524 m
40 lbs/ft
59.53 kg/m
46 lbs/ft
68.46 kg/m
52 lbs/ft
77.38 kg/m
57 lbs/ft
84.83 kg/m
56 lbs/ft
83.34 kg/m
49 lbs/ft
72.92 kg/m
55 lbs/ft
81.85 kg/m
61 lbs/ft
90.78 kg/m
66 lbs/ft
98.22 kg/m
65 lbs/ft
96.73 kg/m
56 lbs/ft
83.34 kg/m
68 lbs/ft
101.20 kg/m
69 lbs/ft
102.68 kg/m
44 lbs/ft
65.48 kg/m
63 lbs/ft
93.75 kg/m
82 lbs/ft
122.03 kg/m
5.5 ft
1.676 m
58 lbs/ft
86.31 kg/m
72 lbs/ft
107.15 kg/m
72 lbs/ft
107.15 kg/m
48 lbs/ft
71.43 kg/m
68 lbs/ft
101.20 kg/m
88 lbs/ft
130.96 kg/m
*Hood weight calculations are based on standard selection. Hood height, accessories and material gauge affect overall hood weight.
6 ft
1.829 m
61 lbs/ft
90.78 kg/m
75 lbs/ft
111.61 kg/m
81 lbs/ft
120.54 kg/m
76 lbs/ft
113.10 kg/m
52 lbs/ft
77.38 kg/m
73 lbs/ft
108.64 kg/m
94 lbs/ft
139.89 kg/m
6.5 ft
1.981 m
63 lbs/ft
93.75 kg/m
79 lbs/ft
117.56 kg/m
84 lbs/ft
125.01 kg/m
79 lbs/ft
117.56 kg/m
7 ft
2.134 m
87 lbs/ft
129.47 kg/m
7.5 ft
2.286 m
90 lbs/ft
133.93 kg/m
®
Kitchen Hoods • Type I and Type II
3
Installation
Wall or Single Island Style Hoods
NOTE
If you have a back supply plenum (BSP), this must be installed before the hood. Please see page 5.
The installation of the canopy hoods shall be in accordance with NFPA 96 (latest edition) Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations and ULC-S650 in Canada.
Greenheck does not recommend walking or standing on the hood top as damage can result and may void the warranty. If you must walk on the hood top, protect the hood with additional support and planks for flooring.
For wall/single island style hoods, prior to installation, check with local authorities having jurisdiction on clearances to combustible surfaces, etc.
With the hood still inside its packing crate, position the unit beneath its installation location. Carefully remove the packing crate. Place some protective material on the floor next to the crate to avoid damaging the hood as it is tipped on its side. Tip the hood carefully onto the protective material. If you have filler panels, install them now; refer to page 5, Filler Panel Installation. If you have integral filler panels, no additional installation is needed.
Hanging the Hood
Before hanging the hood according to the hood installation instructions, please check the following if applicable:
1. Make sure the back supply plenum is properly secured, as described on page 5.
2. If the ductwork for the back supply will not interfere with the hood installation, it should be connected now.
3. Any filler panels should be attached to the hood before the hood installation. See page 5 for instructions.
4. Lift the hood, and position it so the filler panels are resting lightly on the top outside edges of the back supply. The back supply is used to position the
hood only, it is not intended to hold any hood weight.
Bottom of Hood
Pallet
Protective Material
Hood Installation Overview
If a back supply plenum is provided, install it first. Before raising the hood, insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into hanger brackets on hood top. Check the engineering drawings or UL label located on the inside of the hood for proper hood height above finished floor. Install filler panels if needed. Raise and hang the hood from adequate roof or ceiling supports All hanger brackets must be used and the hood must be properly supported while lifting to prevent damage or distortion to the hood. The hood must be hung level to operate properly. After the hood is secured, make the exhaust duct connections. The fire system distributor must be contacted at this time. After the fire system has been installed, mount the enclosures, then the supply plenums. If a horizontal supply plenum is provided, it should be installed before the enclosures. Finally, make the electrical connections from the switches to the fans and complete the fire system circuits as required by the job specification.
5. Connect the remaining ductwork for the back supply and the hood. It is recommended that caulk be applied at the mating seams and surfaces of the back supply, the hood, and the wall.
6. If the hood is equipped with clearance reduction methods, refer to page 8 for special considerations with hanging the hood.
Kitchen Hoods • Type I and Type II
4
®
Filler Panel Installation
1. Uncrate the hood and lay it on the floor with protective material between the hood and the floor.
2. Bolt the filler panels together with 5/16 in. bolts provided in the hardware package.
3. Position the filler panels to the hood back, and tack­weld them into place.
HOOD
HOOD
HOOD
TACK-WELDED TO HOOD BACK
5/16 IN. X 3/4 IN. BOLTS WITH WASHERS & NUTS
4. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
RIGHT FILLER PANEL
BOTTOM FILLER PANEL
Hanging the Back Supply Plenum
5. Hang the back supply plenum from the ceiling.
The back supply plenum needs to be mounted
31.25in. (79.375 cm) above the finished floor. This is measured from the lowest rear edge of the back supply plenum to the finished floor.
Hang using threaded rod placed through the hanger brackets.
6. Fasten the back supply to the wall, going through the
lower back supply wall.
These fasteners are to help maintain the location of the back supply, and are not intended to hold the weight of the back supply unit.
The fasteners should not interfere with the removable air diffusers
Installing the Back Supply Plenum
Installing the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is to have one opening, cut the opening such that it is centered at L /2 from the plenum end. (Fig.1)
3. If the back supply plenum is to have two openings, cut openings such that they are centered at L /4 from each end of the plenum. (Fig. 2)
4. Place the duct collar(s) over the opening(s), fastening with screws or tack-welds every 4 to 6 in. (10.16 to 15.24 cm). (Fig. 3)
Fig. 3
L/4
L (MODULE LENGTH)
L (MODULE LENGTH)
L/2
L/2
Fig. 1
L/2
Fig. 2
L/4
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
31.25 INCH CRITICAL
DIMENSION
Hood Hanging Height
The hood hanging height is critical. Hanging the hood at the incorrect height may significantly reduce the ability of the hood to function properly and may be in violation of codes. The hood hanging height, typically 78in. (198.12 cm) above the finished floor, is given on the UL label located on the end panel on the inside of the hood. The hood must be hung level to operate properly. The grease trough is pitched to drain into the grease container.
®
Kitchen Hoods • Type I and Type II
5
Double Island Style Hoods
DOUBLE ISLAND CLIP
BOLT OR WELD
HOOD TOP
HOOD END
SUPPORT ANGLES
CAULK
BOLT
U-CLIP
HOOD
ACORN NUT
2. RAISE AND SU
3. FASTE
4. FASTE
5. CAULK
& CAP
1. REMO
HOOD FRONT
HOOD FRONT
REMOVE SUPPORT ANGLES ON THE OPEN END PANEL
A double island hood is created by installing two wall style hoods back to back. Use the installation procedure described on page 4 for single island hoods; install and level both hoods. After leveling, secure the hoods together by tack-welding and/or bolting the rear mounting brackets together.
Installing U-Channel Strip
1. After the hood
2. Position and
3. Caulk edges to seal out grease and allow for ease
Continuous Capture Plenum Hoods
Remove the support angles provided for support during shipping on the open end panels. Use the installation procedure described on page 4 for single island hoods; install and level both hoods.
After leveling, secure the hoods together by tack­welding and/or bolting the angles that are located at the top of the hoods along its width (Fig. 4).
Next, fasten the hoods together at its inside plenum profile using u-clips and bolts (Fig. 5). Caulk this joint with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
After the hood is installed, remove all protective plastic.
6
NOTE
Before hanging the hoods, please verify the hood marks to make sure the correct hood is hung on the correct side.
is hung in position and leveled, apply caulk to the inside edge of the double island clip.
install the clip by tapping into position along clip (friction fit).
of cleaning. Caulk with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
Kitchen Hoods • Type I and Type II
ITEM-1B
ITEM-1A
HOOD-1A
HOOD FRONT
Fig. 4
Fig. 5
HOOD-1B
SILICONE CAULK (GE SCS1009)
DOUBLE ISLAND CLIP
Electrical Connections
Access for wiring the hood control panel (when applicable) is provided by a junction box located on top of the hood when the control panel is mounted in the hood, or by the switch junction box when the control panel is mounted in the fire protection cabinet. The box is labeled “Control Voltage Wiring to Roof Top Fan Package”. Use minimum 14 AWG copper wire. After all the wiring is completed, install the light bulbs (light bulbs not provided; standard light bulbs up to 100 watt may be used).
CAUTION
For multiple hood systems that have more than 14 lights total (incandescent or fluorescent), the hood lights must be wired to multiple circuits. Each circuit must have less than 14 lights total.
Standard Greenheck light switches shipped on hoods are rated for 15 amps and shall not have more than 14lights connected to them. Higher amperage switches are available upon special request.
Ductwork
Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the following manner:
Materials: Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm (0.054 in.) (No. 16 MSG) in thickness, or stainless steel not less than
1.09 mm (0.043 in.) (No. 18 MSG) in thickness.
Installation: All seams, joints, penetrations, and duct to hood collar connections shall have a liquid-tight external weld. If you have an automatic fire damper, please refer to that manual for installation instructions now.
Supply
Supply ductwork (where applicable) should be connected to the hood in a manner approved by the local code authorities.
NOTE
For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but should not exceed 18 in. (45.72 cm).
For proper installation of duct collars when they are shipped unattached, see page 11.
®
Installing External Supply Plenums
NOTE
The supply plenum is provided with plenum clips that assist in hanging the plenum. Do not hang plenums using only the clips. Threaded rod or uni-strut must also be used.
Using the Supply Plenum Clip
1. Fasten the hanging clip to the supply plenum. Two clips are needed for plenums less than 96 in. (243.84 cm) long and three for plenums greater than 96 in. (243.84 cm). The third clip is located in the center of the plenum length. If there is a cabinet, the clip should be 23.5 in. (59.69 cm) from the outside edge of the cabinet.
Supply Plenum Clip
TOP VIEW HOOD
Using the Uni-strut
THREADED ROD
THREADED ROD
THE UNI-STRUT (U-CHANNEL) THAT HOLDS THE
HOOD UP CANTILEVERS OVER THE END OF
THE HOOD AND IS MOUNTED TO THE ASP
HANGER BRACKETS
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood, may be cantilevered over the end of the hood and used to mount to the hanger brackets on the supply plenums.
Using Hanger Brackets and Threaded Rod
FOR PLENUMS <= 96 INCHES (243.8 CM) 2 CLIPS ARE NEEDED
FOR PLENUMS > 96 INCHES (243.8 CM) 3 CLIPS ARE NEEDED THE THIRD CLIP IS LOCATED IN THE CENTER OF THE PLENUM LENGTH
ATTACH HANGING CLIP TO HOOD STANDING SEAM WITH THE SUPPLIED "C" CLAMPS
(OPTIONAL: DRILL AND BOLT A
OPTIONAL UTILITY CABINET
23.5 IN.
(59.69 CM)
11.5 IN.
(29.2 CM)
1/4-20 SS BOLT THROUGH THE CLIP AND HOOD STANDING SEAM)
TOP VIEW SUPPLY PLENUM
HANGING CLIP COULD BE 23.5 INCHES (59.69 CM) FROM END IF THERE IS A UTILITY CABINET ON THE END OF THE HOOD
2. Using the c-clamps provided, clamp the supply plenum hanging clip to the hood standing seam. Option: Drill and bolt a 1/4-20 SS bolt through the clip and hood standing seam.
"C" CLAMP
HOOD FRONT
HOOD STANDING SEAM
HANGING CLIP FASTENED TO PLENUM SHELL
HANGING CLIP
SUPPLY PLENUM SHELL
Air Curtain Supply Plenum
ASP
HSP or VSP
Variable Supply Plenum
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into hanger brackets on the supply plenum top. Raise and hang the external supply plenum from adequate roof or ceiling supports.
2. The external supply plenum should be resting lightly against the hood. The hood is used to position the plenum only, it is not intended to support the plenum. All hanger brackets must be used and the plenum must be properly supported while lifting to prevent damage or distortion. The supply plenum must be hung level to operate properly.
3. It is recommended that caulk be applied at the mating seams and surfaces of the plenum, the hood, and the wall. If the supply plenum is next to a wall, you will also need to caulk around the surface next to the wall. Caulk the joints with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm) intervals.
®
Kitchen Hoods • Type I and Type II
7
Weights and Dimensions
External Supply
Plenum Type
Back Supply 35.0 52.09 6 152.4 Variable Variable 3 to 16 .91 to 4.88
Air Curtain Supply
• 14 inch
Air Curtain Supply
• 24 inch
Variable Supply 16.0 23.81 12 304.8 18 457.20 3 to 16 .91 to 4.88
Horizontal Supply 14.0 20.83 12 304.8 18 457.20 3 to 16 .91 to 4.88
Weight Width Height
(lbs/ft) (kg/m) (in) (mm) (in) (mm) (ft) (m)
9.5 14.14 14 355.6 10 254 3 to 16 .91 to 4.88
12.5 18.60 24 609.6 10 254 3 to 16 .91 to 4.88
Length
per section
Clearance Reduction Methods
Clearance reduction methods have been evaluated and tested and are listed by UL (Underwriters Laboratory). The method of test was derived from the UL 710 test standard.
The hood may be installed with zero clearance to combustible materials if constructed in the following manner.
1. One inch (2.54 cm) thick layer of insulation of Owens Corning® Type 475, Johns Manville Type 475, IIG® MinWool-1200® Flexible Batt, or Knauf Insulation Type EI 475.
2. Insulation must be held securely in place. Pins that are welded or secured with an adhesive may be used.
3. A backsplash panel must be attached to the wall (insulated or uninsulated).
To comply with the UL listing, the cooking appliances must be as follows:
• Maximum surface temperature is 700°F (371°C)
• Appliances are located at least 3 in. (7.62 cm) from the rear wall
• Appliances are at least 40 in. (101.6 cm) below the bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance to limited combustible materials per NFPA 96 if constructed in one of the following methods:
• 3 in. (7.62 cm) rear uninsulated stand-off
• 3 in. (7.62 cm) top enclosure panel system
• 3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer of insulation installed on top of the hood (optional) meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reductions methods.
Three inches (7.62cm) insulated airspace installed on top of hood (optional) meets NFPA 96 requirements for clearance to limited combustible surfaces.
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer of insulation in 3 in. (7.62 cm) back stand-off meets zero inch requirements for clearance to combustible surfaces as outlined under the clearance reduction methods.
Three inches (7.62 cm) uninsulated back stand-off meets NFPA 96 requirements for clearance to limited combustible surfaces.
One inch (2.54 cm) layer of insulation factory-installed on the front of the hood (optional) meets zero inch requirements for clearance to combustible surfaces.
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed on the end of the hood (optional) meets zero inch requirements for clearance to combustible surfaces under the clearance reduction methods.
Three inches (7.62 cm) uninsulated airspace installed on end of hood (optional). Meets NFPA 96 requirements for clearance to limited combustible surfaces.
Kitchen Hoods • Type I and Type II
8
®
Installing Enclosure Panels
Installing End Skirts
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork attached and electrical connections completed.
1. Position the end enclosure panels on the hood, and clamp into place with clamps provided or tack-weld the panels into place.
2. Fasten the end enclosure panels to the wall, method depends on wall construction. (Fasteners provided by others).
If the hood is a double island, bolt the end enclosure
panels together. (Fasteners provided by others).
3. Position the front enclosure panel(s) on the hood, and bolt to the end enclosure panels with the 5/16 in. bolts provided in the hardware package.
4. Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be positioned 4in. (10.16 cm) from the ends and in the center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
6. Installation instructions may not be applicable for concrete ceilings.
1. After the hood is hung in position, line up the top of the end skirt with the end panels of the hood.
2. Drill a hole in the hood end panel to line up with the hole in the end skirt. Attach the end skirt with a 1/4in. bolt and cap nut to the inside of the hood, or tack-weld the end skirt to the hood.
3. Position the end skirt against the wall and attach. The method depends on the wall construction. (Fasteners provided by others).
4. Caulk the internal joint formed by the end skirt and the hood end panel with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
5. To allow for ease in cleaning, also caulk all the external seams.
HOLE DRILLED BY INSTALLER
1/4 INCH BOLT AND CAP NUT SUPPLIED BY MANUFACTURER
END ENSLOSURE PANEL
HOOD TOP
HOOD BACK
BOLT PANELS TOGETHER WITH 5/16 INCH BOLTS SUPPLIED BY MANUFACTURER
CLAMP PANELS TO HOOD STANDING SEAM WITH HARDWARE SUPPLIED BY MANUFACTURER
FRONT ENCLOSURE PANEL
END ENSLOSURE PANEL
FULL END SKIRT
ATTACH TO WALL
FASTENERS BY OTHERS
HEMMED EDGE
ATTACH TO WALL FASTENERS BY OTHERS
®
Kitchen Hoods • Type I and Type II
9
Installing Backsplash Panels
WALL
WALL
Flat Backsplash Panel
Material: Stainless
LENGTH
Inches Millimeters
<=47 <=1193.8 1
>47 <=93 >1193.8 <=2362.2 2
>93 <=138.8 >2362.2 <=3525.5 3
>138.8 <=185 >3525.5 <=4699 4
>185<=231.3 >4699 <=5875.0 5
QTY
HEIGHT
HOOD END PANEL
HOOD FRONT PANEL
LENGTH
NOTE
Panels up to 47 in. (1193.8 mm) wide ship in one piece; over 47 in. (1193.8 mm) in multiple pieces.
Insulated Backsplash Panel
Material: Stainless Insulation: 1 in. (25.4 mm)
LENGTH
Inches Millimeters
<=45 <=1143 1
>45 <=90 >1143 <=2286 2
>90 <=135 >2286 <=3429 3
>135 <=180 >3429 <=4572 4
>180 <=225 >4572 <=5715 5
QTY
1 IN. (25.4 MM)
HEIGHT
SLIDE FLANGE BEHIND BACK OF THE HOOD
BACKSPLASH PANEL
SECTION VIEW OF BACKSPLASH PANEL OVERLAP
1. After the hood is hung in position, slide the flat flange of the backsplash panel behind the back of the hood.
Note: If the backsplash panel length is greater than
45 in. (1143 mm), it will be shipped in multiple pieces.
2. After the backsplash panel has been positioned, drill holes in the panel and fasten to the wall. (Fasteners provided by others).
Note: The holes should be spaced to adequately
secure the panel to the wall.
3. Caulk the joints between the hood and the backsplash panel with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
4. Caulk the joint between the backsplash panels when multiple panels are required, with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
LENGTH
NOTE
Panels up to 45 in. (1143 mm) wide ship in one piece; over 45 in. (1143 mm) in multiple pieces.
Kitchen Hoods • Type I and Type II
10
®
Loading...
+ 22 hidden pages