Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
Type IIType I
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
DANGER
Always disconnect power before working on or near a
fan. Lock and tag the disconnect switch or breaker to
prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) and ULC-S650 in
Canada.
2. The rotation of the fan wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Fan motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan rpm. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to a duct while the fan is
running.
®
Kitchen Hoods • Type I and Type II
1
Receiving
Upon receiving the product, check to make sure all
items are accounted for by referencing the packing
list and ensuring all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery receipt
acknowledging any damage to the product. All damage
should be noted on all the copies of the bill of lading
which is countersigned by the delivering carrier. A
Carrier Inspection Report should be filled out by the
carrier upon arrival and filed with the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not the
responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited
to only items on the bill of lading. Filters are shipped
on a separate skid in their original packaging. Do not
remove factory packaging or install filters until just prior
to commissioning. Remove all other shipping/packing
materials including fan tie down straps.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR - The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C)
and 110°F (43°C). Wide temperature swings may
cause condensation and “sweating” of metal parts.
All accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts, allow cold parts to reach
room temperature. To dry parts and packages, use a
portable electric heater to get rid of any moisture
buildup. Leave coverings loose to permit air circulation
and to allow for periodic inspection.
OUTDOOR - Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The unit should be placed on a level surface to prevent
water from leaking into it. The unit should be elevated
on an adequate number of wooden blocks so that it is
above water and snow levels and has enough blocking
to prevent it from settling into soft ground. Locate parts
far enough apart to permit air circulation, sunlight,
and space for periodic inspection. To minimize water
accumulation, place all unit parts on blocking supports
so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lintfree cloths. Polish any remaining rust from surface
with crocus cloth or fine emery paper and oil. Do not
destroy the continuity of the surfaces. Wipe thoroughly
clean with Tectyl® 506 (Ashland Inc.) or the equivalent.
For hard to reach internal surfaces or for occasional
use, consider using Tectyl® 511M Rust Preventive or
WD-40
Removing from Storage
As units are removed from storage to be installed
in their final location, they should be protected and
maintained in a similar fashion until the equipment goes
into operation. Prior to installing the unit and system
components, inspect the unit assembly to make sure it
is in working order.
• Check all fasteners, set screws on the fan, wheel,
• Rotate the fan wheel(s), where applicable, by hand
® or the equivalent.
bearings, drive, motor base, and accessories for
tightness.
and assure no parts are rubbing.
Kitchen Hoods • Type I and Type II
2
®
Table of Contents
Receiving, Unpacking, Handling and Storage . . . . .2
Inspection and Maintenance during Storage . . . . . .2
*Hood weight calculations are based on standard selection. Hood height, accessories and material gauge affect overall hood weight.
6 ft
1.829 m
61 lbs/ft
90.78 kg/m
75 lbs/ft
111.61 kg/m
81 lbs/ft
120.54 kg/m
76 lbs/ft
113.10 kg/m
52 lbs/ft
77.38 kg/m
73 lbs/ft
108.64 kg/m
94 lbs/ft
139.89 kg/m
6.5 ft
1.981 m
63 lbs/ft
93.75 kg/m
79 lbs/ft
117.56 kg/m
84 lbs/ft
125.01 kg/m
79 lbs/ft
117.56 kg/m
7 ft
2.134 m
87 lbs/ft
129.47 kg/m
7.5 ft
2.286 m
90 lbs/ft
133.93 kg/m
®
Kitchen Hoods • Type I and Type II
3
Installation
Wall or Single Island Style Hoods
NOTE
If you have a back supply plenum (BSP), this must be
installed before the hood. Please see page 5.
The installation of the canopy hoods shall be in
accordance with NFPA 96 (latest edition) Standard for
Ventilation Control and Fire Protection of Commercial
Cooking Operations and ULC-S650 in Canada.
Greenheck does not recommend walking or standing
on the hood top as damage can result and may
void the warranty. If you must walk on the hood top,
protect the hood with additional support and planks
for flooring.
For wall/single island style hoods, prior to installation,
check with local authorities having jurisdiction on
clearances to combustible surfaces, etc.
With the hood still inside its packing crate, position the
unit beneath its installation location. Carefully remove
the packing crate. Place some protective material on
the floor next to the crate to avoid damaging the hood
as it is tipped on its side. Tip the hood carefully onto the
protective material. If you have filler panels, install them
now; refer to page 5, Filler Panel Installation. If you have
integral filler panels, no additional installation is needed.
Hanging the Hood
Before hanging the hood according to the hood
installation instructions, please check the following if
applicable:
1. Make sure the back supply plenum is properly
secured, as described on page 5.
2. If the ductwork for the back supply will not interfere
with the hood installation, it should be connected
now.
3. Any filler panels should be attached to the hood
before the hood installation. See page 5 for
instructions.
4. Lift the hood, and position it so the filler panels are
resting lightly on the top outside edges of the back
supply. The back supply is used to position the
hood only, it is not intended to hold any hood
weight.
Bottom of Hood
Pallet
Protective Material
Hood Installation Overview
If a back supply plenum is provided, install it first. Before
raising the hood, insert 1/2 in. (12.7 mm) diameter
threaded rod (by others) into hanger brackets on hood
top. Check the engineering drawings or UL label located
on the inside of the hood for proper hood height above
finished floor. Install filler panels if needed. Raise and
hang the hood from adequate roof or ceiling supports
All hanger brackets must be used and the hood must
be properly supported while lifting to prevent damage
or distortion to the hood. The hood must be hung level
to operate properly. After the hood is secured, make the
exhaust duct connections. The fire system distributor
must be contacted at this time. After the fire system has
been installed, mount the enclosures, then the supply
plenums. If a horizontal supply plenum is provided, it
should be installed before the enclosures. Finally, make
the electrical connections from the switches to the fans
and complete the fire system circuits as required by the
job specification.
5. Connect the remaining ductwork for the back supply
and the hood. It is recommended that caulk be
applied at the mating seams and surfaces of the
back supply, the hood, and the wall.
6. If the hood is equipped with clearance reduction
methods, refer to page 8 for special considerations
with hanging the hood.
Kitchen Hoods • Type I and Type II
4
®
Filler Panel Installation
1. Uncrate the hood and lay it on the floor with
protective material between the hood and the floor.
2. Bolt the filler panels together with 5/16 in. bolts
provided in the hardware package.
3. Position the filler panels to the hood back, and tackweld them into place.
HOOD
HOOD
HOOD
TACK-WELDED TO
HOOD BACK
5/16 IN. X 3/4 IN. BOLTS
WITH WASHERS & NUTS
4. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk (GE
SCS1009, or its equivalent). The caulk is not
provided.
RIGHT FILLER PANEL
BOTTOM FILLER PANEL
Hanging the Back Supply Plenum
5. Hang the back supply plenum from the ceiling.
• The back supply plenum needs to be mounted
31.25in. (79.375 cm) above the finished floor. This
is measured from the lowest rear edge of the back
supply plenum to the finished floor.
• Hang using threaded rod placed through the hanger
brackets.
6. Fasten the back supply to the wall, going through the
lower back supply wall.
• These fasteners are to help maintain the location of
the back supply, and are not intended to hold the
weight of the back supply unit.
• The fasteners should not interfere with the
removable air diffusers
Installing the Back Supply Plenum
Installing the Supply Duct Collar
1. Find the center of the back supply plenum.
2. If the back supply plenum is
to have one opening, cut the
opening such that it is centered
at L /2 from the plenum end.
(Fig.1)
3. If the back supply plenum is to
have two openings, cut openings
such that they are centered
at L /4 from each end of the
plenum. (Fig. 2)
4. Place the duct collar(s) over the
opening(s), fastening with screws
or tack-welds
every 4 to 6 in.
(10.16 to 15.24
cm). (Fig. 3)
Fig. 3
L/4
L (MODULE LENGTH)
L (MODULE LENGTH)
L/2
L/2
Fig. 1
L/2
Fig. 2
L/4
FASTENERS HOLDING THE
BACKSUPPLY TO THE WALL
31.25 INCH
CRITICAL
DIMENSION
Hood Hanging Height
The hood hanging height is critical. Hanging the hood at
the incorrect height may significantly reduce the ability
of the hood to function properly and may be in violation
of codes. The hood hanging height, typically 78in.
(198.12 cm) above the finished floor, is given on the
UL label located on the end panel on the inside of the
hood. The hood must be hung level to operate properly.
The grease trough is pitched to drain into the grease
container.
®
Kitchen Hoods • Type I and Type II
5
Double Island Style Hoods
DOUBLE ISLAND CLIP
BOLT OR WELD
HOOD TOP
HOOD END
SUPPORT ANGLES
CAULK
BOLT
U-CLIP
HOOD
ACORN
NUT
2. RAISE AND SU
3. FASTE
4. FASTE
5. CAULK
& CAP
1. REMO
HOOD FRONT
HOOD FRONT
REMOVE
SUPPORT
ANGLES ON
THE OPEN
END PANEL
A double island hood is created by installing two
wall style hoods back to back. Use the installation
procedure described on page 4 for single island hoods;
install and level both hoods. After leveling, secure the
hoods together by tack-welding and/or bolting the rear
mounting brackets together.
Installing U-Channel Strip
1. After the hood
2. Position and
3. Caulk edges to seal out grease and allow for ease
Continuous Capture Plenum Hoods
Remove the support angles provided
for support during shipping on
the open end panels. Use the
installation procedure
described on page 4
for single island
hoods;
install
and level
both
hoods.
After
leveling, secure
the hoods together by tackwelding and/or bolting the
angles that are located at
the top of the hoods along
its width (Fig. 4).
Next, fasten the hoods
together at its inside plenum
profile using u-clips and
bolts (Fig. 5). Caulk this joint
with NSF Approved silicone
caulk (GE SCS1009 or its
equivalent). The caulk is not
provided.
After the hood is installed, remove all protective plastic.
6
NOTE
Before hanging the hoods, please verify the hood
marks to make sure the correct hood is hung on the
correct side.
is hung in
position and
leveled, apply
caulk to the
inside edge
of the double
island clip.
install the clip
by tapping
into position along clip (friction fit).
of cleaning. Caulk with NSF Approved silicone caulk
(GE SCS1009 or its equivalent). The caulk is not
provided.
Kitchen Hoods • Type I and Type II
ITEM-1B
ITEM-1A
HOOD-1A
HOOD FRONT
Fig. 4
Fig. 5
HOOD-1B
SILICONE CAULK
(GE SCS1009)
DOUBLE ISLAND CLIP
Electrical Connections
Access for wiring the hood control panel (when
applicable) is provided by a junction box located on top
of the hood when the control panel is mounted in the
hood, or by the switch junction box when the control
panel is mounted in the fire protection cabinet. The
box is labeled “Control Voltage Wiring to Roof Top Fan
Package”. Use minimum 14 AWG copper wire. After
all the wiring is completed, install the light bulbs (light
bulbs not provided; standard light bulbs up to 100 watt
may be used).
CAUTION
For multiple hood systems that have more than 14
lights total (incandescent or fluorescent), the hood
lights must be wired to multiple circuits. Each circuit
must have less than 14 lights total.
Standard Greenheck light switches shipped on hoods
are rated for 15 amps and shall not have more than
14lights connected to them. Higher amperage switches
are available upon special request.
Ductwork
Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust
duct systems must be constructed in the following
manner:
Materials: Ducts shall be constructed of and supported
by carbon steel not less than 1.37 mm (0.054 in.) (No.
16 MSG) in thickness, or stainless steel not less than
1.09 mm (0.043 in.) (No. 18 MSG) in thickness.
Installation: All seams, joints, penetrations, and duct to
hood collar connections shall have a liquid-tight external
weld. If you have an automatic fire damper, please refer
to that manual for installation instructions now.
Supply
Supply ductwork (where applicable) should be
connected to the hood in a manner approved by the
local code authorities.
NOTE
For hoods with fire dampers in the exhaust and
supply duct collars, an access panel for cleaning and
inspection shall be provided in the duct. This panel
shall be as close to the hood as possible but should
not exceed 18 in. (45.72 cm).
For proper installation of duct collars when they are
shipped unattached, see page 11.
®
Installing External Supply Plenums
NOTE
The supply plenum is provided with plenum clips that
assist in hanging the plenum. Do not hang plenums
using only the clips. Threaded rod or uni-strut must
also be used.
Using the Supply Plenum Clip
1. Fasten the hanging clip to the
supply plenum. Two clips are
needed for plenums less than
96 in. (243.84 cm) long and
three for plenums greater than
96 in. (243.84 cm). The third
clip is located in the center
of the plenum length. If there is a cabinet, the clip
should be 23.5 in. (59.69 cm) from the outside edge
of the cabinet.
Supply Plenum Clip
TOP VIEW
HOOD
Using the Uni-strut
THREADED ROD
THREADED ROD
THE UNI-STRUT (U-CHANNEL) THAT HOLDS THE
HOOD UP CANTILEVERS OVER THE END OF
THE HOOD AND IS MOUNTED TO THE ASP
HANGER BRACKETS
SUPPLIED BY OTHERS
END VIEW
HOOD
The uni-strut (supplied by others) supporting the hood,
may be cantilevered over the end of the hood and used
to mount to the hanger brackets on the supply plenums.
Using Hanger Brackets and Threaded Rod
FOR PLENUMS <= 96 INCHES (243.8 CM)
2 CLIPS ARE NEEDED
FOR PLENUMS > 96 INCHES (243.8 CM)
3 CLIPS ARE NEEDED
THE THIRD CLIP IS LOCATED
IN THE CENTER OF THE
PLENUM LENGTH
ATTACH HANGING CLIP TO
HOOD STANDING SEAM WITH
THE SUPPLIED "C" CLAMPS
(OPTIONAL: DRILL AND BOLT A
OPTIONAL UTILITY CABINET
23.5 IN.
(59.69 CM)
11.5 IN.
(29.2 CM)
1/4-20 SS BOLT THROUGH
THE CLIP AND HOOD STANDING
SEAM)
TOP VIEW
SUPPLY PLENUM
HANGING CLIP COULD BE 23.5 INCHES (59.69 CM) FROM END IF THERE IS
A UTILITY CABINET ON THE END OF THE HOOD
2. Using the c-clamps provided, clamp the supply
plenum hanging clip to the hood standing seam.
Option: Drill and bolt a 1/4-20 SS bolt through the
clip and hood standing seam.
"C" CLAMP
HOOD FRONT
HOOD STANDING SEAM
HANGING CLIP FASTENED TO PLENUM SHELL
HANGING CLIP
SUPPLY PLENUM SHELL
Air Curtain Supply Plenum
ASP
HSP or VSP
Variable Supply Plenum
1. Insert 1/2 in. (12.7 mm) diameter threaded rod (by
others) into hanger brackets on the supply plenum
top. Raise and hang the external supply plenum from
adequate roof or ceiling supports.
2. The external supply plenum should be resting lightly
against the hood. The hood is used to position the
plenum only, it is not intended to support the plenum.
All hanger brackets must be used and the plenum
must be properly supported while lifting to prevent
damage or distortion. The supply plenum must be
hung level to operate properly.
3. It is recommended that caulk be applied at the
mating seams and surfaces of the plenum, the hood,
and the wall. If the supply plenum is next to a wall,
you will also need to caulk around the surface next to
the wall. Caulk the joints with NSF Approved silicone
caulk (GE SCS1009, or its equivalent). The caulk is
not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening
with tack-welds at 1 to 2 in. (2.54 to 5.08 cm) intervals,
or sheet metal screws at 3 to 6 in. (7.62 to 15.24 cm)
intervals.
®
Kitchen Hoods • Type I and Type II
7
Weights and Dimensions
External Supply
Plenum Type
Back Supply35.052.096152.4Variable Variable 3 to 16 .91 to 4.88
Air Curtain Supply
• 14 inch
Air Curtain Supply
• 24 inch
Variable Supply16.023.8112304.818457.203 to 16 .91 to 4.88
Horizontal Supply14.020.8312304.818457.203 to 16 .91 to 4.88
WeightWidthHeight
(lbs/ft)(kg/m)(in)(mm)(in)(mm)(ft)(m)
9.514.1414355.6102543 to 16 .91 to 4.88
12.518.6024609.6102543 to 16 .91 to 4.88
Length
per section
Clearance Reduction Methods
Clearance reduction methods have been evaluated and
tested and are listed by UL (Underwriters Laboratory).
The method of test was derived from the UL 710 test
standard.
The hood may be installed with zero clearance to
combustible materials if constructed in the following
manner.
1. One inch (2.54 cm) thick layer of insulation of Owens
Corning® Type 475, Johns Manville Type 475, IIG®
MinWool-1200® Flexible Batt, or Knauf Insulation
Type EI 475.
2. Insulation must be held securely in place. Pins that
are welded or secured with an adhesive may be
used.
3. A backsplash panel must be attached to the wall
(insulated or uninsulated).
To comply with the UL listing, the cooking appliances
must be as follows:
• Maximum surface temperature is 700°F (371°C)
• Appliances are located at least 3 in. (7.62 cm) from
the rear wall
• Appliances are at least 40 in. (101.6 cm) below the
bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance
to limited combustible materials per NFPA 96 if
constructed in one of the following methods:
• 3 in. (7.62 cm) rear uninsulated stand-off
• 3 in. (7.62 cm) top enclosure panel system
• 3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer
of insulation installed
on top of the hood
(optional) meets zero
inch requirements for
clearance to combustible
surfaces as outlined under
the clearance reductions methods.
Three inches (7.62cm)
insulated airspace
installed on top of hood
(optional) meets NFPA 96
requirements for clearance
to limited combustible
surfaces.
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer
of insulation in 3 in. (7.62
cm) back stand-off meets
zero inch requirements for
clearance to combustible
surfaces as outlined under
the clearance reduction
methods.
Three inches (7.62 cm) uninsulated back stand-off
meets NFPA 96 requirements for clearance to limited
combustible surfaces.
One inch (2.54 cm) layer of insulation factory-installed
on the front of the hood (optional) meets zero inch
requirements for clearance to combustible surfaces.
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed
on the end of the hood (optional) meets zero inch
requirements for clearance to combustible surfaces
under the clearance reduction methods.
Three inches (7.62 cm) uninsulated airspace installed on
end of hood (optional). Meets NFPA 96 requirements for
clearance to limited combustible surfaces.
Kitchen Hoods • Type I and Type II
8
®
Installing Enclosure Panels
Installing End Skirts
Before installing the enclosure panels, make sure the
hood is hung in position with all the ductwork attached
and electrical connections completed.
1. Position the end enclosure panels on the hood, and
clamp into place with clamps provided or tack-weld
the panels into place.
2. Fasten the end enclosure panels to the wall, method
depends on wall construction. (Fasteners provided
by others).
If the hood is a double island, bolt the end enclosure
panels together. (Fasteners provided by others).
3. Position the front enclosure panel(s) on the hood,
and bolt to the end enclosure panels with the 5/16 in.
bolts provided in the hardware package.
4. Tack-weld or clamp the front enclosure panel(s)
to the hood. If clamps are used, they must be
positioned 4in. (10.16 cm) from the ends and in the
center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external
seams with NSF Approved silicone caulk
(GE SCS1009, or its equivalent). The caulk is not
provided.
6. Installation instructions may not be applicable for
concrete ceilings.
1. After the hood is hung in position, line up the top of
the end skirt with the end panels of the hood.
2. Drill a hole in the hood end panel to line up with
the hole in the end skirt. Attach the end skirt with a
1/4in. bolt and cap nut to the inside of the hood, or
tack-weld the end skirt to the hood.
3. Position the end skirt against the wall and attach. The
method depends on the wall construction. (Fasteners
provided by others).
4. Caulk the internal joint formed by the end skirt and
the hood end panel with NSF Approved silicone caulk
(GE SCS1009 or its equivalent). The caulk is not
provided.
5. To allow for ease in cleaning, also caulk all the
external seams.
HOLE DRILLED
BY INSTALLER
1/4 INCH BOLT AND CAP NUT
SUPPLIED BY MANUFACTURER
END ENSLOSURE
PANEL
HOOD TOP
HOOD BACK
BOLT PANELS TOGETHER
WITH 5/16 INCH BOLTS
SUPPLIED BY MANUFACTURER
CLAMP PANELS TO HOOD
STANDING SEAM WITH HARDWARE
SUPPLIED BY MANUFACTURER
FRONT ENCLOSURE PANEL
END ENSLOSURE
PANEL
FULL END SKIRT
ATTACH TO WALL
FASTENERS BY OTHERS
HEMMED EDGE
ATTACH TO WALL
FASTENERS BY OTHERS
®
Kitchen Hoods • Type I and Type II
9
Installing Backsplash Panels
WALL
WALL
Flat Backsplash Panel
Material: Stainless
LENGTH
InchesMillimeters
<=47<=1193.81
>47 <=93 >1193.8 <=2362.2 2
>93 <=138.8 >2362.2 <=3525.5 3
>138.8 <=185 >3525.5 <=4699 4
>185<=231.3 >4699 <=5875.0 5
QTY
HEIGHT
HOOD END PANEL
HOOD FRONT PANEL
LENGTH
NOTE
Panels up to 47 in. (1193.8 mm) wide ship in one
piece; over 47 in. (1193.8 mm) in multiple pieces.
Insulated Backsplash Panel
Material: Stainless
Insulation: 1 in. (25.4 mm)
LENGTH
InchesMillimeters
<=45<=11431
>45 <=90>1143 <=22862
>90 <=135>2286 <=34293
>135 <=180 >3429 <=45724
>180 <=225 >4572 <=57155
QTY
1 IN. (25.4 MM)
HEIGHT
SLIDE FLANGE
BEHIND BACK
OF THE HOOD
BACKSPLASH PANEL
SECTION VIEW
OF BACKSPLASH
PANEL OVERLAP
1. After the hood is hung in position, slide the flat flange
of the backsplash panel behind the back of the hood.
Note: If the backsplash panel length is greater than
45 in. (1143 mm), it will be shipped in multiple pieces.
2. After the backsplash panel has been positioned, drill
holes in the panel and fasten to the wall. (Fasteners
provided by others).
Note: The holes should be spaced to adequately
secure the panel to the wall.
3. Caulk the joints between the hood and the
backsplash panel with NSF Approved silicone caulk
(GE SCS1009, or its equivalent). The caulk is not
provided.
4. Caulk the joint between the backsplash panels when
multiple panels are required, with NSF Approved
silicone caulk (GE SCS1009, or its equivalent). The
caulk is not provided.
LENGTH
NOTE
Panels up to 45 in. (1143 mm) wide ship in one piece;
over 45 in. (1143 mm) in multiple pieces.
Kitchen Hoods • Type I and Type II
10
®
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.