All Greenheck products
are supported by the
industry’s best product
literature, electronic
media, and Computer
Aided Product Selection program, CAPS. Online, you can
also find electronic copies of our product literature as well
as storage, installation and maintenance information in our
Installation and Operation Manuals.
And, of course, you can always count on the personal
service and expertise of our national and international
representative organization. To locate your nearest
Greenheck representative call 715-359-6171 or visit our
Web site at www.greenheck.com
To-Scale Drawings and Fan Specifications
To-scale CAD drawings along with detailed centrifugal
specifications can be found online at greenheck.com or
within our Computer Aided Product Selection program
(CAPS).
SOUND
R
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
and
AIR
PERFORMANCE
Greenheck Fan Corporation certifies
that the backward inclined and airfoil
centrifugal fans shown herein are
licensed to bear the AMCA Seal. The
ratings shown are based on tests and
procedures performed in accordance
with AMCA Publication 211 and
Publication 311 and comply with the
requirements of the AMCA Certified
Ratings Program.
®
®
2
Engineering Data
Motor Selection
Greenheck centrifugal fans can be supplied with any motor that is commercially available, and appropriate for the fan size
and performance required. The tables show motor frame sizes corresponding to those motors readily available. See the
maximum motor frame size charts below if motor is for arrangement 9 or 10 fans.
Notes: 1. Fractional horsepower motor frame sizes shown may change due to variations in voltage, special features and
2. Motors shown are ball bearing, continuous duty. Two speed motors are two winding, 1/3 reduction in RPM.
Arrangement 9 and 10 fans have specific motor size limitations based on enclosure type (examples: Open, Totally Enclosed
Fan Cooled) and voltage. The charts below should be used to verify the motor selected will physically fit on the fan.
When selecting a motor for a centrifugal fan, the motor must be
capable of driving the fan at operating speed and also capable of
accelerating the fan wheel, shaft and drive to the operating speed.
The fan performance tables and curves in this catalog show the
brake horsepower required to operate the fan once it is brought to
operating speed. For applications requiring a large air volume at a
low static pressure, the BHP required at the fan’s operating RPM
may not be sufficient to initially start the fan. If the time required to
bring the fan to speed is excessive, the motor winding insulation
can be damaged due to excessive temperature rise and the life of
the motor seriously affected.
For a belt drive fan, the required motor starting torque capability
can be expressed by the following formula:
2
WR
M
2
WR
M
2
WR
F
FRPM =
MRPM =
2
F
x
(
FRPM
MRPM
= WR
The moment of inertia that the motor must be
=
capable of turning at the motor shaft, lb-ft
The moment of inertia of the fan wheel, lb-ft
=
Fan RPM
Motor RPM
)
2
x (1.1)
2
2
V-Belt Drives
Constant Speed Drives
Advantages of constant speed drives include low vibration levels,
ease of assembly and low cost. Fan speed changes can be
accomplished in most cases simply by changing the motor pulley.
Constant speed drives are recommended over variable speed
drives for applications that require motors 15 HP and larger, and all
applications requiring 3600 RPM motors.
Variable Speed Drives
Variable speed drives allow the fan speed to be changed by
adjusting the pitch diameter of the motor pulley. The power to the
fan must be off and locked out, and the belts must be removed
before manually adjusting the variable pitch pulley.
High Temperature Operating Limits
TemperatureMaterialArrangementOptions Included
-20
to
180°F
-20
to
200°F
201
to
500°F
501
to
750°F
751
to
1000°F
Steel
Aluminum
Stainless Steel
Steel
Aluminum
Stainless Steel
Steel
Stainless Steel
Aluminum –
limited to 250ºF
Steel
Stainless Steel
316 Stainless
Steel
3None
1, 9 & 10None
• Heat Slinger
• Shaft Seal 1, 9 & 10
1, 9 & 10
1, 9 & 10
BISW only
1, 9 & 10
BISW only
• Motor Heat Shield on
Arrangements 9 & 10
• Airfoil Blade Weep Holes
• High Temperature Paint
• Heat Slinger
• Shaft Seal
• High Temperature Grease
• Motor Heat Shield on
Arrangements 9 & 10
• High Temperature Paint
All options shown above
except paint
Mill Finish
Moments of Inertia (lb-ft2)
Moments of inertia are shown for steel wheels. Aluminum wheels
are one-third of the value shown.
Class I Class II Class III Class IV Class I Class II Class III
Steel Airfoil
Centrifugal Wheels
Fan RPM Limitations
The maximum allowable wheel RPM shown on the fan performance
pages are for fans of standard steel operating at 70°F. Since the
strength of the fan wheel, shaft and bearings decreases with an
increase in temperature, maximum allowable speeds must be
reduced by the correction factors shown below.
Maximum RPM Correction Factors For High Temperatures
Temperature
(°F)
701.001.001.00
2001.00.97.92
250.95.96.89
300.95.87
400.93.83
500.90.80
600.85.77
700.80.75
800.72.72
900.71
1000.69
AluminumSteel316 SS
Wheel Material
Effect of Air Density — High Suction at Fan Inlet
The density used for fan selection is that which is measured at
the fan inlet. When the inlet total pressure exceeds 10 inches in
suction, the density at the fan inlet should be corrected by the
following values. These values should be multiplied to the fan static
pressure and the result used for the proper fan selection. With
suction pressures less than 10 inches, this correction is typically
ignored.
Inlet P
-10 in.1.03
-14 in.1.04
-18 in.1.05
-22 in.1.06
Example:
10 in. Ps x 1.03 = 10.3 in. Corrected Ps
Use 10.3 in. Ps to select fan in performance pages.
Inlet Density
t
Correction Factor
®
4
Engineering Data
Inlet Vane Performance
As inlet vanes are closed, they impart a spin to the airflow in the direction of wheel rotation and reduce airflow, static pressure and brake
horsepower as shown in the graphs below. The graphs show how CFM, static pressure and brake horsepower are affected as inlet vanes
are modulated from 100% open to 0% open in a typical variable air volume system. Graph 3 provides RPM and BHP correction factors for
fans equipped with inlet vanes.
100
90
80
70
60
0% Open
50
40
30
% Peak Static Pressure
20
10
0
0 10 20 30 40 50 60 70 80 90 100
25% Open
50% Open
% Wide Open Volume
100% Open
75% Open
Without Vanes
100
% Peak Brake Horsepower
Graph 1Graph 2
RPM & BHP Corrections
To compensate for pressure drop through inlet vanes, a
percentage increase in fan RPM and BHP at full-load design
conditions must be applied.
Enter graph 3 with “% wide open volume” (see page 9 for
calculation of % WOV) and the appropriate fan size.
Move horizontally left to the “% increase” scale. Record the
% increase.
Increase the selected fan RPM by the % increase shown.
Also increase the BHP by the % increase shown.
20
18
16
14
12
10
8
% Increase
6
4
2
0
50 60 70 80 90 100
Graph 3
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
25% Open
RPM and BHP Correction Factors for Fans with Inlet Vanes
% Wide Open Volume (without vanes)
50% Open
% Wide Open Volume
BHP Fan Sizes 12-22
BHP Fan Sizes 24-73
RPM Fan Sizes 12-22
RPM Fan Sizes 24-73
75% Open
Without Vanes
100% Open
Minimum Recommended Actuator Torque For Inlet Vanes (inch-lbs.) for Single-Width Fans
Use the table below to determine minimum torque required for an inlet vane actuator.
Ratings in the fan performance tables and curves of this catalog are based on standard air (clean, dry air with a density of 0.075 pounds per
cubic foot, barometric pressure at sea level of 406.75 inches wg, temperature of 70°F). Selecting a fan to operate at conditions other than
standard air requires an adjustment to both static pressure and brake horsepower.
One cubic foot of air has a constant volume regardless of temperature or elevation. However, air density changes with non-standard
temperature or elevation. Therefore, when selecting a fan to operate at a non-standard air density using standard air density tables and
curves, corrections must be made to parameters affected by air density. These parameters are static pressure and brake horsepower.
For example, a size 30 BISW
centrifugal fan is to deliver
16,500 CFM at 8.1 incheswg
static pressure. Elevation
is 2000 feet, temperature is
150°F.
The 8.1 inches wg static
pressure refers to the static
Barometric Pressure
Multiply Standard Air Density, 0.075 lbm / ft3 by the Factor to obtain Density at Condition p
Altitude, (Z)ft.-1000
)
( p
b
pressure at the operating air
density, in this case at 2000
feet, 150°F. Intuitively, we
realize that at higher than
standard elevations and
temperatures, air density
will be lower than standard.
Therefore, we must determine
what static pressure at
standard air density will
equate to 8.1 inches wg static
pressure at our operating
density. Since standard
Temperature °F, (t)
air density is greater than
operating air density in this
case, we would expect the
corrected static pressure to
be greater than the operating
static pressure.
The accompanying table
gives air density correction
factors for non-standard
temperatures and elevations.
The example below shows
the relationship of fan
performance at sea level and
Adapted from AMCA Standard 99-09, section 0200, Charts and Tables, with written permission from Air Movement and
Control Association International, Inc.
at 2000 ft. elevation and 150°F.
Example:
The following example shows how to properly select the fan described above:
1. Since the air volume delivered by the fan is not affected by density, airflow remains 16,500 CFM.
2. Determine correction factor from chart for an elevation of 2000 feet and air temperature of 150°F. The correction factor is 0.808.
3. Divide the specified operating static pressure by the
correction factor to determine the standard air density
equivalent static pressure.
Corrected static pressure = 8.1 inches wg ÷ 0.808 =
10.0inches wg static pressure.
4. Refer to the fan performance table for a 30 BISW. At
16,500 CFM and 10.0 inches wg static pressure:
Fan RPM = 1790, BHP = 35.7
5. 1790 Fan RPM is required to produce the desired
performance.
6. Since the horsepower selected refers to standard air
density, this must be corrected to reflect actual BHP at
the lighter operating air.
Operating BHP = Standard BHP x 0.808, or 35.7 x 0.808
= 28.8 BHP.
If a fan is selected to operate at high temperatures, the
motor must be of sufficient horsepower to handle the
increased load at any lower operating temperature where
the air is more dense. Assume the air entering the 30 BISW
fan at start-up is 0°F. For 0°F and 2000 feet elevation, the air
density correction factor is 1.071
BHP at 0°F = 35.7 x 1.071 = 38.2, therefore, a 40 HP motor
is required.
Ratings presented in the performance tables and curves of this
catalog were derived from tests made in accordance with AMCA
Standard 210 — “Laboratory Methods of Testing Fans for Ratings.”
Inlet Spin
R
o
t
a
Turning
t
i
Vanes
o
n
R
o
t
a
t
i
o
n
The AMCA test procedure utilizes an open inlet and a straight
outlet duct to assure maximum static regain.
Any installation with inlet or discharge configurations that deviate
from this standard may result in reduced fan performance.
Restricted or unstable flow at the fan inlet can cause pre-rotation
of incoming air or uneven loading of the fan wheel yielding large
system losses and increased sound levels. Free discharge or
turbulent flow in the discharge ductwork will also result in system
effect losses.
Static pressure losses due to inlet and discharge conditions can
be expressed in terms of system effect factors. The static pressure
for selection of the fans equals the system static pressure plus the
system effect factor.
Some common inlet and discharge conditions which affect fan
performance are:
Non-Ducted Inlet Clearance
Installation of a fan with an open inlet too close to a wall or
bulkhead will cause reduced fan performance. It is desirable to
have one fan wheel diameter between the fan inlet and the wall.
System effect Curve #3 depicts the pressure loss for one-half
wheel diameter clearance.
Free Discharge
diameter
Free or abrupt discharge into a plenum results in a reduction in fan
One
fan
wheel
Inlet spin is a frequent cause of reduced fan performance. The
change in fan performance is a function of the intensity of spin
and not easily defined. The best solution is proper duct design and
airflow patterns.
Discharge Duct Turns
o
R
t
o
R
Duct turns located near the fan discharge should always be in the
direction of the fan rotation.
Fan performance is reduced when duct turns are made immediately
off the fan discharge. To achieve cataloged fan performance there
should be at least three equivalent duct diameters of straight
ductwork between the fan discharge and any duct turns. Curve#4
shows the system effect factor for two diameters of straight
ductwork and Curve #2 for one diameter.
POOR
n
o
i
t
a
t
n
o
i
t
a
POOR
Length of Straight Duct
GOOD
GOOD
performance. The effect of static regain in discharge is not realized.
System effect Curve #2 depicts the pressure loss for free or abrupt
discharge.
Inlet Duct Turns
Turning
Vanes
One fan
wheel
diameter
GOODPOOR
Installation of a duct turn or elbow too close to the fan inlet
reduces fan performance because the air is loaded unevenly into
the fan wheel. To achieve full fan performance there should be at
least one fan wheel diameter between the turn or elbow and the fan
inlet. Curve #1 shows the system effect factor when less than one diameter is provided. Note: Use of an inlet box in lieu of a turn or
elbow significantly reduces system effect.
System Effect Factor Curves
Additional information on system effect factors can be found
in AMCA Publication 201 — “Fans and Systems” and ASHRAE
Handbooks.
Static Pressure Loss
7
1.2
1.0
0.8
0.6
0.4
0.2
0.0
0 5 10 15 20 25 30 35 40 45
Outlet Velocity (FPM x 100)
Curve 1
Curve 2
®
Curve 3
Curve 4
Sound Performance Testing
ReferenceSound Source
Microphone
Path
Reverberant
Room
ReferenceSound Source
Microphone
Path
Reverberant
Room
SINGLE WIDTH
DOUBLE WIDTH
Airflow
Fan
Airflow
Fan
ReferenceSound Source
Microphone
Path
Reverberant
Room
DOUBLE WIDTH
Airflow
Fan
AMCA Licensed Ratings
Sound tests of Model BISW and AFSW were conducted in Greenheck Fan Corporation’s AMCA Accredited sound laboratory in accordance
with AMCA Standard 300. Inlet and outlet sound ratings comply with AMCA Publication 311, qualifying these models to bear the AMCA Seal
for Sound and Air Performance. The sound power levels published here can be compared directly with those of other similarly rated fans, or
used as a baseline to determine sound levels in occupied spaces.
The sound data in this brochure is the result of extensive testing, which included both inlet and outlet sound tests on single-width
centrifugal fans. Typically, fan manufacturers publish only inlet sound for single-width fans. The assumption they make is that outlet sound
is identical to inlet sound. Sound data based on this assumption is simply not accurate enough for today’s sound sensitive installations.
This assumption also ignores duct end corrections for outlet sound.
Test Methods
AMCA Standard 300 clearly defines methods used to test fans in a reverberant sound test room. The reverberant room is specifically
designed to allow sound waves to be dispersed evenly throughout the room. The walls have a hard surface that reflects sound and are
positioned to prevent resonances which could result in quiet areas within the room.
Sound power cannot be directly measured. The test method is based on a Reference Sound Source (RSS) substitution for determining fan
sound power. The RSS is a laboratory calibrated device which has a known sound power output level. The test fan is installed as shown
below. The RSS is energized and the sound pressure levels in the reverberant room are recorded. The fan is then operated without the RSS
and the fan sound pressure levels are recorded for various points of operation. Since the sound power levels of the RSS are known, the
substitution method is used to determine the sound power levels of the fan. This method is illustrated in the following example.
Calculating Fan Sound Power
Octave Band12345678
Center Frequency (Hz)
Calibrated RSS Sound Power (Lwr)
Measured RSS Sound Pressure (Lpq)
Difference (Lwr-Lpq)
Measured Fan Sound Pressure (Lpm)
Substitution (Lwr-Lpq , from above)
Fan Sound Power (Lw)
631252505001000200040008000
8281818181817978
7074757675746961
12765671017
6872696968625746
+12+7+6+5+6+7+10+17
8079757474696763
Note: Sound level shown in dB
Test Setups
The illustrations show where the sound levels were measured with respect to the fan. Inlet sound was tested as in Figure 2 of AMCA
Standard 300 and outlet sound was tested as in Figure 3. Inlet and outlet sound were determined in the same inlet and outlet configurations
as the air tests. (Installation Type B - Free Inlet, Ducted Outlet).
SINGLE WIDTH
Airflow
Fan
Figure 2:
AMCA Standard 300 - Fan Inlet Sound Testing
Installation Type B: Free Inlet, Ducted Outlet
Reference
Sound
Source
Microphone
Path
Reverberant
Room
Fan
Figure 3:
AMCA Standard 300 - Fan Outlet Sound Testing
Installation Type B: Free Inlet, Ducted Outlet
(Ratings include the effects of duct end correction)
Interpreting Sound Data
Sound power levels in this catalog are presented as dB (re 10
63Hz to 8000 Hz. They are also presented as a single A-weighted sound power level, LwA. Charts are provided covering the full range of
fan speeds and percent wide open volume (% WOV) for each fan size. Outlet sound power data is based on a ducted outlet and therefore
includes duct end reflection corrections.
®
-12
watts) in each of the eight full octave bands with center frequencies from
8
Airflow
Microphone
SINGLE WIDTH
Reference
Sound
Source
Reverberant
Path
Room
Sound Performance Testing
Outlet Sound – Duct End Corrections
This correction accounts for sound that is reflected back into the
duct where there is an abrupt termination of the duct.
AMCA Standard 300 requires that outlet sound power for fans with
ducted outlets include Duct End Corrections. These corrections
account for any sound power that may be present in the duct but is
not measured in the reverberant room, because it is reflected back
into the duct at the discharge.
Duct end corrections are included in all outlet sound power ratings.
Size
Duct End Corrections (dB)
Single-Width Fans
63 Hz125 Hz250 Hz
18
20
22
24
27
30
33
36
40
44
49
54
60
66
73
952
941
841
73
63
62
52
52
41
41
3
3
2
2
2
Tolerance and Application
The certification process in AMCA Standard 311 calls for a precertification test to verify original test results. Check tests are also required
every three (3) years for each model licensed. Test data must agree with the published sound power within the following tolerance levels:
Octave Band12345678
Center Frequency (Hz)
Tolerance
631252505001000200040008000
+6+3+3+3+3+3+3+3
These tolerance levels are a good indication of the variance that could occur from one fan or test setup to another. Once installed however,
there are many other factors that can affect the sound power generated by a fan.
The lower frequencies (below 125 Hz) are greatly affected by vibration. Fan wheel balance, motor balance, drive alignment, etc., all affect
the vibration level of the fan and can increase sound power in the 1st and 2nd octaves. When ducts are not properly isolated from the fan,
these vibrations can be transmitted into the ducts, which can generate additional low frequency sound.
Sound power generated by a fan can also be influenced by system effects. System effects are pressure losses caused by inlet or outlet
restrictions, or other conditions causing non-uniform airflow at the inlet or discharge of a fan (see AMCA Publication 201). Examples include
inlet or outlet elbows too close to a fan, restricted inlets and fan accessories. While system effects can prevent fans from reaching their
designed air performance, they can also result in increased sound power levels. Typically, system effects cause pressure fluctuations
which influence the lower frequencies. Poor inlet conditions can also greatly increase sound levels at the blade pass frequency (BPF). The
blade pass frequency refers to how often a blade or wheel fin passes a stationary location of the housing and can be calculated using the
following equation:
Per AMCA: Blade Pass Frequency
BPF (Hz)=
NOTE: All BISW and AFSW wheels have nine blades.
Sound is becoming increasingly critical for most fan installations. Greenheck employs extensive research and testing to provide sound data
that is as thorough and accurate as possible. However, sound pressure levels in occupied spaces are affected by the acoustical qualities
of the space, distance from source to receiver, etc. Therefore, published sound power data can be used only as a baseline for determining
the resulting sound pressure levels an occupant hears. While Greenheck provides products which meet published sound power levels,
no manufacturer can be responsible for poor installations or system designs beyond their control. For further information on installation
practices, see AMCA Publication 201, “Fans and Systems”.
Fan RPM x Number of Blades
(
60
2
)
Sound Power
Sound power data is charted for the full range of RPM and percent wide open volume (% WOV) for each unit size.
The % WOV is a convenient way to indicate the operating point (pressure and CFM) for a given fan RPM. To calculate the % WOV for a
given fan size, use the equation given on the performance page.
% WOV =
Use the following procedure to calculate sound data for a specific Fan RPM and % WOV:
1. Determine the eight sound power levels for the specified % WOV using the higher Fan RPM shown.
2. Determine the eight sound power levels for the specified % WOV using the lower Fan RPM shown.
3. Interpolate between the higher and lower sound power levels using the specified RPM.
CFM x 100
RPM x K
9
®
Sample Fan Selection
36-BISW-41
Fan Size
Series 21 - Permalock™Series 41 - Welded
WheelBI - Backward-InclinedAF-Airfoil
SW - Single-width, single-inlet
The purpose of these two pages is to demonstrate the
manual centrifugal fan selection process. These pages also
contain helpful tips to check your fan selection, as well as a
step-by-step set of instructions on how to use this manual
to properly select a centrifugal fan.
An important point to remember when manually selecting
a centrifugal fan is that more than one fan is available to
meet the desired performance (CFM and Ps). Selection
criteria such as unit size, efficiency, speed, outlet velocity,
horsepower, or construction material may also dictate which
fan is chosen.
36 BISW
AThe Outlet Area is used
for the Outlet Velocity
(OV) calculation.
OV =
CFM
OA
B The Maximum BHP can
be calculated for a given
fan RPM along the fan
curve.
C The minimum starting
HP is determined by the
inertia (WR
2
) of the fan
and motor. See page 4
for a complete motor
starting torque formula.
D The maximum fan RPM
for each fan class is
listed.
E The maximum open
motor frame size is listed
for each fan class by
arrangement. A complete
HP and frame size chart
is listed on page 3.
FConstant HP curves are
plotted for each motor
HP size.
G The % WOV is used to
identify the fan operating
point. The lines in the
fan curve or the equation
can be used.
Sound and Air performance are identical for Greenheck
Series 21 and 41 centrifugal fans.
The following example explains the model number code for
both series of centrifugal fans.
Minimum Starting HP = 1
C
Maximum RPM Class I = 1051
Maximum RPM Class II = 1371
D
Maximum RPM Class III = 1727
Maximum RPM Class IV = 2082
STATIC PRESSURE (in. wg)
E
Maximum Open Motor Frame Size
ClassIIIIIIIV
Arr. 9326T 326T 365TNA
Arr. 10 286T 286TNA
Step 1
STATIC PRESSURE (in. wg)
STATIC PRESSURE (in. wg)
NA
®
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
10
Fan Selection Procedure
BISW-36
STEP 1
Enter the performance table with the desired CFM
and Ps. Obtain the fan RPM, BHP and Class.
EXAMPLE
For this example, we will use 19,100 CFM at 4.0 Ps.
This gives us a fan RPM of 995, requiring 17.2 BHP,
with Class I construction.
NOTE: If your specific fan selection requires inlet
vanes or if the fan operating point is not at standard air
(70°F), refer to the inlet vane and air density correction
factor tables found on pages 5 and 6.
25
75
60
50
20
40
15
30
25
F
20
10
15
Static Pressure (in. wg)
10
7½
5
5
T
O
3
N
O
D
0
010203040506070
125
S
I
H
T
F
O
T
F
1051
150
E
V
R
U
C
M
E
T
S
Y
S
1371
1200
Step 2
100
E
L
E
H
T
O
T
T
C
E
L
E
S
900
750
600
1500
200
50% WOV
60% WOV
2082
1900
1727
1600
Volume (cfm x 1000)
020406080100
Volume (m /hr x 1000)
3
Class Max RPM
D
60
40
Static Pressure (Pa x 100)
20
0
I1051
II1371
III1727
IV2082
G
STEP 2
Enter the Fan Curve with the desired CFM and Ps.
Obtain the fan operating point, % WOV, Motor HP
and verify fan class by curve shading.
EXAMPLE
For this example, the fan operating point is at 60%
WOV using a 20 HP motor.
NOTE: This motor size can be compared to the
Maximum Open Frame Size chart (E) found above the
performance table.
36 BISW
STEP 3
Enter the Fan Sound Table
with the Fan RPM from the
performance table and the % WOV
from the fan curve. Obtain the
eight octave ratings for inlet (L
and Outlet (L
) Sound Power.
o
w
EXAMPLE
For this example, the eight octave
ratings can be calculated by
interpolating between the data
circled in the table.
NOTE: The exact % WOV for your
desired performance can be found
using the equation above the Sound
Power tables if it is not published.
The eight octave ratings can then
be found using the interpolation
instructions found in the Sound
Performance section on pages 8 and
9.
70% WOV
RPM
BHP
% WOV
Density 0.075 lb/ft
Density 1.2 kg/m
80% WOV
90% WOV
3
3
)
i
w
Sound Power [dB Ref 10
RPM %WOV 12345678 L
30010080 73 68 6257 49 4136 65
60010099 93 85 7879 73 6459 84
Step 3
80010095 100 92 86 8683 73 6891
1200 100 102 108 104 97 9594 87 81 102
1727 100 109 115 119 108 103 102 99 92 113
2082 100 112 118 122 116 109 107 104 98 118
The sound power level ratings shown are in decibels, referred to 10
, L
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
L
w
w
o
o
ratings shown have been calculated per AMCA International Standard 301.
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
A sound power levels for Installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction. The A-weighted sound
w
o
o
Inlet Sound Power, L
w
i
A
RPM %WOV 12345678L
i
w
-12
watts calculated per AMCA Standard 301. Values shown are for inlet L
Performance certified is for model BISW Arrangement 1, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.