Installation Instructions
Ultrasonic Ceiling Mounted Low
Voltage Occupancy Sensor
P/N 9850-000171-01
General Information
• Read all instructions on both sides of this sheet rst
• Install in accordance with ALL local codes
• For indoor use only
Specifications
Power Requirements:
Input:
• 10-30 VDC from Greengate Switchpack or Greengate
system. Maximum current needed is 25mA per sensor
Output:
• Open collector output to switch up to ten
Greengate Switchpacks.
Description
The OAC-U Ceiling Mount Low Voltage Occupancy Sensor is an Ultrasonic (US) motion sensing lighting control,
used for energy savings and convenience. The sensor produces a low intensity, inaudible sound to detect occupancy
in a room. Changes in the sensor’s acoustic wave caused by motion, such as walking in the room, reaching for a
telephone or swiveling in a chair, will cause the lights to turn ON. The sensor does not respond to audible sound.
When motion is detected, the blue wire is electronically connected to the red wire, energizing the relay in the
switchpack to turn on the load. If vacancy is detected, the blue wire is disconnected from the red, causing the relay
to open turning OFF the load. The red lead is 10-30 VDC supply, the black lead is common, and the blue is the relay
control.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and
time delay in real-time.
Coverage
20 ft
(6.096m)
12 ft
(3.65 m)
9 ft
(2.74 m)
0
9 ft
(2.74 m)
12 ft
(3.65 m)
20 ft
(6.096m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
5 ft
10 ft
(1.52 m)
(3.05 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
(4.57 m)
OAC-U-0501-R Coverage Diagram
15 ft
coverage patterns.
(7.01 m)
23 ft
20 ft
(6.096m)
12 ft
(3.65 m)
9 ft
(2.74 m)
0
9 ft
(2.74 m)
12 ft
(3.65 m)
20 ft
(6.096m)
• For Use with Greengate Switchpacks & Systems Only
• Do not run any Greengate Low Voltage Wiring in
thesame conduit as power conductors
• BAS with Isolated Form C Relay (-R model)
• Isolated Form C Relay Ratings: 1A 30 VDC/VAC
Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: up to 90% non-condensing
DT1k
23 ft
(7.01 m)
15 ft
17 ft
(4.57 m)
(5.18 m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
10 ft
(3 m)
0
5 ft
(1.5 m)
(1.5 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
5 ft
10 ft
(4.57 m)
(3 m)
OAC-U-1000-R Coverage Diagram
15 ft
17 ft
23 ft
(5.18 m)
(7.01 m)
Ultrasonic
Activated
(6.096m)
16 ft
(4.87 m)
12 ft
(3.65 m)
0
12 ft
(3.65 m)
16 ft
(4.87 m)
20 ft
(6.096m)
32 ft
(9.75 m)
23 ft
15 ft
(7.01 m)
(4.57 m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
10 ft
(3 m)
5 ft
(1.52 m)
5 ft
0
(1.52 m)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
10 ft
(3 m)
15 ft
(4.57 m)
23 ft
(7.01 m)
32 ft
(9.75 m)
OAC-U-2000-R Coverage Diagram
Location
The maximum coverage area may vary somewhat according to room shape and the presence of obstacles. Decrease
total coverage area by 15% for “soft” rooms (for example, heavy draperies or heavy carpeting). The sensor must have a
clear view of the area to be controlled. The sensor will not “see” through glass. Mounting height should not exceed 12
feet. Optimum mounting height is 8 to 10 feet. Mount the sensor so the grilles face the open portion of the room and
are not facing a nearby wall, door, window, or other obstructing object. Avoid pointing into hallways. Mounting at xture
height is most effective. *To prevent false activation, the sensor should be mounted away from the air supply duct a
minimum of 4 to 6 feet.
9.14 m
OAC-U-1000 & OAC-U-2000
30 ft
9.14 m
4.57 m
OAC-U-0501
15 ft
4.57 m
Installation
The OAC-U sensor can be mounted to the ceiling, junction box, or round xture with raceway.
OAC-STEM Threaded Rod
(sold separately)
Model # OAC-U-0501
Model # OAC-U-0501-R
Model # OAC-U-1000
Model # OAC-U-1000-R
Model # OAC-U-2000
Model # OAC-U-2000-R
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at
the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch
for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in
compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened
by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. (Use twist-on wire connectors
for all connections) CAP ALL UNUSED WIRE LEADS.
3. Mount unit to ceiling, junction box, or round xture with raceway.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
One Sensor, One Switchpack
Line
Neutral
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Red (15 VDC)
Blue (Control)
Black (Common)
Red
Blue
Black
Manual or Automatic-On Control of
Two Standard Switchpacks
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Red (15 VDC)
Blue (Control)
Black (Common)
Red
Blue
Black
Brown
Yellow
Purple
Gray
Orange
White/Brown
Manual Mode Operation:
Switches are required to
turn corresponding loads ON.
Lights turn OFF when sensor
times out or with the
switch.
Automatic Mode Operation:
Sensor turns ON both
switchpacks. Switches can
be used to turn lights ON
or OFF.
If daylight sensor is
enabled and light level is
above setpoint, switchpack
connected to yellow lead
will not turn ON.
Recommended Wire:
18-3 AWG Stranded Wire
non/shielded.
SWITCH-
PACK
To additional sensors
Maximum of 5 sensors
per switchpack
To additional switchpacks
Maximum of 10 switchpacks
per sensor
Hot
Line
Neutral
SWITCH-
PACK
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Red (15 VDC)
Blue (Control)
Black (Common)
Model GMDS - Load 2
(Normally Open
Momentary Switch)
Model GMDS - Load 1
(Normally Open
Momentary Switch)
**Hot
**Hot
Blue
Blue
White
White
Line
Blue
Load
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30 VDC)
Blue (Control - Occupancy)
Yellow (Control - Occupancy and Daylight)
Brown (Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally Closed)
Hot
Neutral
SWITCH-
PACK
Load 1
**Hot
White
Blue
Blue
Blue
Load 2
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
DIP Switch Settings
Zero Time Delay
(-R model only)
(-R model only)
Daylight Sensor Adjustment
Not Used
Ultrasonic Sensitivity Adjustment
ON
12345678 910
LEDs
11 12
Full/Half Logic HVAC/Tracking
SweepOverride
(-R model only)
(-R model only)
Checkout and Adjustment
LED Indicators Functionality
During Installer/Test Mode While in User Mode
LED Flashing Speed
Duration
LEDs will ash once per ¼ second LEDs will ash once per second
10 minutes 10 to 30 minutes
Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.
Self-Adjust
Sensor is shipped in the Self-Adjust Mode. This applies to time delay and US sensitivity. In preparation for the
Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered-ON and has stabilized, the
unit will time-out 15 seconds after the last motion detected. Coverage and sensitivity can be conrmed by watching
the Green (US) indicator LEDs on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs. LEDs should only turn ON for ¼ second with each motion. (If LEDs do
not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)
2. Stand still six to eight feet away from the sensor for ve seconds. LEDs should not turn ON. (If any LED turns
ON, note LED and go to Installer Adjustments – Sensitivity Adjustment section)
3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer
Adjustments Section)
4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 10 minutes then automatically exit Test Mode and go for 10 min. Time
Delay User Mode setting.
Note: To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in
to its original position. To force into 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and
2 are already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original
position) While in Test Mode, the LEDs will ash once per 1/4 second.
Installer Adjustments
Full and Half Logic Modes (See DIP Switch legend):
In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy
activation, should the ambient light level exceed the preset foot-candle level.
After activation:
Full Logic Mode - should the ambient light level exceed the preset foot-candle level, the lights connected to the yellow
control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.
Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after occupancy activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn the
lights OFF while occupancy is being detected.
Note: Set the light level when the ambient light is at the level where no articial light is needed. In order for this fea-
ture to function, the yellow control lead must be wired.
1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 10 out of its current
position, wait 3 seconds and then back in to its original position.
2. Set DIP Switch 10 to Full or Half Logic Mode.
3. Set the Light level to Minimum (fully CCW).
4. Leave the room and let the sensor Time-out so lights are OFF. Enter the space and lights should remain OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small
increments until the lights are ON. (Pause 5 seconds between each adjustment)
6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current
illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 minutes. As long as Auto is enabled, the sensor will respond to each pair of False-offs with no normal OFF in between, by
alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so there should be no
need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend.
Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are
already down, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back to its original position)
Automatic Mode
In Automatic-ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage switches
are used along with Automatic-ON Mode, activating the switch(es) while the load is ON turns the load OFF. When the
load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After the Time
Delay expires, the lights stay OFF and the sensor goes back to Automatic-ON Mode. For wiring information for the
optional momentary low voltage switch(es), please see the wiring section of the installation instructions.
Manual Mode (-R Model Only)
In Manual-ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated
the sensor will maintain the lights ON until motion ceases and the Time Delay expires. While the room is occupied the
BAS relay remains active. After the Time Delay expires, the load(s) will automatically be turned OFF and the switch(es)
must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.
Lighting Sweep Option
If selected, this DIP Switch option forces an initial 60 second delay upon “power up” to prevent false activation in
buildings with computer control systems.
1. Move DIP Switch 9 up. If not selected (Dip Switch 9 down), upon initial “power up” or restoration of power the sen-
sor will force the lights ON no matter the state of occupancy.
HVAC/Tracking Mode (-R model only)
If selected, Tracking Mode allows the load connection to the Form C relay to follow the state of the sensor’s blue
lead. HVAC Mode allows the load connected to the Form C relay to remain ON when the lights are turned OFF manually.
Applications may include keeping the room at a desired temperature while giving a presentation and the lights are OFF.
Troubleshooting
Issue Possible Causes Suggestions
Wall Switch OFF Turn Wall Switch ON.
Lights
Will Not
Turn ON
automatically
Lights
Will Not
Turn ON
manually
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Lights Will Not
Turn OFF
manually
If low voltage switch option is used, lights may
have been turned-off manually.
Daylight Feature Enabled
Power interruption Check incoming voltage and/or wiring
Daylight Feature Enabled
Power interruption Check incoming voltage and/or wiring
Override Make sure sensor is not in Override Mode (DIP Switch 8 up).
Sensor installed close to an air vent
Sensor installed close to indirect lighting. Sensors should be mounted away from indirect lighting.
Self-adjust
30 Minute Delay
Bypass
Override Make sure sensor is not in Override Mode (DIP Switch 8 up).
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
If all lights are required to turn ON adjust DIP Switch 10 and/
If all lights are required adjust DIP switch 10 and/or daylight
Sensors should be installed minimum 4 - 6 feet away from
It may be possible for the unit to have self-adjusted the time
delay to a 30 minute delay. If the lights do not turn OFF after
Maximum time delay is 30 Minutes. Check DIP Switches to
verify DIP Switch settings. If lights do not turn OFF at the set
Check wiring to make sure sensor or switchpack are not
Press low-voltage switch.
or daylight potentiometer
potentiometer.
any air vent and out of path of heavy airow.
30 minutes follow next step.
time delay, check next step.
bypassed.
Warranties and Limitation of Liability
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
Sensitivity Adjustments
Ultrasonic Sensitivity (Green LED)
1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning the green potentiometer clockwise in
small increments. Repeat Step 1.
3. Stand still six to eight feet away from sensor for ve seconds. LED should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the US sensitivity by turning the green
potentiometer counter-clock-wise in small decrements. Repeat Step 3.
Field-of-view outside the space
1. Adjust Ultrasonic sensitivity.
Daylight Adjustments (-R Model Only 0 to 300 foot-candles)
If this feature is not needed, leave the light level at maximum (fully clockwise).
The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural
light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not
enough light in the room, the sensor will allow the lights to turn ON when occupied.
Zero Time Delay Mode
In Zero Time Delay Mode, the output is actuated for one second to signal another device that the space being
monitored is occupied. Applications may include the use of a lighting control system to manage the delay of the lighting
deactivation. Please see the wiring diagram section for wiring details.
When in Zero Time Delay Mode and Tracking Mode the load connected to the Form C relay shall follow the state of
the sensor’s blue lead (zero Time Delay for the form C relay).
When in Zero Time Delay Mode and HVAC Mode, the load connected to the Form C relay remains ON for the standard
Time Delay.
Override
The Override setting allows the lights to remain ON in the unlikely event of sensor failure.
1. Move DIP Switch 8 up.
While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).
Printed in Malaysia
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com