Greengate GDS Installation Manual

Installation Instructions
Model# GDS
Greengate Digital Switch Interrupteur numérique Greengate Interruptor digital Greengate
INS #
General Information
The Greengate Digital Switch station from Eaton’s Cooper Controls Business provides a sleek appearance combined with complete control and flexibility. The adaptable design allows you to easily choose from a range of button configurations.
GDS Supplied Parts
Main Body
Inner Plate
Front Cover
GDS Dimensions
The Greengate Digital Switch is intended to fit into a single gang wall box with a minimum internal depth of 2 inches (51 mm).
0.25 in
3.25 in
(83 mm)
(6.4 mm)
1.38 in
(35 mm)
GDS Installation
1. On the underside of the front cover, beneath the lower buttons, locate the small central recess. Carefully insert a small implement (such as a pen or screw driver) into the recess and lever the front cover gently away from the inner plate.
2. Unclip the front cover from the top of the inner plate.
3. Remove the two retaining screws located above and below the buttons and lift the inner plate away from the main body.
Zone 1
Zone 2
4.75 in
(121 mm)

Mounts to standard NEMA style wall box, standard digital switch insert size
Zone 3
Zone 4
Zone 5
Zone 6
3.26 in
(83 mm)
0.65 in
(17 mm)
GDS Installation
4. Store all removed parts safe from damage.
Wall Box Installation
The Greengate Digital Switch is intended to fit into a single gang wall box with a minimum internal depth of 2 inches (51 mm). With the Greengate Digital Switch disassembled, use the two supplied long screws to secure the rear chassis plate to the wall box.
CANbus Connections
The Greengate Digital Switch uses CANbus connections to ensure reliable and responsive transfer of control signals between multiple devices.
CANbus devices must be installed in a “daisy-chain” configuration. Avoid installing GDS stations in Star or T-tap configurations.
Cable connections are made to a removable 5-way connector block located at the rear of the Greengate Digital Switch main body:
0V
(black)
CAN-L
(blue)
DRAIN
(gray)
CAN-H (white)
+24V
(red)
Termination
The CANbus link is a ‘daisy-chain’ protocol that requires termination on the devices located at either end of the chain.
Device Device Device
ControlKeeper M
The Greengate Digital Switch is supplied with termination enabled as standard. If the Greengate digital switch is not connected as an end device in the chain, you need to disable termination.
To disable termination, move the jumper from the upper two pins to the lower two pins as shown here.
Termination ON Termination OFF
Changing Buttons
The Greengate Digital Switch station allows you to change the buttons in order to customize its appearance.
1. Remove the front cover and inner plate as discussed in ‘Disassembling the wall station’.
2. Locate the four clips (two on each side) of the button frame. Carefully press in all four clips to disengage the button frame and pull the frame away from the main body.
3. You can now remove the buttons from the frame and replace.
Cable Type
Max. cable length 1000 ft/305 m
Devices per segment
2
Eaton’s Cooper LCCNP (Non Plenum) or Eaton’s Cooper LCCP (Plenum) or Belden1502R (Non Plenum) or 1502P (plenum)
Refer to panel Installation Instructions for proper # of devices. If additional devices are required the EXPS-24 accessory power supply will allow an additional 25 devices per panel.
Greengate Digital Switch
Main body
Button frame
with buttons
4. With the new buttons in place within the frame, align its clips with the four holes of the main body and press it into place so that all four clips click as they lock.
5. Place the inner plate onto the main body (noting the orientation arrow). With the plate in place, insert and lightly tighten the two retaining screws.
Reassembling the GDS
1. Place the inner plate onto the main body (noting the orientation arrow). With the plate in place, insert and lightly tighten the two retaining screws.
Reassembling the GDS
2. Attach the top edge of the front cover to the main body.
3. Angle the front cover down and press the lower part of it against the inner plate until it clicks into place.
Ambient Atmosphere Requirements
Temperature: 32° F to 104° F (0° C to +40° C) Humidity: 0 to 95% non-condensing
Greengate Digital Switch
3