Greengate ControlKeeper 4 Installation Manual

Installation Instructions
ControlKeeper 4
Model# CK4-120NO Model# CK4-277NO
INS #
General Information
The ControlKeeper 4 model is shipped in one package and is configured with either a 120V or a 277V transformer. It is factory configured with Normally Open relays. Please refer to your order information to determine which model you have purchased.
Getting Started
1. Do not discard these installation instructions. Please keep for future reference and operation information.
2. Always disconnect all power before wiring.
3. Use only as intended and at the listed voltage.
4. All installation and service must be performed by qualified personnel or service technicians.
5. Install in accordance with the National Electrical Code and any other codes which may apply.
6. Installation and wiring information contained in this document is based on industry-accepted standards and practices. If conflicts exist between these instructions and any applicable codes or ordinances, please contact Greengate before proceeding with the installation.
7. High voltage is present inside the enclosure. Use extreme caution when performing maintenance on this equipment. Failure to follow this warning and proper safety procedures could result in severe injury or death, and/or damage to the equipment.
8. Document all wiring and device terminations and locations so that devices can be properly configured and programmed for operation.
Mounting the Cabinet
1. Choose a dry location on a firm surface convenient to the circuits being controlled. Allow full clearance for the door of the enclosure to open fully.
2. Mount the ControlKeeper 4 cabinet using the holes provided in the back of the enclosure. It is recommended that the panel be mounted vertically.
3. All line voltage conductors must enter the cabinet on the right side of the enclosure.
4. All low voltage conductors must enter the cabinet on the left side of the enclosure.
5. Remove all debris and metal shavings from the enclosure before applying power to the ControlKeeper 4.
Bring low voltage in through the Left Side of the Enclosure
Figure 1. ControlKeeper 4 Enclosure
Bring high voltage in through the Right Side of the Enclosure
Power Supply Wiring
The ControlKeeper 4 is factory configured with either a 120V or a 277V transformer. Transformer voltages are color coded. It is recommended that a dedicated branch circuit with circuit protection be used for power supply wiring.
1. Connect neutral wire to the white wire.
2. If the transformer is a 277V model, connect orange wire to a 277V circuit. If the transformer is a 120V model, connect black wire to a 120V circuit.
General Information
Netural=White
Netural=White
Line=120V (Black) 277 (Orange) Netural=White
120V Transformer Line=Black
277V Transformer Line=Orange
Figure 2. ControlKeeper 4 Enclosure
Connecting Relay Loads
1. Test branch circuits for short circuits prior to connecting and energizing the ControlKeeper 4.
2. Relay terminal blocks have a maximum limit of 10 AWG wire.
3. Relays are rated for single-pole circuit use. Connection of 2 pole circuits/loads to the ControlKeeper 4 will void the equipment warranty.
4. Connect a 120 or 277 volt, 20 amp maximum, de-energized branch circuit breaker to the relay terminal block position labeled LINE.
5. Connect the load to the output terminal block position labeled LOAD.
6. Tighten down relay terminal screws. Manufacturer’s recommended torque rating is 7 lbs-in. (0.59 lbs-foot) (0.8Nm).
Relay Wiring
Wire: 10 AWG Max
Relay Rating: 20 amps, 277V
RELAY 1
LINE
LOAD
LINE
From Branch Circuit
To Lighting Load
Network Wiring Notes
The ControlKeeper 4 is designed to communicate with other ControlKeeper network panels using a lighting control RS-485 network for communications. This allows the panels to share information and to be programmed from one central location by a computer with the Keeper Enterprise Software.
Please refer to Table 1 for information on recommended wiring for network.
Acceptable
Network Wiring
Standard RS485 Belden 9841 (Shield is not used)
Plenum RS485 Belden 89841 (Shield is not used)
Table 1. Network Wiring Recommendations
For best network performance, one of the suggested cables should be used. If the specified cable is not used and communications problems occur that require troubleshooting assistance, additional charges for support may be assessed.
1. All low voltage wiring is Class 2.
2. All low voltage wiring must enter the cabinet from the left side of the enclosure.
3. All low voltage wiring must be run in separate conduit from line voltage wiring.
4. Test all network wiring for shorts to AC ground before connecting to the ControlKeeper 4 panel.
5. If using Belden 9841 or 89841, leave all shields disconnected making certain that shield is not exposed.
6. Panels and devices on the RS-485 lighting network should be daisy-chained. Do not create a Star or T-Tapped configuration.
Suggested Cable
LOAD
RELAY 2
LINE
LOAD
RELAY 3
LINE
RELAY 4
LOAD
Figure 3. Address Switch Information
ote:N Neutrals terminate within the adjoining lighting panel.
2
ControlKeeper 4
7. Total network length should not exceed 4000 feet.
Network Wiring Details
1. Before wiring, select the two panels that are going to be the end panels of the network and plan a wiring scheme accordingly. Panels should be daisy-chained, not Star or T-Tapped.
2. Starting at one of the end panels, connect the network (+) and (-) terminals to the next panel’s network (+) and (-) terminals. Continue this process through the network
making certain to observe polarity. When finished, the two end panels will have a single pair of wires coming into the network terminal block while all middle panels in the network will have two sets of wires.
3. Set the network termination jumpers. On the end panels on the network set to the terminated position. For all panels in the middle of the network, remove the network termination jumper. See Figures 4 & 5 for details.
4. On the two end panels in the network, set the network termination jumpers to the terminated position.
5. On the middle panels in the network, remove the network termination jumpers.
6. Set all panel addresses using the panel network identification DIP Switches on each panel. See Figures 5 & 6 for location and details.
7. Using the panel reset switch, issue a soft reset to each panel to initialize the panel address. See Figure 5 for location of the reset switch.
General Information
RS232 DIGITA NETWORK
Network Wiring Terminal Block
Figure 5. Item Reference for Network Details
Switch Position
Value
Network Address Switch
Panel Reset Switch
Network Termination Jumper
ON
OFF
End Panel Network Wiring Detail
Middle Panel Network Wiring Detail
End Panel Network Wiring Detail
Figure 4. Network Wiring Detail
Termination Jumper ON
Termination Jumper OFF
Termination Jumper ON
All panels must be assigned a unique Network Address in order to communicate over the lighting network. Switch positions are labeled 1 through 8 and are valued at 1 through 128 as shown above. The network address is calculated by adding the value of the switch positions that are in the ON position. In the example above, switches 1 and 3 are ON giving the panel the network address of 5. Addresses 1 through 254 are valid addresses. Zero and 255 are reserved for system use. To initialize the network address with the controller, press the panel reset button after the address is set.
Figure 6. Address Switch Information
Connecting Low Voltage Inputs
The ControlKeeper 4 logic board can support both dry contact closure and Digital Switch inputs. If a combination of contact input switches and Digital Switches are being used, the combined total cannot exceed 64 inputs. Regardless of input type used, it is recommended that all input wiring be done prior to applying power to the logic board or at the very least with the terminal blocks removed from the logic board. Please verify that there are no shorts to AC Ground prior to connection of input devices. Regardless of input type, the following notes apply.
1. All low voltage wiring is Class 2 wiring.
2. All low voltage wiring must enter the cabinet into the Low voltage section of the enclosure. Low voltage wiring can be brought into the enclosure from the left side of the enclosure. Failure to separate high voltage from low voltage wiring may cause interference with logic board function.
3. All low voltage wiring must be run in separate conduit from line voltage wiring.
4. Test all low voltage wiring for shorts to AC ground before connection to the relay panel.
ControlKeeper 4
3
General Information
5. When powering peripheral devices such as motion sensors and photosensors from the ControlKeeper 4 panel, there may be a limitation on the number of sensors that can be supported. This is also true if Digital Switches are used with the system. See the recommendations below or contact Cooper Controls for further information.
6. It is recommended that the terminal blocks be removed from the board or power removed from the logic board when doing initial switch input wiring.
Contact Input Switch Wiring
This section describes the wiring for dry contact closure devices. There are four switch input wiring terminals on the left side of the ControlKeeper 4 to allow for wiring of the dry contact closure devices.
1. Use 18 AWG twisted, unshielded wire for all low voltage dry contact closure device wiring.
2. Maximum length for dry contact closure device wiring is 1000 feet.
3. Please see wiring detail below for details on connections of different devices to the ControlKeeper 4 system.
Momentary Switch
(3 wire)
Toggle Switch (2 wire)
C20
U21
C26
U26
RN1
TB4
ON
+24VDC
OFF
Maintaned Switch (2 wire)
+24
OFFON
CH1
ON
+24VDC
ON +24
+24VDC
CH2
U17
U18
U19
U24
U23
U22
U27
41235687
U29
ON +24
ON +24
OFF
OFF
CH4
CH3
ON
U28
TB5
+24
OFF
VDCDCGND
U20
U25
J2J1
S7
RESET
NET TERM
TB7
J3
-+
NETWORKDIGITARS232
Figure 7. Standard Relay Card Wiring
Contact Input Photosensor and Greengate Sensor Note
It is possible to use a contact input photosensor and Greengate Motion Sensors in conjunction with the lighting control system. The ControlKeeper 4 is capable of powering a number of these devices. Please refer to the chart below for details on how many devices the transformer can support.
Greengate
PIR Sensor
Greengate
Dual-Technol
Greengate Ultrasonic
Sensor
PPS-4 Indoor
Photosensor
40 16 20 20 4
Please contact technical support if it is necessary to power
PPS-5
Outdoor
Photosensor
additional sensors beyond the numbers listed above. These figures do not account for additional devices such as Digital Switches being used. If using a combination of devices, please contact technical support for exact details on how many devices the logic panel can power.
Black
ON
+24VDC (Red Wire)
Yellow & White Wires Not Used
PPS4
Black
PPS5
Black
Black
Typical Greengate
iW kcalB( er )
DNG CD RWP MER
Contact Input Photosensor Wiring
ON
(Blue
Wire)
(White Wire)
+24VDC (Red Wire)
(Blue Wire)
+24VDC (Red Wire)
ON
Motion Sensor Wiring
Figure 8. Photosensor and Motion Sensor Wiring
Digital Switch Wiring
Each ControlKeeper 4 panel is capable of supporting up to 7 Digital Switch device stations and 1 GDS-I gateway device (the number the controller is able to support is dependent on the number of other low voltage devices wired that require power from our logic board. Please contact Technical Support for exact details of how many devices your logic board can power.)
Digital Switch cable type should be Eaton’s Cooper LC Cable, Belden 1502R (non-plenum), or Belden 1502P (plenum).
For best network performance, one of the suggested cables should be used. If the specified cable is not used and communications problems occur that require troubleshooting assistance, additional charges for support may be assessed.
Digital Switches do not wire directly to the ControlKeeper 4 panel, but are wired to a CAN Bus network that connects to the ControlKeeper 4 through a GDS-I device. Digital Switch devices should be networked together in a daisy-chain
4
ControlKeeper 4
General Information
Individual Relay
Override Switches
Hardware Override Switch
ControlKeeper® 4 Upper Left Corner
configuration. No T-Taps/Stars should be used. The GDS-I device should reside somewhere within the daisy-chain switch net work. Total daisy-chain network length should not exceed 1000 feet.
The following instructions describe the GDS-I device connection to the ControlKeeper 4. Please refer to the Digital Switch Installation Instructions for information on wiring the Digital Switch network to the GDS-I.
1. Mount the GDS-I next to the ControlKeeper 4 panel. A six foot phone style cable has been provided for connectionto the ControlKeeper 4 panel.
2. Run a length of the Digital Switch LC or Belden cabling from the GDS-I location to the low voltage section of the ControlKeeper 4.
3. Connect the RED wire in the cable to the +V terminal on the back of the GDS-I and to the ControlKeeper 4 at one of the switch input +24VDC terminals.
4. Connect the BLACK wire in the cable to the GND terminal on the back of the GDS-I and to the ControlKeeper 4 remote power connector GND terminal.
5. Tape back or cap the blue and white wires and shield wire for the cable. They will not be used for connection between the GDS-I and lighting controller.
6. Locate the 6 foot phone style cable included in the GDS-I box. Run this from the GDS-I into the low voltage section of the ControlKeeper 4 enclosure plugging the end with 9 pin head into the GDS-I. Plug the end the RJ11 phone style plug into the ControlKeeper 4.
Applying Power
1. After wiring is complete, make certain to clean panel of all wire clippings and fragments ensuring that no fragments get lodged between the circuit board and enclosure.
2. Ensure that there are no loose wires or exposed wires that could short out.
3. Make certain that the line voltage section of the enclosure is closed and secure.
4. Power-up the unit. It is recommended that the unit be cleared of all programming unless the unit has been sent pre-programmed to you by the factory. To perform this step, hold down the reset button for about 15 seconds.
5. Please refer to the operation section of this instruction for information on turning ON and OFF lighting loads. Refer to the Keeper Enterprise Software manual for information regarding the programming of the ControlKeeper 4 jumper.
Relay Override Operation
The ControlKeeper 4 has two means of override located on the logic board: individual relay override buttons and a hardware override switch. It is possible to control lighting loads and override programming using these override mechanisms.
C20
U21
C26
U26
RN1
U29
TB4
+24
ON +24
OFFON
CH2
CH1
BLACK Wire From GDS-I GND to CK4 GND
RED Wire From GDS-I V + to CK4 +24VDC
Cabling is Eaton’s Cooper LC Cable,
Belden 1502R, or Belden 1502P
Figure 9. GDS-I Wiring Detail
U17
U18
U23
U22
U27
U28
TB5
ON +24
ON +24
OFF
OFF
OFF
+24 VDCDCGND
CH4
CH3
U20
U19
U24
U25
41235687
J2J1
S7
RESET
NET TERM
TB7
J3
-+
NETWORKRS232
Wire Phone Style Cable to RJ11 Jack on CK4 and to GDS-I
Figure 10. ControlKeeper 4 Status LEDs
Individual Relay Override Notes
Each relay on the ControlKeeper 4 may be overridden using the individual relay override switches located at the top
GDS-I
left of the low voltage section. See Figure 9 for location of these switches. These override switches will toggle the associated relay’s state with each push of the button. This type of over ride is temporary in that the override will last until the next command that the relay is given.
Hardware Override Switch Notes
In addition to the individual relay override switches, there is a hardware override switch that allows the override of all relays on the board. If this switch is moved to the ALL ON or ALL OFF position, all four relays will remain ON or OFF as long as the switch is in that ALL ON or ALL OFF position. The ON or OFF state is maintained regardless of programmed state. In order for relays to run programmed
ControlKeeper 4
5
General Information
scheduling the hardware override switch must be in the AUTO or center position. See Figure 9 for location of the hardware override switch.
LED Operation
The ControlKeeper 4 has LEDs for status monitoring. They consist of System Status LEDs and Relay Status LEDs.
ControlKeeper® 4 Upper Left Corner
Digita Switch
Status Power Network
System Status LEDs
Relay Status LEDs
Relay 1 Through 4
Figure 11. ControlKeeper 4 Status LEDs
System Status LEDs
There are six (6) system status LEDs that are located in the upper left corner of the ControlKeeper 4. Please refer to Figure 10 for location of these status LEDs. These status LEDs will indicate proper operation or potential problems with the ControlKeeper 4. Normal Operation includes the following LED states.
Status LED:
The Status LED will flash ON and OFF continuously under normal operation. The LED is an indication of microprocessor health. If the LED is ON or OFF all the time, please use the soft reset button on the controller. If the LED does not resume normal flashing state, contact Technical Support.
Digital Switch LEDs:
These LEDs, labeled CAN-TX and CAN-RX, will flash when Digital Switch information is being passed back and forth between the Digital Switch Gateway and the ControlKeeper
4.
Power LEDs:
These LEDs, labeled POWER and ISO POWER, indicate that the ControlKeeper 4 is getting the proper expected voltage from the transformer. If one or both of these LEDs is not lit, there is a problem with power to the board. Please contact Technical Support for further details.
Network LED:
The Network LED should flash only when activity is present on the network wire. If communications commands are not being transmitted over the network wire from the Keeper
Enterprise Software or broadcast switches and this LED is flickering, ON constant, or flashing, it is an indication of noise on the network wire that may interfere with proper system operation. Please check all network wiring carefully for shorts to AC Ground if this condition exists. Contact Technical Support for further troubleshooting help.
Relay Status LEDs
There are four relay status LEDs, one for each of the relays on the ControlKeeper 4. Please refer to Figure 10 for location of these LEDs. The relay status LEDs are an indication of whether the associated relay is energized or de-energized. If the relay LED is ON, the relay load should be ON. If the relay LED is OFF, the relay load should be OFF.
ControlKeeper 4 RS232 Port
The ControlKeeper 4 has an on board RS232 port for communications to peripheral accessory devices or to the Keeper Enterprise Software. This RJ style jack should not be connected to any device not intended for use with the lighting control system. Connection to a phone line will cause damage to the lighting control system that is not covered under warranty. Please use only Greengate approved device connections for connection to this port.
System Reset and Clear Commands
Under certain circumstances, you may want to reset the ControlKeeper 4. There are two different types of reset commands available in the ControlKeeper 4 system: a soft reset command and a clear reset command.
Soft Reset Command:
A soft reset command is used to initialize a new panel address with the panel. It can also be used as a troubleshooting technique if the panel is not responding or to free up the microprocessor if the unit’s STATUS LED is not flashing. The Soft Reset Command will not cause loss of panel programming. To perform a Soft Reset Command, press in and then immediately release the reset button in the lower right corner of the logic panel. When the reset button is pressed and released, the status LED may hesitate briefly then resume normal operation.
Clear Settings Command:
A clear settings command is used to remove all programming from a ControlKeeper 4 unit. It should be done before downloading programming to the unit for the first time or when asked to by a Technical Support representative. Please use caution with this command! When performing a Clear command, all relay loads will turn OFF. Use the Hardware Override Switch to keep lighting ON if necessary.
In order to reprogram the unit, you will need to use the Keeper Enterprise Software. To perform a Clear Command, press and hold down the reset button in the lower right corner of the low voltage section for a period of 15 seconds
6
ControlKeeper 4
General Information
until the STATUS LED turns OFF. Once the STATUS LED turns OFF, release the reset button. The ControlKeeper 4 unit will be reset back to factory default settings.
Programming the ControlKeeper 4
The ControlKeeper 4 is programmed using Keeper Enterprise Software. Please refer to the Keeper Enterprise Manual for programming details. It is recommended that a Clear Command be performed on the controller before the first programming download to clear any test data that may be left in the controller from factory testing.
Item Reference
The ControlKeeper 4 consists of a logic board with a clear separation of line-voltage and low voltage components. There are several features of note on the logic board as pointed out in the below item reference diagram.
2
3
4
1
Repair Information
If a repair becomes necessary on your ControlKeeper 4 unit, please refer all service to Greengate’s technical support line at 1-800-553-3879. The ControlKeeper 4 contains no user serviceable parts.
5
14
Figure 12. Item Reference
1. Individual Relay Override Switches (Temporary override)
2. System Status LEDs
3. Relay Status LEDs
4. Panel Hardware Override Switch (ALL OFF, AUTO, ALL ON)
5. Transformer Wiring Leads: White = Neutral, Orange = 277V, Black = 120V
6. Relay Wiring Terminals
6
78910111213
7. Panel Reset Switch
8. Network Terminator Jumper
9. Network Wiring Terminal Block
10. Digital Switch Port
11. Panel Communications Port
12. Peripheral Power Terminal: +24 VDC, DC Ground
13. Switch Input Wiring Channels
14. Panel Network Address DIP Switches
ControlKeeper 4
7
Renseignements généraux
Renseignements généraux
Le modèle ControlKeeper 4 est livré en une seule boîte et est doté d’un transformateur soit de 120V soit de 277V. Il est configuré en usine et est muni de relais normalement ouverts. Pour connaître le type de modèle en votre possession, consultez votre commande.
Pour commencer
1. Ne jetez pas ces instructions d’installation. Veuillez les conserver pour une référence ultérieure.
2. Débranchez toujours toutes les alimentations électriques avant de procéder au câblage.
3. Utilisez uniquement aux fins prévues et à la tension indiquée.
4. L’installation, les réparations et l’entretien doivent être effectués par des techniciens en entretien et réparation ou par du personnel qualifié.
5. L’installation doit se faire conformément au Code national de l’électricité et à tout autre code applicable.
6. Les renseignements sur l’installation et le câblage qui sont fournis dans ce document sont fondés sur des normes et des pratiques reconnues dans l’industrie. Si ces instructions vont à l’encontre de codes ou de règlements applicables, veuillez communiquer avec Greengate avant de commencer l’installation.
7. Une haute tension est présente dans le boîtier. Prenez des précautions extrêmes lorsque vous effectuez l’entretien de cet équipement. Le non-respect de cet avertissement et des procédures de sécurité appropriées peut entraîner des blessures sérieuses ou la mort et/ des dommages à l’équipement.
8. Pour vous aider à configurer et à programmer les dispositifs par la suite, prenez en note l’emplacement de ces derniers et des connexions.
Faire passer les ls à basse
tension par le côté gauche du boîtier
Faire passer les ls à haute
tension par le côté droit du boîtier
Figure 1. Boîtier du ControlKeeper 4
Câblage de l’alimentation
Le modèle ControlKeeper 4, configuré en usine, est doté d’un transformateur de 120V ou de 277V. Les tensions du transformateur sont codées par couleur. Il est conseillé de réserver un circuit de dérivation avec protection des circuits à l’utilisation du câblage du bloc d’alimentation.
1. Connectez le câble neutre au câble blanc.
2. Si le transformateur de votre appareil est de 277V, brachez le fil orange à un circuit de 277V. Si le transformateur de votre appareil est de 120V, branchez le fil noir à un circuit de 120V.
Ligne = 120V (noir), 277 (Orange) Neutre=blanc
Montage de l’armoire électrique
1. Choisissez un endroit sec sur une surface dure, proche des circuits à commander. Prévoyez un dégagement suffisant pour l’ouverture complète de la porte.
2. Montez l’armoire ControlKeeper 4A à l’aide des trous ménagés au dos du boîtier. Il est recommandé d’assembler le panneau à la verticale.
3. Tous les conducteurs à haute tension doivent pénétrer dans l’armoire par le côté droit du boîtier.
4. Tous les conducteurs à basse tension doivent pénétrer dans l’armoire par le côté gauche du boîtier.
5. Dégagez tous les débris et les rognures de métal du boîtier avant de mettre le ControlKeeper 4 sous tension.
8
ControlKeeper 4
120V Transformateur Ligne=noir Neutre=blanc
277V Transformateur Ligne=Orange Neutre=blanc
Figure 2. Boîtier du ControlKeeper 4
Branchement des charges du relais
1. Effectuez un essai des circuits de dérivation pour des courts-circuits avant de brancher et de mettre le ControlKeeper 4 sous tension.
2. Les borniers des relais ont une limite maximum de
3. 10 AWG pour le câblage.
4. Les relais sont destinés à être utilisés avec les circuits unipolaires seulement. Le branchement du ControlKeeper 4 à des circuits ou des charges bipolaires annulera la garantie de l’appareil.
Loading...
+ 16 hidden pages