Serial Enclosure (CKT)
Boîtier série (CKT)
Alojamiento Serial (CKT)
Model # CKT16
Model # CKT32
Model # CKT48
INS #
General Information
The Serial Enclosure is packaged separately from the
ControlKeeper TouchScreen Logic Board to protect
components during shipping. This installation instruction
pertains to the installation of the enclosure for this unit.
Please refer to the ControlKeeper T installation instruction
included in the box with the ControlKeeper Logic Board
for information specific to the logic board installation.
The ControlKeeper T enclosure is available in three
different sizes: 16 size, 32 size and 48 size. It can be
configured with different relay types as needed to achieve
your lighting needs.
Getting Started
1. Do not discard these installation instructions. Please
keep for future reference and operation information.
2. The relays and center rail are protected by shrinkwrap. Leave shrink-wrap in place until all drilling and
metal work is complete to protect against metal
shards getting into component circuitry.
3. Always disconnect all power before wiring.
4. Use only as intended and at the listed voltage.
5. All installation service must be performed by qualified
personnel or service technicians.
6. Install in accordance with National Electrical Code
and any other codes that may apply.
7. High voltage is present inside the lighting enclosure.
Use extreme caution when performing maintenance
on this equipment. Failure to follow this warning and
proper safety procedures could result in severe injury
or death and/or damage to the equipment.
8. Document all wiring that is terminated to the relays
so that the lighting control equipment can be properly
configured and programmed for operation.
Mounting the Enclosure
1. If the enclosure is a 32 or 48 size, remove the upper
backplate from the enclosure by using the 1/4 turn
screws provided. The proper operation of these
screws is to push in gently and turn 1/4 turn left until
the screw head is horizontal to release the catch
mechanism. Turning these screws more than 1/4 turn
may cause them to break.
2. Choose a dry location convenient to the circuit
breaker panel.
3. Mount the panel on a firm surface using pre-drilled
holes.
4. Connect the enclosure to the circuit breaker panel
using conduit. The conduit punch hole can not exceed
3 inches from the back of the enclosure. If this
measurement is exceeded, the logic board will not fit
properly inside the enclosure.
5. Remove all cuttings and dirt before removing shrinkwrap from the relays and center rails.
ote:NMake certain that high voltage and low voltage
wiring enters the enclosure separately. High
voltage wiring should not be brought into the
enclosure through the bottom or bottom left corner
of the enclosure.
Low voltage wiring can be brought into the enclosure
from the bottom or bottom left of the enclosure. If low
voltage wire must be brought into the cabinet from the
top section, there is a knockout reserved on the left side
which will allow conduit to be run from the top of the
enclosure into the low voltage wiring area. Failure to
separate high voltage from low voltage wiring may cause
interference with logic board function.
Wiring the Transformer
Conduit Knockout
for Piping
High Voltage
Compartment
Conduit Knockout
for Piping
Low Voltage
Compartment
Conduit Knockout
for Piping
Wiring the Transformer
The transformer provides power to the Relay Stack
Controller (RSC) and to the ControlKeeper T logic board. The
transformer is multi-tapped and voltages are color coded.
The transformer is available in 120V, 277V, 347V 60 Hz or
220V, 230V, 240V 50/60 Hz models. It is recommended that
a dedicated branch circuit with circuit protection be provided
for the transformer.
1. Connect the solid black wire to the dedicated branch
circuit that is powering the transformer.
2. Connect neutral wire to the wire with the appropriate
color coding for the voltage being used.
See chart below for clarification.
Table 1. Transformer Color Chart
Line VoltageBlack
120 VACWhite/Black
277 VACWhite/Orange
347 VACBrown
220 VAC 50/60 HzWhite/Red
230 VAC 50/60 HzWhite/Blue
240 VAC 50/60 HzWhite/Blue
Connecting Relay Loads
The relay cards will be pre-mounted by the manufacturer
in the enclosure per the order specifications.There are
currently three available relay types for the ControlKeeper
T enclosure. This includes the Serial Standard Relay Card,
the Serial Two Pole Relay Card and the Serial Latching Relay
Card. Please refer to the specific section for your relay card
type that you are wiring. For all relay types:
1. Verify that all wire cuttings are removed from the
enclosure.
2. Take the protective shrink-wrap off of the relay cards
once the wire cuttings are removed from the enclosure.
3. Test branch circuits for short circuits prior to landing
wiring on relays.
ote:NNeutrals terminate within the adjoining lighting panel.
Standard Relay Card Notes
1. The Standard Relay Card is rated for single-pole load
use only. Connection of 2 pole circuits/loads to the
Standard Relay Card will void the equipment warranty
and may result in severe injury or death, and/or damage
to the equipment.
2. Relay ratings are 120 or 277 volt, 20 amp maximum.
Standard relays are available in a Normally Open
configuration.
3. Relay terminal blocks have a maximum limit of 10 AWG
wire.
Standard Relay Card Wiring
The standard relay is a simple contact closure, breaking the
line and load wires of a normal circuit. To wire the relay into
the control circuit:
1. Connect a 120 or 277 volt, 20 amp max, de-energized
branch circuit breaker to the relay terminal block
position labeled LINE.
2. Connect the load wiring to the output terminal block
position labeled LOAD.
3. Tighten down relay terminal screws. Manufacturer’s
recommended torque rating is 7 lbs-in. (0.59 lbs-foot)
(0.8 Nm).
4. Document relay to circuit information for future
reference.
2
www.eaton.com/lightingsystems
Connecting Relay Loads
Relay Wiring
Wire: 10 AWG Max.
Relay Rating: 20 amps, 120/277V
To Lighting Load
From Branch Circuit
Standard Relay Card Wiring
Latching Relay Card Notes
1. The Latching Relay Card is rated for single-pole load use
only. Connection of 2 pole circuits/loads to the Latching
Relay Card will void the equipment warranty and may
result in severe injury or death, and/or damage to the
equipment.
2. Relay ratings are 120/277/347 volt, 20 amp maximum.
3. Relay terminal blocks have a maximum limit of 6 AWG
wire.
Relay Wiring
Wire: 6 AWG Max.
Relay Rating: 20 amps, 120/277/347V
To Lighting Load
From Branch Circuit
Latching Relay Card Wiring
Two Pole Relay Card Notes
1. Two Pole Relay ratings are 208/240/480 volt, 20 amp
maximum.
2. Relay terminal blocks have a maximum limit of 6 AWG
wire.
3. Two Pole Relays take up two relay slots in the
enclosure.
4. Two Pole Relays come in a Normally Open
configuration.
Latching Relay Card Wiring
The latching relay is a simple closure, breaking the line and
load wires of a normal circuit. To wire the relay into the
control circuit:
1. Connect a 120, 277 or 347 volt, 20 amp maximum,
de-energized branch circuit breaker to the relay terminal
block position labeled LINE.
2. Connect the load wiring to the output terminal block
position labeled LOAD.
3. Tighten down relay terminal screws. Manufacturer’s
recommended torque rating is 18 lb-in. (1.475 foot-lbs)
(2.0 Nm).
4. Document relay to circuit information for future
reference.
Two Pole Relay Card Wiring
1. Connect one de-energized branch circuit breaker to one
of the relay terminal block LINE locations.
2. Connect the load side to the output terminal block
position of this same terminal block, labeled LOAD.
3. Connect the other de-energized branch circuit breaker
to the other relay terminal block LINE location.
4. Connect the second load wire to the second terminal
block, labeled LOAD.
5. Tighten down relay terminal screws. Manufacturer’s
recommended torque rating is 18 lbs-in. (1.475 foot-lbs)
(2.0 Nm).
6. Document relay to circuit information for future
reference.
www.eaton.com/lightingsystems
3
Applying Power
Relay Wiring
Wire: 6 AWG max.
Relay Rating: 20 amps, 208/240/480V
To Lighting Load 2
From Branch Circuit 2
To Lighting Load 1
From Branch Circuit 1
Two Pole Relay Card Wiring
Applying Power
1. Once the wiring is complete, make certain that the
enclosure is clean of any wire clippings and that no
fragments are lodged in the relay circuit boards.
2. Ensure that there are no loose wires or exposed wires
that could short.
3. Power-up the unit from the circuit breaker.
4. Once power is applied to the unit, the power LED on
the RSC (right next to the override switch) should light
up and stay ON. The status LED on the RSC should
flash. The Status LEDs on each relay card should also
flash indicating that the relay card microprocessor is
operating.
5. At this point, lighting loads may be operated via the
individual relay override switches on the relay cards or
by using the Relay Stack Controller Override Switch.
6. If the enclosure is a 32 or 48 size enclosure, make
sure that the upper backplate is in place. To mount
the upper backplate, ensure that the 1/4 turn screws
are all vertically aligned before trying to place them in
place. Starting with the upper left corner, gently press
the 1/4 turn screw into its mounting hole. Press all 1/4
turn screws in place in a clockwise method. Once all
screws are in place, press down on each screw in turn
and gently turn the 1/4 turn screw to the right until
the screw head is horizontally aligned. This will lock it
in place. Turning the screw further than 1/4 turn may
result in it breaking.
Manually Controlling Relays
The relays in the ControlKeeper T enclosure may be
controlled before the logic board is in place using the Relay
Stack Controller or the individual relay override switches on
each relay.
Relay Stack Controller
The Relay Stack Controller (RSC) is at the bottom of the
enclosure. It acts as a master override to the system.
The RSC contains a three position rocker switch: ALL OFF,
AUTO, ALL ON. By moving the rocker switch to the right,
the Green LED will be lit and the relays will close. By
moving the rocker switch to the left, the Red LED will be lit
and the relays will open. The middle, AUTO, position allows
the relays to be controlled by the individual relay switches or
from the logic controller.
RSC Override Switch
ALL OFF/AUTO/ALL ON
RSC Override Switch
Individual Relay Override Switch
Each individual relay has its own individual relay override
switch that may be used as a temporary override to panel
programming. If used, that relay will be in the commanded
overridden state until the next command from the
ControlKeeper T to that relay. The RSC three position rocker
switch will be able to override the individual relay override
switches. However, when the RSC is moved back to AUTO,
it will revert control back to the logic panel or individual relay
override switches.
All relay cards have a small round button next to each
relay on the board. This button will allow the relay to be
overridden ON or OFF. To override the relay ON, press
the button until the LED next to the relay lights up. This
indicates that the relay has been commanded to close. To
override the relay OFF, press the button until the LED next
to the relay turns OFF. This indicates that the relay has been
commanded to open.
4
www.eaton.com/lightingsystems
Individual Relay
Override Switch
Standard Relay Override Switch
Individual Relay
Override Switch
Two Pole Relay Override Switch
sSRC
sTPRC
Low Voltage Wiring Notes
Network Wiring Notes
The ControlKeeper T is designed to communicate with
other ControlKeeper network panels using a lighting control
RS-485 network for communications. This allows the panels
to share information and to be programmed from one
central location by a computer with the Keeper Enterprise
Software.
For best network performance, Belden 9841 cable
should be used. If the specified cable is not used
and communications problems occur that require
troubleshooting assistance, additional charges for support
may be assessed.
1. All low voltage wiring is Class 2.
2. All low voltage wiring must enter the cabinet from the
lower-left side of the enclosure or be piped through
the high voltage section in conduit using the special
knockouts reserved for this section.
3. All low voltage wiring must be run in separate conduit
from line voltage wiring.
4. Test all network wiring for shorts to AC ground before
connecting to the ControlKeeper T panel.
5. Leave all shields disconnected making certain that
shield is not exposed.
6. Panels and devices on the RS-485 lighting network
should be daisy-chained. Do not create a Star or
T-tapped configuration.
sLRC
Individual Relay
Override Switch
Latching Relay Override Switch
Low Voltage Wiring Notes
Low voltage wiring in the ControlKeeper T consists of
switch wiring and network wiring. Please refer to the
installation instructions with the ControlKeeper T for more
in-depth information on low voltage wiring.
7. Total network length should not exceed 4000 feet.
8. Include a network repeater (RPTR) if network exceeds
32 panels or 4000 feet.
Low Voltage Dry Contact Switch Wiring
This section describes the wiring for dry contact closure
devices.
1. All low voltage wiring is Class 2 wiring.
2. All low voltage wiring must enter the cabinet from the
lower-left side of the enclosure or be piped through
the high voltage section in conduit using the special
knockouts reserved for this section.
3. All low voltage wiring must be run in separate conduit
from line voltage wiring.
4. Use 18 AWG twisted, unshielded wire for all low
voltage dry contact closure device wiring.
5. Maximum length for dry contact closure device wiring
is 1000 feet.
www.eaton.com/lightingsystems
5
GDS Switch Wiring
6. Test all low voltage wiring for shorts to AC ground
before connection to the ControlKeeper T panel.
Low Voltage Analog Input Wiring
This section describes the wiring for analog input devices.
1. All low voltage wiring is Class 2 wiring.
2. All low voltage wiring must enter the cabinet from the
lower-left side of the enclosure or be piped through
the high voltage section in conduit using the special
knockouts reserved for this section.
3. All low voltage wiring must be run in separate conduit
from line voltage wiring.
4. Use 18 AWG twisted, unshielded wire for all low
voltage analog device wiring.
5. Maximum length for analog device wiring is 500 feet.
6. Test all low voltage wiring for shorts to AC ground
before connection to the ControlKeeper T panel.
GDS Switch Wiring
Each ControlKeeper T unit is capable of supporting the
Greengate Digital Switch (GDS) station. The GDS does
not wire directly to the ControlKeeper T logic board, but
is wired using a CAN Bus network that connects to the
ControlKeeper T through a gateway called the GDS-I. GDS
stations are wired using the Eaton’s Cooper LCCP or LCCNP
cable, or Belden 1502P or 1502R equivallents.
See the ControlKeeper T logic board installation instructions
for further details on the connection. All connections to
the ControlKeeper T from these devices should be made
through the low voltage section of the controller.
For best network performance, one of the suggested
cables should be used. If the specified cable is not
used and communications problems occur that require
troubleshooting assistance, additional charges for support
may be assessed.
Logic Board Grounding Strap
The enclosure has a grounding strap located in the left
corner of the enclosure which should be connected to the
grounding strap provided on the ControlKeeper T logic panel.
Please refer to the ControlKeeper T instructions for further
information regarding this grounding strap.
Logic Board
Ground Strap
UL 924 Compliance
With the addition of the Relay Interface Module accessory,
the lighting control system has been approved in
compliance with UL 924. If using the Relay Interface
Module, it will be necessary to wire the transformer to
an emergency power source. Please refer to the Relay
Interface Module’s installation instructions for further
details.
6
www.eaton.com/lightingsystems
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.