Installation/ Operating
Instructions for 7 Day
echanical Socket Box Timer
M
- T101A-C
Please read the instructions fully before
attempting installation.
IMPORTANT
This unit should be installed to current
IET wiring regulations if in doubt
consult a qualified electrician.
• Timer must not be mounted on a
flammable surface.
• Ensure that the timer does not come
into contact with any combustible
materials such as towels or bedding.
• Ensure at least a 300mm air space
is allowed around the timer.
INSTALLATION
• Prepare cable ends for connection to
terminals.
• Remove the 2 screws holding the
timeswitch cover to the backplate.
Remove cover leaving the timeswitch
hanging loose by its connnection wires
to the backplate.
DO NOT INTERFERE WITH THESE
FIXED CONNECTIONS.
IMPORTANT: Ensure all Terminal screws
re fully tightened.
a
• When the wiring is complete screw the
backplate to the fitted wall box using
two 3.5mm screws.
• Push the timeswitch back in to its
seating on the backplate, taking care
that all the wires are tucked in. Fit the
cover and tighten the two screws.
SETTING THE CLOCK
Turn the dial in the direction of the
•
arrow (clockwise) until the correct
day and time of day is exactly
opposite time set marker on the
lock face.(weekly clock).
c
• For the “ON ” period push the
switching riders out towards the
outside edge of the face. The timer
will operate for the duration set (each
segment is approximately 2 hours
duration). i.e. If it is required to switch
on between 16.00 and 22.00, all the
segments between these times should
be moved to the outer edge.
SETTING THE
PROGRAMME
• By moving the switch located centre
right of the dock face the following
operations can be achieved.
= Permanently ON.
= Switching programme as set on dial.
= Permanently OFF.
TECHNICAL INFORMATION
Switching Capacity: 230V AC,16A
Ambient Temperature: -10°C to + 55°C
Shortest Switching Time: 2 Hours
Wattage: 3000W
Conforms To: EN 60730-1:2011,
resistive,2A Inductive
EN 60730-2-7:2010/
C11:2011
WIRING
• Connect all earth wires to earthing
point in wall box.
• Offer up the backplate to the wall box
and connect the wiring as below.
CONNECTION FOR 230V
SWITCHED OUTPUT
1. Neutral from mains and Neutral to
appliance
2. Not used
3. Live in from mains
4. Live output to appliance
GUARANTEE
Your KingShield 7 Day Mechanical Socket
Box Timer is guaranteed for
12 months from the date of purchase.
This does not affect your statutory rights.
CE INFORMATION
ACTION TYPE: IB
POLLUTION SITUATION: NORMAL
CLASS 2 INSULATION:
:MICRO-DISCONNECTION LIVE
POLE ONLY
PLEASE KEEP THESE INSTRUCTIONS
SAFE FOR FUTURE REFERENCE
Issue no: 703907