GreenBrook M22M, M22W Installation Instructions

Installation Instructions
or SafetySure Twin RCD Socket
f
M22W, M22M
IMPORTANT
This product should be installed by a
ompetent person and in accordance
c with the current IEE Wiring Regulations. If in doubt, consult a qualified electrician.
Electricity is dangerous and an RCD must not be used as a substitute for normal precautionary measures.
lways disconnect from mains
A supply before any inspection or repair to equipment. Do not allow children to tamper with electrical devices.
This device will protect against live and neutral leakage faults to earth, it will not protect against electric shock due to contact with both
conductors, short circuits between live and neutral, or a fault in the wiring supplying this device.
TO FIT THIS SAFETYSURE RCD SOCKET –
Switch off the power supply at the mains in order to isolate the existing socket. Remove the old socket, then simply connect using the easy to follow wiring diagram.
Green/Yellow(E)
If earth conductors are bare, they must be sleeved with appropriate green/
yellow sleeving. If you are in any doubt about
connecting this product consult a qualified electrician.
Brown(L)
Blue(N)
N.B. Green/yellow earth wire may be connected to either earth terminal. Wiring insulation tests should be completed before setting the SafetySure RCD Socket to avoid misleading instrument readings and possible internal damage to the unit.
PLEASE CARRY OUT THIS SIMPLE TEST PROCEDURE PRIOR TO EACH
SE.
U
1. Press green (R) ON button.
2. Indicator window will turn red*.
. Press white Test button (T).
3
4. Red window indicator will
disappear*. This means the RCD has tripped successfully.
. To reset – press green (R) ON button
5
and use as a normal
ocket.
s
* If indicator fails to work, do not use
and return to place of
urchase.
p
OTE 1:
N
If the red window indicator disappears once the socket has been reset and appliance is firmly plugged in the
socket, this may mean that the appliance or the cable lead is faulty, and
should be checked by a qualified electrician.
NOTE 2:
Remove this RCD from circuit before performing any high voltage insulation tests.
TECHNICAL DATA
Rated voltage: 230V AC 50Hz Maximum operating current: 13A (3A inductive) Rated trip current: 30mA Trip speed: 30mS RCD contact break: Double pole Test/Reset buttons: Responsive to both
Dimensions: 145mm x 85mm
Conforms to BS7288:1990 & BS1363
positive and negative cycles
x 35mm
GUARANTEE
Your KingShield Twin RCD Socket
is guaranteed for 12 months from the
date of purchase.
This does not affect your statutory
rights.
Please keep these instructions for future
reference.
INSTALLER - Please pass instruction manual
onto the owner of the unit